CHAPTER 8
DESIGN OF COMPOSITE BEAM PART 3
Shear
connector
Steel deck
Concrete floor
Steel deck
• Typical composite system
Composite primary beams
Floor slab
span between columns
secondary beam
Steel deck (embossed decking)
Shear Stud
Metal/steel decking
Without shear
connector
L/2 L/2
(a) elevation (b) section
fb fv
No interaction
Full interaction
• NO INTERACTION
My max 1 / 8( w / 2) L2 (h / 2) 3wL2
Bending stress: fb 3
I 1 / 12bh 8bh 2
3 V 3 wL 1 3wL
Shear stress: f v , max
2 A 2 4 bh 8bh
5 ( w / 2) L4 5wL4
Maximum deflection:
384 EI 64 Ebh 3
• FULL INTERACTION
3 wL 1 3wL
Shear stress: f v , max
2 2 b(2h) 8bh
5wL4
Maximum deflection:
256 Ebh 3
8.3 Elastic Stress Analysis
Mc VQ
fb and fv
I tI
We first require that the strain in the concrete at any point be equal to the
strain in any replacement steel at that point:
fc f
c s; s
Ec E s
Es E
f s fc nf c , n s is modular ratio
Ec Ec
b b/n
ts ts
y yt
yb
We can then compute bending stresses with the flexure formula. At the top
of the steel,
My t fc
f st
I tr
My b f st
At the bottom of the steel: f sb
I tr
My
The stress in the concrete: fc f sb
nI tr strain
Actual stress
Contoh : Tentukan tegangan pada penampang komposit WF dengan pelat
beton, bila momen yang bekerja 320 kNm
b 2040mm b / n 240mm
t s 140mm 140mm
y
yt
450 x200x9x14 yb
f c' 25MPa
Section properties WF 450 x200 x9 x14
E 4700 f c' 23500MPa
I x 33500cm , I y 180cm , A 96.8cm
4 4 2
S x 1490cm 3 Es 200000
n 8.5
Ec 23500
Assumed the neutral axis at steel section
Taking moment at the top of the slab
1
I tr (240)(125) 3 (33500 x10 4 ) (9680)( 225 15) 2
3
I tr 1.049 x109 mm 4
Shear connector be L / 4 s
In accordance with AISC 360 Sec. I3.1a, the maximum effective width
of the concrete slab, on either side of the beam centerline, is given as
be = one-eighth of the beam span
≤ one-half of the beam spacing
≤ the distance to edge of the slab
• Nominal Strength
At the ultimate load, the location of the plastic neutral axis may be
either within the depth of the concrete slab, within the flange of the
steel beam, or within the web of the steel beam
It is further assumed that any portion of the concrete slab below the
plastic neutral axis has zero stress and is neglected.
• Nominal Strength of Fully Composite Beam
be 0.85 f c'
a a/2
ycon t c y2 PNA
tf y
d /2
d As
tw T As Fy
(a)
bf
0.85 f c' Fy
0.85 f c'
a a
PNA
PNA
(b) (c)
Fy Fy Fy Fy
Case a: As Fy 0.85 f c' Ac
ycon t c
The distance from top of steel beam to compression force in concrete slab is
y2 ycon a / 2
The moment arm between centroids of the tensile force and the
compressive force is
y y2 d / 2
The nominal flexural capacity is then
M n Ty As Fy ( y2 d / 2)
b M n 0.9 As Fy ( y2 d / 2)
M n / b As Fy ( y2 d / 2) / 1.67
When the plastic neutral axis is in the concrete slab, the steel beam has
fully yielded in tension. Then the shear force developed at the interface
between the point of maximum positive moment and the point of zero
moment is given by AISC 360 Eq. (I3-1b) as
Vr' Fy As
When the plastic neutral axis is within the steel beam, the full depth of the
concrete slab is stressed to its maximum capacity in compression. Then
the shear force developed at the interface between the point of maximum
positive moment and the point of zero moment is given by AISC 360 Eq.
(I3-1a) as
n Vr' / Qn
where is Qn nominal strength of one steel anchor