0% found this document useful (0 votes)
726 views

Power System Analysis Complex Engineering Problem

This project report describes the load flow and fault analysis of an extended 13-bus power system using ETAP software. The system includes 4 generators, 4 transformers, 13 buses, 9 transmission lines, and 5 loads. Load flow analysis was performed and fault currents and short circuit capacities were calculated for faults at each bus. In conclusion, the objectives of designing a power system and performing load flow and fault analysis using a modern tool were achieved.

Uploaded by

mhrs11
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
726 views

Power System Analysis Complex Engineering Problem

This project report describes the load flow and fault analysis of an extended 13-bus power system using ETAP software. The system includes 4 generators, 4 transformers, 13 buses, 9 transmission lines, and 5 loads. Load flow analysis was performed and fault currents and short circuit capacities were calculated for faults at each bus. In conclusion, the objectives of designing a power system and performing load flow and fault analysis using a modern tool were achieved.

Uploaded by

mhrs11
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 13

POWER SYSTEM ANALYSIS LAB

PROJECT REPORT

Engineering Attributes
PLO-3: Design and Development
PLO-5: Modern tool usage

Submitted by: Muhammad Haris


Registration Number: 13R/14-EE-179
Group: C2

JANUARY 19, 2018


UNIVERSITY OF ENGINEERING & TECHNOLOGY TAXILA
Electrical Engineering department
Power system Analysis | Project report

Objective:
To Design a power system for the given requirements on any modern tool and
to perform load flow and short circuit analysis of that system.

Chosen Power system:


The standard IEEE 9-Bus system has been chosen as the base of this system
having an extension of 4 more buses. Following are the main components of
the Power system:
1. 4 Generators
2. 4 Transformers
3. 13 Buses
4. 9 Transmission Lines
5. 5 Loads

Extension of IEEE- 9 Bus System

1
Power system Analysis | Project report

Load Flow Analysis:

2
Power system Analysis | Project report

General Info:

Transformer information:

Loads:

Sources:

3
Power system Analysis | Project report

Fault Analysis
Fault at Bus 1:

Fault Current= 63.51kA


Pre-fault Voltage= 17.16 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1887.6 MVA

Fault at Bus 2:

Fault Current= 53.96kA


Pre-fault Voltage= 18.45 kV

4
Power system Analysis | Project report

Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent


= 1724.4 MVA

Fault at Bus 3:

Fault Current= 59.09kA


Pre-fault Voltage= 14.145 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1447.7 MVA

Fault at Bus 4:

5
Power system Analysis | Project report

Fault Current= 4.82kA


Pre-fault Voltage= 229.7 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA

Fault at Bus 5:

Fault Current= 4.82kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1916.8 MVA

Fault at Bus 6:

6
Power system Analysis | Project report

Fault Current= 4.81kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1912.8 MVA

Fault at Bus 7:

Fault Current= 4.82kA

7
Power system Analysis | Project report

Pre-fault Voltage= 229.7 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA
Fault at Bus 8:

Fault Current= 4.78kA


Pre-fault Voltage= 229.7 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1901.7 MVA

Fault at Bus 9:

8
Power system Analysis | Project report

Fault Current= 34.65kA


Pre-fault Voltage= 18 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 10803 MVA

Fault at Bus 10:

Fault Current= 4.82kA

9
Power system Analysis | Project report

Pre-fault Voltage= 229.6 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA

Fault at Bus 11:

Fault Current= 4.8kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.8 MVA

Fault at Bus 12:

10
Power system Analysis | Project report

Fault Current= 4.8kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.9 MVA

Fault at Bus 13:

Fault Current= 4.8kA

11
Power system Analysis | Project report

Pre-fault Voltage= 229.6 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.8 MVA

Conclusion:
Hence Load flow Analysis and Fault Analysis has been done under given
constraints on ETAP.

12