Calculation Details
Calculation Details
2 Case 1 : Dead and live load from out side of while no water pressure from inside.
Self weight og top slab = 0.58 x 1 x 1 x 25000 = 14500 N/m2
Live load and dead load = 2E+05 + 12000 = 162000 N/m2
Total load on top = 176500 N/m2
Weight of side wall = 5.135 x 0.58 x 25000 = 74457.5 N/m
\ Upward soil reaction at base = ( 2E+05 x 4.58 )+( 2 x 74458 )=
209014.2 N/m2
4.58
Ka =
1 - sin 30
=
1 - 0.5
=
0.5 = 1
= 0.333
1 + sin 30 1 + 0.5 1.5 3
\ Latral pressure due to dead load and live load = Pv x Ka
p = 162000 x 0.3333 = 54000 N/m2
Latral pressure due to soil Ka x w x h = 0.3333 x 18000 h= 6000 h
Hence total pressure = 54000 + 6000 h
Latral presure intencity at top = 54000 N/m2
Latral pressure intencity at bottom = 54000 + 6000 x 5.135 = 84810 N/m2
Fig 1 show the box culvert w= 176500 N/m2
1 1/2
Distribution factore for AD and DA= = 2/3 Distribution factore for AB and DC= = 1/3
1+1/2 1+1/2
1/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
2 2
M/S MJ CONSULTANCY
wL 176500 x 5.135 =
Fix end moments will be as under : MFAB= = -387833 N-m
12 12
Mfdc= +
wL2
=
209014 x 5.135 2= 459277.8 N - m
12 12
MFAD = +
54000 x 5.135 2
+ 30810 x 5.135
x
5.135 = 145738 N-m
12 2 15
2
pL WL
MFDA = - -
12 15
MFDA = -
54000 x 5.135 2-
- 30810 x 5.135
x
5.135 = -118657 -40620 = -159277
12 2 10
The Moment distribution is carried out as illustrate in table
Fixed End Moments
Member DC DA AD AB 259567 176500 259567
459277.8 -159277 145738 -387833 134740
Member DC DA AD AB 134740
259567
Distribution factore 0.33 0.67 0.67 0.33 54000 203225
2/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
M/S MJ CONSULTANCY
Net B.M. at F = 548045.663 - 316538 = 231508 N-m
For vertical member AD , Simply supported B.M. At mid span
54000 x 4.58 2+
Simply supporetd at mid sapn = 1/16 x 30810 x 4.58 2= 181983
8
316538 + 259567
Net B.M. = = 288053 - 181983 = 106069 N-m
2
3 Case 2 : Dead load and live load from out side and water pressure from inside.
In this case , water pressure having an intensity of zero at A and 9800 x 5.14 = 50323 N/m2
At D, is acting, in addition to the pressure
considered in case 1. The various pressures are
w= 176500 N/m2
marked in fig 3 .The vertical walls will thus be
subjected to a net latral pressure of 54000 54000 54000
Itensity = 54000 N/m2 At the Top 19513
D F C
84810 84810 34487
w = 209014 N/m2
Fig 3
2
wL = 176500 x 4.58 2=
Fix end moments will be as under : MFAB= -308528 N-m
12 12
Mfdc= wL
=
2
209014 x 4.58 = 365363.8 N - m
2
12 12
MFAD = +
34487 x 4.58 2
+ 19513 x 4.58
x
4.58 = 80751 N-m
12 2 10
MFDA = - pL2 WL
-
12 15
MFDA = -
34487 x 4.58 2- 19513 x 4.58
x
4.58 = -73928 N -m
12 2 15
The moment distribution is carrired out as illustred in table.
Fixed End Moments
Member DC DA AD AB 186701 176500 186701
365363.8 -73928 80751 -308528 113976
Member DC DA AD AB
186701
Distribution factore 0.33 0.67 0.67 0.33 54000 113976 395048
3/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
M/S MJ CONSULTANCY
4 Case 3 : Dead load and live load on top water pressure from inside no live load on side.
in this case, it is assume that there is no latral oressure due to live load . As before .
The top slab is subjected to a load of '= 176500 N/m2
and the bottom slab is subjected to a load w= 176500 N/m2
Earth pressure intensity at top = 4000 N/m2 50323 w= 209014 N/m 50323
Fig 5
Earth pressure intensity at Bottom= 4000 + 6000 x 5.14 = 34810 N/m2
In addition to these, the vertical wall lslab subjectednto water pressure of intensity ZERO at top and 50323
N/m2 at Bottom, acting from inside . The lateral pressure on vertical walls Is shown in fig 5 and 6
Mfdc= wL2
=
209014 x 4.58 2= 365363.8 N - m
12 12
MFAD = +
4000 x 4.58 2
- 19513 x 4.58
x
4.58 = -6652 N-m
12 2 15
MFDA = - pL2 WL 6992.1 - 13644
+
12 10
MFDA = -
4000 x 4.58 2- 19513 x 4.58
x
4.58 = 13473 N -m
12 2 10
The moment distribution is carrired out as illustred in table.
4/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
M/S MJ CONSULTANCY
Fixed End Moments
Member DC DA AD AB 143007 176500 143007
365363.8 13473 -6652 -308528 =
The moment distribution carried out as per table 1 for case 1
Joint D A 453163.75 453163.8
Member DC DA AD AB
143007
Distribution factore 0.33 0.67 0.67 0.33 4000 319785
Fix end moment 365363.8 13473 -6652 -308528 A A
Balance -126279 -252558 210120 105060 143007 2.5675
5/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
M/S MJ CONSULTANCY
The section will be design for maximum B.M. = 395048 N -m
for water side force
sst = = 150 N/mm2 wt. of concrete = 25000 N/m3
scbc = = 7 N/mm2 wt of water = 9800 N/mm2
m = 13 for water side force
m*c 13 x 7
k= = = 0.378 K = 0.378
m*c+sst 13 x 7 + 150
j=1-k/3 = 1 - 0.378 / 3 = 0.874 J = 0.874
R=1/2xc x j x k = 0.5 x 7 x 0.87x 0.378 = 1.155 R = 1.155
Provide over all thickness = 580 mm so effective thicknesss = 530 mm
Mr = R . B .D2 = 1.155 x 1000 x 530 2= 324506137 < 395048000 O.K.
395048000 = 5685 mm2
Ast = BMx100/sstxjxD=
150 x 0.874 x 530
3.14xdia2 3.14 x 25 x 25
using 25 mm F bars A = = = 491 mm2
4 x100 4
Spacing of Bars =Ax1000/Ast 491 x 1000 / 5685 = 86 say = 80 mm
Hence Provided 25 mm F Bars @ 80 mm c/c
Acual Ast provided 1000 x 491 / 80 = 6133 mm2
Bend half bars up near support at distance of L/5 = 4.58 / 5 = 1.00 m
0.1 x( 580 - 100 %
Area of distributionn steel = 0.3 - = 0.16
450 - 100
Ast = 0.16 x 580 x 10 = 945 mm2 area on each face= # mm2
2
3.14xdia 3.14 x 12 x 12
using 12 mm F bars A = = = 113 mm2
4 x100 4
Spacing of Bars = Ax1000/Ast = 113 x 1000 / 473 = 239 say = 230 mm
Hence Provided # mm F Bars @ 230 mm c/c on each face
Section at supports :-
Maximum B.M.= 259567 N-m. There is direct compression of 134740 N also.
But it effect is not considered because the slab is actually reinforced both at top and bottom .
Since steel is at top sst = 230 N/mm2 concrete M 20
k = 0.283 J = 0.9055 R = 0.8985
259567000
\ Ast = = 2352 mm2
230 x 0.906 x 530
Area available from the bars bentup from the middle section = 6133 / 2 = 3066 mm2
2352 < 3066 Hence these bars will serve the purpose. However, provide 8 mm dia. Additional bars
@ 200 mm c/c
6 Design of bottom slab:
The bottom slab has the following value of B.M. and direct force.
Case B.M. at Center (F) B.M. at ends (D) Direct force (ha)
(i) 231508 316538 183135
(II) 461292 227625 113215
(II) 364116 183930 15160
The section will be design for maximum B.M. = 316538 N -m, and direct force = 536644 N
316538 x 1000
Eccentricity = = 590 mm
536644
proposed thickness of side wall '= 580 mm \ e/D 590 / 580 = 1.017 < 1.5 OK
thickness of side wall is OK
Let us reinforce the section with 20 mm F bars @ 110 mm c/c provided on both faces, as shown
in fig xxx . With cover of 50
mm and D = 580 mm
1000 3.14 x 20 x 20
Asc = Ast = x = 2855 mm2
110 4
The depth of N.A. is computed from following expression:
b n D - dt - n + (m - 1)Asc 1 (n - dc)(D - dt- dc)
3 3 n D
= e+ - dt
b n + (m -1) Asc n - dc D - dt - n 2
- m Ast
n n
1000 n n 2854.5
580 - 50 - + 12 x x n - 50 x -100
or 2 3 n
1000 n+ 2855 2854.5
12 x x n - 50 - 13 x x 580 - 50 -n
2 n n
7/8
DESIGN OF BOX TYPE CULVERT(SIZE 4mX4.55m) FOR AAI, BARAPANI, SHILLONG PREPARED BY:
M/S MJ CONSULTANCY
n -3425455
500 n 530 - + n - 50 x
3 n
= 590 + 240
34255 37109
500 n+ x n - 50 - x 530 - n
n n
-171272727
265000 n - 167 n2 + -3425455 -
n
= 830
1712727.3 19667818
500 n + 34254.5455 - - + 37109
n n
multiply by n
265000 n2 - 167 n3 + -3425455 n - -171272727
= 830
500 n2 + 34254.5455 n- 1712727.3 - 19667818 + 37109 n
8/8