1) Tertiary windings in autotransformers are usually delta-connected but may not always be necessary. Their main purposes are to carry a third voltage, stabilize the neutral during unbalanced loads, and suppress third-harmonic voltages.
2) If included, the tertiary winding should be adequately sized to withstand short-circuit currents it could experience. Its size should not be arbitrarily limited to 35% of other windings.
3) Calculating short-circuit currents on the tertiary involves determining the zero-sequence impedances of the autotransformer and connected systems, which can be estimated but sometimes known only roughly.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
321 views1 page
Tertiary Windings in Autotransformers: 0H H L H L
1) Tertiary windings in autotransformers are usually delta-connected but may not always be necessary. Their main purposes are to carry a third voltage, stabilize the neutral during unbalanced loads, and suppress third-harmonic voltages.
2) If included, the tertiary winding should be adequately sized to withstand short-circuit currents it could experience. Its size should not be arbitrarily limited to 35% of other windings.
3) Calculating short-circuit currents on the tertiary involves determining the zero-sequence impedances of the autotransformer and connected systems, which can be estimated but sometimes known only roughly.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Tertiary Windings in Autotransformers
O. T . FARRY FELLOW AIEE
A UTOTRANSFORMERS in power systems are usu-
ally Y-connected and commonly have delta-con- nected tertiary windings. Is the tertiary winding needed? quence impedance of the autOtransformer and of the high- and low-voltage systems. 2. Determination of the zero-sequence impedance of If needed, what should be its size? These are two ques- the high- and low-voltage systems, the high- and low- tions to consider when applying an autOtransformer. voltage circuits of the autOtransformer, and the neutral Sometimes the tertiary winding is not needed and circuit of the autOtransformer. may be a liability. This is particularly true of low 3. Calculation of the line-to-neutral fault current. coratio units, the applications offering the largest bene- 4. Segregation of the zero-sequence component of the fit from the use of autotransformers. An analysis of the fault current. need of a tertiary winding involves its three uses: 5. Separation of the zero-sequence component into its parts to determine how much flows in the autOtrans- 1. The tertiary winding may carry load at a third former neutral circuit. voltage. Sometimes this may justify its inclusion. 6. Comparison of this part of the zero-sequence cur- 2. The tertiary winding may be needed to stabilize rent with the current rating of the delta-connected the neutral when unbalanced single-phase line-to-neu- winding to determine how many times rated current tral loads are served. This purpose can usually be may be imposed on the winding. avoided. If loads of this type must be served, the neutral might be stabilized by some other means, such as carry- The most severe circulating current will usually oc- ing a neutral conductor through from the system source. cur in the case of simultaneous line-to-neutral faults on 3. The tertiary winding may be used to suppress the same phase of both the high- and low-voltage sys- third-harmonic voltages by carrying third-harmonic ex- tems. System grounding at other places will relieve the citing current. Generally this is an inadequate reason autOtransformer of part of the zero-sequence fault-cur- for specifying a tertiary winding. The third-harmonic rent. Lowering the ground impedance of the systems component of exciting current can be supplied through reduces the neutral current in the autOtransformer. a neutral connection to the system source or a ground- Determination of the zero-sequence impedances is the ing transformer. Even a ground return circuit may be most illusive part of the calculation. Sometimes the adequate. A modern core-type unit with grain-oriented zero-sequence impedance of the system can only be steel has very low third-harmonic exciting current. roughly estimated. In the autOtransformer the zero- sequence impedances bear some relation to the positive- If a delta-connected tertiary winding is included, it sequence impedances. If the autOtransformer is of the should not be limited in size to 35% of the size of other shell type or consists of a bank of three single-phase windings. It should be large enough to withstand short- units, the zero-sequence impedances are equal to the circuit currents to which it may be subjected. If the corresponding positive-sequence impedances. However, tertiary-winding terminals are brought out, its size in a core-type 3-phase unit, the zero-sequence imped- should be adequate to withstand a short circuit at these ances are lower than the corresponding positive-se- terminals. Frequently, a minimum-size tertiary is not quence impedances. For the purpose of estimating the large enough.-Calculation of short-circuit current of probable zero-sequence impedances of a normally con- this type involves the positive-sequence impedances of structed 3-phase core-type power autOtransformer, the the autOtransformer and of the connected systems. following rules have been deduced from the analysis of If the terminals are not brought out, the problem is a number of designs of units ranging from 34.5 to 230 less serious, but there is still a possibility of excessive kv and having coratios from 0.167 to 0.8: fault current flowing in a delta-connected tertiary wind- The zero-sequence impedance of the high-voltage cir- ing. A line-to-neutral fault on either the high- or low- cuit, %IZ0H, is about 0.8 times the positive-sequence voltage system, or both, will produce zero-sequence cur- impedance, %IZH_L. In individual units the value may rent, part of which circulates in the tertiary winding. vary from 0.65 to 0.9, with 0.8 times %IZH.L a fair av- Steps in calculating the possible magnitude of this erage to use. The zero-sequence impedance of the low- current include voltage circuit, %IZ0L, can be taken as zero. It may be 1. Determination of the positive and negative se- either positive or negative in value ranging from —0.2 to -)-0.2 times %IZH.L. Zero is a convenient average to use. The zero-sequence impedance of the neutral circuit, Digest of paper 61-13, recommended by the AIEE Transformers Com- %IZ0N, including the tertiary winding, is largely de- mittee and approved by the AIEE Technical Operations Department for presentation at the AIEE Winter General Meeting, New York, N. Y., Jan. pendent on the coratio of the autOtransformer. It can 29-Feb. 3, 1961. Published in AIEE Power Apparatus and Systems, Apr. 1961, pp. 78-85. be estimated by the empirical equation %IZ0N — K X 19 O. T . Farry is with the Wagner Electric Corporation, St. Louis, Mo. 7OIZH-L> where K = 0.5 (coratio)- —0.3.
MAY 1961 Farry—Tertiary Windings in Autotransformers 359