si2a2018
i ] 6+ More NextBloge
Power Engineering: Susbar size and calculation
{create Blog Sign
Power Engineering
SUNDAY, 27 OCTOBER 2013,
Busbar size and calculation
Bushar
‘A bus bar (also spelled busbar, buss bar or busbar, is
4 strip or bar of copper, brass or aluminum that
conducts electricity within a switehboard,
distribution board, substation, battery bank or other
electrical apparatus. Its mein purpose is to conduct
electricity, not to funetion as a structural member.
Bushars are typically either flat strips or hollow
tubes as these shapes allow heat to dissipate more
efficiently due to their high surface area to cross
sectional area ratio. A hollow section has higher
stiffness than a solid rod of equivalent current.
cearying capacity, which allows a greater span
between busbar suppors in outdoor switch yards
‘A busbar may either be supported on insulators, or
‘else insulation may completely surround it. Busbars
are protected from accidental contact cither by a
metal earthed enclosure or by elevation out of
normal reach. Power Neutral busbars may also be insulated. Farth (safety grounding)
bushars are typically bare and bolted directly onto any metal chassis oftheir enclosure
Busbars may be enclosed in a metal housing, in the form of bus duct or busway,
‘segregated-phase bus, or isolated-phase bus.
Busbars may be connected to each other and to electrical apparatus by bolted, clamp, or
‘welded connections. Often joints between high-current bus sections have matching
surfaces that are silver-plated to reduce the contact resistance, At extn-high voltages
{more than 300 KV) in outdoor buses, corona around the connections becomes a soures of
radio-frequency interference and power loss, so connection fittings designed for these
voltages are used,
Busbars are typically contained inside switchgear, panel boards, or busway. Distribution
boards split the eleetical supply into separate circuits at one location. Busways, or bus
ducts, are long busbars with a protective eover. Rather than branching the main supply at
‘one location, they allow new circuits to branch off anywhere along the route of the
Dusway.
‘Advantages
Following are some advantages of Bus bar trunking system over normal cabling system:-
On-site installation times are reduced compared to hard-wired systems, thus leading to
‘cost savings
provides increased flexibility in design and versatility with regard to future
modifications.
Greater safety and peace of mind for specifiers, contractors and end-users
Because ofthe simplicity of busbar, iti easy to estimate costs from the design/stimating
stage through to installation on site. This is because the technical characteristics and
price ofeach component are always known,
Ins shortsighted to compare the cast of busbar against that of a length of cable —and
not the real cost of cable instalation to include multiple runs of cable, tay and fixing,
letalone the protracted time and effort of pulling cables.
Distribution busbar distributes power along its length through tap-off points along the
busbar at typically at 0.$ or I m centers. Tap-off units are plugged in along the length of
the busbar to supply a load; this could be a sub distribution board or, in a factory, 0
individual machines. Tap-olfs can normally be added or removed with busbar live,
inating production down
Installed vertically the same systems can be used for rsing-mains applications, with tap-
‘offs feeding individual floors. Ceniied fire barriers are available at points where the
‘busbar passes through a floor slab, Protection devices such as fuses, switchfuses or circuit
os bar
_ntplorlpowerassociate blogspot n/2013/"0fbusbar-size-ane-calculation him!
FOLLOWERS
Followers (173) sox
BLOG ARCHIVE
> 2018 (1)
> 2017 6)
> 2016 (a)
> 2015 26)
> 2014 6)
¥ 201321)
> November (2)
¥ October (4)
Busbar size and cleulaton
Voltage crop calculation in cable
able current eating
Cable lying abstract,
» September (2)
> August (1)
> uy)
> une ()
> May (@)
> Aoai()
> 2012 (68)
ABOUT ME
‘Bhagawan Pr
Panipat, Haryana, India
local Engineer having 20,
yoars experience in Power
Distibuton, Electrical
Maintenance, Electrical Projects, basi of
‘SAP, Design estimation and costing of
ower istibuton,EPC fo indoor
substaton street ightng, Language wih
English, Hind, Bhojpur Kean interested in
‘Sharing nformaton/experence and help
{echnical enthusiasts to update themselves
con various Enginooring
Topics, CONTACT [email protected]
View my complete prot
18arearzo18
1
14,
1s.
‘breakers are located along the busbar run, reducing the need for large distribution boards
and the large quantities of distribution cables running to and from installed equipment,
‘Very compact so provides space savings
‘Where aesthetics have to be considered, busbar trunking can be installed with natural
galvanized, aluminium, of painted finish, Special colours to match switehboards or a
specific colour scheme are also available on request.
Busbar trunking has several key advantages over conventional forms of power
distribution including:
() Reduced, onsite installation times when compared to hard-wired systems thus leading
to cost savings
‘4. Increased flexibility in design and versatility with regard to future
modifications.
Increased safety features brought about by the use of high quality,
‘mansfactured components, which provide greater safety and peace of mind
for specifies, contractors and end-users
Uneven distribution of curent takes place where multiple runs of cables are used in
parallel
Busbar trunking has tap-off points at regular intervals along each length to allow power to
bbe taken off and distributed to where itis needed, Because it is fully self-contained it
needs only to he mechanically mounted and electrically connected tobe operational,
For higher ratings of power distribution we need to have multiple runs of cable. In such
conditions unbalanced distribution of curent takes place and causing overeating of some
cable, This is completely avoided in the BTS systems.
‘When multiple runs of cable are used it often leads to improper end connections thereby
‘causing overheating of contacts, burning of cables ends, and is a major eause of fire. This
is completely avoided in Bus Bar Trunking systems
Current carrying capacity
‘The current-canying capacity of a busbar is usually determined by the maximum
temperature at which the bar is permitted to operate, as defined by national and
international standards such as British Standard BS 159, American Standard ANSI
(€97.20, ete. These standards give maximum temperature rises as well as maximum
ambien temperatures,
BS 159 stipulates a maximum temperature rise of SO°C above a 24 hour mean ambient
temperature of up to 35°C, and a peak ambient temperature of 40°C.
[ANSI.C37.20 alternatively permits a temperature rise of 65°C above a maximum ambient
‘of 40°C, provided that silver-plated (or acceptable alternative) bolted terminations are
used, Ifnot, a temperature rise of 30°C is allowed,
{A very approximate method of estimating the current carrying capacity of a copper busbar
is fo assume a current density of 2 A/mm2 (1250 AVin2) instil air. Tis method should
conly be used to estimate a likely size of busbar, the final size being chosen after
‘consideration has been given to the calculation methods. Refer estalogue of
‘manufacturers.
The more popilar thumb rule being followed in India is to assume current density of 1.0
‘Amps / Sqmm for Aluminium and 1.6 Amps for Copper for any standard rectangular
conductor profile
Standard size of bus bar
Se] Application — ] Cable Dasbar
T] Number of One creuit per floor | Tost one eieult can cover all Hoos
circuits Hence for a 20-floor
building, you need 20,
circuits,
2 | Mam Need 1 outgoing Tor | Need only 1 outgoing for each rer
Switchboard | each citcuit. Hence 20 | Lower cost and size of main panel,
ros. MCCB outgoings,
Higher cost and larger
space requirement in
electrical room
Shak Size [Using 4 core cables, | Typical sizeof TO00A wiser Ie
and considering 1 | 185mm x 180mm, Leads to big
cable per feeder, you | savings on riser shaft size, and hence
reed 20 cables on the | more usable floor area’ on every
lowest floor. Large | floor
space required for
cables! cable ta
T| Fire & safety] The high concentration | The volume of tasuating materials
of insulating materials | used in trunking is reduced to a
used in cables and | minimum so combustive energy is
conductors involves | considerably lower than cables, The
very high level of | insulating) materials used donot
combustive energy. | release corrosive or toxic gases in the
event of a fire. Once the source of
|ntplforlpowerassociate blogspot. n/2013/"0/busbar-size-ane-calculation him!
Power Engineering: Susbar size and calculation
218arearz018 Power Engineering: Susbar size and calculation
the fire is removed, these materials
ae extinguished in a few seconds so
thatthe effect of the fire is minimised
3 | Farure Toad on any floor | By providing extra tap off slots on
expansion | exceeds initial_plan, | each floor at the design stage, owner
‘owner has to run an| only has to procure a tap off box and
‘additional cable from a | plug itn wherever additional load is
spare feeder on main | required. As the plug in ean be done
board tothat floor. | live, there is no shut down required
any of the existing clients
circuits, Puture Flexibility
6 | Faulk Timited by conductor | Much higher — typically @ 1600 A
withstand | size ofeach circuit, | riser has a fault withstand capability
levels, ‘of 60 10 70 KA, Safer in an electrical
fault
7 [Installation | Much longer Each riser on & 20-Tloor building cam
time be installed in approximately 2 to 3
days,
| Vokage drop [High impedance you | Much Tower impedance, Hence
choose cable size | substantially lower voltage drop,
based on each floor
current rating,
Busbars Reduce System Costs
‘A laminated busbar will lower manufacturing costs by decreasing assembly time as well
a intemal material handling costs. Various conductors are terminated at customer
specified locations to eliminate the guesswork usually associated with assembly operating
procedures. A reduced parts count will reduce ordering, material handling and iaventory
Bus bars Improve Reliability
[Laminated bus bars can help your organization build quality into processes. The
reduction of wiring errors results in fewer reworks, lower service costs and lower quality
Bus bars Increase Capa
Tnereased capacitance results in decreasing characteristic impedance. This will ultimately
lead to greater effective signal suppression and noise elimination, Keeping the dielectrics
thin and using dielectrics with a high relative K factor will increase capacitance,
Eliminate Wiring Errors
By replacing a standard cable harnesses with bus bars, the possibility for miss-witings is
eliminated. Wiring hamesses have high failure rates relative to bus bars, which have
vvirually none. These problems are very costly to repair. Adding bus bars to your systems
is effective insuran
Bus bars Lower Inductance
‘Any conductor carrying current will develop an electromagnetic field, The use of thin
parallel conductors with a thin dieloctie laminated together minimizes the effect of
inductance on electrical circuits. Magnetic lux eancellation is maximized when opposing
poteatials are laminated together. Laminated bus bars have been designed to reduce the
proximity effect in many semiconductor applications as well as applications that involve
high electromagnetic interference (EMI)
Bus bars Lower Impedance
Increasing the capacitance and reducing the inductance is a determining factor in
eliminating noise. Keeping the dielectric thickness to a minimum will accomplish the
highly desired low iempedance,
Bus bars Provide Denser Packaging
The use of wide, thin conductors laminated together led to decreased space requirements,
[Laminated bus bars have helped decrease total system size and cost.
Bus bars Provide Wider Variety of Interconnection Methods
The flexibility of bus bars has allowed an unlimited mumber of interconnection styles to
‘choose from, Bushings, embossments, and fasten fabs are most commonly used.
‘Bus bars Improve Thermal Characteristics
The wide, thin conductors are favourable to allowing better airflow in systems. As
package sizes decrease, the cost of removing heat ftom systems has greatly ineressed. A
‘bus bar cannot only reduce the overall size required, but it ean also improve airflow with
its sleek design,
Material: The copper will be of ETP grade as per DIN 13601-2002 and with oxygen free
‘copper.
‘Chemical composition: Purity of copper will be es per DIN EN 13601:2002. Copper +
Silver 99.90% min,
‘Typical example
Rating Current: 3200Amp.
System:415Vae, TPN, SOF.
|ntpiforalpowerassociate,blogspo.ni2013/1O/busbar-size-and-calculation im! 38arearzo18 Power Engineering: Susbar size and calculation
Fault Level: SOKA. For | Sec.
‘Operation Temp:40® C rise over 45 * C ambient
CONSIDERATION
losure size: 1400 mm. wide X 400mm, height
Bus bar Size: 2:200x10 per Ph, 1:200x10 for Neutral,
Bus bar material: Electrolytic gr. AL. (0S 62401/AA6101)
Short Circuit Rating
upto 400A rated current 25KA for | see.
-600 to 10004 rated eurtent SOKA for | see
-1250 0 2000 rated current: 65-100KA for 1 se.
2500 0 SO00A rated current: 100-225KA for | sec.
The minimum eross section needed in sqram for busbar in various common eases ean be
listed as below=
‘Waterial | Fault Tovel ‘Wistand ime
(KA)
Tae, [00 mace] a0 ms Tm
= 33 1S, 39 a
Aluminium [-—~3o. oe 283 127, ia
65 32 368 165 BD
2S Ta, 3 =
Copper 407 2 SI a1
528 236 106 SH
Lotus select a busbar with an example:
1) Aluminium busbar for 2000, 35 kA for 1 sec withstand — From the table the
‘minimum cross-section needed would be 443 mm2. Thus we can select a 100mm x Sram
ction, Considering a current density of 1A/ mm? by
‘considering temperature as well a skin effect, we shall require 4 x 1mm x Smm
‘busbars for this case.
‘busbar a the minimum cross
2) Copper busbar for 2000, 35 kA for 1 see withstand — From the table the minimum
‘cross-section needed would be 285 m2, Thus we can select a 60mm x Sram busbar as
the minimum cross-section. Considering a eurent density of L.6A/ mm? by considering
‘temperature as well as skin effect, we shall require 4 x 60mm x Smm busbars for this
‘Ths, by using the above formula and table, we can casily select busbars for our
witchboards
Size in] Area] Weigh | current carrying capacity in amp (copper Yate degC
sam | sqmm | vm “AC (0. of bus} ‘DC (10. of bus)
T a
Teese [ao 1s _[ 205
1x2 [30 0262 [ao 200 14s [345
1X3 [75 0396_[170 500 175305
2ox> fan —[oasi_[ iss [is 19 [325
2oxs_ [oa [0529 [220 [x0 225] 390
auxs[ 100 [ose [295 | so0 300 | S10
asxs_ [7s — [0.663 [370 [ast ans [70
25xs_[ as. [350 —[a00 355] 0
Toxt [oo 07 _P ssa 320 [60
3oxs [1s [a [To 10 [720
aoxs [120 | 196 [a0 30 [740
aoxs_[ 200 [1.77 [320 [900 330 930
aoxto [ano [353 | 760 | 1350_[1850_[ 3500 [ 770 1400_| 3000
‘soxs [250 [222 [630 | tion i6s0_| 2100 [6501150 [1750
Soxi0 | 300} 8.8 [920 | 1600 [2250 | 3000 | 960 —[ 1700 2500
‘soxs [300 [2.66 [60 [1250 [1760 | 2400} 780] 1300 | 1900 [2500
‘sox 10 [600 [5.33 | 1060 [1900 [ 2600 [3500] 1100 | 2000 2x00 [3600
‘soxs [ano [3.35 [970 —[ 1700 [2300 | 3000 1000| 1x00 2500 [3200
‘sox10 | 800 [7.11 [1380 [2300 3100 [e200 11450 2600 37004800
ToOXS [500 [444 | 1200 [2050] 2es0_[ S500 1950_[ 2250 | 150 4050
ToOXT | 1000 | RA] 1700] 2KDO| 3650 S000 | TsoO | 3200] 4500] SHOT
0
TORT | 1200 | TOT] BON | STOO | a1OO STOO | aTsO | S700] SIT | oT
°
TORT] Tao 142] 3500 900 | SIT] THOU ISON | ARO | OGY SHO
°
|ntplforlpowerassociate blogspot. n/2013/"O/busbar-size-ane-calculation him!
48arearz018 Power Engineering: Susbar size and calculation
200xi | 2000 [178 | 3000 [4750 | 6350 | sHo0 | 8400 | 6000 | x500 | 1900
o
‘Temperature rise
During the short circuiting, the bus bar should be able to withstand the thermal as well as
‘mechanical sttess. When a sort circuiting takes place, the temperature rise is directly
proportional to the squire of the rms value of the fault curent. The duration of short
circuiting is very small ie. one second till the breakers opens and clears the fault. The
heat dissipation through convection and radiation during this short duration is negligible
and all the heat is observed by the busbar itself. The temperature rise due tothe fault ean
be calculated by applying the formulae.
T=K (A)? (1+a0) 107
‘Tetemperature rise per second
‘A= conductor eross section area
a= temperature coefficient of resistivity at 20 deg.Cideg.C
0.00398 for copper
000386 for alminium
K=constant
9.52 for copp
166 for aluminium
tant at which the temperature rise is being
‘Typical ealeulation
Rated curent = 10004
Fault eutent = SOKA for 1 see
Permissible temperature ise 40 degC
Bashar material ~sminium ally E91E
Deerating factor due to material “1
Deering factor du to temperature ise 0.86
De-ratng factor dus to enclosure 0.75
‘Total de-rating factor 110.75x0:86-0.66
Minimum eros section area required to withstand short circuit for 1 sec.
= Merve ios
Where i= fal level cuent in KA
= 1 second
Area A = (50x, 0.08 = 625 sqm
CConsiering all de-rating factor, A = 625/0.66 -946 97
Say, ros sectional area per phase ~ 1000 sqrim
For neatal, eos sectional area per phase = 500 sqmm
{or more study refer a practical que to cable installation anc tool box talk
In ngia-
eT
Ty
Avtilable with book shop and -
Ihttp:!'vwweamazon.in
butp://www.abebooks.com
wuv.ciscoverypublishinggroup.com
Price: Rs. 375/- excluding delivery charges
|ntplforlpowerassociate blogspot. n/2013/"0/busbar-size-ane-calculation him!
58312872018 Power Engineering: Susbar size and calculation
Posted by Bhagawan Prasad at 18:52 c=} o
19 comments:
e row anco # March 2014 at 0115
main satchboards
Is a specialist Switchboard Manufacturing company incorporated in 1873.We have
‘stabshed a leading reputation forthe design and delivery of high quaiy.cost effective
sstenboars,
Reply
RB Wlay chowdary 12 March 2014 a 02:56
| would tke to recommended your blog. You can
for more information.
0 refer tous *1KV Busduct see this
Reply
Bhagawan Prasad 19 Apri 2014 at 799
Reader can see more information on
htpzien sanaytechnicalin'tk-bus- uct! kv-bus- duct him
Realy
Replies
‘sandeop rawat 16 August 2014 at 00:35
How to select BUS BAR for chiler contol panel when chiler takes 352
AMPS 400V, SOKA,
e BRAMHA 29 December 2017 at 01:97
40 X 6 MM COPPER BUSBAR CAN HOLD 50KA FOR 0.25 SEC WITH
RUNNING BUSBAR CAPACITY OF 415 AMPS.
Reply
@ sagar adhau 16 December 2014 at 02:26
Under Typical Calculation How do you have taken 0.08 vale, please cn?
Reply
Q erro 28sec atstorar
ce one. great into
Reply
e Unknown 2 Decomber 2015 at 23:24
How to calelata bus bar curent
Roly
Replies
e Unknown 23 Docomber 2017 at 01:31
IF BUSBAR IS OF 40x6 nine
'80 40x8=240
‘CONDUCTIVITY OF COPPER=1.6 AMM?
‘CONDUCTIVITY OF ALUMMINIUM=0.2 A”MM2
SO IF COPPER BUSBAR = 240 X 1.6 =384 AMPERE
ALUMINIUM BUSBAR= 240 X 0.6182 AMPERE
Reply
|ntplforlpowerassociate blogspot. n/2013/"0/busbar-size-ane-calculation him!
68312872018
e
e
Power Engineering: Susbar size and calculation
Mahesh Ghadge 2 Decomber 2016 at 23.25,
How tocatelate bus bar curont
Realy
Unknown 26 May 2016 at 25:58
| want to clearly which product make cross sectonal area, Pease clear me.
Reply
prabhas 27 June 2018 at 01:20
Calculate your BMI by using our Body mass indox Calculator for adults & children.
Calculated by diving the weight in klograms by the square of height in meters. Weight
Calculator
Realy
Abhay Phadke 24 January 2017 at 20.23
hich bus baris better? Having curent donsty 1.2 0°18
Realy
Roplos
e BRAMHA 29 December 2017 at 01:23
SURELY 1.6, SO CURRENT FLOWING THROUGH MM2 OF BUSBAR IS
MORE
Reply
"Noha Sharma & February 2017 at 06:15,
Calculate your BMI by using our Body mass indox Calculator for adults & children.
Calculated by dvting tho weight in klograms by the square of hoight in meters. Woignt
Calealator
Realy
MP Jain Tubing Solutions LLP 25 February 2017 t 03:28
‘ice poston welded tings can u wie blog on shims
Roly
Gas eh May 2017 at 01:08
My understanding of doing this is that due to that BELLY FAT DOES NOT HAVE ANY
YVAINS INT ~ which makes imposible fr blood steam to reach the faty sources there
to consume them (Thats why the bey fat ress to be burned out and lst longer than
‘other Body fats), when some cats demage thre is made, a body needs to develop a
‘way to reach the damaged areas and clean that out. when a ody ata same time lacks
fn energy voila - an energy source is finally found tu cv ke . After some Belly
Punching sessions =, Body may develop a creuaton system there and burn the
belly fat slong your regular taining. | dont nave any prove fortis, fis ust my theory, |
just bogun this pretica Tow days ago, because | remombored when | was faking some
lf defense lessons some years back, each lesson was starting with this "unolesant™
‘excercise (in pars). trainor was former boxer J? he , 60 thnk this is something a
boxers have some experience wth | can say just fom tis few days experience | stated
now, Im postive about the eflecs, ean say my bely fs for few days much warmer
hich hope is due to blood culation, before that it was col athe time even during
20 trainings. Im tying to not hurt myself, always asking a friend in gym, when my abs
fre relaxed and tensed enough in a same tme fo punch me allover my abs for few
minutes (23m) wth increasing intonsty - unl fel fine withthe intensity. 2s 5ae
one
Roly
Tanjir Ahmmed 19 October 2017 at 20:42
|ntplforlpowerassociate blogspot. n/2013/"0/busbar-size-ane-calculation im!
718arearz018 Power Engineering: Susbar size and calculation
e rice atcale
Realy
a Ankur Afre 30 October 2017 a 00:08
[As per my requirement, Iam searching Sus Bar Cross Section (Thickness & With) for
IK, 5A. SOK, JOA, 408, 1008, 2508 Current ating,
Thanks Wit Best Regards,
| Ankur Af. | Mob. No 91 - 9421511797 | Desk No :97-2086209365
| Mall: [email protected] |
Realy
Enter your coment.
Comment as: Select profit.
one
Newer Post Home Older Post
‘Subscribe to: Pst Comments (Atom)
Piet
sdow theme, Powered by Blogger.
|ntpioralpowerassociate blogspot. n/2013/1O/busbar-size-and-calculation im! a8