Design of Composite Floor System Using Profiled Sheets

The document summarizes the design of a composite floor system using profiled steel sheets. It provides the section properties of the Tata Steel ComFlor 80 profile, including a thickness of 0.9mm and profile weight of 0.12 kN/m2. It then calculates the design moment resistance of the section as 44.12 kN/m. The document also analyzes an interior panel from the model that is 4.6m x 10.2m in size. It calculates the self-weight, floor finish, and live loads and determines the maximum factored bending moment is 36.1664 kN/m, which is less than the design moment resistance, confirming the assumed section details are safe.

Uploaded by

Arya Asokan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
559 views2 pages

Design of Composite Floor System Using Profiled Sheets

The document summarizes the design of a composite floor system using profiled steel sheets. It provides the section properties of the Tata Steel ComFlor 80 profile, including a thickness of 0.9mm and profile weight of 0.12 kN/m2. It then calculates the design moment resistance of the section as 44.12 kN/m. The document also analyzes an interior panel from the model that is 4.6m x 10.2m in size. It calculates the self-weight, floor finish, and live loads and determines the maximum factored bending moment is 36.1664 kN/m, which is less than the design moment resistance, confirming the assumed section details are safe.

Uploaded by

Arya Asokan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

1) Design of Composite floor system using profiled sheets

Choosing Tata steel profiled composite deck ComFlor 80 of 450 grade steel

a) Section Properties
Steel grade= 450 N/mm2
Nominal thickness= 0.9 mm
Profile Weight= 0.12 kN/m2 (Manufacture Standards)
Area of Steel, Ap= 1387 mm2/m
Height to NA,e= 47.6 mm
Anti‐crack mesh= A393

b) Design Data
Assume Overall depth of composite slab,ht= 150 mm
Depth of profilre sheet= 80 mm (Manufacture Standards)
Depth of slab,hc= 70 mm
ɼ ap = 1.15
fck = 30 kN/m2
Assume Width,b = 1000 mm

c) Design Method
Compressive force  Ncf= Ap x  fyp = 542739.1304 N
ɼ ap
Depth of neutral Axis,x= 50.25362 mm NA lies within concrete slab

Lever Arm= 81.29348 mm

Design moment resistance,Mrd = 44121151.7 Nmm


44.1211517 kN/m
2) Considering an interior Panel from the Model

a) Design Data
Panel Size 4.6 m X 10.2 m

Designing as one way slab
3
Unit wt of concrete= 2400 kg/m
Volume of concrete of 150 mm tk slab(AS per manufacture standards)= 0.106 m3/m
Concrete wt/m2 2.495664 kN/m
2

2
Self Weight of concrete= 2.495664 kN/m
Self Weight of Profile sheet= 0.12 kN/m2 (Manufacture Standards)
2
Floor Finish= 1.5 kN/m
Live Load= 5 kN/m2
2
Total Load(Factored)= 13.6735 kN/m

Max BM(Sagging)= 36.1664 kN/m

BM < Mrd Hence  Assumed section details are safe