Specifications: R410A Tropical Split Type Technical Manual Specifications

The document provides specifications for 4 models of split type air conditioners that use R410A refrigerant. The specifications include power supply requirements, temperature settings, capacities, airflow, noise levels, refrigerant type, dimensions, weights and shipping information. Key specifications are the cooling capacities of 76,000 and 96,000 BTU/h, heating capacities of 78,000 and 105,000 BTU/h, and SEER ratings of 2.92 to 2.93. Indoor units have centrifugal fans and remote controllers. Outdoor units use capillary tubes and have copper tube and aluminum fin coils.

Uploaded by

grwg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views

Specifications: R410A Tropical Split Type Technical Manual Specifications

The document provides specifications for 4 models of split type air conditioners that use R410A refrigerant. The specifications include power supply requirements, temperature settings, capacities, airflow, noise levels, refrigerant type, dimensions, weights and shipping information. Key specifications are the cooling capacities of 76,000 and 96,000 BTU/h, heating capacities of 78,000 and 105,000 BTU/h, and SEER ratings of 2.92 to 2.93. Indoor units have centrifugal fans and remote controllers. Outdoor units use capillary tubes and have copper tube and aluminum fin coils.

Uploaded by

grwg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

R410A Tropical Split Type Technical Manual Specifications

2. Specifications
Model MTA-76CRN1 MTA-76HRN1 MTA-96CRN1 MTA-96HRN1
Power supply - 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz
Temp. setting range ℃ ≥17 ≤30 ≥17 ≤30
Rated input power W 11700 11700 14400 14400
Rated current A 19.3 19.3 23.7 23.7
Btu/h 76000 76000 96000 96000
Capacity
W 22000 22000 28000 28000
Cooling
Input W 7500 7500 9600 9600
EER W/W 2.93 2.93 2.92 2.92
Btu/h / 78000 / 105000
Capacity
W / 25000 / 31000
Heating
Input W / 8300 / 10300
COP W/W / 3.01 / 3.01
3
Indoor air flow m /h 4250 4250 5100 5100
Indoor standard ESP Pa 100 100 100(98) 100(98)
Indoor noise level dB(A) 54 54 55 55
Type - R410A R410A R410A R410A
Refrigerant
Control - Capillary Capillary
Type - Centrifugal fan Centrifugal fan Centrifugal fan Centrifugal fan
Dimension mm Φ307 Φ307 Φ307 Φ307
Fan Drive type/ Motor step - Direct/ Single Direct/ Single Direct/ Single Direct/ Single
Motor input* No. W 446*2 446*2 725*2 725*2
Motor speed rpm 877 877 1136 1136
Type - Copper tube and aluminum fin Copper tube and aluminum fin
Tube size mm Φ9.52 Φ9.52 Φ9.52 Φ9.52
Coil No. of rows - 3 3 4 4
Fin per inch FPI 17 17 17 17
Length* height mm 1200*406.4 1200*406.4 1200*406 1200*406
Controller - Remote controller Remote controller
Drain pipe size mm 41 41 41 41
Dimension (W*H*D) mm 1350*760*450 1350*760*450 1350*760*450 1350*760*450
Packing (W*H*D) mm 1549*476*917 1549*476*917 1549*917*476 1549*917*476
Net/Gross weight kg 105/120 105/120 105/120 105/120
Shipping Qty.(20’/40’/40’HQ) pcs. 30/64/64 30/64/64 30/64/64 30/64/64

Notes:
1. ESP: external static pressure
2. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB, 24 °CWB; Equivalent refrigerant piping: 7.5m (horizonta l).
3. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB, 15°CWB; Outdoor temp: 7°CDB, 6°C WB; Equivalent refrigerant piping: 7.5m (horizontal).