Test
Test
TRANSFORMER ACTION
is the action that creates the emf.
PRIMARY COIL
is the coil that’s connected to the primary source of supply or
takes electrical energy from AC source of supply.
SECONDARY COIL
is the coil which the voltage of mutual induction is induced and
which “feeds” energy to the load. It received energy by
electromagnetic induction and deliver to loads.
Note:
• both induced emf’s are created by the same mutual flux.
• coils are form wound and are of the cylindrical type. The
general form of this coils maybe circular or oval. In small type
size core type transformer, “a simple rectangular core is used
with cylindrical coils which are either circular or rectangular in
form. “but for large size core type transformer” round or
circular cylindrical coils are used.
Where:
Eav – average induced emf in coil.
ŋ– number of turns in coils.
Ф – maximum flux
t – time for flux to change by Ф m (mxwell)
Note:
electrical energy can be transformed by:
I₁ I₂
Vg Ep Es VL
Where:
Where:
Np / Ns = turns ratio
Ip / Is = current ratio
a = transformer ratio
Where:
Zp / Zs = impedence ratio
Ep = voltage induced in primary winding
Es = voltage induced in secondary winding
• Additive Polarity
• Subtractive Polarity
Example:
The 2,300 volt primary winding of a 60-cycle transformer has
4,800 turns. Calculate: (a) the mutual flux; (b) the number of
turns in the 230-volt secondary winding.
Given:
Ep = 2,300v F = 60 hz
Np = 4,800
Solution:
a.)
b.)
Example:
the maximum flux in the core of a 60-cycle transformer that
has 1,320 primary turns and 46 secondary turns is 3.76 x
maxwells. Calculate the primary and secondary induced
voltages.
Calculate Ep and Es
Solution:
Example:
the secondary winding of a 4,600/230-volt transformer has 36
turns. How many turns are there in the primary winding?
Given:
Vp = 4,600 v Vs = 230 v Ns = 36 turn
Solution:
Example:
The volts per turn in a 25-cycle 2,400/230-volts transformer is
8. calculate: (a) the primary and secondary turns; (b) the
maximum flux in the core.
Given:
Vp = 2,400 v Vs = 230 v
Solution:
a.)
b.)
VOLTAGE AND CURRENT RATIO:
Solution:
Example:
The primary and secondary currents of a transformer were
measured and found to be 3.8 and 152 amp, respectively. If
the secondary load voltage is 116 volts, what is the primary
emf?
Solution:
Transformation Ratio:
The ratio of primary to secondary turns Np:Ns, which equals
the ratio of primary to secondary induced voltages Ep:Es,
indicates how much the primary voltage is lowered or raised.
The turn ratio, or the induced-voltage ratio, is called the ratio
of transformation, and is represented by the symbol a. thus
Where the no-load and full load voltages and are those
measured at the secondary terminals.
Equivalent Resistance, Reactance and Impedance.
} in secondary terms
} in primary terms
SEATWORK
Example 1
A 25-kva 2,300/230-volt distribution transformer has the following
resistance and leakage-reactance values: Rp = 0.8; Xp = 3.2; Rs =
0.009; Xs = 0.03. calculate the equivalent values of resistance,
reactance and impedance; (a) in secondary terms; (b) in primary
terms.
Example 2
A 25-kva 2,300/230-volt distribution transformer has the following
resistance and leakage-reactance values: Rp = 0.8; Xp = 3.2; Rs =
0.009; Xs = 0.03. calculate the equivalent values of resistance,
reactance voltage drops for a secondary load current of 109 amp: (a)
in secondary terms: (b) in primary terms.
OIL – is primarily used for insulation and cooling of windings.
ASKAREL OIL – is non-flammable insulating liquid w/c when
decomposed by an electric are evolves non-explosive gases.
OBJECTIVE QUESTIONS
1. The transformer is usually used to change the values of
voltage.
2. Transformer operates at a power factor depending on the
power factor of the load.
3. A good transformer oil should absolutely free from sulfur,
alkalies & moisture.
4. The working principle of transformer is mutual induction.
5. The lamination of a core on a transformer are made of silicon
steel sheet.
6. The purpose of laminating the core of a transformer is to
reduce eddy current losses.
Defined parameters
Note:
No load voltage – means the input voltage to the
transformer when it is in operation or load
PRIMARY SIDE
SECONDARY SIDE
Is = rated secondary current
Vs = rated secondary voltage (output voltage) (real output)
Rs = resistance of the secondary winding
Xs = reactance of the secondary winding
Es = induced voltage in the secondary (because of mutual flux)
Zs = impedance of the secondary winding
Zs = Rs + j X s
Ns = number of turns in the secondary winding
Vsnl = input voltage to the secondary side. (no load secondary
voltage) – fictious.
GENERALLY
Ф m = maximum mutual flux (common to primary and
secondary). This flux travels around the core.
= this is a useful flux
= this is a working flux
a = transformation ratio
= turns ratio
= induced voltage ratio
= rated voltage ratio
= no load voltage ratio
= inverse current ratio
Approximate:
In = too small; temporary neglected
L
VPNL Vp = aVs O
A
D
ELECTRICAL LOSSES: (cupper losses) ; Is = aIp
EL = ELP + ELS
= Ip2Rp + Is2Rs
= Ip2Rp + a2Ip2Rs
= Ip2 (Rp + a2Rs)
Ip Rep Xep
VPNL O
A Vp
D
VPNL = Vp + IpZep
Rp/a² Xp/a² Rs Xs Is
aIp
= VSNL LO
A
D
KVA LOAD =
= KVAsec
ELECTRICAL LOSSES;
EL = ELP + ELS
= Ip2Rp + Is2Rs
EL =
Is2Res
Xes – equivalent reactance of transformer referred to secondary
side.
L
VSNL VS O
A
D
VSNL = Vs + Is
Zes
PERCENT VOLTAGE REGULATION
Additional Formulas:
GENERALLY
%Z = %R + j%X
(%Z)2 = (%R)2 + (%X)2
RULES:
• Use subscript “(1)” to designate transformer operating at full
load or rated load.
TRANSFORMER LOSSES
a) Electrical losses – is also called resistance or cupper
losses. These losses are primarily due to the
resistance of primary (Rp) and secondary (Rs)
windings. These losses vary with the “Square of
the KVA load”.
• 1st condition; (@ full load or rated load)
EL1 =
Ip12Rep
• 2nd condition; (below rated or above rated)
EL2 =
Ip22Rep
• Divide ②/①
NOTE:
this is loss will only change or vary if there is change in the
primary voltage (Vp) or supply frequency.
TYPES OF CORE LOSSES
1. HYSTERESIS LOSS (Ph) - This loss can be minimized only
by using high quality of material to construct the core
(such as high grade silicon steel) because it has high value of
permeability and low hysteresis.
Coreloss = PH +
Pe
TYPES OF TRANSFORMER EFFICIENCY
TL = EL +
COL
Where:
Po = KVAOUTPUT x
P.F.
PIN = Po + TLOSSES
@ FULL LOAD:
but
Po’ = KVA’ x P.F.
EL’ = CL (max.)
PIN’ = Po’ + TL’
TL’ = EL’ + COLOSS
TL’ = 2EL’ = 2CL
EQUIVALENT FORMULAS:
Note:
KVA’ KVAoutp at maximum efficiency condition.
ut
Where:
KVA1 = Ip1 Vp / EL1 = Ip12 Rep
1000 EL2 = Ip22 Rep
KVA2 = Ip2 Vp /
EL’ = (Ip’)2 Rep = CL
1000
OBJECTIVE QUESTION:
when will maximum efficiency occur and at what KVA load?
1. It could happen at “full load”
KVA1 = KVA’
ŋ1 = ŋ’max
EL1 = EL’ = CL
2. It could happen at either “overload or below rated load”
Given:
@full load: KVA1 = ? EL1 = 400w
@full load: KVA2 = ½ KVA1
Req’d:
EL2 = ?
Solution:
Rp = 1.2 ohm
Rs = 0.058 ohm
Vp = 2400 v
Vs = 240 v
Solution:
EL1 (using primary value)
=?
Rep = Rp1 + a2Rs
= (1.2) + (10)2
(0.058)
= 7 ohms
EL = Ip2Rep
= 4.17 Amp. = (4.17)2 (7)
EL = 121.7 watts
Example problem:
the full load cupper loss and core loss of a 20 KVA, 2500/250v
transformer are 300 watts and 320 watts respectively. What is
the efficiency at half load and unity power factor.
Given:
@ 1st condition: (full load) @ 2nd Condition: (half load)
Solution:
But
KVA2 = ½ KVA₁
= 75 Watts
TL2 = EL2 + CL
= 75 + 320
= 395 watts
Subs. Values:
= 98.06%
REGULATION CALCULATIONS USING VOLTAGES VALUES:
Transformer percent regulation (%Reg)
THREE FLUXES
1. Mutual flux (φ m) = links both the primary and secondary
windings.
2. Primary leakage flux (φ₁) = links with primary winding only
and is varrying I₁
3. Secondary leakage flux (φ₂) = links with secondary winding
only and is varrying I₂.
VOLTAGE DROPS IN TRANSFORMER (INTERNAL)
a) Voltage drop due to leakage reactance = IsRs
b) Voltage drop due to leakage reactance = IsXs
Below are the phasor. Diagram showing how the resistance and
leakage-reactance drop are subtracted from the induced
secondary voltage to yield the secondary terminal voltage.
Es
a) @ unity power factor
IsXs
Vs
Is
IsRs
b.) @ lagging power factor
Es
IsXs
Is
Rs
V
PF
s
co
s Vs
Is sin
Rs
Is
c.) @ leading power factor Is
s IsXs
R
Is
s Es
c o
s Vs
V
si
n
PF
Vs
Below are phasor diagrams showing how the resistance and
leakage – reactance drops are subtracted from the impressed
primary voltage to yield primary induced voltage.
Vp
a. @ unity power
factor
IpXp
Vp
Ep
Ip
IpRp
IpXp
Ep
Ip
Rp
PF
Ep
b. @ lagging power factor Ep
si
co
n
s
Ip
Rp
Ip
I
c. @ leading power factor
p IpXp
R
Ip
Vp
c os
Ep Ep
si
n
PF IpRp
Ep
Rp Xp Ip
Iφ
Ig
Rm Xm Ep Es V₂
Eg
Where:
Rp = Resistance of primary winding
Xp = Reactance of primary winding
Rs = Resistance of secondary
Xs = Reactance of secondary winding
Eg = Supply voltage or primary voltage
Ep = Induced emf of the primary winding
Es = Induced emf of the secondary winding
Ig = Supply current
If = Primary current
Is = Secondary current
Rm = Resistance representing iron losses
Pm = Iron losses
Xm = Magnetizing reactance of primary winding
Io = Exciting current
Qm = Reactive power needed to set-up the mutual flux (VAR)
EQUIVALENT CIRCUIT DIAGRAM OF A PRACTICAL
TRANSFORMER AT “NO LOAD”
Rp Xp Ip = 0
Rs Xs
Ig = Io Io Is = o
Rm Xm Ep Es
Eg Vs = Es
Rp Xp Rs Xs
Eg Ep Es Vs
NOTE:
@ full load, “Ig” is at least 20 times bigger than “Io”
EQUIVALENT RESISTANCE REACTANCE AND IMPEDANCE
Xep = a²Xs + Xp
Notation:
Rep = equivalent resistance in primary side.
Xep = equivalent reactance in primary side.
Ip = primary current.
Res = equivalent resistance in secondary side.
Xes = equivalent reactance in secondary side.
Is = secondary load current.
PERCENT REGULATION OF TRANSFORMER AT DIFFERENT
LOADING.
Thus:
Example problem:
a) Mutual flux, Фm
b) No. of turns in the 230V, sec.
c) Transformation ratio of voltage and winding
Given: Req’d:
Ep = 2300 v Фm, Ns, a
Es = 230 v
f = 60 cps
Np = 4800 turns
Solution:
NS = 480 turns
c.) or
Example Problem:
a 25 KVA, 2300/230 volts distribution transformer has the
following resistance and leakage reactance value of 0.8 and 3.2
respectively. For primary and 0.009Ω and 0.03Ω for secondary
respectively. Calculate the equivalent values of resistance,
reactance and impedance in secondary terms:
a) Secondary terms
b) Primary terms
Xes = Xs + Xp/a²
= 0.03 + 3.2/102
= 0.062 Ω
Rep = Rp + a2Rs
= 0.8 + (10)2 (0.009)
= 1.7 Ω
Xep = Xp + a2Xs
= 3.2 + (10)2 (0.03)
= 6.2 Ω
PRIMARY SECONDARY
VDSX = IsXes
= (109)(0.062)
= 18.53 volts = 6.75 volts
VDPX = IpXep
= 67.5 volts
d.) Percent Regulation @ unity
P.F. = 1
= cos-1 (1)
= 00
= 10.87 amps
For unity
VPNL = VP + IpZep
= cos-1 (0.866)
= 300
VPNL = Vp + IpZep
Cos = 1
Sin = 0
For 0.8 lagging: = 36.870
cos = 0.8
sin = 0.6
For 0.866 leading: = 300
cos = 0.866
sin = 0.5
EXAMPLE PROBLEM:
a 10 KVA, 2400/240 volt distribution. Transformer has a
primary resistance of 1.2 ohm and a secondary resistance of
0.058 ohm. What is the full load cupper loss (Electrical loss).
Given: Req’d:
Pa = 10 KVA
E = 2400/240 V
Rp = 1.2 ohm
Xp = 0.058 ohm ( NOTE: STOP HERE)
Solution:
Using primary values:
Rep = Rp + a2Rs
= 1.2 + (10)2 (0.058)
=7
ELOSS = Ip2Rep
= (4.17)2 (7)
ELOSS = 121.7223 watts
EXAMPLE PROBLEM:
The full load cupper loss and core loss of 20 KVA, 2500/250
volt transformer are 300 and 320 w respectively. What is the
efficiency at haf-load and unity P.F.
Given:
@ condition 1: (full load)
COL = 320 w
Solution:
Sample Problem:
In a 50 kva transformer, the full load cupper loss are exactly
twice the iron losses, and that quarter load, the efficiency is
95%. Calculate the full load efficiency at unity P.F.
@ condition 1: (full load)
KVA1 = 50 kva
KVA2 = ¼ kva1
= ¼(50) = 12.5 kva
ŋ₂ = 95%
Req’d:
ŋ₁ = ?
Solution:
= 13,157.89 – 12500
= 657.89 watts
But:
TL2 = EL2 + CL ------------ ②
Substitute ① to ②
TL2 = EL2 + CL
= 0.5625 EL1
From eqn.①
CL = 0.5 EL1
= 0.5 (1,169.6)
= 584.79 watts
Example Problem
The core loss of a 50 KVA single phase transformer with normal
voltage applied to the primary is 75 watts. The max efficiency
at 60% load of full load. What is the full load efficiency of the
transformer at 0.8 P.F.
Given:
@ condition 1 : (full load)
KVA₁ = 50 KVA
CL = 75 watts (constant)
Note:
Core loss (CL) don’t vary at any time of change except when
the applied voltage and frequency is change.
EL1 = ?
= 4000 watts
Req’d: ŋ₁ = ?
Solution
@ max eff. (E ’ = C )
L L
but
TL1 = EL1 + CL
subs.values:
Pin1 = PO1 + EL1 + CL
= 4000 + 208.3 + 75
= 4283.3 watts
Example Problem:
A 100 KVA transformer has a maximum efficiency of 98% at
10% underload at unity power factor. Evaluate the efficiency at
quarter-load at 0.8 power factor.
Given:
@ max.load: @ full load condition:
Solution:
KVA’ = 0.1 KVA1 PO’ = 10 KVA (1)
= 0.1 (100) = 10,000 watts
= 10 KVA
T L’ = E L’ + C L
But for maximum efficiency: (E ’ = C )
L L
TL’ = 2 CL -------------- ①
@ quarter load:
TL2 = EL2 + CL
= 637.75 + 102.04
= 739.79 watts
All day efficiency – also known as commercial efficiency. The all
day efficiency of the transformer. The ration of electrical energy
(kilowatt-hours) output delivered by the transformer in a 24-
hour period to the energy input in the same period of time (or
a day operation.)
Where:
Wo – Electrical energy output Win - Electrical input
- ЄP x time (kw-hr) - ЄP x time (kw-hr)
- Wo + WL
WL – Electrical Energy Losses
= WCORELOSS + WCOPPERLOSS
= WCL + WEL
Note:
1. Full load values/rated values must always be given
(reference data).
2. Solutions maybe in a tabulated form.
3. When transformer is loaded 24 hrs a day operation, energy
coreloss is always constant to be multiplied by 24 hrs .
Example problem:
calculate the all day efficiency of 100 kva transformer
operating under the following conditions;
Solution:
TABULATION FORM
KW LOAD P.F. # OF KVA LOAD ENERGY ENERGY ENERGY
Kw HRS (Kw/P.F.) OUTPUT COL CUL
Hr. KVA Kw-Hr (CL - t) (EL - t)
= 2.98
N
O
0 15 - - 1 (15) 0
L
= 15
O
A
D
390 24 3.41
TOTAL: Wo WCL WCUL
WO = 300 + 90
= 390 Kw-Hr
WCL = 6 + 3 + 15
= 24 Kw-Hr
WCU = 2.98 + 0.43
= 3.41 Kw-Hr
Win = WO + WLOSSES
= 390 + (24 + 3.41)
= 417.41 Kw-Hr
Example problem:
a 30 kva, 2400/240 volts, 60 hz distribution transformer has a
full load P.F. of unity over a period of 24 hrs. the maximum
efficiency is 95% and it occurs at full load. Calculate the all day
efficiency if it is loaded as follows:
Req’d:
= 5.033 kw-hr
Example problem:
a 100 kva, 6600/400 volts 60 hz, single phase, core type
transformer has the following average daily load:
full load at 0.8 PF for 8 hrs
half-load at 0.7 PF for 10 hrs
no load for 6 hrs
Calculate the ratio of the full load cupper loss to the iron loss for
the transformer to be “most economical” for the above loading.
Req’d:
Solution:
@ full load condition:
ЄL1 = ?
Note:
most economical at maximum eff.
TABULATED FORM
No load - 0 6 - CL (6) 0
= 6 CL
24 CL 10.5 EL1
WCL = 8CL + 10 CL + 6 CL
= 24 CL
= 10.5 EL1
24 CL = 10.5 EL1
Example Problem:
a 25 kva, single phase transformer operates for one hr @ 20%
overload @ 0.8 PF lagging; three hrs @ full load @ 0.9 PF
leading; 6 hrs @ half-load @ a unity power factor and 10%
loaded @ unity power factor for the rest of the day, the cipper
loss and core loss @ full load are 500 watts and 150 watts
respectively. Find the all-day efficiency.
• @ condition 2: (overload) t₂ = 1 hr
= 1.2 (25) = 24 kw
= 30 KVA
@ condition 3: (half-load) t₃ = 6 hrs.
EL1 = 500 watts (0.5 kw) CL1 = 150 watts (0.15 kw)
Req’d: ŋd = ?
Solution: Wo = ЄPo x time
= W1 + W2 + W3 + W4
Wo = 67.5 + 24 + 75 + 35
= 201.5 kw-hr
If the full load cupper loss and @ unity PF is 140 watts. Calculate
the value of core loss.
PF1 = 1 PF2 = 1
t1 = 4 hrs. T2 = 20 hrs
Solution:
WO = ЄP x time
= (10)(1)(4) + (0)(1)(20)
= 40 kw-hr
Problems on percent voltage regulation (%VR)
Case I:
if given data are in terms on Zep, Rep and Xep.
Example Problem:
A 10 kva, 2400/240 volt single phase transformer has the
following resistances and leakage reactances.
Given: rp = 3 ohms
rs = 0.03 ohms
Xp = 15 ohms
Xs = 0.15 ohm
Solution:
KVAP = KVAS = KVAoutput
(full or rated load)
KVA’ = ?
EL1 = IP2Rep
= (4.17)2 (6)
= 104.33 watts
VPNL = VP + IP’Zep
Solution:
By applying formula
Case II
id the given data of transformer are in terms of %Z, %R & %X.
DERIVATION OF FORMULAS:
Where
Voltage equation:
Transformer Testing Assumed: (step-down transformer) Vp Vs
Where:
Vp = high voltage windage
Vs = low voltage windage
Procedure:
a) The low voltage side is short circuited.
b) All measuring AC instrument such as ammeter, voltmeter,
wattmeter are placed on the high voltage side.
c) Energize the high side by a small input voltage.
d) Then solve for; Zep, Rep, Xep.
Figure:
ammeter
Isc
variable
A
resistor
wattmeter
V shorted
+
Vin
HVW LVW
(primary) (secondary)
Where:
Ise = short circuit current on the low voltage side must be
equal to rated secondary current Is.
Where:
Where:
@ full load:
b.) OPEN CIRCUIT TEST (OCT)
Purpose: To determine the total rated iron loss
(CORE LOSS).
Procedure:
W V
Vin
autotransformer
d.)
• Slight change in efficiency
• No change of %VR
• Copper loss is slightly affected
• Core loss will change (very much affected)
Formulas
Pe = Kefβm2
Where:
f = frequency of the AC source
Where:
B = maximum flux density (not constant)
m
фm = maximum mutual flux
A = net cross-sectional area of the core
Ph = hysteresis loss; watts
Pe = eddy current loss; watts CLOSS = Ph + Pe
From Ep:
Ep = 4.44NpfФm x 10-8
Therefore:
Let K1 = design constant
STEINMITZ LAW:
Ration:
Therefore:
Example Problem:
Note:
if the problem does not mentioned coreloss is constant
therefore, do not assume constant.
Given:
Vp₁ = 4400 v Vp₂ = 4600 v
f₁ = 60 hz f₂ = 50 hz
CL₁ = 840 w
Pe₁ = ⅓ (CL₁)
= ⅓ (840)
= 280 w
Req’d:
CL₂ = ?
Solution: (Case 1)
CL₂ = Ph₂ + Pe₂ ---------- working formula.
Example Problem:
a 25 cycles, 1000 kva transformer is applied to a 60 cps
system. The full load efficiency of the transformer at 25 cps is
98%. Half of the core, the hysteresis and eddy current loss are
equal at 25 cps. What would be the rating of this transformer
at 60 cps if the transformer was operated at rated voltage.
= 0.5 (10,205)
= 5,102.5 watts
@ 2nd condition: (assume Vp₁ = Vp₂)
= 3017.56 + 5102.5
= 8116.08 watts
TL2 = CL2 + EL2
Given:
@ 1st month condition: @ 2nd condition:
f1 = 50 cps f2 = 25 cps
Pe₁ = ?
Solution:
@ condition 1:
= Ke Vp12 + Kh
2500 = Ke (400)2 + Kh
850 = Ke (220)2 + Kh
Substitute eq ① in ②
Given: f = 60 Hz
KVA2 = 100 KVA VS1 = 600 V
Solution:
load load
1 2
Given:
Np = 500 turns Z₁ = 60 ohms
N₁ = 125 turns Z₂ = 3 ohms
N₂ = 36 turns Vp = 120 v
f = 60 hz
FIGURE:
load load
1 2
For currents:
• Primary - Secondary
• Y - Y
• Y - Δ
• Δ - Y
• Δ - Δ
• The reasons for choosing a Y or Δ configuration for transformer
winding connections are the same as for any other three-phase
application: Y connections provide the opportunity for multiple
voltages, while Δ connections enjoy a higher level of reliability
(if one winding fails open, the other two can still maintain full
line voltages to the load).
X Ip = Iф Is 1
Ap As
Bp Bs
Y Cp Cs 2
Z 3
Ip = Iф
X
Y
Bp Ap 2
Cs As
Cp Bs
2
Z 3
Iф = Is
1
2
X
As
Bs
Ap Cp
Bp
Y Cs
Z 3
2
X
Cs As
Ap Cp
Bs
Bp
Y 2
Z 3
Closing a Delta:
• When closing a delta system, connections should be checked
for proper polarity before making the final connection and
applying power. If the phase winding of one transformer is
reversed, an extremely high current will flow when power is
applied. Proper phasing can be checked with a voltmeter at
delta opening.
If power is applied to the transformer bank before the delta
connection is closed, the voltmeter should indicate 0 volts. If
one phase winding has been reversed, however, the voltmeter
will indicate double the amount of voltage.
To solve: P / I x E
• 112.5 kVA X 1000 = 112500 VA
• 112500 VA divided by 831 (480 x 1.732) = 135.4 amps
• Since the transformer is more than 9 amps you have to use
125 %.
• 135.4 X 1.25 = 169 amps.
Answer: 175 amp fuses (the next higher standard, Electrical
Code 240-6).
Example #2:
To solve: P / I x E
• 3kVA X 1000 = 3000 VA
• 3000 VA divided by 360 (208 x 1.732) = 8.3 amps
• Since the transformer is 9 amps or less you have to use 167%.
• 8.3 X 1.67 = 13.8 amps
To solve : P / I x E
• 112.5 kVA x 1000 = 112500 VA
• 112500 divided by 360 (208 x 1.732) = 312.5 amps
• 312.5 X 1.25 = 390.6 amps
EQUIVALENT CIRCUIT DIAGRAM
X 1
Ap As
Cp
Cs
Y 2
Z 3
Note:
86.6%
C 4
3
50%
A B
1 2
3ф
L
O
A
D
Let:
Note:
OPEN-DELTA BANK
3
ф
L
O
A
D
Example Problem:
two transformer are connected open delta delivering a load of
100 KVA at a power factor of 0.8 lagging. Calculate the power
delivered by each x’4mer?
Given:
SL = 100 KVA
L = 0.8 lagging
= -36.870 3ф
Given:
Example Problem:
An electrical utility company is supplied by two single phase
x’4mers bank in rated 75 KVA capacity. What is the maximum
3ф load in kw that the bank can carry without overloading
considering that the load has a lagging PF of 0.8.
Given:
Example Problem:
Three single phase (3ф) transformer each rated 75 KVA are
bank in delta supplying a 3ф load drawing 160 KVA at 0.8
lagging PF. If one x’4mer has burned out and is removed for
repair, solve for the amount of overloading of the remaining
units.
Given:
Example Problem:
An open-delta bank, consisting of two single phase x’4mers is
operating with a balance 3ф load of 50 KVA, 440 V at 0.8 PF
lag and a single phase load of 10 kw resistive connected across
AC leg. Determine minimum ratings of the two x’4mers.
Assume a phase sequence a-b-c.
Given:
50
a 10 kw kva
0.8
lag
C Icc L
T-1 T-2 O
440 V A
N D
b Ibb
a Ia
C L 10kw 440 v
PF = 1
Ic
N
Example Problem:
a 3ф transformer connected on delta on the primary side step
down. The voltage from 13200 v – 460 v and delivers 750 kva, 0.8
PF lagging to the load. Calculate:
a) Transformation ratio
b) The current delivered to the load
c) The current in primary line wires
d) The current that flows in the transformer winding
Given:
∆ Connected SL = 750 kva
Vp = 13200 V PFL = 0.8 lag
Vs = 460 V
Req’d: a, ISL, IPL and IpФ = ?
Example Problem:
A power transformer rated 50,000 KVA, 34.5/13.8 kvolts is
connected Y-Y. what are the line currents at full load.
Given:
Example Problem:
A power transformer is rated 50,000 KVA 34.5/13.8 kvolts is
connected Y-Grounded on the primary and delta on the
secondary. Determine the full load phase currents on the
secondary side.
Given:
Y (grounde) = ∆ connection
IpL
Ipф
N
Example Problem:
What should be the turns ratio of the 3ф transformers that
transform from 230 kvolts to 4160 volts if the transformer is to
be connected Y-∆ & ∆-Y
Given:
PARALLEL OPERATION OF TRANSFORMER
requirements to be met for ideal operation of two or more
transformers in parallel.
Note:
if this condition is not met, the transformer will not share
the load in proportion to their respective KVA ratings. A possibility
that the large transformer operates at a underload condition while
smaller transformer operates at overload conditions.
d.) The ratio of the equivalent resistances (Res) and reactances
(Xes) referred to the secondary side must be the same.
Note:
if this condition is not met each transformer will operate at
different power factor with that of the connected load.
OR
2.) Always perform vector addition for apparent power and
current.
When connected in parallel:
CASE 1: (Equal turn Ration)
5. KVA rating of each transformer is not necessary.
Example Problem:
two transformer are connected in parallel supplying a common
load of 175 KVA @ 0.8 PF lag. Both transformer has a voltage
rating of 2300/230 V single phase and each rated 100 KVA.
Transformer 1 has equivalent impedance of 16 ohms and that
of transformer 2 is 13 ohms. Referred both to the primary. Find
KVA load in each transformer.
Given:
CASE2: (equal turn ratio)
Example Problem:
Determine the KW ratio of the KW output of transformer T-1 to
that transformer T-2 when they are connected in parallel
supplying a load of 150 KW @ 0.8 PF lagging.
Given:
CASE 3: (Equal Turn Ratio)
Where:
AUTO-TRANSFORMER
Calculate:
WHERE:
Ns = synchronous speed in RPM
f = frequency of the incoming source supplying the
induction motor. Stator frequency.
P = number of poles of the machine.
air gap
STATOR ROTOR
air gap
SPI RPD
STATOR ROTOR
RPO
RPI
(RPO=FPI)
TEST PERFORMED IN AN INDUCTION MOTOR
@ No load condition:
b.) Blocked Rotor Test
this test is similar to short circuit test performed in a
transformer. During this test the rotor is blocked and the rotor
windings are short circuited, cut slip rings if the motor has a
wound rotor. A reduced voltage is applied to the stator
terminals and is so adjusted that full load current flows in the
stator. The values of the current voltage and power input are
measured.
Purpose:
To determine the equivalent resistance per phase referred on
the stator side
c.) Load Test
- Motor is loaded with its normal load or visual load.
- During this test, the motor is loaded. The problem should
clearly specified what is the specified load on the motor.
- This is not an assurance that the motor is tested at full
load.
Example Problem:
A 5 hp, 6 pole, 3ф, 60 Hz induction motor operates with a slip
of 2% and requires 11 amp and 3500 watts, when during its
visual load. When the rotor is blocked, 440 watts at 52 volts
are required to circulate a current of 14 amp. Calculate the
following when motor is driving its visual load.
a) Horsepower output
b) Torque Excerted
c) Efficiency (Assume Y-connected stator)
Given:
SPI RPI RPD
STATOR ROTOR
RPO
Given:
H20
8.7 ft
Pop
M P
Example Problem:
A 4 pole, 60 Hz, 3ф induction motor draws 8200 watts from
the line. The losses in the machines are:
Note: When the given data regarding core loss and friction
and windage (F & W) are incorporated as one in the stray
power loss (SPL).
air gap
SPI RPD
STATOR ROTOR
SCL
RCL
SPL=(F&W)+CL
Example Problem:
A 6 pole, 3ф, 60 Hz induction motor takes 48 kw in power at
1140 RPM. The stator copper loss is 1.6 kw and stray power
losses are 1 kw. Find the eff.
Pom Pip
Pop
200 ft
SPI
M P
DC RESISTANCE TEST OR OHMIC TEST.
RCL
(electrical) F&W
(mechanical)
Example Problem:
A 40 Hp, 230 v, 8 pole, 25 Hz 3ф induction motor is running at
355 RPM @ rated load. The torque lost by friction is 24 n-m. if
the total stator loss is 1000 watts. Calculate the eff.of the
motor at this load.
Solution:
RPI RPO
ROTOR
RCL
STARTING AN INDUCTION MOTOR
Note: for small motors (usually 10 hp below) use across the line,
magnetic starter (full voltage starting method)
The starting line current is always proportional to the starting line
voltage:
Ratio
Where:
Vs – starting line voltage
Ts – starting torque
Is - starting current
Td – rated or full load torque developed
IL – rated or full load current
Example Problem:
A 25 hp, 230 volt, 3ф induction motor with 85% PF has a
starting current of 5.5 times its rated current. To reduced the
starting current, at “Y-∆” starter is installed. What will be the
new starting current?
Given:
Example Problem:
A 10 hp, 550v, 3ф induction motor has a starting torque of
160% of full load torque and a starting current of 425% of full
load current. If the motor is used on 440v, 60hz system. What
will be the starting torque express in percent of full load value?
Example Problem
An induction motor of 30 hp, 220v, 3ф, draws 450% of rated
current with rated voltage and delivers during the starting
period of 130% of the normal torque. The full load efficiency of
the motor and full load PF is 80% and 70% respectively. If the
auto-transformer unit is used as a starting unit and the
starting torque of the loads is only 50% of the rated torque of
the motor. Find the starting current of the line.
REDUCED VOLTAGE METHOD FOR LARGE 3ф MOTORS
3. Auto-transformer method
Line 1
Line 2
Line 3 Start
Stop
OLR Coil
Circuit
Breaker
Normally
Open
Overload
Relay
Motor
SYNCHRONOUS MOTOR
TYPES OF S.M.
ίƒ
field circuit
separately
Vf excited by Vф
DC source
Supply
Voltage
armature
circuit
Notations:
If – DC shield current taken from the exciter
Where:
- deflection angle
- torque angle
Electrical Mechanical
Pin Pd Pd Po
ARMATURE
SPL
Notes:
a) Unity
b) 0.8 lag
c) 0.8 leading