Socket

This document discusses radial final circuits according to BS 7671:2008. It contains a figure showing a diagram of radial final circuits including a 20A and 32A circuit. The 20A circuit uses 2.5mm2 cable for all live conductors and a BS1363 socket outlet. The 32A circuit uses 4.0mm2 cable for live conductors, allows an unfused spur from the origin in the consumer unit using 2.5mm2 cable for a single or twin socket outlet, and notes the number of socket outlets from a fused connection unit depends on the load characteristics and diversity.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views

Socket

This document discusses radial final circuits according to BS 7671:2008. It contains a figure showing a diagram of radial final circuits including a 20A and 32A circuit. The 20A circuit uses 2.5mm2 cable for all live conductors and a BS1363 socket outlet. The 32A circuit uses 4.0mm2 cable for live conductors, allows an unfused spur from the origin in the consumer unit using 2.5mm2 cable for a single or twin socket outlet, and notes the number of socket outlets from a fused connection unit depends on the load characteristics and diversity.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Circuitry and Related Parts of BS 7671: 2008

C 11.3 Radial final circuits


Figure C 11.2 is based upon that in Appendix 15 of BS 7671:2008.

20A Radial 32A Radial

20A 30/32A

All live conductors 2.5 mm2 Live conductors 4.0 mm 2

BS 1363 BS 1363
socket-outlet socket-outlet

Unfused spur
An unfused spur run in 2.5 mm 2
cable should feed one single or one
twin socket-outlet only.
An unfused spur may be connected
to the origin of the circuit in the
consumer unit.

2
2.5 mm
Spur circuit using an FCU
The number of socket-outlets
supplied from a fused connection
unit is dependent upon the load
characteristics having taken
diversity into account.

1.5 mm 2

Figure C 11.2  Radial final circuit information diagram.