Omicron Overcurrent Example
Omicron Overcurrent Example
Author
OMICRON electronics
Date
September 2010
Application Area
Overcurrent
Version
DirOvcrEx.AE.1
© OMICRON Page 1 of 22
Content
Preface ......................................................................................................................................................... 3
1 Application Example ............................................................................................................................ 3
2 Theoretical Introduction ...................................................................................................................... 4
2.1 Tripping Characteristics ................................................................................................................. 4
2.2 IDMT-Characteristics (51, 51N, 67) ............................................................................................... 5
2.3 Directional Overcurrent Protection (67) ......................................................................................... 6
3 Practical Introduction ........................................................................................................................... 8
3.1 Defining the Test Object ................................................................................................................ 9
3.1.1 Device Settings ................................................................................................................................. 9
3.1.2 Defining the Overcurrent Protection Parameters ............................................................................ 10
3.2 Global Hardware Configuration CMC .......................................................................................... 14
3.2.1 Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A ................... 14
3.2.2 Output Configuration for Protection Relays with a Secondary Nominal Current of 5 A ................... 15
3.2.3 Analog Outputs ............................................................................................................................... 16
3.2.4 Binary Inputs ................................................................................................................................... 16
3.2.5 Wiring of the Test Set ..................................................................................................................... 17
3.3 Defining the Test Configuration ................................................................................................... 18
3.3.1 General Approach ........................................................................................................................... 18
3.3.2 Pick-up Test .................................................................................................................................... 18
3.3.3 Trip Time Characteristic Test .......................................................................................................... 19
3.3.4 Directional characteristic test .......................................................................................................... 21
Please use this note only in combination with the related product manual which contains several
important safety instructions. The user is responsible for every application that makes use of an
OMICRON product.
OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON.
© OMICRON 2010. All rights reserved. This application note is a publication of OMICRON.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical
character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON.
Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this application note represent the technical
status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present.
OMICRON translates this application note from the source language English into a number of other languages. Any
translation of this document is done for local requirements, and in the event of a dispute between the English and a non-
English version, the English version of this note shall govern.
Supplements: Sample Control Center file Overcurrent Example.occ (referred to in this document).
Requirements: Test Universe 2.40 or later; Overcurrent and Control Center licenses.
1 Application Example
Tripping characteristics
t[s] t[s]
t I> t I>
t I>> t I>>
0.14
SI (standard inverse) t TP
I IP 0.02 1
13.5
t T
VI (very inverse)
I IP 1 P
80
EI (extremely inverse) t TP Good adjustment on fuse tripping
I IP 1
2
characteristics possible.
Table 2: IDMT tripping characteristics (range / show IEC 60255-3 or BS 142, section 3.5.2)
1 1
3 3 2 2
4 4
5 5 6 6
7 7
8 8
1. Tripping characteristic for the I> stage (for this example IDMT IEC very inverse)
2. Directional function (for this example forward)
3. Pick-up value of I> stage
4. Time multiplier for the I> stage
5. Tripping characteristic for the I>> stage (DMT for this example)
6. Pick-up value of I>> stage
7. Trip time delay of I>> stage
8. Relay characteristic angle RCA (only for the directional function)
4 4
1 1
7 7 3 3 6 6
Figure 3: Comparison of IEC very inverse tripping characteristics with different time multiplier
Table 3: Short-circuit angle of overhead lines and cables depending on the voltage level
The short-circuit angle sc can be calculated from the resistance R and the reactance X of the
protected object.
X
sc arctan
R
It is clear that the short-circuit current has to be used for determining the direction. For the selection
of the voltage to be applied the following conditions have to be taken into account:
For this, relay connections have been developed which make use of different reference voltages with
corrected phase angles.
0 Iph , Vph Maximum sensitivity with
arc faults.
Not feasible in HV-systems, no
decision with a close fault.
30 Iph , Vph Vph a Reference voltage depending on
the fault.
60 Iph , Vph a
90 Iph , Vph a 2 Vph a Maximum reference voltage
with PhE- and PhPh- faults.
Not feasible for arc faults.
Note: The method that is used for the reference voltage depends on the relay manufacturer. For the
following discussion, we use the overcurrent relay P14x (AREVA).
Va Vsc
φsc
Re
Vb
directional
characteristic line 45° Isc
-45°
Vref
-Vc
Note: The forward direction for the measuring element "phase A" results from the angle range
45 ° > sc > -135 °.
The test module can be found at the Start Page of the OMICRON Test Universe. It can be inserted
into an OCC File as well.
Relay Parameters
This first tab contains the definition of the directional behavior as well as the relay tolerances.
1 1 2 2 3 3
4 4
1 1
5 5
2 2
3 3
4 4
The default overcurrent characteristic is shown above. It contains an IEC Definite Time scheme with
one stage for a phase overcurrent protection. This characteristic has to be adjusted to parameters of
the relay (Table 1):
1. In order to define the elements of the phase overcurrent protection, select Phase as the
Selected element type. Note: In case other element types would also be present in the relay
select the related element types one after another in (1) to enter these elements. The selection
field shows the number of already defined related stages and how many of these are marked as
active.
2. This table shows the elements which define the tripping characteristic for the selected element
type. The name of the first element may be changed according to the name used in the relay,
e.g. "I> stage".
3. The characteristic type of the first element has to be changed to IEC Very inverse (Error!
Reference source not found.).
4. Afterwards I pick-up and the Time index have to be set.
5. Now the second element can be added. It has an IEC Definite Time characteristic, which might
be renamed to "I>> stage". Also I pick-up and the Trip time have to be set.
4 4
1 12 2
The adjustments of the directional characteristic have to be done in the tab Define Element
Directional Behavior:
3. As the relay characteristic angle cannot be entered in the Test Object directly, the Trip sector
definition has to be calculated. Figure 5 shows the difference between the relay characteristic
angle, which is a relay setting, and the Maximum torque angle that can be set in the
Test Object.
Va Vsc
Re
Vb
directional -45°
Vref MTA = -90° + RCA
characteristic line
-Vc
Figure 5: Difference between the relay characteristic angle and the maximum torque angle.
3.2.1 Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A
VA VC
VB Vn
IA
IB
IC
In
VA VC
VB Vn
IA IC
IB In
The analog outputs as well as the binary inputs and binary outputs can be activated individually in
the local Hardware Configuration of the specific test module.
4 4
3 3
1 1
2 2
1. The start command is optional (it is needed if you select Starting as time reference in the test
module or if you want to perform a pick-up / drop-off test).
2. The trip command has to be connected to a binary input. You can use BI1 … BI10.
3. For wet contacts the nominal voltages of the binary inputs have to be adapted to the voltage of
the CB trip command. Or check Potential Free for dry contacts.
4. The binary outputs, the analog inputs etc. will not be used for the following tests.
Start
Trip
Protective
Relay
Va
Vb
Vc
(-) (-)
Ia
Ib
Ic
IE
Trip
(+)
optional
Start
(+)
Pick-up Test: Testing the pick-up value of the overcurrent protection (only if start contact is wired
for this relay).
Trip time characteristic: Verifying the trip times of every element of the tripping characteristic.
Directional characteristic: Verifying the angle of the directional characteristic.
Each of these tests can be done with the Overcurrent test module.
3 3
4 54 5 6 6
1. The trigger for this test has to be set in the Trigger tab. For this example the trigger will be the
start contact. This is the reason why this test cannot be performed if the start contact is not
wired.
2. Settings in the Fault tab will not be needed in this test.
3. As we use the start contact to trigger, Relay with start contact has to be chosen.
4. The phase overcurrent function is tested with a three phase fault. Otherwise a ground fault
protection or a negative sequence protection may interfere.
Note: The pick-up value will be measured and assessed automatically. The drop-off value will be
measured as well, but it will not be assessed. The assessment of the drop-off value and the reset
ratio has to be done manually.
You can add more test lines if needed, e.g., a test in backward direction.
2 2
1 1
3 3
1 1 2 2
3 3
4 4
5 5
6 6
1. As the function to test is a phase overcurrent function, a three phase fault is used. Otherwise a
ground fault protection or a negative sequence protection may interfere.
NOTE: If these functions or elements are present they may be specified in the Test Object in the
same manner as the phase elements were entered in this example. The resulting characteristic
will individually be calculated and shown for each test shot depending on its fault type (1) and
fault angle (2), ensuring a proper assessment according to the expected overall relay behavior.
2. The Angle for the forward direction should be the Maximum torque angle. For reverse
direction it has to be entered shifted by 180 °.
3. As the trip time of the IDMT stage depends on the current, this element has to be confirmed with
more than one test point.
4. Whereas the trip time of the "I>> stage" can be confirmed with only one test point.
5. The directional behavior is tested with one shot in each zone in reverse direction.
6. The value of the "I>> stage" is also confirmed by placing two test points outside of the tolerance
band of this setting.
Instead of directly entering the magnitude value you can express the magnitude by its relation to
an element setting, e.g., set Relative to: to "I>> stage" and set the factor to 1.06 (i.e. 6 % above
the threshold) or 0.94 (i.e. 6 % below the threshold).
Note: Regarding the ways to enter and modify test data please also have a look at the Help of the
module (press F1).
The Trigger and Load settings are the same as explained for the trip time characteristic test. The
Absolute max. time can be reduced, because the test current will be set shortly below the lower
tolerance of the "I>> stage" value.
As this test confirms the angle of the directional characteristic, the test points have to be placed on
both sides of the directional characteristic line. In order to get a correct assessment, they should be
placed just outside of the angle tolerance.