Inv04a-Lhc Detection en
Inv04a-Lhc Detection en
Version : 1
Date : 30/09/2015
Vapour and liquid hydrocarbons
MS/AMO/LA/LOG
Page 1 / 2
MS/AMO/HSEQ-DD
1) EQUIPMENTS AIM :
To detect the presence of combustible gas in the air or the presence of layers of liquid hydrocarbons.
2) STANDARDS OF INSTALLATION :
GS-AMO-SL-029 and STD-AMO-SL-354.
3) CONCERNED INSTALLATIONS :
All liquid hydrocarbon tanks with a storage temperature higher than the flash-point and with
3
operational capacity up to 100 m .
All liquid hydrocarbon tanks with a storage temperature lower than the flash-point and with operational
3
capacity up to than 5.000 m .
All separators of liquid hydrocarbon depots whatever are their capacities.
Sensors are failsafe connected: in case of failure they have to indicate the defect (loss of current,
break in the cable…). Information acquisition could be managed by automate or by a dedicated
station. The minimal action will be audible and visual alarm activation. This equipment will be protected
with an uninterruptible power supply (UPS).
Bund compartment Pump house
Stored products (at the lowest point) (at the lowest point)
Separator
Product with T°C of storage 1 HCL (HK2H type)
1 HCV 1 HCV Into the second last
higher than the flash-point
Product with T°C of storage separator compartment
1 HCL 1 HCL (concrete)
lower than the flash-point
Or into the last separator
Mixed 1 HCV + 1HCL 1 HCV + 1HCL compartment
(prefabricated)
Version : 1
Date : 30/09/2015
Vapour and liquid hydrocarbons
MS/AMO/LA/LOG
Page 2 / 2
MS/AMO/HSEQ-DD
8) DOWNGRADED SITUATION :
HCL DETECTION
Problem on the detector or on the
Increase frequency of rounds – replacement by a HCL detector in stock if
connection between the HCL detector and
available.
the electrical office
The power supply of the HCL detectors has to be automatically secured by a
Failure of site general power supply
generator or UPS (electronic cards have to be protected).
Increase frequency of rounds – replacement by a HCL detector in stock if
Defect of a HCL detector
available.
HCV DETECTION
Problem on the detector or on the
Increase frequency of rounds and implementation of a mobile detector (reload
connection between the HCV detector and
it regularly and alternate with another mobile detector).
the electrical office
The power supply of the HCV detectors has to be automatically secured by a
Failure of site general power supply
generator or an inverter (electronic cards have to be protected).
Increase frequency of rounds and implementation of a mobile detector (reload
Defect of a HCV detector it regularly and alternate with another mobile detector). Replacement if
possible with another HCV detector.