Control Valve
Control Valve
2
Control Valve
Final Control Elements (FCE):
Electric :
• Electric Heater, Thyristor Bridge
• Solenoid
• Stepping Motor
• DC Motor
• AC Motor 3
Control Valve
Direct Acting Actuator: A diaphragm actuator in which the actuator stem moves down
with increasing diaphragm pressure. 6
Major Components of Control Valve
Reverse Acting Actuator: A diaphragm actuator in which the actuator stem moves up with
increasing diaphragm pressure. 7
Major Components of Control Valve
8
Control Valve
The control valve assembly typically consists of
• the valve body,
• the internal trim parts,
• an actuator to provide the motive power to operate the
valve,
• positioners,
• transducers,
• supply pressure regulators,
• manual operators,
• limit switches.
9
Control Valve - Trim
10
Control Valve
11
Types of Regulating Valves
GATE VALVES
GLOBE VALVES
PLUG VALVES
DIAPHRAGM VALVES
BALL VALVES
BUTTERFLY VALVES
NEEDLE VALVES
CHECK VALVES
PRESSURE RELIEF VALVES
12
Gate Valves
The flow in the valve takes a vertical path from down to top through the seat
ring, allowing effective flow control with shorter plug travel . 14
Globe Valves
In the port-guided valve, the
seat ring acts as a guide for
the plug to keep the
centerlines of the plug and
seat always aligned,
minimizing guiding stresses
that would otherwise be placed
on the stem. This means that
the stem may be made smaller
in diameter than if the valve
trim were stem-guided,
minimizing sliding friction and
improving control behavior.
15
Globe Valves
A balanced plug has one or more ports drilled from top to bottom,
allowing fluid pressure to equalize on both sides of the plug. This helps
minimize the forces acting on the plug which must be overcome by the
actuator. 16
Globe Valves
18
Diaphragm Valves
19
Ball Valves
20
Butterfly Valves
21
Niddle Valves
22
Check Valves
1. Valve Body
2. Inlet Port
3. Outlet Port
4. Coil / Solenoid
5. Coil Windings
6. Lead Wires
7. Plunger
8. Spring
9. Orifice 25
Two Port Valve
26
Three Port Valve
27
Valve Packing
All stem-actuated control valves require some form of seal allowing motion of
the stem from some external device (an actuator ) while sealing process fluid
such that no leak occurs between the moving stem and the body of the
valve. The general term for this sealing mechanism is packing. 28
Valve Seat Leakage
It is important that the control valve be able to completely stop fluid flow
when placed in the “closed” position. Although this may seem to be a
fundamental requirement of any valve, it is not necessarily so. In many
applications, there may have some allowable leakage, where as in
some other application needs tight shut-off. For this reason, several
classifications for control valves, rating them in their ability to fully shut
off are available in accordance with ANSI/FCI 70−2 and IEC 60534-4.
29
Pneumatic Actuators
The fail-safe mode of a pneumatic/spring valve is a function of both the
actuator’s action and the valve body’s action, where, upon loss of
actuating energy supply, will cause a valve closure member to be fully
closed, fully open, or remain in the last position, whichever position is
defined as necessary to protect the process.
Direct/Reverse acting Actuators:
Direct-acting actuator pushes down on the stem with increasing pressure.
Reverse-acting actuator pulls up on the stem with increasing pressure.
Direct/Reverse acting Valve Bodies:
Direct-acting if they open up when the stem is lifted.
Reverse-acting if they shut off (close) when the stem is lifted.
Thus, a sliding-stem, pneumatically actuated control valve may be made
air-to-open or air-to-close simply by matching the appropriate actuator and
body types. 30
Pneumatic Actuators
31
Pneumatic Actuators
32
Air To Close Valve
∆PFLOW =−
P1 P2
ΔP SHUTOFF = P1 - PLOAD
1. Usually Δ P SHUTOFF > Δ P FLOW
2. ΣFup = ΣFdown
P1 × Aport + Fspring + ζPacking
=PLOAD × ADiaphragm + P2 × Aplug
37
Actuator Bench-Set
If the stem connector is set with the actuator and valve stems spaced too far apart (i.e. the
total stem length is too long), the actuator diaphragm will bind travel at the upper end and
the valve plug will bind travel at the lower end. The result is a valve that cannot ever fully
38
open.
Actuator Bench-Set
If the stem connector is set with the actuator and valve stems too closely coupled (i.e. the
total stem length is too short), the actuator diaphragm will bind travel at the lower end
and the valve plug will bind travel at the upper end. The result is a valve that cannot ever
39
fully close.
Pneumatic Actuator Response
A limitation inherent to pneumatic valve actuators is the amount of air
flow required to or from the actuator to cause rapid valve motion.
The combined effect of air-flow friction in the tube, flow limitations
inherent to the controller mechanism, and volume inside the valve
actuator conspire to create a sluggish valve response to sudden
changes in controller output signal.
40
Pneumatic Actuator Response
If the pneumatic valve actuator is driven by an I/P transducer instead of directly
by a pneumatic controller, the problem is lessened by the ability to locate the I/P
close to the actuator, thus greatly minimizing tube friction and thus minimizing
the “time constant” (τ ) of the control valve’s response.
42
Pneumatic Actuator Response
A pneumatic control system equipped with a volume booster
would look something like this.
Of course, enhanced air flow to and from the actuator does not
completely eliminate time delays in valve response. So long as
the flow rate into or out of an actuator is finite, some time will be
required to change pressure inside the actuator and thus
change valve position. 43
Valve Positioners
Springs work quite nicely to convert mechanical force into
mechanical motion (Hooke’s Law : F = kx) for valve actuators if
and only if the sole forces involved are the diaphragm or piston
force against the spring’s resistance force. If any other force
acts upon the system, the relationship between actuating fluid
pressure and valve stem travel will not necessarily be
proportional.
Unfortunately, there typically are other forces acting on a valve
stem besides the actuating fluid pressure’s force and the
spring’s reaction force. Friction from the stem packing is one
force, and reaction force at the valve plug caused by differential
pressure across the plug’s area is another. These forces
conspire to re-position the valve stem so stem travel does not
precisely correlate to actuating fluid pressure.
A common solution to this dilemma is to add a positioner to the
control valve assembly.
44
Valve Positioners
A positioner is a motion-control device designed to actively compare
stem position against the control signal, adjusting pressure to the
actuator diaphragm or piston until the correct stem position is reached.
The technical term for this type of control system is cascade, where one
controller’s output becomes the set-point for a different controller. In the
case of a valve positioner, the positioner receives a valve stem position
set-point from the main process controller.
45
Valve Positioners
Inputs are:
• Supply air (usually 20PSI)
• Valve position (PV)
• A valve position (command) signal (SP)
Either 3-15PSI or
4-20ma
50
Valve Signature
The red graph shows the valve’s response in the opening direction where additional
pressure is required to overcome packing friction as the valve moves open (up).
The blue graph shows the valve as it closes, less pressure applied to the diaphragm now to
allow the spring’s compression to overcome packing friction as the valve moves closed
(down) to its resting state.
The sharp turns at each end of this graph show where the valve stem reaches its end
positions and cannot move farther despite further changes in actuator pressure.
Each plot is roughly linear in accordance with Hooke’s Law describing the behavior of the
valve spring, Any departure from a single linear plot indicates the onset of some other
force(s) on the valve stem other than the spring’s compression. This is why we see two plots
vertically offset from each other.
Packing friction is another force acting on the valve stem besides the spring’s compression.
When the valve is opening, friction works against the actuator’s air pressure (assuming an
air-to-open valve), requiring additional air pressure to maintain motion. When the valve is
closing, though, packing friction works in the same direction as the actuator’s air pressure
“helping” the valve stay more open than it should. This is why the positioner must maintain
less actuator air pressure for any given position while moving closed than while the valve
moves open. The difference in air pressure moving open versus moving closed at any given
stem position is proportional to twice the dynamic packing friction. Stated mathematically,
Fpacking = (Popening − Pclosing )A.
51
Control Valve Split-Ranging
52
Complementary Valve Sequencing
With this form of split-ranging, there is never a condition in the controller’s
output range where both valves are fully open or fully shut. Rather, each
valve complements the other’s position.
53
Complementary Valve Sequencing
Both base and pigment valves operate from the same 3 to 15 PSI pneumatic
signal output by the I/P transducer (AY), but one of the valves is Air-To-Open
while the other is Air-To-Close.
54
Complementary Valve Sequencing
An alternative to complementary valve sequencing in a process where two
fluid streams mix (or diverge) is to use one three-way valve rather than a pair
of two-way valves:
55
Exclusive Valve Sequencing
With this form of valve sequencing, both valves are fully closed at a 50% controller output signal,
with one valve opening fully as the controller output drives toward 100% and the other valve
opening fully as the controller output goes to 0%.
The nature of this valve sequencing is to have an “either-or” throttled path for process fluid. That
is, either process fluid flows through one valve or through the other, but never through both at
the same time.
56
Exclusive Valve Sequencing
Both reagent control valves operate from the same 3 to 15 PSI pneumatic signal
output by the I/P transducer (AY), but the two valves’ calibrated ranges are not the
same.
The Air-To-Open acid valve has an operating range of 9 to 15 PSI, while the Air-To-
Close caustic valve has an operating range of 9 to 3 PSI.
57
Progressive Valve Sequencing
Some processes demand a greater range of control than any single valve can deliver,
and it is within these processes, a pair of progressively-sequenced control valves is a
valid solution.
The combination of two differently-sized (small and large) control valves are used to
satisfy the process demand.
58
Progressive Valve Sequencing
A pH control process where the incoming liquid always has a high pH value, and must
be neutralized with acid, the progressive valve sequencing may be used.
59
Flow Capacity or Flow Coefficient (Cv)
The amount of kinetic energy represented by a volume of moving fluid in turbulent
motion with velocity v and is given by
Hence
60
Flow Capacity or Flow Coefficient (Cv)
This pressure drop (P1 − P2, or ΔP) is equivalent to dissipated energy per unit volume.
With Q = Av, solving for a quotient with pressure drop (P1 − P2) in the numerator
and flow rate Q in the denominator so the equation bears a resemblance to
Ohm’s Law (R = V/I ):
61
Flow Capacity or Flow Coefficient (Cv)
Either side of the last equation represents a sort of “Ohm’s Law” for turbulent liquid
restrictions.
The left-hand side expressing fluid “resistance” in the state variables of pressure drop
and volumetric flow.
The right-hand term expressing fluid “resistance” as a function of fluid density and
restriction geometry.
We can see how pressure drop (P1 − P2) and volumetric flow rate (Q) are not linearly
related as voltage and current are for resistors, but that nevertheless we still have a
quantity that acts like a “resistance” term:
Where,
R = Fluid “resistance” P1 = Upstream fluid pressure
P2 = Downstream fluid pressure Q = Volumetric fluid flow rate
k = Turbulent energy dissipation factor ρ = Mass density of fluid
A = Cross-sectional area of restriction
62
Flow Capacity or Flow Coefficient (Cv)
The fluid “resistance” of a restriction depends on several
variables: the proportion of kinetic energy lost due to turbulence
(k), the density of the fluid (ρ), and the cross-sectional area of the
restriction (A).
In a control valve throttling a liquid flow stream, only k and A are
subject to change with stem position, fluid density remaining
relatively constant.
It is customary in control valve engineering to express the
“restrictiveness” of any valve in terms of how much flow it will
pass given a certain pressure drop and fluid specific gravity (Gf ).
This measure of valve performance is called flow capacity or flow
coefficient, symbolized as Cv.
A greater flow capacity value represents a less restrictive (less
“resistive”) valve, able to pass greater rates of flow for the same
pressure drop. 63
Flow Capacity or Flow Coefficient (Cv)
65
Control Valve Characterization
Inherent Characteristics
When control valves are tested in a laboratory setting, they are connected to a piping
system that is able to provide a nearly constant pressure difference between upstream
and downstream (P1 − P2).
With a fluid of constant density and a constant pressure drop across the valve, flow rate
becomes a direct function of flow coefficient (Cv ).
The amount of “resistance” offered by a restriction of any kind to a turbulent fluid
depends on the cross-sectional area of that restriction and also the proportion of fluid
kinetic energy dissipated in turbulence.
If a control valve is designed such that the combined effect of these two parameters vary
linearly with stem motion, the Cv of the valve will likewise be proportional to stem
position.
66
Control Valve Characterization
Installed Characteristics
Most real valve installations do not place the control valve under a condition of constant
pressure drop.
Due to frictional pressure losses in piping and changes in supply/demand pressures
that vary with flow rate, a typical control valve “sees” substantial changes in differential
pressure as its controlled flow rate changes.
Generally speaking, the pressure drop available to the control valve will decrease as
flow rate increases.
The result of this pressure drop versus flow relationship is that the actual flow rate of
the same valve installed in a real process will not linearly track valve stem position.
Instead, it will “droop” as the valve is further opened . This “drooping” graph is called
the valve’s installed characteristic.
67
Control Valve Characterization
Let us assume the control valve has a “linear” inherent characteristic and a maximum
flow capacity (Cv rating) of 18.
This means the valve’s Cv will be 18 at 100% open, 13.5 at 75% open, 9 at 50% open, 4.5
at 25% open, and 0 at fully closed (0% open).
We may plot the behavior of this control valve at these four stem positions by graphing
the amount of flow through the valve for varying degrees of pressure drop across the
valve. The result is a set of characteristic curves for our hypothetical control valve.
68
Control Valve Characterization
Inherent Installed
69
Control Valve Characterization
If we plot the valve’s performance in both scenarios we see the difference very clearly.
The “drooping” graph shows how the valve responds when it does not receive a
constant pressure drop throughout the flow range. This is how the valve responds when
installed in a non-ideal process, compared to the straight-line response it exhibits under
ideal conditions of constant pressure.
Any piping system that fails to provide constant pressure across a control valve will
“distort” the valve’s inherent characteristic in the same “drooping” manner, and this
must be compensated in some way if we desire linear response from the valve. 70
Control Valve Characterization
Note how the installed characteristic graph is relatively steep at the beginning
where the valve is nearly closed, and how the graph grows “flatter” at the end
where the valve is nearly full-open. The rate of response (rate-of-change of flow
Q compared to stem position x, which may be expressed as the derivative
(dQ/dx) is much greater at low flow rates than it is at high flow rates, all due to
diminished pressure drop at higher flow rates.
This means the valve will respond more “sensitively” at the low end of its travel
and more “sluggishly” at the high end of its travel.
From the perspective of a flow control system, this varying valve
responsiveness means the system will be unstable at low flow rates and
unresponsive at high flow rates.
At low flow rates, there the valve is nearly closed, any small movement of the
valve stem will have a relatively large effect on flow. However, at high flow rates,
a much greater stem motion will be required to effect the same change in flow.
Thus, the control system will tend to over-react at low flow rates and under-
react at high flow rates, simply because the control valve fails to exert the same
degree of control over process flow at different flow rates.
71
Characterized Valve Trim
The root cause of the problem – a varying pressure drop caused by frictional losses in
the piping and other factors – generally cannot be eliminated.
However, there is a clever way to to purposely design the valve such that its inherent
characteristic complements the process “distortion” caused by changing pressure drop.
In other words, we design the control valve trim so it opens up gradually during the
initial stem travel (near the closed position), then opens up more rapidly during the final
stages of stem travel (near the full-open position).
With the valve made to open up in a nonlinear fashion inverse to the “droop” caused by
the installed pressure changes, the two non-linearities should cancel each other and
yield a more linear response.
This re-design will give the valve a nonlinear characteristic when tested in the laboratory
with constant pressure drop, but the installed behavior should be more linear.
72
Valve Trim Characteristics
Control valve trim is manufactured in a variety of different inherent “characteristics” to
provide the desired installed behavior.
Quick-opening
Linear
Equal percentage
73
Valve Trim Characteristics
Quick-opening
The quick−opening flow characteristic provides for maximum
change in flow rate at low valve travels with a nearly linear
relationship. Additional increases in valve travel give sharply
reduced changes in flow rate, and when the valve plug nears the
wide open position, the change in flow rate approaches zero.
Applications:
On/off applications where
significant flow rate must be
established quickly as the valve
begins to open. consequently,
they are often used in relief valve
applications.
74
Valve Trim Characteristics
Linear
The linear flow characteristic curve shows that the flow rate is
directly proportional to the valve travel. This proportional
relationship produces a characteristic with a constant slope so
that with constant pressure drop, the valve gain will be the same
at all flows throughout the travel range.
Applications:
Valves with a linear
characteristic are often specified
for liquid level control and for flow
control applications requiring
constant gain.
75
Valve Trim Characteristics
Equal Percentage
Ideally, for equal increments of valve plug travel, the change in
flow rate regarding travel may be expressed as a constant percent
of the flow rate at the time of the change.
Applications:
Pressure control applications,
on applications where a large
percentage of the pressure drop is
normally absorbed by the system
itself with only a relatively small
percentage available at the control
valve and on applications where
highly varying pressure drop
conditions can be expected. 76
Valve Trim Characteristics
Equal Percentage
e( lnτ ) H Qmax controllable
Q = Qmax ; where,τ ValveRangeability ,
τ
Qmin controllable
H Valve Lift = =
(0 close ,1 fully open);=
Qmax Max. vol. flow through valve.
Qmax = 10 m3/hr
τ=50
77
Valve Trim Characteristics
78
Valve Sizing
STEP 1: Define the system
79
Valve Sizing
STEP 2: Define a maximum allowable pressure drop for the valve
The usual rule of thumb is that a valve should be designed to use 10-
15% of the total pressure drop or 10 psi, whichever is greater.
For our system, 10% of the total pressure drop is 15 psi which is what
we'll use as our allowable pressure drop when the valve is wide open.
80
Valve Sizing
STEP 4: Preliminary valve selection
Don't make the mistake of trying to match a valve with your
calculated Cv value. The Cv value should be used as a guide
in the valve selection, not a hard and fast rule.
Some other considerations are:
Never use a valve that is less than half the pipe size,
Avoid using the lower 10% and upper 20% of the valve stroke. The
valve is much easier to control in the 10-80% stroke range.
Before a valve can be selected, decide what type of valve will be used.
For our case, it appears the 2 inch valve will work well for our Cv value at about 80-85% of
the stroke range. Notice that we're not trying to squeeze our Cv into the 1 1/2 valve which
would need to be at 100% stroke to handle our maximum flow.
82
Valve Sizing
STEP 5: Check the Cv and stroke percentage at the minimum flow
Cv at minimum flowrate:
Referring back to our valve chart, we see that a Cv of 6.5 would correspond
to a stroke percentage of around 35-40% which is certainly acceptable.
Notice that we used the maximum pressure drop of 15 psi once again in our
calculation. Although the pressure drop across the valve will be lower at
smaller flowrates, using the maximum value gives us a "worst case"
scenario. If our Cv at the minimum flow would have been around 1.5, there
would not really be a problem because the valve has a Cv of 1.66 at 10% stroke
and since we use the maximum pressure drop, our estimate is
conservative. Essentially, at lower pressure drops, Cv would only increase
which in this case would be advantageous.
83
Valve Sizing
STEP 6: Check the gain across applicable flow rates
Gain is defined as:
Now, at our three flow rates:
Qmin = 25 gpm
Qop = 110 gpm
Qdes = 150 gpm
We have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages
are 35%, 73%, and 85% respectively. Now we construct the following table:
Flow Stroke Change in flow
Change in Stroke (%)
(gpm) (%) (gpm)
25 35
110-25 = 85 73-35 = 38
110 73
150 85
150-110 = 40 85-73 = 12
So how do you decide which valve control to use? Here are some rules of thumb
for each one:
2. Linear
a. Used in liquid level or flow loops
b. Used in systems where the pressure drop across the valve is expected to
remain fairly constant (ie. steady state systems)
3. Quick Opening
a. Used for frequent on-off service.
b. Used for processes where "instantly" large flow is needed (ie. safety
systems or cooling water systems.) 85
Control Valve Problems
Mechanical Friction
Flashing
Cavitation
Choked flow
Valve noise
Erosion
Chemical Attack
86
Control Valve Problems
Mechanical Friction
Control valves are mechanical devices having moving parts, and as such
they are subject to friction (static or dynamic), primarily between the
valve stem and the stem packing.
The presence of packing friction in a control valve increases the force
necessary from the actuator to cause valve movement.
Instead of the stem smoothly lifting immediately as pressure exceeds
the bench-set value, the valve will remain fully closed until enough extra
pressure has accumulated in the actuator to generate a force large
enough to overcome spring tension plus packing friction.
Effect of static and dynamic friction induces “slip-stick” response of the
stem motion.
In order to reverse the direction of stem motion, not only does the static
friction have to be “relaxed” from the last movement, but additional
static friction must be overcome in the opposite direction before the
stem is able to move that way.
87
Control Valve Problems
Mechanical Friction
To use numerical quantities, if pressure increments of 0.5 PSI are
required to repeatedly overcome static friction in the upward (opening)
direction, a pressure decrement of approximately twice that (1.0 PSI) will
be required to make the stem go downward even just a bit.
88
Control Valve Problems
Mechanical Friction
89
Control Valve Problems
Flashing
If the fluid being throttled by the valve is a liquid and its
absolute pressure ever falls below the vapor pressure of that
substance, the liquid will begin to boil. This phenomenon, when
it happens inside a control valve, is called Flashing.
Where,
FL = Pressure recovery factor (unit less)
P1 = Absolute fluid pressure upstream of the valve
P2 = Absolute fluid pressure downstream of the valve
Pvc = Absolute fluid pressure at the vena contracta (point of minimum fluid
pressure within the valve) 91
Control Valve Problems
Flashing
The style of valve (ball, butterfly, globe, etc.) is very influential on pressure recovery
factor.
The globe valve does a better job of evenly distributing pressure losses throughout
the path of flow. By contrast, the butterfly valve can only drop pressure at the points
of constriction between the disk and the valve body, because the rest of the valve
body is a straight-through path for fluid offering little restriction at all. As a
consequence, the butterfly valve experiences a much lower vena contracta pressure
(i.e. greater pressure recovery, and a lower FL value) than the globe valve for any
given amount of permanent pressure loss, making the butterfly valve more prone to
flashing than the globe valve with all other factors being equal. 92
Control Valve Problems
Cavitation
If, the pressure recovers to a point greater than the vapor pressure of
the liquid, the vapor will re-condense back into liquid again. This is
called Cavitation.
When vapor bubbles re-condense into liquid they often do so
asymmetrically, one side of the bubble collapsing before the rest of
the bubble. This has the effect of translating the kinetic energy of the
bubble’s collapse into a high-speed “jet” of liquid in the direction of
the asymmetrical collapse.
These liquid “microjets” have been experimentally measured at
speeds up to 100 meters per second (over 320 feet per second).
Each microjet strikes the valve component surface over a very small
surface area, resulting in a very high pressure (P = F/A) applied to that
small area.
The effect of each microjet impinging on a metal surface is to carve
out a small pocket in that metal surface. Over time, the metal will
begin to take on a “pock-marked” look over the area where cavitation
occurs.
93
Control Valve Problems
Photographs of a fluted valve plug and its matching seat are shown here as
evidence of flashing and cavitation damage, respectively:
The flashing damage is responsible for the relatively smooth wear areas
seen on the plug.
Cavitation damage is most prominent inside the seat, where almost all the
damage is in the form of pitting.
The mouth of the seat exhibits smooth wear caused by flashing, but deeper
inside you can see the pock-marked surface characteristic of cavitation,
where liquid microjets literally blasted away pieces of metal. 94
Control Valve Problems
Flashing sounds as though sand were flowing through the valve, cavitation
produces a much louder “crackling” sound comprised of distinct impact
pulses, reminiscent of what gravel or rocks might sound like if they were
somehow forced to flow through the valve.
95
Control Valve Problems
Cavitation-control valve trim:
Valve trim may be specially designed for cavitation abatement by providing
multiple stages of pressure drop for the fluid as it passes through the trim.
A valve equipped with cavitation-control trim will have a different pressure
profile, with multiple vena contracta points where the fluid passes through a
series of constrictions within the trim itself.
This way, the same final permanent pressure drop (P1 −P2) may be achieved
without the lowest pressure ever falling below the liquid’s vapor pressure limit.
96
Control Valve Problems
Choked Flow
“Choked flow” is a condition where the rate of flow through a valve does not
change substantially as downstream pressure is reduced.
Choking occurs when the velocity of the fluid reaches the speed of sound for
that fluid.
Pressure changes propagate through any fluid at the speed of sound within
that fluid.
If a fluid stream happens to move at or above the speed of sound, pressure
changes downstream are simply not able to overcome the stream’s velocity to
affect anything upstream, which explains why the flow rate through a control
valve experiencing sonic (critical) flow velocities does not change with
changes in downstream pressure: those downstream pressure changes cannot
propagate upstream against the fast-moving flow, and so will have no effect on
the flow as it accelerates to sonic velocity at the point(s) of constriction.
97
Control Valve Problems
Choked Flow
99
Control Valve Problems
Erosion
A problem common to control valves used in slurry service (where the process
fluid is a liquid containing a substantial quantity of hard, solid particles) is
erosion, where the valve trim and body are worn by the passage of solid
particles.
Chemical attack
100
References
101
Thank You
102