Modular Laf

This document provides specifications for a CleanFLOW vertical laminar flow booth. The booth uses a stainless steel body structure, aluminum filter grid, G3 prefilters with 80-90% efficiency, and H14 HEPA main filters with 99.995% efficiency. It comes in standard sizes that can be customized and is designed to provide a Class 3 clean room environment according to ISO 14644-1 standards. The booth features electrical components, automatic air flow control, and accessories like protective grids and curtains.

Uploaded by

annunakipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
74 views

Modular Laf

This document provides specifications for a CleanFLOW vertical laminar flow booth. The booth uses a stainless steel body structure, aluminum filter grid, G3 prefilters with 80-90% efficiency, and H14 HEPA main filters with 99.995% efficiency. It comes in standard sizes that can be customized and is designed to provide a Class 3 clean room environment according to ISO 14644-1 standards. The booth features electrical components, automatic air flow control, and accessories like protective grids and curtains.

Uploaded by

annunakipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

VERTICAL LAMINAR FLOW

BOOTH

CleanFLOW Booth
VFU unit
Vertical Clean Room Booth

PROTECTION, SAFETY, RELIABILITY.


AND MORE.
CleanFLOW VFU unit
Ver tical Clean Room Booth
Class 3 - EN ISO 14 6 6 4 4 -1

TECHNICAL SPECIFICATION
 Body structure fully made in stainless steel AISI 304L
4B (Scotch Brite) and press-bent metal sheets with a
radius of 3 mm for easy cleaning and roughness lower
than 0,8Ra.
 Anodized aluminium filter protective grid.
 Prefiltration stage consisting of G3 filtration cells made
in AISI 304L stainless steel with typicall arrestance of
80 ≤ Am > 90 according to EN 779.
STANDARD MODULE SIZES
 Filtration stage consisting of main H14 HEPA filter (width x depth x height)
certified low pressure drop with typical efficiency of  FU 22 BR/SR 680 x 680 x 600 mm

99.995% MPPS according to CEN EN 1822.  FU 24 BR/SR 1360 x 680 x 600 mm

 Filters replacement from the bottom (BR series)  FU 33 BR/SR 1000 x 1000 x 600 mm
or from the side of the module (SR series).  FU 34 BR/SR 1360 x 1000 x 600 mm

 Improved bag plenum design for better air flow Custom dimensions are always available upon request.
diffusion and lower noise level.
 Negative pressure pattern conforming to GMP Faster Unit modules are Vertical Laminar Flow units
requirements to prevent risks of escape of providing Class ISO 3 according to ISO 14644-1 - which
contaminated external air – or it by-passing filter can be joined together to build up small to room size
- and to reduce pressure transition losses. clean room environments. These LAF modules can be
supported by stainless steel legs or suspended from the
 Outlet for DEHS filter integrity test.
ceiling by means of eye-bolts positioned on top of each
 Ventilation is provided by double inlet centrifugal AC module.
motorblower.

Faster/CleanFLOWBoth2015/01/In this brochure all pictures and specifications are purely indicative and may vary without notice
Polycarbonate or PVC strip curtains with quick release
 Electrical supply 230 V/50 Hz monophase. system on the surrounding edges of the modules,
contain and separate the clean area from the external
environment. Tailor-cut size modular units can be
MAIN ACCESSORIES
assembled and suspended on top of the restricted
 Automatic air flow speed regulation with digital area barrier (RABS) over drug-making pharmaceutical
display. machines to protect the sterility of the products during
 ABS or Stainless Steel remote control box. filling operations.

 Stainless steel H14 HEPA filter protective grid. Special FASTER LAF modules, can be used in several
ways in the food and beverage industries to create a
 Backlit functional buttons integrated in stainless steel leg.
strong overpressure inside the food filling machine
Stainless steel legs with castors. to prevent external contaminants to reach the filling
Stainless steel blind panels or fitted with manometer. process.

Faster S.r.l.
Via R. Merendi, 22 20010 Cornaredo (MI) Italy
Tel +39 02 93 991 92 Fax +39 02 93 991 608
www.faster-air.com [email protected]

You might also like