0% found this document useful (0 votes)
196 views

EST2 System Operations Manual

Manual central EST2 GE

Uploaded by

Villamarimjunior
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
196 views

EST2 System Operations Manual

Manual central EST2 GE

Uploaded by

Villamarimjunior
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 84

EST2

System Operations Manual


P/N 270188 • Rev 5.0 • 16AUG00
DEVELOPED BY Edwards Systems Technology
6411 Parkland Drive
Sarasota, FL 34243
(941) 739-4300
COPYRIGHT NOTICE Copyright © 2000 Edwards Systems Technology, Inc.
This manual is copyrighted by Edwards Systems Technology,
Inc. (EST) and others under separate license agreements. You
may not reproduce, translate, transcribe, or transmit any part of
this manual without express, written permission from EST.
This manual contains proprietary information intended for
distribution to authorized persons or companies for the sole
purpose of conducting business with EST. If you distribute any
information contained in this manual to unauthorized persons,
you have violated all distributor agreements and may be subject
to legal action.
TRADEMARKS IBM is a registered trademark of International Business
Machines Corporation.
Microsoft and MS-DOS are registered trademarks, and Microsoft
Mouse and Windows are trademarks of Microsoft Corporation.
Sound Blaster is a trademark of Creative Technology Ltd.
Scan-One is a trademark of Zebra Technologies VTI, Inc.
CREDITS This manual was designed and written by the EST Technical
Services - Documentation Department, Sarasota.

DOCUMENT HISTORY
Date Revision Reason for change
31MAY95 1.0 Initial Release.
01AUG95 2.0 Revised: Drill and test warning notes; Sensitivity Report Output;
misc. editorial corrections
Added: Maintenance level info; DL2 info
20SEP95 2.5 Revised: Editorial corrections throughout manual; updated
autoprogramming.
DEC95 3.0 Added 2-CMDN, SAN, and APSB Power Supply information.
Revised: DL2 information.
MAR97 3.5 Added: CDR-3, 2-SMK, 2-CTM, and 2-PPS/6A information.
Revised: DL2 information.
SEP97 4.0 Added: paging and telephone operations
OCT97 4.1 Added: 2-LSRA(-C) information; deleted 2-CMDN(-C)
information
AUG00 5.0 Added SIGA-MDM information.
Content

Content

Important information • ii
Getting the most out of this manual • iii

Chapter 1 Introduction • 1.1


Using this manual • 1.2
Documentation conventions • 1.4

Chapter 2 Operating panel devices • 2.1


Operating the 2-LCD • 2.3
Reading 2-LCD messages • 2.8
Acknowledging prioritized messages • 2.10
Responding to off-normal conditions • 2.11
Initiating a drill test • 2.15
Checking system status • 2.16
Programming system functions • 2.22
Enabling system functions • 2.25
Disabling system functions • 2.28
Activating system functions • 2.31
Restoring system functions • 2.33
Generating reports • 2.34
Testing system functions • 2.38
Operating LED/switch modules • 2.40
Operating the 2-MIC • 2.42
Operating the 2-TEL • 2.44
Recording voice messages • 2.45

Chapter 3 Operating remote devices • 3.1


Operating remote alphanumeric annunciators • 3.2
Reading and operating SAN annunciators • 3.9

Chapter 4 Operating peripheral devices • 4.1


PT-1S Printer • 4.2
RSAN-PRT Printer • 4.4

Appendix A Operator instructions • A.1


Posting operator instructions • A.2

Index • Z.1

EST2 System Operations Manual i


Content

Important information
Limitation of liability
This product has been designed to meet the requirements of
NFPA Standard 72, 1996 Edition; Underwriters Laboratories,
Inc., Standard 864, 7th Edition; and Underwriters Laboratories
of Canada, Inc., Standard ULC S527. Installation in accordance
with this manual, applicable codes, and the instructions of the
Authority Having Jurisdiction is mandatory. EST shall not under
any circumstances be liable for any incidental or consequential
damages arising from loss of property or other damages or losses
owing to the failure of EST products beyond the cost of repair or
replacement of any defective products. EST reserves the right to
make product improvements and change product specifications
at any time.
While every precaution has been taken during the preparation of
this manual to ensure the accuracy of its contents, EST assumes
no responsibility for errors or omissions.

FCC warning
This equipment can generate and radiate radio frequency energy.
If this equipment is not installed in accordance with this manual,
it may cause interference to radio communications. This
equipment has been tested and found to comply within the limits
for Class A computing devices, pursuant to Subpart B of Part 15
of the FCC Rules. These rules are designed to provide
reasonable protection against such interference when this
equipment is operated in a commercial environment. Operation
of this equipment is likely to cause interference, in which case
the user at his own expense, will be required to take whatever
measures may be required to correct the interference.

ii EST2 System Operations Manual


Content

Getting the most out of this manual


Finding EST2 documentation
A library of related documents supports the EST2 product line.
Here is a complete list of the EST2 library:
• EST2 Installation and Service Manual (P/N 270186)
• EST2 Network Site Manual (P/N 270895)
• EST2 Network Supplement Manual (P/N 270894)
• EST2 System Operations Manual (P/N 270188)
• EST2 System Programming Manual (P/N 270187)
• EST2 Installation Sheets (P/N 3100060)
• 2-SDU Help (P/N180902)
Our technical writers constantly update the information in this
manual. Your comments during our training classes, technical
support phone calls, and field trips improve this document.

Finding related documentation


The Signature Series Intelligent Smoke and Heat Detectors
Applications Bulletin (P/N 270145) provides instructions and
illustrations for various arrays of smoke and heat detectors.
The Signature Series Component Installation Manual (P/N
270497) supports the installation of the Signature Series
detectors and modules.
The Serial Number Log Book (P/N 270267) provides a
convenient means for recording the serial number of each
Signature device installed in the fire alarm system.
The SAN Annunciator Installation Guide (P/N 250084) supports
the SAN annunciators mentioned in this manual.
The EST Speaker Application Guide (P/N 85000-0033) provides
information about the placement and layout of speakers for fire
alarm signaling and emergency voice communications.
The EST Strobe Applications Guide (P/N 85000-0049) provides
information for the placement and layout of strobes for fire alarm
signaling.
The Microline 182 Turbo Printer Handbook, by Okidata
provides all the necessary information for the maintenance and
configuration of the PT-1S Form Printer. The Okidata handbook
comes with the Form Printer.

EST2 System Operations Manual iii


Content

iv EST2 System Operations Manual


Chapter 1
Introduction

Summary
Chapter 1 explains the layout of the System Operations Manual
and provides important references for additional information.

Content
Using this manual • 1.2
Chapter overview • 1.2
Appendix • 1.3
Documentation conventions • 1.4
Important notices • 1.4
System parameters • 1.4
Installation and operation procedures • 1.5

EST2 System Operations Manual 1.1


Introduction

Using this manual


Chapter overview
The System Operations Manual divides the operation of the fire
alarm system into three categories:
• Panel devices
• Remote devices
• Peripheral devices

Operating panel devices


The panel devices include modules, which mount inside the fire
alarm control panel and provide operator interface with the
system. All of the following operator interface devices mount in
the fire alarm control panel:
• 2-LCD
• LED/switch modules
• 2-MIC
• 2-TEL
• SIGA-MDM
The explanation for each device usually includes a picture and
one or two tables, which describe the controls and indicators on
it. The 2-LCD, however, provides the detailed messages and an
extensive amount of operator control over the system. Therefore,
the 2-LCD requires a systematic description of its controls and
an explanation of the procedures for using it.

Operating remote devices


Remote devices provide operator interface at locations away
from the fire alarm control panel. Remote operator interface
devices include:
• 2-CMDN(-C)
• 2-LSRA(-C)
• 2-SANCOM
• 2-SMDN(-C)
• ISP-96-2
• ISP-96-3
• SAN-MICII
• SHO-4
• SLU-16
• SWU-8/3
Again, the explanation for each device usually includes a picture
and one or two tables, which describe the controls and indicators
on it. The notable exceptions include the SWU-8(/3), the SHO-4,
the ISP-96-2, and the ISP-96-3 because of their toggle switch
options.

1.2 EST2 System Operations Manual


Introduction

Operating peripheral devices


The discussion of peripheral devices covers the operational
features of two printers: the PT-1S and the RSAN-PRT. This
manual provides instructions for loading and advancing paper in
the printer to print a history report. Take note, however, that the
operation of peripheral devices requires an operator interface.
Therefore, you will also need to know how to request a history
report from the 2-LCD.
Note: See Generating reports, in this manual, for more
information.

Appendix
The Appendix provides the information and resources you need
for posting operator instructions at the fire alarm control panel.

EST2 System Operations Manual 1.3


Introduction

Documentation conventions
Important notices
Notices throughout this manual inform the reader of practices
and conditions, which will affect physical safety, occupant
safety, equipment performance, and time consumption. Notices
appear as warnings, cautions, and notes.

Warnings
Warnings are posted when injury or loss of life may occur
through the neglect of safe practices and conditions.

WARNING: Testing the system disables the alarm contact. The


system will not notify the fire department in the event of a fire
alarm condition during a test. See the system administrator for
detailed information.

Cautions
Cautions are posted in the manual to prevent damage to the
equipment. A typical caution concerns the prevention of
electrostatic discharge (ESD).

Caution: Observe static-sensitive handling practices.

Notes
Notes instruct the reader to avoid practices or conditions, which
may result in wasted time and effort. For example, a download
will not work unless the programmer disconnects the printer
from the RS-232 port on the Main Controller Module (MCM).
Note: Disconnect the printer when downloading to the MCM.

System parameters
2-LCD keypad entries and fault messages require knowledge of
the system parameters.

Keypad entry parameters


To understand the parameters for 2-LCD keypad entries, see
Making keypad entries in Operating panel devices.

Fault message parameters


To understand the parameters for reading fault messages, see
System service procedures in the Installation and Service
Manual.

1.4 EST2 System Operations Manual


Introduction

Installation and operation procedures


The typical procedure will appear in the following format:

To activate an action:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 2 to select Action.
4. Enter the number of the action being activated (nnnn).
The word “Enter,” in steps 2 and 4 implies that the operator will
press the appropriate numbers and the ENTER key on the 2-LCD
keypad. See Operating panel devices for more information.

EST2 System Operations Manual 1.5


Introduction

1.6 EST2 System Operations Manual


Chapter 2
Operating panel devices

Summary
Chapter 2 discusses the procedures for reading and operating
devices located at the fire alarm control panel.

Content
Operating the 2-LCD • 2.3
Reading status LEDs • 2.4
Operating control switches • 2.4
Scrolling message review switches • 2.5
Making keypad entries • 2.6
Selecting system functions on the 2-LCD • 2.7
Reading 2-LCD messages • 2.8
Current time • 2.8
Messages waiting • 2.8
Event type • 2.8
Event time • 2.9
Event address • 2.9
Event message • 2.9
Acknowledging prioritized messages • 2.10
Responding to off-normal conditions • 2.11
Fire alarms • 2.11
Supervisory points • 2.11
Trouble conditions • 2.12
Monitor points • 2.12
Maintenance message • 2.13
Verification message • 2.13
Initiating a drill test • 2.15
Checking system status • 2.16
Viewing the general status screen • 2.16
Viewing the loop status screens • 2.17
Viewing the field panel status screen • 2.18
Viewing the Relay/LED status screen • 2.19
Viewing disabled device status • 2.19
Programming system functions • 2.22
Setting the system date • 2.22
Setting the system time • 2.22
Changing system passwords • 2.22
Programming the communications class • 2.23
Restarting system devices/functions • 2.24
Reconfiguring SLC1 and SLC2 • 2.24
Enabling system functions • 2.25
Enabling a zone • 2.25
Enabling a message • 2.25
Enabling a time control • 2.25
Enabling an RS-485 channel • 2.26

EST2 System Operations Manual 2.1


Operating panel devices

Enabling a panel address • 2.26


Enabling an action • 2.26
Enabling a sequence • 2.26
Enabling a laptop computer • 2.27
Enabling the mapping function • 2.27
Disabling system functions • 2.28
Disabling a zone • 2.28
Disabling a message • 2.28
Disabling a time control • 2.28
Disabling an RS-485 Channel • 2.29
Disabling a panel address • 2.29
Disabling an action • 2.29
Disabling a sequence • 2.29
Disabling a laptop computer • 2.30
Disabling the mapping function • 2.30
Activating system functions • 2.31
Activating an output • 2.31
Activating an action • 2.31
Activating a sequence • 2.31
Activating smoke sensitivity levels • 2.32
Restoring system functions • 2.33
Restoring an output • 2.33
Restoring an action • 2.33
Restoring a sequence • 2.33
Generating reports • 2.34
Viewing sensitivity reports • 2.34
Printing sensitivity reports • 2.35
Viewing history reports • 2.36
Printing history reports • 2.37
Testing system functions • 2.38
Starting the test function • 2.38
Ending the test function • 2.39
Operating LED/switch modules • 2.40
Reading front panel LEDs • 2.40
Activating devices at the front panel • 2.40
Restoring devices at the front panel • 2.40
Canceling commands at the front panel • 2.41
Operating the 2-MIC • 2.42
Operating the 2-TEL • 2.44
Recording voice messages • 2.45

2.2 EST2 System Operations Manual


Operating panel devices

Operating the 2-LCD

AC POWER
ALARM DISABLE
Status LEDs SUPERVISORY GND FAULT
TROUBLE CPU FAIL
MONITOR TEST

ALARM
RESET
SILENCE
Common User
Control Defined
LOCAL
Switches/LEDs DRILL Switch/LED
SILENCE

Liquid
Crystal
Display

REVIEW

Message
Review ALARM SUPVR TRBLE MONTR
Swtiches

1 2 3 STATUS PROGRAM

4 5 6 ENABLE DISABLE
Numeric Function
Keypad Switches
7 8 9 ACTIVATE RESTORE

0 REPORTS TEST

STDOP009.CDR

Figure 2-1: Panel controls and indicators

EST2 System Operations Manual 2.3


Operating panel devices

Reading status LEDs


The 2-LCD contains nine light emitting diodes (LEDs) which
indicate the status of the fire alarm control panel.

Table 2-1: LEDs


LED Description
AC Power Indicates mains ac is applied to the panel
Alarm Indicates an active alarm point in the system
Supervisory Indicates an active supervisory point
Trouble Indicates an active trouble condition
Monitor Indicates an active monitor point
Disable Indicates one or more zones are disabled
GND Fault Indicates a ground fault exists
CPU Fail Indicates a failure in the main controller module
Test Indicates that the panel is in test mode
User-defined Site-specific programmed option

Operating control switches


The 2-LCD provides four switches for executing common
controls and one user-definable switch.

Table 2-2: Control switches


Control Switch Description
Reset When pressed, the Reset switch returns the panel to normal standby
operation. The Reset switch also features an integral LED. When lit, the
LED indicates that the panel is resetting. When flashing, the LED indicates
that the Reset switch is inhibited.
Note: The cause of any off-normal condition must be identified and
restored to normal before the panel will reset. Site-specific programming
may prevent the operation of this switch for 1 or 3 minutes after the first
alarm is received.
Reset inhibit (check one): __none __1 minute __3 minutes
Local Silence When pressed, the Local Silence switch quiets the panel buzzer. The
Local Silence switch also features an integral LED. When lit, the LED
indicates that the panel is in local silence mode.
Note: Upon receipt of a new alarm, trouble, or supervisory condition, the
controller will exit the local silence mode and resound the panel buzzer.

2.4 EST2 System Operations Manual


Operating panel devices

Table 2-2: Control switches


Control Switch Description
Alarm Silence When pressed, the Alarm Silence switch turns off all audibles or visuals
as defined in the 2-SDU. The Alarm Silence switch also features an
integral LED. When lit, the LED indicates that the notification appliances
are off. When flashing, the LED indicates that the Alarm Silence switch is
inhibited.
Silence inhibit (check one): __none __1 minute __3 minutes
Drill When pressed, the Drill switch activates all audibles or visuals as defined
in the 2-SDU. Drill switch also features an integral LED. When lit, the LED
indicates that the Drill mode is on.
User Defined Site-specific programmed option. This switch will activate:
Enter the rule label:
The User-defined switch permits the operator to activate an action by
pressing it. The programmer determines the function of the User-defined
switch and enters it in the 2-SDU. See the 2-SDU Help for details on
programming user-defined switch.

Scrolling message review switches


Note: The operator must press the Local Silence switch to
review messages on the 2-LCD. Messages are listed with the
first (most recent) at the top of the queue and the last (oldest) at
the bottom.

Table 2-3: Message review switches


Message Description
Switch
ALARM Press the down arrow to scroll from the first alarm message to the last one.
Press the up arrow to scroll from last alarm message to the first one.
Press both arrows simultaneously to jump to the first message.
SUPVR Press the down arrow to scroll from the first supervisory message to the last one.
Press the up arrow to scroll from last supervisory message to the first one.
Press both arrows simultaneously to jump to the first message.
TRBLE Press the down arrow to scroll from the first trouble message to the last one.
Press the up arrow to scroll from last trouble message to the first one.
Press both arrows simultaneously to jump to the first message.
MONTR Press the down arrow to scroll from the first monitor message to the last one.
Press the up arrow to scroll from last monitor message to the first one.
Press both arrows simultaneously to jump to the first message.

EST2 System Operations Manual 2.5


Operating panel devices

Making keypad entries

Table 2-4: Keypad entries


Keypad Switch Description
0–9 When pressed, switches 0 – 9 enter the corresponding number or select
the corresponding menu item.
When pressed, the Delete switch deletes the character to the immediate
left of the cursor or cancels the menu selection.
When pressed, the Enter switch causes the panel to process the
information shown in the display.

The operator must know the system addresses to make entries on


the 2-LCD keypad. System addresses often appear as alphabet
characters on the 2-LCD, where:
• pp = panel address (00 through 63)
• zz = zone number
A panel address locates a module or part of a module, either
internal or external to the fire alarm control panel. For example,
the main controller module (MCM) resides in the control panel
and has two panel addresses (01 and 02). The LSRA, however,
is a remote annunciator that may have one of several panel
addresses (10 through 63).
Note: See Programming the communications class.
A zone number locates a device or function, that is either part of
a module or wired to it. Zone numbers 01 – 96, on panel
addresses 01 and 03, locate Signature series detectors. Zone
numbers 03 – 96, on panel addresses 02 and 04 locate Signature
series modules. Zone numbers 01 and 02, on panel addresses 02
and 04, locate NACs. Switches, LEDs, and actions may also
have zone numbers.

2.6 EST2 System Operations Manual


Operating panel devices

The operator also needs to know parameters for other keypad


entries, where:
• yyyy = year
• mm = month
• dd = day
• 01 - 07 = day of week
• hh = hour
• mm = minute
• ss = second
• nnnn = password, action number, sequence number
• tttt = time control
• PP = Priority
Note: Do not confuse a priority (PP) with the panel address (pp).

Selecting system functions on the 2-LCD

Table 2-5: Function switches


Function Switch Description
Status When pressed, the Status switch displays menus for viewing the status of
the general panel, the Signature Data Circuit (SDC), relays, LEDs, and
disabled devices.
Program When pressed, the Program switch displays menus for setting the time
and date, setting user passwords, configuring the RS-485 port, restarting
the system, and autoprogramming.
Enable When pressed, the Enable switch displays menus for enabling the
following system components: zones, zone messages, time controls, data
line, panels, actions, sequences, laptop, mapping.
Disable When pressed, the Disable switch displays menus for disabling the
following system components: zones, zone messages, time controls, data
line, panels, actions, sequences, laptop, mapping.
Activate When pressed, the Activate switch displays menus for activating the
following system components: output devices, actions, sequences,
primary smoke sensitivity levels, and alternate smoke sensitivity levels.
Restore When pressed, the Restore switch displays menus for returning the
following system components to the restored state: output devices,
actions, and sequences.
Reports When pressed, the Reports switch displays menus for obtaining system
sensitivity and history reports. Reports may be viewed on the main
controller display or sent to a printer.
Test When pressed, the Test switch activates the walk test function for testing
individual initiating device circuits.

EST2 System Operations Manual 2.7


Operating panel devices

Reading 2-LCD messages


Each message on the 2-LCD indicates several details about
itself. Figure 2-2 illustrates a typical fire alarm message.

Messages STDOP001.CDR
Current Time Waiting Event Type

14:55:18 M:001 13:40 Event Time


Fire Alarm 0101 Event Address
4 Fl Nurse's Station Event Message
East Wing Sub-station

Figure 2-2: Typical fire alarm message

Current time
The current time appears in twenty-four hour format, and
constantly changes to indicate the present system time.

Messages waiting
Messages waiting indicates the number of messages presently in
the message queue. The message with the highest priority
appears on the 2-LCD while the other messages wait in the
queue.

Event type
The 2-LCD displays the following types of events:
• 1st Fire Alarm
• Fire Alarm
• Supervisory
• Short Fault
• Open Fault
• Comm. Fault
• Ground Fault
• Dev/Line Fault
• Watchdog Fault
• Monitor Act
• PreAlarm Act
• Verification
• Maintenance
• Event
• Disable Flt

2.8 EST2 System Operations Manual


Operating panel devices

Event time
The event time also appears in a twenty-four hour format, but it
only indicates the time the event occurred and does not change.

Event address
Each address in the system consists of the following
components:
• Panel addresses (01 or 63)
• Zone numbers (01 - 96)
The event address in Figure 2-2 signifies that the Main
Controller Module (MCM) received an alarm condition from a
detector at address 01.

Event message
The message below the event address indicates the specific
location of the condition and any other relevant information. The
programmer customizes the message in the 2-SDU.
See System service procedures, in the Installation and Service
Manual, for a complete table of system fault messages.

EST2 System Operations Manual 2.9


Operating panel devices

Acknowledging prioritized messages


The 2-LCD has separate queues for each message type, and
displays them according to the following priority levels:
• Alarm messages (highest priority)
• Supervisory messages
• Trouble messages
• Monitor messages (lowest priority)

Display Message queues Comments


Quiescent State Alarm Supervisory Trouble Monitor
Display shows current time (13:45:55) and no
13:45:55 AP000 DP000 active points.

Project Description

Monitor Events Received


An event on Monitor device #234 occured at
13:47:56 AP001 DP000 13:47. Nothing is displayed, because the
event did not occur during an alarm. On the
other hand, the AP counter increases by the
Project Description number of events.

Fire Alarm Received


0126 0235 A fire alarm on device #0126 occured at
13:51:00 M:004 13:51 13:51, followed by 3 monitor events: 0235,
1st Fire Alarm 0126 0236 0236, and 0237. The alarm message is
5 floor elevator immediately displayed, and the Message
0237
Lobby smoke detector Waiting counter increments to 004.

Fire Alarm Acknowledged


The fire alarm on device #0126 was reviewed
0126 0235
13:54:12 AP004 DP000 using the ALARM switch.
0236
0237
Project Description

Monitor Event Acknowleged


0126 0235 The MONTR switch displays the first
13:57:12 M:004 13:51 monitor event message.
Monitor Alrm 0235 0236
High temperature on 0237
chiller A27

Trouble Event Received


0126 0288 0235 A trouble on device #0288 occured at 13:57.
14:03:33 M:005 13:57 The trouble message replaces the monitor
Open fault 0288 0236 messages on the display, because it has a
1 floor Laboratory 0237 higher priority. The Message Waiting counter
incremented to 005.

Monitor Events Acknowleged


0126 0288 0235 The monitor events on devices 0236 and 0237
14:05:55 AP005 DP000 were reviewed in order, using the MONTR
0236 switch.
0237
Project Description

Trouble Event Acknowleged


0126 0288 0235 The trouble on device #0208 was reviewed
14:05:55 AP005 DP000 using the TRBLE switch.
0236
0237
Project Description
STDOP043.CDR

Figure 2-3: Message priorities

2.10 EST2 System Operations Manual


Operating panel devices

Responding to off-normal conditions


During off-normal conditions, the 2-LCD sounds its internal
buzzer and displays a message to indicate a problem in the
system. You must press the Local Silence switch before you can
view messages other than the one displayed during the off-
normal condition. Once you press Local Silence, you may view
any message in any order by pressing the message review
switches.

Fire alarms
Smoke detectors, heat detectors, fire alarm stations, and
sprinkler systems may initiate fire alarms. The Alarm LED,
when on, indicates a fire alarm.

To respond to a fire alarm:

1. Press the Local Silence switch to silence the buzzer.


2. Read the display to determine the location of the fire alarm
condition.
3. Press the Alarm Review switch to view the alarm
message(s).
The Alarm Review switch will display any additional alarm
locations. Before you can reset the panel, the appropriate
personnel must:
• Put out the fire
• Investigate the cause of the fire
• Declare the building safe for re-entry

To reset the panel after a fire alarm:

1. Press the Alarm Silence switch to silence the audible


notification appliances.
2. Press the Local Silence switch to silence the buzzer.
3. Press the Reset switch to restore the panel to normal.
If either the Alarm Silence LED or Reset LED flashes, wait until
the inhibit period ends, then press the appropriate switch again.
The maximum inhibit period is three minutes.

Supervisory points
Active supervisory points indicate that a fire protection system
other than the fire alarm panel is off-normal. Conditions like
closed sprinkler valves and disabled supplementary fire
extinguishing systems may cause supervisory conditions. The
Supervisory LED, when lit, indicates a supervisory condition.

EST2 System Operations Manual 2.11


Operating panel devices

To respond to a supervisory condition:

1. Read the display to determine the location of the supervisory


condition.
2. Press the Local Silence switch to silence the buzzer.
3. Press the SUPVR switch to review the supervisory condition
message(s).
4. Investigate the cause of the supervisory condition.
5. Press the Reset switch to restore the panel to normal.
The supervisory condition must be corrected before the panel
will reset. Latching circuits require a manual reset. Non-latching
circuits automatically reset. The 2-LCD display will indicate any
additional supervisory conditions. The most recent location
appears at the top of the list.

Trouble conditions
Active trouble conditions indicate that some portion of the fire
alarm panel is in an off-normal condition, and may affect its
proper operation. The Trouble LED, when lit, indicates a trouble
condition.

To respond to a trouble condition:

1. Read the display to determine the location of the trouble


condition.
2. Press the Local Silence switch to silence the buzzer.
3. Press the TRBLE switch to review the supervisory condition
message(s).
4. Investigate the cause of the trouble condition.
5. Call for service if you cannot immediately determine the
cause of the trouble condition.
6. Press the Reset switch to restore the system to normal.
The panel will not reset until the trouble is repaired. The 2-LCD
display will indicate any additional trouble locations. The
Trouble LED lights steady when you have acknowledged all the
trouble messages.

Monitor points
Active monitor points indicate off-normal conditions in
equipment monitored by the fire alarm panel. A typical cause for
an active monitor point might be a signal, which indicates the
status of the fan systems. The Monitor LED, when on, indicates

2.12 EST2 System Operations Manual


Operating panel devices

an active monitor point. In the alarm mode, the 2-LCD will also
display active monitor messages.

To respond to a monitor point:

1. Read the display to determine the location of the monitor


condition.
2. Press the Local Silence switch to silence the buzzer.
3. Read the monitor point message by pressing the MONTR
switch.
4. Investigate the cause of the monitor point.
5. Call for service if you cannot immediately determine the
cause of the monitor point.
6. Press the Reset switch to restore the system to normal.
The panel will not reset until the monitor point condition is
corrected. The 2-LCD display will indicate any additional
monitor point messages. The Monitor LED will light steady
when you have acknowledged all the monitor point messages.
The 2-LCD displays monitor points only during alarm
conditions.

Maintenance message
The 2-LCD will display a maintenance message and sound the
buzzer to indicate a maintenance condition. For example, a dirty
detector may cause a maintenance condition. The display will
annunciate the device address and any programmed message
assigned to that device.

To respond to a maintenance message:

1. Press the Local Silence switch to silence the buzzer.


2. Press the MONTR switch to view the maintenance message.
3. Investigate the device indicating the maintenance message.
4. Clean the device.
You can view the maintenance messages on the 2-LCD
sensitivity report or a printout.

Verification message
The 2-LCD will display a verification message and sound the
buzzer to indicate a verification condition. The display will
indicate the device address and any programmed message(s).

EST2 System Operations Manual 2.13


Operating panel devices

To respond to a verification message:

1. Press the Local Silence switch to silence the internal buzzer.


2. Press the MONTR switch to view the verification message.
3. Investigate the cause of the verification condition.
If the device indicating the verification or any other device
detects smoke within the specified period of time, both devices
will go into alarm and send a message to the display.

2.14 EST2 System Operations Manual


Operating panel devices

Initiating a drill test


The drill function operates all building fire alarm signals as
programmed.

To initiate a fire drill:

1. Inform the building occupants that you will be performing a


drill.
2. Press the DRILL switch.
3. Press the DRILL switch again to end the drill.

EST2 System Operations Manual 2.15


Operating panel devices

Checking system status


This section explains the functions of the Status switch. In the
Status mode, the 2-LCD displays the following screens:
• General Status
• Loop 1 Status
• Loop 2 Status
• Field Panel Status (if conditions exist)
• Relay/LED Status (if conditions exist)
• Disabled Components/Functions (if conditions exist)
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

To access the system status menu:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Make the appropriate selection based on the screen in Figure
2-4.

Status Report
[ent] key scrolls.
[del] key terminates
Revision X.XX
STDOP021.CDR

Figure 2-4: System status menu

Viewing the general status screen

To view the general status screen:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Press Enter until you see the general status screen (Figure
2-5).

STDOP004.CDR
Status Legend Status: (1=Fault)
485 Comm. Status
AC Power ACp0 Bat0 MPw0 SPw0 Smoke Power
Ground Fault Gnd0 Ann0 Prn0 Dia0 Dialer

Battery NAC Power


Remote Annunciator Printer/External Command Port

Figure 2-5: General status screen

2.16 EST2 System Operations Manual


Operating panel devices

“0” indicates a normal condition for the associated parameter;


“1” indicates a fault.

Table 2-6: General status legend


Legend Cause
ACp AC Power
Gnd Ground Fault
Bat Battery
Ann Remote Annunciator
MPw NAC Power
Prn Printer
Spw Smoke Power
Dia Dialer

Viewing the loop status screens

To view the loop status screens:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Press Enter until you see the loop 1 status screen (Figure
2-6).
4. Press Enter one more time to see the loop 2 status screen.
The loop 2 status screen displays the same items as the loop 1
status window.

STDOP005.CDR
Circuit ID Loop 1 status:
1= flt/act, 0=ok/inact. Status Legend
Communications Com0 Res0 Bal0 Mpg0 Mapping in Progress
Programming Prg0 Gnd0 Lin0 Map0 Map Fault

Circuit Reset Balanced Map


Circuit Ground Fault Class A Line Fault

Figure 2-6: Loop status screen

“0” indicates a normal condition for the associated parameter;


“1” indicates a fault.

EST2 System Operations Manual 2.17


Operating panel devices

Table 2-7: Loop status legend


Legend Cause
Com Communications fault between loop electronics
and main controller module (MCM)
Res Signature Data Circuit (SDC) is resetting
Bal SDC is balanced
Mpg SDC is actively mapping
Prg Writing to Signature memory
Gnd Ground Fault on SDC
Lin Class A Fault on SDC
Map Map Fault on SDC

Viewing the field panel status screen


If a panel has connections to annunciators or audio equipment,
the 2-LCD status function will feature the Field Panel status
screen. The Field Panel Status screen indicates the condition of a
panel’s communications to the annunciators or audio equipment
connected to it.

To view the field panel status screen:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Press Enter until you see the field panel status screen
(Figure 2-7).

Field panel status.


Address: 10 Power: ok
Com.Prm: ok ComSec:na
Com.Enabled: ok
STDOP022.CDR

Figure 2-7: Typical field panel status screen

2.18 EST2 System Operations Manual


Operating panel devices

Table 2-8: Field panel status legend


Legend Cause
Com.Prm Primary Communications
ComSec Secondary Communications
Com.Enabled Communications Enabled

Viewing the Relay/LED status screen


If the system activates a relay or LED, the 2-LCD status function
will feature the Relay/LED status screen.

To view the Relay/LED status screen:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Press Enter until you see the Relay/LED status screen
(Figure 2-8).

SDC (Signature data circuit) Relay/Led status:


MCM (Main Controller Module)

Signature module at address 0208 (S50) Set with Priority 50


08 on the MCM SDC

STDOP006.CDR

Relay/Led status:

Signature module at address 0208 (R51) Reset with Priority 51


08 on the MCM SDC

Figure 2-8: Typical LED/relay status screens

Viewing disabled device status


If the operator disables a device or function of the system, the
2-LCD status function will generate a status screen to show it.
Status screens will show the following disabled components or
functions:
• Points
• Messages
• Actions
• Time Controls
• Sequences

EST2 System Operations Manual 2.19


Operating panel devices

To view the disabled status screens:

1. At the 2-LCD, press Status.


2. Enter a level 1, 2, or 3 password.
3. Press Enter until you see the disabled status screen (Figure
2-9 through Figure 2-13).

Disabled Points:
0208 0209

STDOP023.CDR

Figure 2-9: Typical disabled points screen

Disabled Message:
0211

STDOP024.CDR

Figure 2-10: Typical disabled message screen

Disabled Actions:
5600

STDOP025.CDR

Figure 2-11: Typical disabled actions screen

Disabled Time Control:


1130

STDOP026.CDR

Figure 2-12: Typical disabled time control screen

2.20 EST2 System Operations Manual


Operating panel devices

Disabled Sequence:
4800

STDOP027.CDR

Figure 2-13: Typical disabled sequence screen

EST2 System Operations Manual 2.21


Operating panel devices

Programming system functions


This section explains the functions of the Program switch. In the
Program mode, the 2-LCD offers the following menu options:
• Date
• Time
• Password
• RS-485 Port Communications
• System Restart
• Reconfigure (Autoprogram)
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Setting the system date

To set the system date:

1. At the 2-LCD, press Program.


2. Press 1 to select Date.
3. Enter a level 3 password.
4. Enter the year (yyyy).
5. Enter the month (mm).
6. Enter the day (dd).
7. Enter the day of the week (Sun=01).

Setting the system time

To set the system time:

1. At the 2-LCD, press Program.


2. Press 2 to select Time.
3. Enter a level 3 password.
4. Enter the time (hhmmss).

Changing system passwords

To change a system password:

1. At the 2-LCD, press Program.


2. Press 3 to select Password.
3. Enter a level 3 password.
4. Change the password level (1, 2, or 3).

2.22 EST2 System Operations Manual


Operating panel devices

5. Enter the new password (nnnn).

Table 2-9: System passwords


Level Personnel Default Access Privileges
1 Operators 1111 All Status, Activate,
Restore, and Reports
functions
2 Supervisors 2222 All Level 1 privileges and
all Enable, Disable, and
Test functions
3 Administrators 3333 All Level 1 and 2
privileges and all program
functions.

Note: The system installer should change all passwords after the
system has been installed.

Programming the communications class


The fire alarm control panel receives the 64 panel addresses
listed below:
• 00: Primary power supply
• 01: MCM Signature detectors
• 02: MCM NACs and Signature modules
• 03: LCX Signature detectors
• 04: LCX NACs and Signature modules
• 05: Front panel LED/switch modules
• 06 through 09: Future use
• 10 through 63: Devices and accessories

To program a panel for Class A (Style 7) communications:

1. At the 2-LCD, press Program.


2. Press 4 to select communications class.
3. Enter a level 3 password.
4. Enter the panel address (pp).
5. Enter 1 to program the panel as a Class A (Style 7) circuit.

EST2 System Operations Manual 2.23


Operating panel devices

To program a panel for Class B (Style 4) communications:

1. At the 2-LCD, press Program.


2. Press 4 to select communications class.
3. Enter a level 3 password.
4. Enter the panel address (pp).
5. Enter 2 to program the panel as a Class B (Style 6) circuit.

Restarting system devices/functions


In the Restart menu, you can restart the:
• CPU
• SLCs
• History report

To restart a system device or function:

1. At the 2-LCD, press Program.


2. Press 5 to select Restart.
3. Enter a level 2 or 3 password.
4. Enter the number for the item you want to restart.

Reconfiguring SLC1 and SLC2

To reconfigure the SLCs:

1. At the 2-LCD, press Program.


2. Press 6 to select Reconfig.
3. Enter a level 2 or 3 password.
4. Press Enter to accept the settings and Delete to exit the
sequence.

2.24 EST2 System Operations Manual


Operating panel devices

Enabling system functions


This section explains the functions of the Enable switch. In the
Enable mode, the 2-LCD offers the following menu options:
• Zones
• Messages
• Time Controls
• RS-485 Channels
• Panels
• Actions
• Sequences
• Laptop Computer Downloading
• Mapping
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Enabling a zone

To enable a zone:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 1 to select zone.
4. Enter the device address (ppzz).

Enabling a message

To enable a message:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 2 to select message.
4. Enter the device address (ppzz).

Enabling a time control


Note: Do not enable more than 127 time controls at a time.

To enable a time control:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 3 to select time control.
4. Enter the time-control numbers (tttt).

EST2 System Operations Manual 2.25


Operating panel devices

Enabling an RS-485 channel

To enable RS-485 communications on channel 0:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 4 to select RS-485 communications channels.
4. Enter 0 to enable channel 0.

To enable RS-485 communications on channel 1:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 4 to select RS-485 communications channels.
4. Enter 1 to enable channel 1.

Enabling a panel address

To enable a panel:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 5 to select panel.
4. Enter the panel address (pp).

Enabling an action

To enable an action:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 6 to select action.
4. Enter the action number (nnnn).

Enabling a sequence

To enable a sequence:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 7 to select sequence.
4. Enter the sequence number (nnnn).

2.26 EST2 System Operations Manual


Operating panel devices

Enabling a laptop computer

To enable a laptop computer:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 8 to enable the laptop.

Enabling the mapping function

To enable mapping:

1. At the 2-LCD, press Enable.


2. Enter a level 2 or 3 password.
3. Enter 9 to enable mapping.

EST2 System Operations Manual 2.27


Operating panel devices

Disabling system functions


This section explains the functions of the Disable switch. In the
Disable mode, the 2-LCD offers the following menu options:
• Zones
• Messages
• Time Controls
• RS-485 Channels
• Panels
• Actions
• Sequences
• Laptop Computer Downloading
• Mapping
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Disabling a zone

To disable a zone:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 1 to select zone.
4. Enter the device address (ppzz).

Disabling a message

To disable a message:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 2 to select message.
4. Enter the device address (ppzz).

Disabling a time control

To disable a time control:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 3 to select time control.
4. Enter the time control number (tttt).

2.28 EST2 System Operations Manual


Operating panel devices

Disabling an RS-485 Channel

To disable RS-485 communications on channel 0:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 4 to select RS-485 communications channels.
4. Enter 0 to disable the channel 0.

To disable RS-485 communications on channel 1:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 4 to select RS-485 communications channels (data
line).
4. Enter 1 to disable the channel 1.

Disabling a panel address

To disable a panel:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 5 to select panel.
4. Enter the panel address (pp).

Disabling an action

To disable an action:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 6 to select action.
4. Enter the action number (nnnn).

Disabling a sequence

To disable a sequence:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 7 to select sequence.
4. Enter the sequence number (nnnn).

EST2 System Operations Manual 2.29


Operating panel devices

Disabling a laptop computer

To disable a laptop computer:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 8 to select laptop.

Disabling the mapping function

To disable mapping:

1. At the 2-LCD, press Disable.


2. Enter a level 2, or 3 password.
3. Enter 9 to select mapping.

2.30 EST2 System Operations Manual


Operating panel devices

Activating system functions


This section explains the functions of the Activate switch. In the
Activate mode, the 2-LCD offers the following menu options:
• Outputs
• Actions
• Sequences
• Primary Smoke Sensitivity
• Alternate Smoke Sensitivity
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Activating an output

To activate an output:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 1 to select Output.
4. Enter the priority and address for the output device being
activated (PPppzz).

Activating an action

To activate an action:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 2 to select Action.
4. Enter the number of the action being activated (nnnn).

Activating a sequence

To activate a sequence:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 3 to select Sequence.
4. Enter the number of the sequence being activated (nnnn).

EST2 System Operations Manual 2.31


Operating panel devices

Activating smoke sensitivity levels

To activate the primary smoke sensitivity level:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 4 to activate the primary smoke sensitivity level.

To activate the alternate smoke sensitivity level:

1. At the 2-LCD, press Activate.


2. Enter a level 1, 2, or 3 password.
3. Press 5 to activate the alternate smoke sensitivity level.

2.32 EST2 System Operations Manual


Operating panel devices

Restoring system functions


This section explains the functions of the Restore switch. In the
Restore mode, the 2-LCD offers the following menu options:
• Outputs
• Actions
• Sequences
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Restoring an output

To restore an output:

1. At the 2-LCD, press Restore.


2. Enter a level 1, 2, or 3 password.
3. Press 1 to select Output.
4. Enter the priority and address for the output device being
restored (PPppzz).

Restoring an action

To restore an action:

1. At the 2-LCD, press Restore.


2. Enter a level 1, 2, or 3 password.
3. Press 2 to select Action.
4. Enter the number of the action being restored (nnnn).

Restoring a sequence

To restore a sequence:

1. At the 2-LCD, press Restore.


2. Enter a level 1, 2, or 3 password.
3. Press 3 to select Sequence.
4. Enter the number of the sequence being restored (nnnn).

EST2 System Operations Manual 2.33


Operating panel devices

Generating reports
This section explains the functions of the Reports switch. In the
Reports mode, the 2-LCD offers two report options: sensitivity
and history. Both reports may be sent to either the 2-LCD
display or a printer.
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.

Viewing sensitivity reports

To view a sensitivity report:

1. At the 2-LCD, press Reports.


2. Enter a level 1, 2, or 3 password.
3. Enter 1 to choose a sensitivity report.
4. Enter 1 to send the report to the 2-LCD display.
5. Follow the instructions on the screen illustrated in Figure
2-14.

For All Press [ENT]


For Range ppaa [ENT]
[DEL] will terminate
Enter Choice
STDOP028.CDR

Figure 2-14: Sensitivity report instructions

Note: If the fire alarm control panel has been on for less than 15
minutes, the 2-LCD will display the screen in Figure 2-15.

Sensitivity Report
is only valid after
15 minutes of opera-
tion. Press [del].
STDOP045.CDR

Figure 2-15: Sensitivity report delay

The parameters “ppaa” stand for the panel and device address.
For example, a detector at address 56 on an MCM Signature
data circuit would require 0156 for its entry.
Figure 2-16 illustrates a typical sensitivity report on the 2-LCD.

2.34 EST2 System Operations Manual


Operating panel devices

Press [ENT] for more


Add: 0101 Type 3D
Alarm Level: 3%
Maint. Level: 00%
STDOP029.CDR

Figure 2-16: Typical sensitivity report on 2-LCD

Printing sensitivity reports

To print a sensitivity report:

1. At the 2-LCD, press Reports.


2. Enter a level 1, 2, or 3 password.
3. Enter 1 to choose a sensitivity report.
4. Enter 2 to send the report to the printer.
5. Enter the device address of the desired report only on local
reports.
Figure 2-17 illustrates the typical printed format of a sensitivity
report.

====4D Panel Sensitivity Report====


Facility: Project Name
Date: 03-23-1998
Time: 03:59:08

Sensitivity Report for 4D, 3D, Photo, and Ion Sensors


Sensor Sensor Alarm Maintenance
Address Type Setting Indicator

0101 3D Detector 2.0% 04


0102 3D Detector 2.0% 00

Percentage of allowed maintenance


range, which becomes critical at 80%

STDOP002.CDR

Figure 2-17: Typical sensitivity report print format

EST2 System Operations Manual 2.35


Operating panel devices

Viewing history reports

To view a history report:

1. At the 2-LCD, press Reports.


2. Enter a level 1, 2, or 3 password.
3. Enter 2 to choose a history report.
4. Enter 1 to send the report to the 2-LCD display.
The 2-LCD will display the screens in Figure 2-18 and Figure
2-19.

Comp. Rev: X.Y


Proj Rev M.N
Last updated on:
01/03/99 01:01:01
STDOP030.CDR

Figure 2-18: History report revision

Press:
[MONTR ] for older
[MONTR ] for newer
[DEL] to terminate
STDOP031.CDR

Figure 2-19: History report instructions

Figure 2-20 illustrates two typical history reports on the 2-LCD.

01/03/99 01:01
A XXXXXXXXXXXXXXXX: ppaa A: Active
Response Msg Line 1
Response Msg Line 2

01/03/99 01:01
R XXXXXXXXXXXXXXXX: ppaa R: Restore
Response Msg Line 1
Response Msg Line 2
STDOP032.CDR

Figure 2-20: Typical history reports on the 2-LCD

2.36 EST2 System Operations Manual


Operating panel devices

Printing history reports


Note: A History Report will contain the last 650 events.

To print a history report:

1. At the 2-LCD, press Reports.


2. Enter a level 1, 2, or 3 password.
3. Enter 2 to choose a history report.
4. Enter 2 to send the report to the printer.
Figure 2-21 illustrates the typical printed format of a history
report.

==== System History Report ====


Facility Name: Medical Arts Center

Licensee: 00114-P. Smith


Compiled on 10/31/99 22:16:53
Compiler Rev: 01.03.0
Project Rev: 14.6
Report Date: 10-31-1999
and Time: 23:30:20
ACTIVATION 1st Fire Alarm: 0301 Date: 10/31/99 Time 01:01
SMOKE DETECTOR #1
ACTIVATION Fire Alarm: 0302 Date: 10/31/99 Time 01:03
SMOKE DETECTOR #2
ACTIVATION Switch: 0535 Date: 10/31/99 Time: 01:09
FAN ON
Restoration Switch: 0535 Date: 10/31/99 Time 01:11
ACTIVATION Relay/Output: 0221 Date:)10/31/99 Time: 16:11
CC2 LOOP 1 STDOP003.CDR

Figure 2-21: Typical history report print format

EST2 System Operations Manual 2.37


Operating panel devices

Testing system functions

WARNING: Testing the system disables the alarm contact. The


system will not notify the fire department in the event of a fire
alarm condition during a test. See the system administrator for
detailed information.

This section explains the functions of the Test switch. The Test
switch temporarily disables normal system responses during the
testing of panels, detectors, and modules. The 2-LCD and the
printer report all responses from activated devices and devices
with trouble conditions.
The system programmer sets the test function for silent or
audible operation in the system definition utility (2-SDU). In
silent operation, the device under test will not activate
Notification Appliance Circuits (NACs). In audible operation,
the device under test activates programmed NACs for
approximately 2 seconds. The system programmer may also
program test only functions.

Starting the test function


For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.
Note: The buzzer will sound when you have successfully
entered the test mode. Press Local Silence to silence the buzzer.

To start the Test function:

1. At the 2-LCD, press Test.


2. Enter a level 2 or 3 password.
3. Follow the instructions on the test screen (Figure 2-22).

Test mode will end


If no test done for
30 minutes. Press
[ENTER] key to start

STDOP033.CDR

Figure 2-22: Test screen

2.38 EST2 System Operations Manual


Operating panel devices

Figure 2-23 illustrates the 2-LCD display during the test mode.

13:18:12 M002 @13:27


Open Fault 0030
System in Test Mode

STDOP034.CDR

Figure 2-23: Typical test mode screen

Ending the test function


The Test function ends through operator input or automatic
system response and resets the fire alarm control panel.

To end the Test function manually:

1. At the 2-LCD, press Test.


2. Press Delete.
The test function will automatically end if you let 30 minutes
pass without testing a device. The 2-LCD provides a reminder of
the 30-minute test window, as seen in Figure 2-22.
See the site-specific information, provided with the panel, for
customized test functions.

EST2 System Operations Manual 2.39


Operating panel devices

Operating LED/switch modules


The front panel LED/switch modules provide manual control to
various portions of the system. The operator may view LEDs to
determine the status of a device, or press an associated switch
pad to change its state. During any change of state, the LEDs
flash through a duty cycle. All commands may be cancelled by
pressing the switch pad a second time before the command is
executed.

Reading front panel LEDs


Each switch has two LEDs. A flashing sequence on the upper
LED indicates the activation or restoration of a device. The
lower LED operates independently, but it usually indicates the
status of a function related to the switch pad.

Upper LED
Function Label
Switch Pad
Lower LED

STDOP035.CDR

Figure 2-24: Front panel LED/switch module

Activating devices at the front panel


To activate a device, press its corresponding switch. The upper
LED will flash with a 10% duty cycle as shown in Figure 2-25
(top). During the 10% duty cycle, the LED is off more than it is
on. The LED stops flashing and remains lit when the device is
fully activated.

Restoring devices at the front panel


To restore a device, press its corresponding switch. The upper
LED will flash with a 90% duty cycle as shown in Figure 2-25
(bottom). During the 90% duty cycle, the LED is on more than it
is off. The LED turns off completely when the device is fully
restored.

2.40 EST2 System Operations Manual


Operating panel devices

Activating a device
LED 10% duty cycle: device turning on LED on Steady
Upper LED on

Device on

Upper LED off


Time
Restoring a device
LED 90% duty cycle: device turning off LED off
Upper LED on

Device off
Upper LED off
STDOP010.CDR

An operator presses the switch. The device responds.

Figure 2-25: LED/switch module activation and restoration duty cycles

Canceling commands at the front panel


If you change your mind while a device is turning on, you can
cancel the command to turn it on. Before the command is
executed, press the switch a second time. The duty cycle will
stop and the LED will return to its previous state. See the upper
half of Figure 2-26.

Canceling the activation of a device


LED 10% duty cycle: device turning on LED off
Upper LED on

Device remains off

Upper LED off


Time
Canceling the restoration of a device
LED 90% duty cycle: device turning off LED on Steady
Upper LED on

Device remains on
Upper LED off
STDOP011.CDR

An operator presses the switch.


The operator presses the switch again.

Figure 2-26: LED/switch module cancellation duty cycles

You may also cancel a command if you change your mind while
a device is turning off. Before the command is executed, press
the switch a second time. The duty cycle will stop and the LED
will return to its previous state. See the lower half of Figure
2-26.

EST2 System Operations Manual 2.41


Operating panel devices

Operating the 2-MIC

Microphone handset

PHONE TO EVAC
PHONE TO ALERT
PAGE TO EVAC
PAGE TO ALERT
EVAC
ALERT

STDOP037.CDR
Push-to-Talk (PTT) switch

Figure 2-27: 2-MIC microphone module

Table 2-10: 2-MIC controls and indicators


Item Control Description
1 Phone to Evac switch When pressed, the Phone to Evac switch immediately connects
the firefighter telephone (2-TEL) to the building's evacuation area
through the paging system. The Phone to Evac switch features
an integral LED, which lights when it is active. See Table 2-11
(item 4) for the application of this switch to the 2-TEL.
2 Phone to Alert switch When pressed, the Phone to Alert switch immediately connects
the firefighter telephone (2-TEL) to the building's alert area
through the paging system. The Phone to Alert switch features
an integral LED, which lights when it is active. See Table 2-11
(item 5) for the application of this switch to the 2-TEL.
3 Page to Evac switch When pressed, the Page to Evac switch enables the microphone
and directs its output to the building's evacuation area through
the paging system. The Page to Evac switch features an integral
LED, which lights when it is active.
4 Page to Alert switch When pressed, the Page to ALERT switch enables the
microphone and directs its output to the building's alert area
through the paging system. The Page to ALERT switch features
an integral LED, which lights when it is active.
5 Evac switch When pressed, the Evac switch manually activates the
evacuation signal. The Evac switch features an integral LED,
which lights when it is active. The Evac switch requires manual
activation of the desired evacuation areas on the LED
annunciator/switch modules. See the site-specific instructions for
information on selecting specific areas within your facility.

2.42 EST2 System Operations Manual


Operating panel devices

Table 2-10: 2-MIC controls and indicators


Item Control Description
6 Alert switch When pressed, the Alert switch manually activates the
evacuation signal. The Alert switch features an integral LED,
which lights when it is active. The Alert switch requires manual
activation of the desired alert areas on the LED
annunciator/switch modules. See the site-specific instructions for
information on selecting specific areas within your facility.
7 Microphone Use the microphone to issue a page message. See the paging
procedure below.
8 Push-to-Talk [PTT] When pressed, the PTT switch activates the pre-announcement
switch tone and the microphone. The microphone will not transmit any
messages until the PTT switch has been operated and the pre-
announcement tone has ended.

Note: The mode setting of the 2-AAC will affect the operation
of the 2-MIC. See the 2-AAC installation sheet.

To issue a page message:

1. Remove the microphone from its bracket.


2. Hold the microphone near your mouth and press the PTT
switch.
3. When the pre-announcement tone ends, speak.

EST2 System Operations Manual 2.43


Operating panel devices

Operating the 2-TEL

Telephone handset

2-MIC controls

PHONE TO EVAC
PHONE TO ALERT

STDOP036.CDR

SILENCE CALL IN PHONE CALL IN SILENCED

Figure 2-28: 2-TEL telephone module

Table 2-11: 2-TEL controls and indicators


Item Control/Indicator Description
1 Master handset The master handset provides two-way communication for
firefighter telephones located throughout the facility. Replace the
handset on the hook when not in use.
2 Silence Call-In switch When pressed, the Silence Call In switch turns off the internal
call-in buzzer. Any attempt to call the master handset from a
remote firefighter telephone will sound the buzzer.
3 Phone Call-In When lit, the Phone Call In Silenced LED indicates that someone
Silenced LED pressed the Silence Call-in switch to silence the internal call-in
buzzer.
4 Phone to Evac switch The Phone To Evac switch is a part of the 2-MIC. Use this switch
with the 2-TEL to page the evacuation area. See the description
in Table 2-10 (item 1).
5 Phone to Alert switch The Phone To Alert switch is a part of the 2-MIC. Use this switch
with the 2-TEL to page the alert area. See the description in
Table 2-10 (item 2).

2.44 EST2 System Operations Manual


Operating panel devices

Recording voice messages


The SIGA-MDM is a digital message module, which provides
up to two voice quality audio messages. Each message lasts for
up to 30 seconds. The SIGA-MDM can function as a standalone
audio source or in conjunction with the 2-AAC.

TOP

1 NORMAL
Message select switch MSG Normal LED
2
SDC
Active LED
ACTIVE
Clip LED CLIP

MIC. Record LED


MIC/Line switch
LINE
REC.
Record switch
MIC./LINE

MIC/Line jack Play LED

IN PLAY
HEAD
Play switch

Headphonet jack
PHONES

STDOP042.CDR

Figure 2-29: SIGA-MDM Digital Message Module

Table 2-12: Indicators


LED Description
Clip The Clip LED flashes while you record a message to indicate that its amplitude
is exceeding the recording level. The SIGA-MDM is clipping the audio spike to
hold the message's amplitude down. The Clip LED should flash only
occasionally.
Normal The Normal LED, when lit, indicates that the SIGA-MDM is communicating with
the Signature Loop Controller.
Active The Active LED, when lit, indicates that the SIGA-MDM is playing a message.
Record The Record LED, when lit, indicates that the SIGA-MDM is recording and how
much time remains.
Play The Play LED, when lit, indicates that the SIGA-MDM is in the playback mode.

EST2 System Operations Manual 2.45


Operating panel devices

Table 2-13: SIGA-MDM Controls


Switch Description
Message select The Message Select switch, when toggled, selects the message for recording
and playback.
MIC/Line select The MIC/Line switch, when toggled, sets the audio input jack signal level.
Record The Record switch, when pressed, turns the recording function on and off.
Play The play switch, when pressed, turns the play function on and off.

Table 2-14: SIGA-MDM Jacks


Jacks Description
MIC/Line in The MIC/Line jack accepts the microphone or remote source for recording.
Head phones The Head Phones jack accepts the headphones for playback.

2.46 EST2 System Operations Manual


Chapter 3
Operating remote devices

Summary
Chapter 3 discusses the indicators and controls of remote
annunciators.

Content
Operating remote alphanumeric annunciators • 3.2
2-SMDN(-C) • 3.2
2-CMDN(-C) • 3.3
2-LSRA(-C) • 3.4
Controls and indicators • 3.5
Reading LCD messages • 3.8
Reading and operating SAN annunciators • 3.9
2-SANCOM • 3.9
SLU-16 • 3.11
SWU-8 • 3.11
SWU-8/3 • 3.12
SHO-4 • 3.13
ISP-96 • 3.14
Selecting system functions on SAN annunciators • 3.15
SAN-MIC II • 3.16

EST2 System Operations Manual 3.1


Operating remote devices

Operating remote alphanumeric annunciators


2-SMDN(-C)
Figure 3-1 shows the 2-SMDN and the 2-SMDN-C. The
2-SMDN offers only the ability to acknowledge and review
messages. The 2-SMDN-C also features indicators and operator
input switches.

Liquid Liquid
Crystal Crystal
Display Display
SYSTEM ANNUNCIATOR SYSTEM ANNUNCIATOR

Status NORMAL BACK NEXT/ACK NORMAL BACK NEXT/ACK


ALARM Status ALARM
LEDs SUPERVISORY SUPERVISORY
LEDs
TROUBLE TROUBLE

RESET
ALARM DISABLE
Operator SILENCE
control TROUBLE
switches SILENCE ENABLE
DRILL/
ALL CALL

STDOP013.CDR

BACK NEXT/ BACK NEXT/ Enable


switch ACK switch ACK Disable
switch switch
switch

Figure 3-1: 2-SMDN (left), 2-SMDN-C (right)

3.2 EST2 System Operations Manual


Operating remote devices

2-CMDN(-C)
Figure 3-2 shows the 2-CMDN-C and the 2-CMDN. The
2-CMDN offers only the ability to acknowledge and review
messages. The 2-CMDN-C also features indicators and operator
input switches.

Liquid Liquid
Status Crystal Status Crystal
LEDs Display LEDs Display

SYSTEM ANNUNCIATOR SYSTEM ANNUNCIATOR

NORMAL BACK NEXT/ACK NORMAL BACK NEXT/ACK


ALARM ALARM
SUPERVISORY SUPERVISORY
TROUBLE TROUBLE

RESET
ALARM DISABLE
SILENCE
TROUBLE
SILENCE ENABLE
DRILL/
ALL CALL

STDOP012.CDR

BACK NEXT/ Operator BACK NEXT/ Enable


switch ACK control switch ACK Disable
switch switches switch switch

Figure 3-2: 2-CMDN (left), 2-CMDN-C (right)

EST2 System Operations Manual 3.3


Operating remote devices

2-LSRA(-C)
Figure 3-3 shows the 2-LSRA and the 2-LSRA-C. The 2-LSRA
offers only the ability to acknowledge and review messages. The
2-LSRA-C also features indicators and operator input switches.

Liquid
Crystal
Display

Life Safety Remote Annunciator

NORMAL
Status ALARM BACK NEXT/ACK
LEDs SUPERVISORY
TROUBLE

BACK switch NEXT/ACK switch

Liquid RESET
Crystal
1
Display
ALARM
Life Safety Remote Annunciator 2 SILENCE
Operator
NORMAL TROUBLE Control
Status ALARM BACK NEXT/ACK 3 SILENCE Switches
LEDs SUPERVISORY
TROUBLE DRILL/
4 ALL CALL

STDOP014.CDR

BACK switch NEXT/ACK switch

Figure 3-3: 2-LSRA (top), 2-LSRA-C (bottom)

3.4 EST2 System Operations Manual


Operating remote devices

Controls and indicators

Table 3-1: Remote alphanumeric annunciator controls


Control Availability Description
Next/Ack switch 2-SMDN-C The Next/Ack switch, when pressed, acknowledges the
2-SMDN receipt of new messages at the remote alphanumeric
2-CMDN-C annunciator and automatically advances to the next
2-CMDN unacknowledged message.
2-LSRA-C
When there are no unacknowledged messages, the
2-LSRA
Next/Ack switch may be used to scroll forward through
the review buffer. The review buffer only displays active
points. A point will not appear in the review buffer if it
becomes active and restores.
Back switch 2-SMDN-C The Back switch, when pressed, scrolls in reverse
2-SMDN through the review buffer. Press the Back and Next/Ack
2-CMDN-C switches simultaneously to clear the LCD after the
2-CMDN acknowledgement of every message.
2-LSRA-C
2-LSRA
Enable/Disable switch 2-SMDN-C The Enable/Disable switch requires a key. Depending on
2-CMDN-C which position you turn the key to, and the way the
switch is configured, it can enable or disable any
combination of the front panel Reset, Alarm Silence,
Trouble Silence, and Drill switches.
Reset switch 2-SMDN-C The Reset switch, when pressed, directs the control
2-CMDN-C panel to issue a system-wide reset command after all
2-LSRA-C system wide-status points have been acknowledged.
Alarm Silence switch 2-SMDN-C The Alarm Silence switch, when pressed, directs the
2-CMDN-C control panel to issue a system-wide alarm silence
2-LSRA-C command. Operating the Alarm Silence switch
generates a trouble LED on the display and activates the
internal trouble buzzer. Pressing the Alarm Silence and
Local Silence switches simultaneously starts a 15
second LED test sequence.
Trouble Silence switch 2-SMDN-C The Trouble Silence switch, when pressed, silences the
2-CMDN-C local trouble buzzer after all messages have been
2-LSRA-C acknowledged. This is a system-wide function.
Drill/ All Call switch 2-SMDN-C The Drill/ All Call switch, when pressed, directs the
2-CMDN-C control panel to issue a drill command.
2-LSRA-C

Note: You do not have to acknowledge messages at the remote


alphanumeric annunciators. You can acknowledge the message
at the control panel. The system automatically acknowledges and
silences any message through the Local Silence switch. Upon the
acknowledgment of the message, the control panel will restore
the remote alphanumeric annunciators.

EST2 System Operations Manual 3.5


Operating remote devices

Table 3-2: Remote alphanumeric annunciator indicators


Event Indication Regional patterns Availability Notes
USA/Canada Europe
Normal operations Green Steady Steady 2-SMDN-C Indicates that
LED 2-SMDN the system has
2-CMDN-C no faults or off-
2-CMDN normal
2-LSRA-C conditions.
2-LSRA
Alarm condition Red Steady Steady 2-SMDN-C Indicates that
LED 2-SMDN the system has
2-CMDN-C detected a fire
2-CMDN alarm condition.
2-LSRA-C
2-LSRA
Trouble condition Amber Steady Steady 2-SMDN-C Indicates that
LED 2-SMDN some portion of
2-CMDN-C the system is off-
2-CMDN normal, and may
2-LSRA-C degrade the
2-LSRA system's
operation.
Supervisory Amber Steady Steady 2-SMDN-C Indicates that a
condition LED 2-SMDN fire protection
2-CMDN-C system other
2-CMDN than the fire
2-LSRA-C alarm panel is
2-LSRA off-normal.
Closed sprinkler
valves and
disabled
supplementary
fire extinguishing
systems may
cause
supervisory
conditions.
Unacknowledged Internal Pulses Pulses 2-SMDN-C The operator
message buzzer 2-SMDN must
2-CMDN-C acknowledge all
2-CMDN messages to
2-LSRA-C silence the
2-LSRA buzzer.

3.6 EST2 System Operations Manual


Operating remote devices

Table 3-2: Remote alphanumeric annunciator indicators


Event Indication Regional patterns Availability Notes
USA/Canada Europe
Trouble Internal Pulses Steady 2-SMDN-C In Europe, the
buzzer 2-SMDN buzzer will pulse
2-CMDN-C steadily until an
2-CMDN operator
2-LSRA-C silences it. When
2-LSRA the buzzer is
silenced, it will
generate a half-
second pulse
every 14
seconds as a
reminder of the
trouble
condition.
Alarm silence Amber Flash Flash 2-SMDN-C The Alarm
LED 2-CMDN-C Silence LED
2-LSRA-C lights when the
system-wide
alarm silence
function has
been initiated.
Trouble or Amber Flash Flash 2-SMDN-C The Trouble
supervisory LED 2-CMDN-C Silence LED
condition silence 2-LSRA-C lights when the
system-wide
trouble silence
function has
been initiated.
2-SMDN,
2-CMDN, and
2-LSRA buzzers
sound only for
unacknowledged
messages.
Drill/all call test Amber Flash Flash 2-SMDN-C The Drill LED
LED 2-CMDN-C lights when the
2-LSRA-C system-wide
drill/all call
function has
been initiated.

EST2 System Operations Manual 3.7


Operating remote devices

Reading LCD messages


The 2-CMDN(-C), the 2-SMDN(-C), and the 2-LSRA(-C)
feature a liquid crystal display (LCD). The LCD turns off after 4
minutes of inactivity to save power. Any change of state, off-
normal condition, or front panel switch activation will turn on
the LCD's back-lighting. The system's main controller module
automatically updates time and date information. The LCD does
not display point address information unless the system
programmer includes it as part of the message.
Figure 3-4 illustrates an LCD with no messages pending. The
fire alarm system has no problems at the moment of the display.
In Figure 3-5, however, the LCD indicates a trouble condition
for a Signature series device in the Janitor’s closet.

Current date Current time

JAN 03 11:15:44

STDOP040.CDR

Figure 3-4: LCD during normal conditions

Current date Current time

JAN 03 11:15:44
Condition TROUBLE
LOWER LOBBY Message line 1
JANITOR CLOSET Message line 2

STDOP041.CDR

Figure 3-5: Sample alarm message on the LCD

3.8 EST2 System Operations Manual


Operating remote devices

Reading and operating SAN annunciators


SAN annunciators provide point status indication and switching
functions at a location remote from the fire alarm control panel.
Each SAN annunciator requires a SAN-CPU. This section
discusses the indicators and controls of the following SAN
annunciators:
• 2-SANCOM
• SLU-16
• SWU-8(/3)
• SHO-4
• ISP-96(-2 or -3)

2-SANCOM
The 2-SANCOM Remote Network Control module provides
basic network indicators and controls in a SAN series package.

POWER
ALARM
SUPERVISORY
TROUBLE
SECURITY

RESET

ALARM
SILENCE

TROUBLE
SILENCE

DRILL

LAMP TEST

DISABLE

ENABLE

STDOP015.CDR

Figure 3-6: 2-SANCOM

EST2 System Operations Manual 3.9


Operating remote devices

Table 3-3: 2-SANCOM indicators


Indicator Description
Power LED The Power LED, when lit, indicates that the system has no faults or off-
normal conditions.
Alarm LED The Alarm LED, when lit, indicates that the system has detected a fire
alarm condition.
Supervisory LED The Supervisory LED, when lit, indicates that a fire protection system
other than the fire alarm panel is off-normal.
Trouble LED The trouble LED, when lit, indicates that some portion of the system is
off-normal, and may degrade the system's operation.
Alarm Silence LED The Alarm Silence LED lights when the system-wide alarm silence
function has been initiated.
Trouble Silence LED The Trouble Silence LED lights when the system-wide trouble silence
function has been initiated.
Drill LED The Drill LED lights when the system-wide drill/ all call function has been
initiated.
Security LED The Security LED, when lit, indicates a security condition.
Trouble buzzer Operates on system trouble, and when the trouble silence is in the off-
normal position when no trouble exists on the system

Table 3-4: 2-SANCOM controls


Control Description
Reset switch The Reset switch, when toggled, directs the control panel to issue a
system-wide reset command after all the system wide-status points have
been acknowledged.
Alarm Silence switch The Alarm Silence switch, when toggled, directs the control panel to
issue a system-wide alarm silence command. Operating the Alarm
Silence switch lights the Trouble LED on the 2-LCD and activates the
internal trouble buzzer. Toggling the Alarm Silence and Local Silence
switches simultaneously starts a 15-second LED test sequence.
Trouble Silence The Trouble Silence switch, when toggled, silences the local trouble
switch buzzer after all messages have been acknowledged. This is a system-
wide function.
Drill/All Call switch The Drill/All Call switch, when toggled, directs the control panel to issue
a drill command.
Enable/Disable The Enable/Disable switch requires a key. Depending on which position
switch you turn the key to, and the way the switch is configured, it can enable or
disable any combination of the front panel Reset, Alarm Silence, Trouble
Silence, and Drill switches.
Lamp Test switch The Lamp Test, when toggled, tests all the 2-SANCOM indicators.

3.10 EST2 System Operations Manual


Operating remote devices

SLU-16
The SLU-16 Remote Annunciator Lamp module has 16 LEDs
for remote annunciator applications when using the SAN-CPU.
The system software individually controls all LEDs and
switches. When a pre-defined input exists on the system, the
appropriate LED will illuminate to report the condition.

Model Description
SLU-16R 16 red LEDs
SLU-16Y 16 yellow LEDs
SLU-16R/Y 8 red LEDs/8 yellow LEDs

STDOP017.CDR

Figure 3-7: SLU-16SWU-8(/3)

SWU-8
The SWU-8 consists of 8 two-position toggle switches and 16
red or yellow LEDs. Each switch forms a distinct functional
group with two independently programmed LEDs. Placing a
switch in the up position generates an active (off normal)
condition. The down position is the normal state.
In a typical firefighter telephone application using the SWU-8,
the upper switch position selects an incoming call; the lower
switch position places the circuit to normal or off-line operation.
One of the associated LEDs indicates the circuit calling in; the
other LED indicates that the circuit has been connected to the
master handset.

EST2 System Operations Manual 3.11


Operating remote devices

Each Switch/LED group consists of a switch


and two LEDs

Slip-in label protector

Two-position toggle switches on


an SWU-8 or three-position
toggle switches on an SWU-8/3

STDOP016.CDR

Figure 3-8: SWU-8(/3)

SWU-8/3
The SWU-8/3 consists of 8 three-position toggle switches and 16
red or yellow LEDs. Each switch forms a distinct functional
group with two independently programmed LEDs. Placing a
switch in the up or down positions generates one of two active
(off-normal) conditions. The center position is the normal state.
In a typical HVAC application, the SWU-8/3 switches may be
used as hands off automatic (HOA) controls to override the
automatic operation of the system. The two associated LEDs
may be programmed to indicate the status of Run/Stop contacts,
fans or dampers with limit switches, etc.
In typical audio evacuation application using the SWU-8/3, the
upper switch position initiates circuit paging. The center switch
position allows normal/automatic control mode of the speaker
circuit. The LEDs indicate the active condition of the speaker
circuit.

3.12 EST2 System Operations Manual


Operating remote devices

SHO-4
The SHO-4 module provides 4 three-position rotary switches and
12 LEDs for remote switching and annunciator applications.
Two yellow LEDs and one green LED are positioned next to
each switch. The yellow LEDs operate independent of the
switches, which the system program controls. The green LED
illuminates when the switch is in the center position. Typical
applications include Hand-Off-Automatic (HOA) control and the
override of automatic systems.
The SHO-4 switches activate control fans, dampers, etc. The
center switch position is the automatic operational position. The
switch, in the center position, lights the green LED to show that
the HVAC system is using its normal control cycle.
In a typical program, the upper switch position forces the device
to turn on through a control module or zone. The lower switch
position forces the device to turn off again. Status zones
connected to vane or limit switches, contractor status switches,
etc. activate the upper and lower LEDs to indicate a device's
status.

LED/switch group

Slip-in label protector

STDOP018.CDR

Figure 3-9: SHO-4 Remote annunciator lamp and switch module

EST2 System Operations Manual 3.13


Operating remote devices

ISP-96
The ISP-96 annunciator/switch panels mount to a 19-inch rack.
Forty-eight switches provide manual control of system functions.
Each switch has two associated LEDs to indicate the status of the
function or the system. All LEDs and switches are independently
programmed and controlled. Typical uses include HVAC
control, firefighter telephone circuits, audio evacuation, and
paging systems. Two ISP-96 models are available: the ISP-96-2
and the ISP-96-3.

STDOP019.CDR

Figure 3-10: ISP-96

ISP-96-2
The ISP-96-2 provides 48 switch/LED groups consisting of a
two- position toggle switch and two amber LEDs. Placing a
switch in the up position generates an active (off normal)
condition. The down position is the normal state.
In a typical firefighter telephone application using the ISP-96,
the upper switch position selects an incoming call; the lower
switch position places the circuit to normal or off-line operation.
One of the associated LEDs indicates the circuit calling in; the
other LED indicates that the circuit has been connected to the
master handset.

ISP-96-3
The ISP-96-3 provides 48 switch/LED groups consisting of a
three-position toggle switch and two amber LEDs. Placing a
switch in the up or down positions generates one of two active
(off-normal) conditions. The center position is the normal state.
In a typical HVAC application, the ISP-96-3 switches may be
used as HOA controls to override the automatic operation of the
system. The two associated LEDs may be programmed to
indicate the status of Run/Stop contacts, fans or dampers with
limit switches, etc.
In typical audio evacuation system application using the
ISP-96-3, the upper switch position initiates circuit paging. The
center switch position allows normal/automatic control mode of

3.14 EST2 System Operations Manual


Operating remote devices

the speaker circuit. The LEDs indicate the active condition of the
speaker circuit.

Selecting system functions on SAN annunciators


The SWU-8 and the ISP-96 series annunciators provide two-
position and three-position toggle switch options. The SHO-4
provides three-position rotary switches. Apart from operator
intervention the SAN annunciators will allow the system to
function automatically. During off-normal conditions, however,
the operator has the option of toggling or turning switches to
activate programmed functions or override normal system
functions.
Each three-position toggle switch has two LEDs. When the
switch is in the center position, the system will function
automatically and keep both LEDs off. When an operator toggles
the switch up or down, it will activate a programmed function,
and turn on the appropriate LED.
The three-position rotary switch is like the three-position toggle
switch, but it has a third LED. When the switch is in the center
position the system will function automatically and turn on the
center LED. The upper and lower LEDs operate independent of
the switch.
The two-position toggle switch has two LEDs. When the switch
is down the system will function automatically. When an
operator toggles the switch up, it will activate a programmed
function and turn on the upper LED.

EST2 System Operations Manual 3.15


Operating remote devices

Three-position toggle switch: SWU-8/3 and ISP-96-3

Programmed
function
Automatic
system
function

Programmed
function

Three-position rotary switch: SHO-4

Programmed
function
Automatic
system
function

Programmed
function

Two-position toggle switch: SWU-8 and ISP-96-2


LED indications
Programmed
function LED is off:

LED is on:
Automatic
system
function STDOP020.CDR

Figure 3-11: SAN annunciator switch positions

SAN-MIC II
The SAN-MIC II module is a supervised microphone and tone
generator capable of operation remotely from the audio power
amplifier. The SAN-MIC II provides a pre-amp level signal,
which may be transmitted over 2,000 feet of shielded cable. In
addition, the SAN-MIC II provides a PTT Dynamic Microphone,
three tone generators, auxiliary audio input, solid state VU
meter, and a supervisory pulse generator.

3.16 EST2 System Operations Manual


Operating remote devices

Emergency tone select positions


Push to talk switch (PTT)

Emergency tone 1
Microphone handset

VU meter
Normal

Emergency tone select switch


Slip-in
label
Fire tone switch protector
Emergency tone 2
INST053.CDR

*
Figure 3-12: SAN-MIC II and emergency tone select positions

In the normal state, the SAN-MIC II generates a supervisory pulse


tone for supervision of the audio wiring and circuitry.

Switches
The Fire Tone switch sends the jumper-defined alarm tone to the
module output terminals as long as the Emergency Tone Select
switch is in the normal position. The Auxiliary Input overrides the
Fire Tone. The Speaker Select relay closes upon the activation of
the Fire Tone switch.
The Emergency Tone Select switch sends the jumper-defined
emergency tone 1 or emergency tone 2 to the module output
terminals as long as the microphone is not in active operation. The
auxiliary input overrides the emergency tones. The activation of
the Emergency Tone switch also closes the speaker select relay.
The Microphone PTT sends the microphone output to the module
output terminals, and overrides all tone generators. The auxiliary
input overrides the all microphone tones. The activation of the
microphone PTT closes the speaker select relay.

VU meter
The VU meter is a row of LEDs that form a bar graph to indicate
the input level from the microphone. The amplitude of your voice
determines the microphone's input level. If the bar graph does not
light up when you talk, you may not be talking loud enough. If the
bar graph runs all the way to the left, you are talking too loud. The
ideal indication on the VU meter is a bar graph that runs to the
middle.

EST2 System Operations Manual 3.17


Operating remote devices

VU Meter

Low input level

VU Meter

Optimal input level

VU Meter

High input level

STDOP044.CDR

Figure 3-13: SAN-MIC II VU meter

3.18 EST2 System Operations Manual


Appendix A
Operator instructions

Summary
Appendix A presents the procedure for filling out and posting
operator instructions for fire alarm control panels.

Content
Posting operator instructions • A.2

EST2 System Operations Manual A.1


Operator instructions

Posting operator instructions


The following pages feature two sets of operator instructions.
The first set of instructions (Figure A-1) outlines the procedures
for operating the fire alarm panel without emergency
communications equipment.
The second set of instructions (Figure A-2) provides the
procedures for operating the fire alarm control panel with
emergency communications equipment.

To post operator instructions:

1. Photocopy the master set of operator instructions.


2. Write down the location of control panel in the space
provided at the top of the form.
3. Frame the operator instructions.
4. Mount the operator instructions next to the control panel.

A.2 EST2 System Operations Manual


Operator instructions

Fire Alarm Control Panel Operating Instructions

Installed By: Location:

Normal Condition: The Power LED (green) is on. All other LEDs are off.
Alarm Condition: The Alarm LED (red) turns on, the display shows the alarm location
Per NFPA Standard: and zone, and the internal buzzer pulses.
To view other alarm messages: Press the ALARM review switch (down arrow).
72, Ch 3 - Local To silence audible devices: Press the Alarm Silence switch.
72, Ch 4 - Auxiliary To reset the system: Find the cause of the alarm condition, correct it, and press the
Reset switch.
72, Ch 4 - Remote Sta.
Note: Each new alarm will resound the audible devices, but you cannot resound
72, Ch 4 - Proprietary them by pressing the Alarm Silence switch a second time.
72, Ch 4 - Central Sta. Supervisory Condition: The Supervisory LED (yellow) turns on, the display shows the
supervisory condition, location, and zone, and the internal buzzer pulses.
Dated: To view other supervisory messages: Press the SUPVR review switch (down arrow).
To silence buzzer: Press Local Silence switch.
For Service Contact: To clear the system: Find the cause of supervisory condition, correct it, and p ress
the Reset switch.
Trouble Condition: The system Trouble LED (yellow) turns on, the display shows the
trouble location and zone, and the internal buzzer pulses.
To view other trouble messages: Press the TRBLE review switch (down arrow).
To silence the buzzer: Press the Local Silence switch.
To clear the system: Find the cause of the trouble and correct it. The system
automatically clears itself upon correction of trouble condition.
Inspected By: Monitor Condition: The Monitor LED (yellow) turns on, the display shows monitor
conditions, and the internal buzzer pulses during a non-fire alarm condition.
To view other monitor conditions: Press the MONTR review switch ( down arrow).
To clear system: The system automatically clears itself upon restoration of monitor
condition.
Fire Drill: Notify the fire department before you run the test. All audible and visual
Date: notification appliances will operate during a drill.
To drill all notification appliances: Press the Drill switch.
Power Supply: To end the drill: Press the Drill switch a second time, or press Alarm Silence.
Primary Frame these instructions and mount them next to the fire alarm control panel. For
Location additional information, See the System Operations Manual.

Fuses
Secondary
Type
Specs.
STDOP007.CDR

Figure A-1: Fire alarm control panel operating instructions

EST2 System Operations Manual A.3


Operator instructions

Emergency Communications Operating Instructions

Installed By: Location:


Normal Condition: The Power LED (green) is on. All other LEDs are off.
Alarm Condition: The Alarm LED (red) turns on, the display shows the alarm location
and zone, and the internal buzzer pulses.
To view other alarm messages: Press the ALARM review switch (down arrow).
To silence audible devices: Press the Alarm Silence switch.
To reset the system: Find the cause of alarm condition correct it, and press the
Reset switch.
Per NFPA Standard: Note: Each new alarm will resound the audible devices, but you cannot resound
72, Ch 3 - Local them by pressing the Alarm Silence switch a second time.

72, Ch 4 - Auxiliary Supervisory Condition: The Supervisory LED (yellow) turns on, the display shows the
supervisory condition, location, and zone, and the internal buzzer pulses.
72, Ch 4 - Remote Sta.
To view other supervisory messages: Press the SUPVR review switch (down arrow).
72, Ch 4 - Proprietary To silence buzzer: Press Local Silence switch. Investigate the cause.
To clear the system: Find the cause of the supervisory condition, correct it, and press
72, Ch 4 - Central Sta. the Reset switch.
Dated: Trouble Condition: The system Trouble LED (yellow) turns on, the display shows the
trouble location and zone, and the internal buzzer pulses.
To view other trouble messages: Press the TRBLE review switch (down arrow).
To silence the buzzer: Press the Local Silence switch.
For Service Contact: To clear the system: Find the cause of the trouble and correct it. The system
automatically clears itself upon correction of trouble condition.
Monitor Condition: The Monitor LED (yellow) turns on, the display shows monitor
conditions, and the internal buzzer pulses during a non-fire alarm condition.
To view other monitor conditions: Press the MONTR review switch ( down arrow).
To clear system: The system automatically clears itself upon restoration of monitor
condition.

Inspected By: Fire Drill: Notify the fire department before you run the test. All audible and visual
notification appliances will operate during a drill.
To drill all notification appliances: Press the Drill switch.
To end the drill: Press the Drill switch a second time, or press Alarm Silence.
Microphone Operation:
To page the fire area:
1 Pick up the microphone handset.
2 Press the Page-to-Evac switch.
Date: 3 Press the Push-to-Talk (PTT) switch on the microphone.
4 When the pre-announcement tone ends, speak into the microphone.
To page the alert area:
Power Supply: 1 Pick up the microphone handset.
2 Press Page-to-Alert switch.
3 Press the PTT switch on the microphone.
4 When the pre-announcement tone ends, speak.
Primary
Telephone Operation: The buzzer indicates an incoming call.
Location To respond to an incoming call:
1 Pick up the telephone handset.
Fuses 2 Press the Silence Call-In switch.
3 Select the incoming phone circuit on the LED/Switch module.
Secondary 4 Communicate with the calling party.
To page by phone:
Type
1 Pick up the telephone handset.
2 Press the Phone-to-Evac (or Alert) switch.
Specs. 3 When the pre-announcement tone ends, speak.
Frame these instructions and mount them next to the emergency communications panel.
For additional information, see the System Operations Manual.
STDOP008.CDR

Figure A-2: Emergency communications operating instructions

A.4 EST2 System Operations Manual


Z
Index

2 Com1 indication • 2.18


communicating with firefighters. See master handset, 2-
2-CMDN(-C) • 3.3, 3.5–3.8 TEL
2-LCD communication classes • 2.23
control switches • 2.4–2.5 computers, laptop
function switches • 2.7, 2.16–2.39 disabling of • 2.30
keypad • 2.6 enabling of • 2.27
LEDs • 2.4 conditions, trouble • 2.12
message review switches • 2.5 control switches, 2-LCD • 2.4–2.5
2-LSRA(-C) • 3.4, 3.5–3.8 controls. See under switches
2-MIC • 2.42–2.43 CPU
2-SANCOM • 3.9–3.10 failure indication • 2.4
2-SMDN(-C) • 3.2, 3.5–3.8 restarting of • 2.24
2-TEL • 2.44
D
A
date, system • 2.22
accessing the system status menu • 2.16 devices, disabled • 2.19–2.21
ACp1 indication • 2.17 Dia1 indication • 2.17
actions digital message module. See SIGA-MDM
activation of • 2.31 disabling system functions. See under actions; laptop
disabling of • 2.29 computers; mapping; messages; panel addresses;
enabling of • 2.26 RS-485 channels; sequences; time controls; zones
restoration of • 2.33 displays, 2-LCD
activating system devices/functions. See under actions; disabled devices/functions • 2.19–2.21
outputs; sequences; smoke sensitivity levels. See field panel status • 2.18
also LED/switch modules fire alarm message • 2.8
Active LED, SIGA-MDM • 2.45 general status • 2.16
addresses, panel • 2.23 history report • 2.36
alarm silence loop status • 2.17
2-CMDN(-C) • 3.5 reading of • 2.8
2-LCD • 2.5 relay/LED status • 2.19
2-LSRA(-C) • 3.5 sensitivity report • 2.34, 2.35
2-SMDN(-C) • 3.5 displays, 2-LCD (continued)
Alert switch, 2-MIC • 2.43 system status • 2.16
alerting building occupants. See Alert switch, 2-MIC; test screens • 2.38, 2.39
Phone to Alert switch, 2-MIC drill test • 2.15
Ann1 indication • 2.17 duty cycles, LED/switch module • 2.41
annunciators, SAN • 3.9–3.18
autoprogramming. See reconfiguring SLCs
E
B enabling system functions. See under actions; laptop
computers; mapping; messages; panel addresses;
Bal1 indication • 2.18 RS-485 channels; sequences; time controls; zones
Bat1 indication • 2.17 ending the test function • 2.39
buzzers Evac switch, 2-MIC • 2.42
2-CMDN(-C). See trouble silence evacuating building occupants. See Evac switch, 2-
2-LCD. See local silence MIC; Phone to Evac switch, 2-MIC
2-LSRA(-C). See trouble silence
2-SMDN(-C). See trouble silence
2-TEL. See Silence Call-In switch F
fire alarms • 2.11
C firefighter telephone. See 2-TEL
function switches, 2-LCD
canceling commands • 2.41 Activate • 2.31–2.32
changing system passwords • 2.22–2.23 described • 2.7
checking system status. See under status screens, 2- Disable • 2.28–2.30
LCD Enable • 2.25–2.27
Clip LED, SIGA-MDM • 2.45 Program • 2.22–2.24

EST2 System Operations Manual Z.1


Index

Reports • 2.34–2.37 2-LCD • 2.4


Restore • 2.33 2-LSRA(-C) • 3.6–3.7
Status • 2.16–2.21 2-MIC • 2.42
Test • 2.38–2.39 2-SANCOM • 3.10
functions, system 2-SMDN(-C) • 3.6–3.7
activation of. See under actions; outputs; 2-TEL • 2.44
sequences; smoke sensitivity levels. See also front panel • 2.40–2.41
LED/switch modules ISP-96-2 • 3.15–3.16
disabling of. See under actions; laptop computers; ISP-96-3 • 3.15–3.16
mapping; messages; panel addresses; RS-485 PT-1S • 4.2–4.3
channels; sequences; time controls; zones RSAN-PRT • 4.4
enabling of. See under actions; laptop computers; SHO-4 • 3.13, 3.15–3.16
mapping; messages; panel addresses; RS-485 LEDs (light emitting diodes) (continued)
channels; sequences; time controls; zones SIGA-MDM • 2.45
restarting of. See under CPU; history reports; SLC SLU-16 • 3.11
restoration of. See under actions; outputs; SWU-8(/3) • 3.15–3.16
sequences. See also LED/switch modules levels, password • 2.23
testing of • 2.38–2.39 light emitting diodes. See LEDs
viewing of disabled • 2.19–2.21 Lin1 indication • 2.18
liquid crystal display. See LCD messages
local silence • 2.4
G
generating reports • 2.34–2.37 M
Gnd1 indication • 2.17, 2.18
maintenance messages • 2.13
making keypad entries • 2.6–2.7
H Map1 indication • 2.18
head phones, SIGA-MDM • 2.46 mapping
history reports disabling of • 2.30
printing of • 2.37 enabling of • 2.27
restarting of • 2.24 master handset, 2-TEL • 2.44
viewing of • 2.36 menus
Activate • 2.31–2.32
Disable • 2.28–2.30
I Enable • 2.25–2.27
indicators, audible. See buzzers Program • 2.22–2.24
indicators, visual. See LCD; LEDs; VU meter Reports • 2.34–2.37
initiating a drill test • 2.15 Restore • 2.33
instructions, operator Status • 2.16–2.21
emergency communications • A.4 message review switches, 2-LCD • 2.5
fire alarm control panel • A.3 Message select switch, SIGA-MDM • 2.46
ISP-96-2 • 3.14, 3.16 messages
ISP-96-3 • 3.14–3.15, 3.16 disabling of • 2.28
issuing a page message. See Page to Alert switch, 2- enabling of • 2.25
MIC; Page to Evac switch, 2-MIC maintenance • 2.13
priorities of • 2.10
voice • 2.45–2.46
J waiting • 2.8
MIC/Line in, SIGA-MDM • 2.46
jacks, SIGA-MDM • 2.46 MIC/Line select switch, SIGA-MDM • 2.46
microphone module. See 2-MIC
K monitor points • 2.12–2.13
Mpg1 indication • 2.18
keypad, 2-LCD • 2.6 MPw1 indication • 2.17

L N
laptop computers Normal LED, SIGA-MDM • 2.45
disabling of • 2.30
enabling of • 2.27
LCD (liquid crystal display) messages O
2-CMDN(-C) • 3.8 operating switches
2-LCD • 2.8 on LED/switch modules • 2.40–2.41
2-LSRA(-C) • 3.8 on the 2-CMDN(-C) • 3.5
2-SMDN(-C) • 3.8 on the 2-LCD • 2.4–2.5
LED/switch modules • 2.40–2.41 on the 2-LSRA(-C) • 3.5
LEDs (light emitting diodes) on the 2-MIC • 2.42–2.43
2-CMDN(-C) • 3.6–3.7 operating switches (continued)

Z.2 EST2 System Operations Manual


Index

on the 2-SANCOM • 3.10 on the 2-TEL • 2.44


on the 2-SMDN(-C) • 3.5 on the ISP-96-2 • 3.15–3.16
on the 2-TEL • 2.44 on the ISP-96-3 • 3.15–3.16
on the ISP-96-2 • 3.15–3.16 on the PT-1S • 4.2
on the ISP-96-3 • 3.15–3.16 on the RSAN-PRT • 4.4
on the PT-1S • 4.2–4.3 on the SHO-4 • 3.15–3.16
on the RSAN-PRT • 4.4–4.5 on the SIGA-MDM • 2.45
on the SAN-MICII • 3.17 on the SLU-16 • 3.11
on the SHO-4 • 3.15–3.16 on the SWU-8(/3) • 3.15–3.16
on the SIGA-MDM • 2.46 reading the VU meters • 3.17–3.18
on the SWU-8(/3) • 3.15–3.16 reconfiguring SLCs • 2.24
operator responses Record LED, SIGA-MDM • 2.45
to fire alarms • 2.11 Record switch, SIGA-MDM • 2.46
to maintenance messages • 2.13 recording voice messages • 2.45
to monitor points • 2.12–2.13 remote alphanumeric annunciators. See 2-CMDN(-C);
to supervisory conditions • 2.11–2.12 2-LSRA(-C); 2-SMDN(-C)
to trouble conditions • 2.12 reports
to verification messages • 2.13–2.14 history • 2.36–2.37
outputs sensitivity • 2.34–2.35
activation of • 2.31 Res1 indication • 2.18
restoration of • 2.33 resetting the panel after a fire alarm • 2.11
responses, operator
to fire alarms • 2.11
P to maintenance messages • 2.13
Page to Alert switch, 2-MIC • 2.42 to monitor points • 2.12–2.13
Page to Evac switch, 2-MIC • 2.42 to supervisory conditions • 2.11–2.12
panel addresses • 2.23 to trouble conditions • 2.12
disabling of • 2.29 to verification messages • 2.13–2.14
enabling of • 2.26 restarting system devices/functions. See under CPU;
passwords, system • 2.22–2.23 history reports; SLC
Phone Call-In Silenced LED, 2-TEL • 2.44 restoring system functions. See under actions; outputs;
Phone to Alert switch, 2-MIC • 2.42, 2.44 sequences. See also LED/switch modules
Phone to Evac switch, 2-MIC • 2.42, 2.44 RS-485 channels
Play LED, SIGA-MDM • 2.45 disabling of • 2.29
Play switch, SIGA-MDM • 2.46 enabling of • 2.26
playing voice messages • 2.46 RSAN-PRT • 4.4–4.5
Prg1 indication • 2.18
printer S
PT-1S • 4.2–4.3
RSAN-PRT • 4.4–4.5 SAN annunciators • 3.9–3.18
printing history reports • 2.37 SAN-MICII • 3.16–3.18
printing sensitivity reports • 2.35 scrolling message review switches • 2.5
priorities, message • 2.10 selecting system functions
privileges, password • 2.23 on SAN annunciators • 3.15–3.16
Prn1 indication • 2.17 on the 2-LCD • 2.7
programming system functions. See changing system selecting voice messages • 2.46
passwords; programming the communications class; sensitivity reports
reconfiguring SLCs; setting the system date; setting printing of • 2.35
the system time. See also under CPU; history viewing of • 2.34–2.35
reports; SLC sequences
programming the communications class • 2.23 activation of • 2.31
PT-1S • 4.2–4.3 disabling of • 2.29
Push-to-Talk switch, 2-MIC • 2.43 enabling of • 2.26
restoration of • 2.33
setting the SIGA-MDM signal level. See MIC/Line select
R switch, SIGA-MDM
reading 2-CMDN(-C) messages • 3.8 setting the system date • 2.22
reading 2-LCD messages • 2.8–2.9 setting the system time • 2.22
reading 2-LSRA(-C) messages • 3.8 SHO-4 • 3.13
reading 2-SMDN(-C) messages • 3.8 SIGA-MDM • 2.45–2.46
reading LEDs Signature loop controller. See SLC
on LED/switch modules • 2.40 Silence Call-In switch, 2-TEL • 2.44
on the 2-CMDN(-C) • 3.6–3.7 silencing buzzers
on the 2-LCD • 2.4 2-CMDN(-C). See trouble silence
on the 2-LSRA(-C) • 3.6–3.7 2-LCD. See local silence
on the 2-MIC • 2.42–2.43 2-LSRA(-C). See trouble silence
on the 2-SANCOM • 3.10 2-SMDN(-C). See trouble silence
on the 2-SMDN(-C) • 3.6–3.7 2-TEL. See Silence Call-In switch

EST2 System Operations Manual Z.3


Index

silencing NACs • See under alarm silence Test • 2.38


SLC (Signature Loop Controller) user-defined • 2.5
reconfiguring of • 2.24 SWU-8 • 3.11–3.12
restarting of • 2.24 SWU-8/3 • 3.12
SLU-16 • 3.11
smoke sensitivity levels
activation of • 2.32
T
viewing of • 2.35 telephone module. See 2-TEL
SPw1 indication • 2.17 test function
starting the test function • 2.38 ending of • 2.39
status screens, 2-LCD starting of • 2.38
disabled devices/functions • 2.19–2.21 testing system functions • 2.38–2.39
field panel status • 2.18–2.19 time controls
general • 2.16–2.17 disabling of • 2.28
loop • 2.17–2.18 enabling of • 2.25
relay/LED • 2.19 time, system • 2.8, 2.22
supervisory points • 2.11–2.12 trouble conditions • 2.12
switches trouble silence • 3.5
2-CMDN(-C) • 3.5
2-LCD • 2.4–2.5, 2.7, 2.16–2.39
2-LSRA(-C) • 3.5 U
2-SANCOM • 3.10 user-defined switch • 2.5
2-SMDN(-C) • 3.5
2-TEL • 2.44
switches (continued) V
Activate • 2.31
Disable • 2.28 verification messages • 2.13–2.14
Drill • 2.15 viewing 2-LCD screens
Enable • 2.25 on disabled device status • 2.19–2.21
function • 2.7 on field panel status • 2.18–2.19
ISP-96-2 • 3.15–3.16 on general status • 2.16–2.17
ISP-96-3 • 3.15–3.16 on loop status • 2.17–2.18
message review • 2.5 on relay/LED status • 2.19
Program • 2.22 voice messages • 2.45–2.46
PT-1S • 4.2 VU meter, SAN-MICII • 3.18
Reports • 2.34
Restore • 2.33 Z
RSAN-PRT • 4.4
SAN-MICII • 3.17 zones
SHO-4 • 3.13, 3.15 disabling of • 2.28
SIGA-MDM • 2.46 enabling of • 2.25
Status • 2.16–2.21
SWU-8(/3) • 3.15–3.16

Z.4 EST2 System Operations Manual

You might also like