Cops, Eers, and Seers: Download Note
Cops, Eers, and Seers: Download Note
1. Introduction
This note discusses performances of air conditioning systems, including heat pumps and chillers.
It describes the efficiencies of systems so you can estimate how much energy a system may use.
The discussion applies equally to residential, commercial, and industrial systems.
When we talk about the size of an air conditioning system (whether by tons of cooling, BTU/h,
or kW), we are specifying the cooling capacity (power) of the system. The actual electrical
power used to operate such a system is less. As described in this document, the electrical power
used is one half to one third (or less) of the cooling power.[1]
In the US, the Department of Energy (DoE) set standards for the minimum performance of
residential central air conditioners and heat pumps and this document lists some of those
requirements.
The COP is therefore a measurement of efficiency; the higher the number, the more efficient the
system is. The COP is dimensionless because the input power and output power are measured in
Watt. The COP is also an instantaneous measurement in that the units are power which can be
Consider a simple electric heater. All of the electricity that is input to the unit is converted to
heat. There is no waste and the power output (in heat) equals the power input (in electricity), so
the COP is one. The COP can be used to describe any system, not just heating and cooling.
An air conditioning system uses power to move heat from one place to another place. When
cooling, the air conditioning system is moving heat from the space being cooled (usually a
room), to somewhere it is unwanted (usually outside). A heat pump uses the same principles, but
it is moving heat from outside (the cold side) to the space being heated inside (the living space).
The maximum theoretical COP for an air conditioning system is expressed by Carnot’s theorem,
reduced to the following equation:
Where TC is the cold temperature and TH is the hot temperature. For space cooling, the cold
temperature is inside the space; for space heating, the cold temperature is outside. All
temperatures are expressed in Kelvin. To convert from °C to Kelvin, add 273.15. To convert
from °F to °C, subtract 32, multiply by 5 and divide by 9.
As you can see from equation 2, as the difference between the hot temperature and the cold
temperature increases, the COP becomes lower, and vice versa. This means that an air
conditioning system is more efficient when the room temperature is closer to the outside
temperature and will use more power when there is a larger difference in these temperatures.
As an example, consider the maximum theoretical efficiency of an air conditioning system that is
cooling a room to 23°C (73.4°F). If the outside air temperature is 32°C (89.6°F), the theoretical
maximum efficiency is:
Typical COP values for air conditioning and heat pump systems are in the range 2 to 4, or about
a tenth of the theoretical maximum. However, this helps to explain where the power is used in
such a system. Consider the heat pump application shown in figure 1.
The heat pump takes power from the environment and uses electrical power to move that power
to the inside space. More power is put into the house than used in electricity. 3 The COP of this
system is 4 (power into the house ÷ power consumed). Observe that the electrical power
consumed goes into the building. In practice some is expended as heat outside the building, so
the actual COP will be slightly less than 4.
An air conditioner operates in the same way, but it is removing power from the space. Consider
the figure above in reverse where 1 kW is used to move 3 kW of power from the space. The air
conditioner puts 4 kW of power into the environment and this power must be dissipated by the
condenser. The air conditioning unit is using more power than is being consumed in electricity.
However, in this case, all the power used to operate the air conditioning unit is dissipated outside
and has no effect on the power removed from the space. Hence, the COP is equal to 3.
The bizarre units of measurement originated in the US to measure the efficiency of an air
conditioning system in a steady state. The units are therefore not dimensionless and EER can be
measured only over time. Typically, with the system stable, one can measure the energy used
over an hour period. One measures the amount of cooling the system has performed during that
time.
Many writers erroneously consider the EER to be a ratio of power, not energy:
The units are the same, but now we are dividing the power of the air conditioning unit (in
BTU/h) by the power to operate it (in Watt). Although incorrect, this view does have the
advantage of allowing us to easily estimate the power used for a certain size of air conditioning
unit.
As an example, consider an air conditioning unit that is five tons and has an EER of 11.6. 4 If we
want to find out how much power is used we rewrite equation 5:
Where the multiplication by 12,000 converts tons of air conditioning to BTU/h. The EER can be
specified only at a specific delta temperature (between inside and outside the space being
cooled), because as we see from equation 2, the efficiency changes with this delta temperature.
The EER is usually specified under the conditions shown in table 1.
To convert EER to COP, we need to accommodate for the units used. We convert the BTU
energy and the electrical input energy to a common energy unit, namely Joule. 5 One BTU
equals 1055 J. One Wh equals 3600 Ws or 3600 J. So:
The US DoE defined the formula to be used to calculate SEER values for residential air
conditioning systems of less than 65,000 BTU/h (19 kW). The manufacturer makes EER or COP
measurements at various values for indoor and outdoor temperature and then computes the
SEER. The result is one number that may guide a prospective purchaser or owner of a system to
As an example, consider a five ton unit (60,000 BTU/h) that runs on average eight hours a day
during the cooling season. 7 At the ends of the season, the system may run only four hours a day
but at the peak of the season, it is running 14 hours a day. Assume the cooling season is 180 days
(about six months). Again, assume that on average throughout the season, the unit runs at two
thirds of its capacity. The cooling energy is:
If the system has a SEER of 13, the total electrical energy used is:
If the cost of electricity is 17 ¢ per kWh, the cost to run this air conditioning unit during the
season is:
The EER is usually specified under the conditions shown in table 1. The SEER is averaged over
a range of temperatures that are less than or equal to this, including one test where the outside
temperature is 82°F (28°C) and the inside temperature is 80°F (27°C). We know that as the delta
temperature goes down, the efficiency goes up, so therefore the SEER is greater than the EER
(typically by about 15% to 35%). One formula, to convert between the two was proposed by a
student in a master’s thesis as follows:8
This implies SEER is 20% more, but in practice the value may be larger. 9 Also, because the
conditions to calculate the SEER are fixed, they may differ widely from where the air
conditioning unit is actually installed where temperatures and operating parameters vary
significantly. Therefore, the actual ratio observed in practice may differ widely from the
published SEER, making it difficult to accurately estimate the energy to run the system during a
season.
In the US, the DoE specifies the minimum values for SEER as shown in table 2. The law was
changed in January 2006 and the table lists the old and new standards.
A split system is one where the evaporator and condenser are in physically different places. The
compressor is usually housed with the condenser and these are in one package that is usually
installed outside or on a roof. The metering device (expansion device) is adjacent to the
evaporator and installed inside the space where the air used to cool the space can flow.
A packaged system has all four major components (evaporator, condenser, metering device, and
evaporator) in a single unit that is usually placed outside. Air ducts transport the supply and
return air to the unit.
Using equation 9, we see that a unit that is rated at SEER of 13 is 30% more efficient than a unit
rated at SEER 10.
As with COP, EER, and SEER, the higher the number of HSPF the greater the efficiency.
In the US, the DoE specifies the minimum values for HSPF as shown in table 3. The law was
changed in January 2006 and the table lists the old and new standards.
For example, Assume a system has an HSPF of 8. Then from equation 16, the COP is 2.3. This
means that 2.3 times the amount of heat is put into the space than is consumed in electricity. Put
another way, for every 1 kWh of electrical energy used by the heat pump, 2.3 kWh of heat
energy is input to the space.
For example, if a chiller has a rating of 1.8 kW/ton, then using equation 17,
the COP is 1.95. Therefore, for every 1 kW of power consumed by the chiller, it will provide
1.95 kW of cooling in the space.
7. Horse Power
Another unit in use in the US is the horse power (HP). This is a unit of power and typically is
used to specify the size of motors. It may also be used to specify the input power of an air
8. Energy Star
In the US, Energy Star is the Environmental Protection Agency’s (EPA’s) indication for products
that have high energy efficiency. it makes it easy for consumers to identify and purchase
products that have higher energy efficiency than those products without such designation.
Systems under 65,000 BTU/h (19 kW) can earn the Energy Star symbol by meeting the
minimum efficiency ratings listed in table 4. The numbers in parentheses are those values that
must be met to qualify for a Federal tax credit. The ratings for HSPF apply only to systems that
combine a heat pump.
9. References
Details about Energy Star (US EPA) are here:
http://www.energystar.gov
The DoE web site with many references for residential systems is:
http://www1.eere.energy.gov/buildings/appliance_standards/residential/central_ac_hp.html
The document 10 CFR Part 430, titled “Energy Conservation Program for Consumer Products:
Test Procedure for Residential Central Air Conditioners and Heat Pumps; Final Rule,” October
2007 describes the test procedures to used to evaluate EER, SEER, and HSPF.
It is interesting to read the discussion regarding the introduction of these news rules. Two
subjects were broached that were not included in the new rules:
Setting a minimum EER. It was proposed that the minimum EER should be set at 11.6. However,
it was concluded that specifying the minimum SEER was a good way of ensuring the efficiencies
required.
Mandating the use of a thermal expansion valve (TXV) for all systems. Previously, fixed orifices
were permitted for the metering device; the DoE concluded that the TXV can make a system
11% more efficient. However, it was eventually decided that the DoE should not dictate the
technology used, so the mandate was dropped. In practice, however, most manufacturers adopted
the use of a TXV to improve the efficiency of the systems they manufacture.
Also, when the new standards were proposed, two of the largest US manufacturers of these
systems opposed the rules. The values for EER, SEER, and HSPF are specified in Standard
210/240 by the Air-Conditioning, Heating and Refrigeration Institute (AHRI) “2008 Standard for
Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment.” You
can freely access this document here:
http://www.ahrinet.org/Content/FindaStandard_218.aspx
The DoE also refers to Standard 90.1-2010 by the American Society of Heating, Refrigerating
and Air-Conditioning Engineers (ASHRAE) “Energy Standard for Buildings Except Low-Rise
Residential Buildings.” You can buy this document ($125 USD at the time of this document)
here:
http://www.techstreet.com/standards/ASHRAE/90_1_2010_I_P_?product_id=1739526
The ASHRAE web site is:
http://www.ashrae.org
d. COP values are obtained using equation 7 and equation 13. These are approximate
conversions and apply only at the conditions under which SEER or EER is specified.
You can see from the table that the input power in W is approximately equal the cooling capacity
in BTU/ h divided by ten. This is a very approximate guide that allows you estimate the size of
current clamps that you may need if you want to monitor such a system.
The table also allows you to calculate kW/ton. Either divide the input power in kW by the size of
the system in tons or use equation 17. For example consider a water cooled air conditioner of
greater than 135,000 BTU/h (the last row). The cooling is 11.3 tons. The kW/ton is 12.2 ÷ 11.3 =
1.1. Alternatively, using equation 17:
11. Conclusion
The efficiency of air conditioning systems changes with operating conditions. Various ratios can
provide a guidance on efficiency. For residential systems, the specifications for SEER are well
documented, but not necessarily applicable for your climate. For commercial systems, an EER
also allows you to compare various systems and to approximate electricity usage. With each
number, however, these figures only give a guidance to the power you will use in practice.
Because suppliers will optimize their systems to give the best performance at the specific test
conditions, you need to proceed with caution in evaluating competing systems – caveat emptor!
A SEER of 13 can be approximated as an EER of 11.2 (using equation 13), or a COP of 3.6
(using equation 8). The theoretical maximum COP for a difference of 2°F is about 100 (using
equation 2), or 25 times more efficient. While there are now residential systems on the market
that have a SEER of over 20, most commercial and industrial systems have efficiencies far below
this.
The point not addressed in this article is that no matter how efficient the system is once it is
installed, its performance degrades in time due to oil fouling. A newly installed SEER 13 unit
can be a SEER 11 unit in a few years. Power Knot can help to restore such a system or even
make it perform better than new.
1. It is possible to run air conditioning systems using gas or other power sources. While some
parts of this discussion apply equally to such systems, the focus of this document is on systems
driven by electrical power.
2. It is important to distinguish between “energy” and “power.” Energy is the amount of work
that is done and is measured in Joule (J) or British thermal units (BTU). Power is work done in
unit time (or the rate of doing work) and is measured in W (W=J/s) or BTU/h.
3. The figure uses the term “heat.” Heat is energy, not power, but is used here to aid in the
understanding.
4. To understand the meaning of a ton of air conditioning, please review Power Knot’s
application note on this topic here.
5. The symbol for Joule is J. One Joule is equal to one Watt-second (Ws).
6. Again, ostensibly, a system with a higher SEER will consume less energy than a system with a
lower SEER.
7. The cooling season is typically summer, but the US DoE specifically uses the term “cooling
season.”
8. This formula seems to have been widely accepted, but this author cannot find the original
document. It is referenced in a US DoE document titled Building America House Simulation
Protocols, June 2010 and attributed to Wassmer (2003).
9. If you are evaluating two different air conditioning systems, compare the EER of one to the
EER of the other, or compare the SEER of one to the SEER of the other. It is not valid to
compare the EER of one unit with the SEER of another unit.
PRODUCTS
LFC
SRA
COMPANY
News
Media Releases
About
Customers
Terms of Use
Privacy Statement
SUPPORT
Contact
LFC Cloud
RECENT NEWS
Team Up with the LFC at 2017 Green Sports Alliance SummitJune 13, 2017
Contact Us
CONTACT INFO
2290 Ringwood Avenue, San Jose, CA 95131, USA
+1 408 889 8433
[email protected]
Directions