Module 4 - Hydraulic Calculation
Module 4 - Hydraulic Calculation
Once the sprinkler spacing and piping layout has been proposed in conformance
with the requirements of NFPA 13, the design engineer should:
a. Demonstrate that the delivery of the prescribed rate of water application will
be accomplished for the sprinklers in the design area that might be
reasonably expected to operate.
b. Demonstrate that the shape of the design area and location of the
sprinklers, regardless of the location of the fire within the building, will be
adequately supplied with water in the event of fire.
c. The design area should be the most challenging and farthest location of
sprinkler in order to ensure that enough water is supplied if it opens in the
event of fire.
Occupancy hazard classification is one the most critical steps in the design
of Automatic Fire Sprinkler System.
NFPA 13 recommends to identify first a design area which
is generally considered the most challenging location in the
building that should be adequately supplied with water in the
event of fire
The standard requires that the design area be divided by the sprinkler
coverage area to determine the number of sprinklers to be considered in
the Design Area
Total sprinklers to
calculate = (Design
area) / (Protection
Area per sprinkler)
For gridded systems, the extra sprinkler (or sprinklers) on branch line 4 can be placed
in any adjacent location from B to E at the designer’s option.
For tree and looped systems, the extra sprinkler on line 4 should be placed closest to
the cross main.
Since the designer should account for a fire that might start
in a location that is challenging to the sprinkler system, the
area to be selected should be large enough to meet the
requirement for the remote area
NFPA 13, states in part: “…the design area shall be a rectangular area having a
dimension parallel to the branch lines at least 1.2 times the square root of the area
of sprinkler operation (A) used…”
Length of the Design Area
No. of Sprinkler in the Branch Line =
Sprinkler Spacing Along the
Branch Line
Where:
Length of the Design Area, L = 1.2 x (Design Area)1/2
L
DESIGN AREA
Sprinkler Flow, Q
Where:
AS = S X L
Walkthrough of Formula
The theoretical foundation formula for water flow through an orifice is:
Q = av
Where
Q = flow in cubic feet per second
a = the cross sectional area in square feet
v = velocity in feet per second
When simplified and the discharge coefficient (cd) is added for the orifice,
a formula is now derived from the basic water flow energy equation to
determine how much water will flow through an orifice based on the water
pressure inside the piping at the orifice:
To simplify things, all factors other than pressure are lumped into what is
experimentally determined as the K-factor of a sprinkler, such that
The K-factor for different sprinkler heads may range from K = 5.6 (standard
½” orifice) to K =14.0 for ESFR sprinklers.
The pressure at the sprinkler head is critical for reasons other than the gpm
flow from the sprinkler.
The pressure at the sprinkler head affects the head discharge droplet size
and spray pattern which are critical characteristics of the fire extinguishing
performance of a sprinkler head.
NFPA 13 sets a minimum pressure of 7 psi (0.48 bar) at the end sprinkler in
any event, so that a proper spray umbrella is ensured.
Sample of K-Factors of different sprinkler manufacturers
Once the minimum pressure at the most remote sprinkler
is determined, the hydraulic calculation method should
proceed backward towards the fire pump
As the calculations proceed toward the system riser, the minimum pressure
requirements increase, because additional pressure is needed at these
points due to elevation and friction losses that must be overcome while
still maintaining the minimum needed pressure at the most remote sprinkler.
This effect on the total water demand is termed hydraulic increase. Hence,
the total water demand of a system is not simply equal to the product of the
minimum density and the design area.
NFPA 13 specifies the use of the Hazen Williams formula
for friction losses resulting from water flow through
piping
Equivalent lengths for pressure losses through system alarm check valve including dry and
deluge valves are determined by the approval laboratories at the time of product listing.
Hazen-Williams Table for Pipe Roughness
Coefficient, C Value
(NFPA 13- Table 14.4.4.5)
C Value Multiplier
For other materials, the Hazen-Williams C factor should be multiplied by the
factors indicated below:
or Pv = 0.001123Q2/d4
Where:
Q = the upstream flow through the piping to an orifice (or
branch line) in gpm or lpm;
d = the actual internal diameter of the upstream pipe in inches
or meter.
Additional pressure must be available within a sprinkler
system water supply to overcome the pressure loss
associated with elevation
The pressure equation required to overcome the
effect of elevation can be explained through
empirical approach.
If a cube whose dimensions are 1 ft in height,
length and width is filled with water and weighed it
would be found that 1 cubic foot of water weighs
62.4 lbs.
From this we can see that the pressure acting on
the bottom of the one square foot column of water
would be 62.4 lbs / 144 square inches or .433 psi.
Thus the pressure needed to overcome pressure loss due to elevation is equal to 0.433
psi per foot (0.099 bar/m) of elevation of the sprinklers above the level where the water
supply is located.
P = 0.433H
Where:
P = Pressure needed to overcome elevation, psi
H = elevation head, in feet
The additional pressure needed to overcome elevation is added at the point where the
elevation change takes place within the system.
The building that houses the technology component of
Embarcadero de Legazpi has been found with multiple
hazard contents or occupancy
Area (Sq.
Description of Contents Hazard Classification
Meters)
384.85 Human Resource Department (Office Tables, cabinets, chairs, computers, Light Hazard
documents, centralized printer, carpeted floor, electrical fixtures)
81 Security and Lobby (Chairs, tables, ornamental plastic plants, body scanner) Light Hazard
90 Clinic and Elevator Area (Medicine cabinet, medical equipment, tables, Light Hazard
chairs, medical records, elevator equipment, electrical fixtures)
137.67 Comfort Rooms and Escalator Area (plastic pail, dipper, electric hand dryers, Light Hazard
electrical lightings and outlets)
327.8 Training Rooms (Tables, chairs, computer, projector, white board, speech Light Hazard
laboratory equipment, projector, white board, electrical lightings and fixtures)
137.69 Lecture Room ( Tables, chairs, white board, projector, computer units) Light Hazard
118.88 Pantry and Concessionaire (chairs, tables, oven, refrigerator) Ordinary Hazard Group 1
81 Gym (Weights, motorized threadmills, TV, refrigerator, aircon, mattings) Light Hazard
98.81 Internet Kiosk, Movie and Videoke Room (computer units, LED television, Ordinary Hazard Group 1
audio equipment, sofa chairs & tables, electrical lightings and outlets)
47.8 Storage Closet (Cabinets, utility tools, lightings) Light Hazard
37.27 Maintenance Room (power tools and equipment, grease and oil, Ordinary Hazard Group 1
maintenance supplies, electrical lightings and outlets)
617 Parking Area ( automobiles, motorcycles, shuttle service vehicles, lightings) Ordinary Hazard Group1
90 Pump Room & Storage (utility water pumps and drivers, pump controllers Ordinary Hazard Group 1
and spare parts, electrical lightings and outlets)
66.9 Fire Pump Room (fire pumps and drivers, pump controller, lightings) Ordinary Hazard Group 1
176.55 Electrical Room/ Power House (Generator, switch and distribution boards, Ordinary Hazard Group 1
back up batteries, control panels, ATS, electrical lightings and outlets)
153.79 Hallways (electrical lightings and fixtures, alarms, security guard control area) Light Hazard
First Floor
Area (Sq. Hazard
Description of Contents
Meters) Classification
827 Production Areas 1&2 (Computer units, chairs, Ordinary Hazard
tables, carpeted floor, ornamental plastic plants, Group 1
office supplies, electrical lightings & outlets)
950 Production Areas 3&4 ( Computer units, chairs, Ordinary Hazard
tables, carpeted floor, ornamental plastic plants, Group 1
office supplies, electrical lightings and outlets)
66 Program Storage & Cabins (Computer units, tables, Ordinary Hazard
chairs, storage of documents, electrical lightings) Group 1
60.3 Locker Areas (lockers, personal belongings) Light Hazard
20.2 Storage Room (utility tools, files, records, electrical Light Hazard
lightings)
120.16 Laboratory & Meeting Rooms (Computer units, Light Hazard
conference table, chairs, white board, multimedia
projector, electrical lightings & outlets)
235.88 Comfort Rooms and Escalator Areas ( plastic pail, Light Hazard
hand dryers, escalator motors and rails)
64.35 Elevator Area (elevator cabin, motors, panel control Ordinary Hazard
boards, lightings fixtures) Group 1
176.11 Hallways (electrical lightings, body scanner) Light Hazard
Second Floor
Third Floor
827 Production Areas 4&5 (Computer units, chairs, tables, Ordinary Hazard
carpeted floor, ornamental plastic plants, office supplies, Group 1
electrical lightings & outlets)
950 Production Areas 6&7 ( Computer units, chairs, tables, Ordinary Hazard
carpeted floor, ornamental plastic plants, office supplies, Group 1
electrical lightings and outlets)
66 Program Storage & Cabins (Computer units, tables, chairs, Ordinary Hazard
storage of documents, electrical lightings) Group 1
60.3 Locker Areas (lockers, personal belongings) Light Hazard
20.2 Storage Room (utility tools, files, records, electrical lightings) Light Hazard
120.16 Laboratory & Meeting Rooms (Computer units, conference Light Hazard
table, chairs, white board, multimedia projector, electrical
lightings & outlets)
235.88 Comfort Rooms and Escalator Areas ( plastic pail, hand Ordinary Hazard
dryers, escalator motors and rails) Group 1
64.35 Elevator Area (elevator cabin, motors, panel control boards, Ordinary Hazard
lightings fixtures) Group 1
176.11 Hallways (electrical lightings, body scanner) Light Hazard
Summary:
Total Floor Area for Fire Protection : 7,687.0 Square Meters
Highest Hazard Occupancy identified: Ordinary Hazard Group 1
Location of Most Challenging Area : Third floor, Production Area 4
Ordinary Hazard Group 1 is identified, from the Density
Area Curve, we can use the design density of 0.15
GPM/ft2 with an area of sprinkler operation of 1,500 ft2
From the design spacing proposal, maximum spacing and protection area
required for one sprinkler satisfied the specifications of NFPA 13 standard
From NFPA 13, the design area shall be a rectangular area having a dimension
parallel to the branch lines where the longest length should be at least 1.2 times
the square root of the area of sprinkler operation (A) used. Thus, computing for the
length of the Design Area:
Pressure needed at the sprinklers to ensure that they flow at the required
level and quantity
Pressure needed to overcome Friction Losses due to valves, pipes and fittings
Example:
You have a project with basic information given below and you are required to
submit to your superior within 2 hours the following data: number of sprinklers,
number of risers, fire pump and water tank capacities.
1. Determine the number of sprinklers, Ns, to calculate. This quantity is the number
of sprinklers expected to operate in case of fire.
A
Ns =
Sr
Ns = pe m² / 12.1 m²
13.4
Ns = ra
11.52, say 12 heads
i o
2 . Determine the Quantity of Water Flow demand
➢ Sprinkler Demand, Qs
Qs = Density x As x Ns x Fs
where: Density = 0.20 gpm/ft
As = 12.1 m² = 130.2ft²
Ns = 12 heads
There is no 600 gpm Fire Pump per NFPA 13 standard, then use the next 750 gpm
capacity for Fire Pump
3 . Determine the Pressure demand
Note: Calculation for friction losses should be done on each pipe size with the
with all the fittings and valves component of a particular size starting from
remotest sprinkler to the discharge flange of the fire pump.
Q = 343.73 gpm
C = 120 for Black Iron (BI) Pipe
d = nominal inside diameter of pipe, inches
L = length of pipe + equivalent length of fittings, feet
Note:
1. It is a good practice to add 10% allowance due to corrosion. With 10% corrosion
factor, your Fire Pump should be rated at 96.9 psi, say 100 psi.
2. This 100 psi can be your system working pressure and the cut-in pressure of your fire
pump is at least 80 psi.
With this quantity of sprinkler heads, you can now plot the ideal branchline and
sprinkler head spacing in the area.
Do you need to follow the 199 heads? Is it absolutely necessary to stick with 199
heads?
5. Determine the number of riser and alarm check valve assembly, R
R = Area of storage warehouse / maximum area per riser, NFPA 13: 8.2.1
= 60 x 40 / 4831 m²
= 0.49, the area is good for 1 riser and alarm check valve only.
Summary:
1. Fire Pump Capacity = rated to deliver 750 gpm at 7 bar (100 psi)
2. Number of sprinkler = 199 heads, upright, ½” dia at 5.6 K-factor
3. Alarm Check Valve = 1 set, 125 mm dia, complete with accessories
4. Water Tank Capacity = 45,000 gpm above ground