W MF D Equivalent) : W D Equivalent) : MF W A A

This document provides specifications for designing a low voltage harmonic filter for a power system operating at 60 Hz with a 480 V nominal bus voltage. It includes system information like filter tuning frequency, load harmonic current percentage, and capacitor bank rating. Capacitor and filter reactor duty calculations are shown to verify the design meets IEEE standards for peak voltage, RMS current, kVAR rating, and RMS voltage. The filter reactor design specification is also given.

Uploaded by

black_eng
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views

W MF D Equivalent) : W D Equivalent) : MF W A A

This document provides specifications for designing a low voltage harmonic filter for a power system operating at 60 Hz with a 480 V nominal bus voltage. It includes system information like filter tuning frequency, load harmonic current percentage, and capacitor bank rating. Capacitor and filter reactor duty calculations are shown to verify the design meets IEEE standards for peak voltage, RMS current, kVAR rating, and RMS voltage. The filter reactor design specification is also given.

Uploaded by

black_eng
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

EPE 642: Power System Qulaity

Low Voltage Harmonic Filter Calculatio Prepared by: Dr. Eyad A. Feilat

System Information:

Filter Specification: 7 th Power System Frequency: 60 Hz

Nominal Bus Voltage: 480 V Capacitor Voltage Rating: 480 V


Capacitor Frequency Rating: 60 Hz
3-ph. Capacitor Bank Rating: 500 kVAR Derated Capacitor: 500 kVAR

Capacitor Current (Rated): 601.4 A Total Harmonic Load: 750 KVA

Capacitor Current (Actual): 601.4 A Filter Tuning Frequency: 282 Hz

Filter Tuning Harmonics: 4.7 th

Capacitor Impedance (Y equivalent): 0.4608 W Capacitor Capacitance (Y equivalent): 5756.4587 mF


Capacitor Impedance (D equivalent): 1.3824 W Capacitor Capacitance (D equivalent): 1918.8196 mF

Filter Reactor Reactance: 0.0209 W Filter Reactor Inductance: 0.0553 mH

Filter Full Load Current (Actual): 629.9 A Fundamental Frequency Compensation: 523.70792 kVAR
Filter Full Load Current (Rated): 629.9 A
Utility Side harmonic Voltage Distortion: 2.50 %
Transformer Name Plate Rating: 1500 KVA
Transformer Name Plate Impedance: 6 %

Load Harmonic Current: 33.3 % Fund. Load Harmonic Current: 300.7 A

Utility harmonic Current: 47.9 A Maximum Total Harmonic Current: 348.6 A

CAPACITOR DUTY CALCULATIONS:

Filter RMS Current: 719.9 A Fundamental Cap. Voltage 502.8 V

Harmonic Capacitor Voltage: 39.7 V Maximum Peak Voltage: 542.5 V

RMS Capacitor Voltage: 504.3 V Maximum Peak Current: 978.5 A

Filter Configuration:
Capacitor Limits: (IEEE Standard 18-2002) Bus Voltage 480
Limit Contingency Actual Value
Peak Voltage (V) 100% 120% 113 543 XL (W) = 0.0209
RMS Current (A) 100% 135% 120 720 500 kVAR @
kVAR 100% 135% 126 629 480 V
RMS Voltage (V) 100% 110% 105 504 XC (W)-Y= 0.4608
XL (W)-D= 1.3824

Filter Reactor Design Specification:

Reactor Impedance 0.0209 W Reactor Rating: 0.0553 mH


Fundamental Current 629.9 A Harmonic Current: 348.6 A