Network Management Card - User Manual PDF
Network Management Card - User Manual PDF
com
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
Contents
1 EATON NETWORK SOLUTION 6
2 INSTALLATION 17
3 CONFIGURATION 20
Network
Management Card
(Network-MS)
User Manual
4.2.2 On-line help 37
4.2.3 Logging In 38
4.2.4 UPS control 39
4.2.5 UPS weekly schedule programming 41
4.2.6 Shutdown parameters 42
4.2.7 Measurements 44
4.2.8 Event log 45
4.2.9 System log 46
4.3 NOTIFICATION 47
4.3.1 Email Notification 47
4.3.2 E-mail Message Settings 49
4.4 CONFIGURATION 51
4.4.1 Network settings 51
4.4.2 RADIUS 54
4.4.3 LDAP 56
4.4.4 System 59
4.4.5 Notified Applications 60
4.4.6 Central shutdown configuration 63
4.4.7 Access control 64
4.4.8 SNMP Setting 66
4.4.9 Date and time 68
4.4.10 Firmware upload 70
4.5 ENVIRONMENT SENSOR (OPTION) 71
4.5.1 Characteristics 71
4.5.2 Environment Status 72
4.5.3 Environment Settings 73
4.5.4 Log 75
5 SERVER PROTECTION 76
6 TELNET/SSH/CLI INTERFACES 84
Network
Management Card
(Network-MS)
User Manual
6.1 INTRODUCTION 84
6.2 SETTINGS LIST 84
6.2.1 Network settings 84
6.2.2 System settings 85
6.2.3 Trap receivers 85
6.2.4 Access control 85
6.2.5 Shutdown settings 85
6.2.6 Authentication settings 86
6.2.7 RADIUS settings 86
6.2.8 LDAP settings 86
6.2.9 SNMP settings 87
6.2.10 Date and time 87
6.2.11 Environment settings 87
6.3 MENU INTERFACE 88
6.3.1 Tree description 89
6.3.2 Main menu 90
6.3.3 Reset item 91
6.3.4 Network menu 91
6.3.5 Trap receivers menu 93
6.3.6 System menu 94
6.3.7 Shutdown menu 94
6.3.8 Access Control menu 95
6.3.9 Date and time menu 96
6.3.10 Environment menu 96
6.3.11 Authentication settings 98
6.3.12 Return to default Login/Password 100
6.3.13 Return to default configuration 100
6.4 COMMAND LINE INTERFACE 100
6.4.1 Generic command 101
6.4.2 Network settings 102
6.4.3 Trap receivers 105
6.4.4 System settings 106
6.4.5 Shutdown settings 107
6.4.6 Access control settings 108
6.4.7 Authentication settings 109
6.4.8 Date and time settings 113
6.4.9 Environment settings 114
6.5 CONSTRAINTS/LIMITATIONS 117
Network
Management Card
(Network-MS)
User Manual
7.2 CHOICE 2: NETWORK CONFIGURATION 119
7.2.1 Choice 1: Read IPv4&IPv6 Network settings 119
7.2.2 Choice 2: Modify IPv4 Network settings 120
7.2.3 Choice 3: Set Ethernet speed 120
7.3 CHOICE 3: LOST PASSWORD / SET LOGIN PASSWORD TO DEFAULT 121
7.4 CHOICE 4: RETURN TO DEFAULT CONFIGURATION 122
8 APPENDIX 123
9 GLOSSARY 141
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
This function can be performed through network Cards inserted in the UPS (Network Management Card).
Also a software "agent" running on a nearby PC that is called the IPP Shutdown controller feature can be used.
IPP Shutdown controller feature allows USB or Serial connected UPS to be seen on the network through the PC.
Operation may be in standard secure mode (the default mode) or in SSL secured mode (Secure Socket Layer
SSL).
This function is performed by Intelligent Power Protector installed on each of the computers to be protected.
Note that Intelligent Power Protector are available on several Operating Systems.
Protection applications:
• Continuously gets information from the Network Management Card/Proxy connected to the UPS.
• Warns administrators and users if AC power fails and proceeds to a graceful system shutdown before
the end of battery backup power is reached.
Network
Management Card
(Network-MS)
User Manual
• Internet browser to monitor each UPS, as IPP Shutdown Controller and Management Card includes a
Web server
• Company’s standard Network Management System (HP-Openview, CA Unicenter, HP Insight Manager,
IBM Tivoli Netview)
To simplify integration of EATON UPSs, use one of the Network Management System Kits for EATON
devices. These kits are available on the Software Suite CD-ROM or on the http://powerquality.eaton.com
website.
• The supervisor "Intelligent Power Manager".
1.1.4 Connection
Before installing the Network Solution, the UPS must be set up as indicated in the steps below.
Shut down the computers to be protected by the UPS.
Connect the UPS to a wall outlet. (For UPSs above 3kVA, please refer to the UPS installation manual).
Connect the power cord of each computer to an outlet on the UPS. (For more details, please refer to the UPS
installation manual)
Network
Management Card
(Network-MS)
User Manual
Insert the optional NMC communication card in the UPS and connect the UPS to the computer network.
Start the UPS, then the computers.
Network
Management Card
(Network-MS)
User Manual
The Minislot Network Management Card is compatible with the UPS listed into the compatibility list:
Pulsar MX All models
9E 20000 / 30000 / 40000 / 60000 / 80000 / 100000 / 120000 / 160000 / 200000 All models
5P 550 / 650 / 750 / 850 / 1000 / 1150 / 1500 / 1550 / 2200 / 3000 All models
93PM 50 / 100 / 150 / 200 / 250 / 300 / 350 / 400 / 450 /500 / 550 / 600 / 650 / 700 / 750 All models
Network Management Card acquires information regarding the operation status of the UPS systems and provides
remote control of the system through the ETHERNET network from any SNMP administration station or Web
browser.
Network
Management Card
(Network-MS)
User Manual
NMC also supplies alarms to the Intelligent Power Protector in order to trigger shutdowns or manage other
automatic actions on protected servers.
When a UPS event occurs, the Network Management Card can directly notify up to 4 addresses by e-mail. (see
E-mail Notification and E-mail message settings)
SMS notification requires the use of a third-party application that converts emails to SMS. The card offers the
possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobile
telephone e-mail/SMS transfer systems proposed by ISPs. The format to be used depends on the service
provider.
1.2.4 Compatibility with the Network Management Systems (NMS) – Trap sending
The Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, CA
Unicenter, HP Insight Manager). The Software Suite offering includes the necessary SNMP plug-ins to allow an
easy integration in the NMS. Events are notified by SNMP trap.
• NMS can subscribe on page “Notified Applications”
• The trap list is given in the appendix.
The optional Environment Sensor (EMP) solution can be connected to the Card Settings port of the
Network Management Cards.
Environment Sensor enables measurement of temperature and humidity around the UPS, allows managing
external alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (see
Environment Status and Environment Configuration)
Network
Management Card
(Network-MS)
User Manual
Dimensions
• Dimensions (L x l x H) 132 x 66 x 42 mm
• Weight (gr) 70 g
Storage
• Storage temperature -10 °C to 70 °C
Ambient conditions
• Operating temperature 0 °C to 40 °C
• Ambient humidity 90 % RH max without condensation
• ROHS 100 % compatible
When correctly installed and used in accordance with the manufacturer's instructions, the Network
ManagementCard complies with the following standards:
• Safety for ATI: IEC/EN 60950-1 2005
• EMC: EN 61000-6-2 (2002), EN 61000-6-3 (2002). IEC/EN 62040-2 (2002).
1.3.3 Configuration
• The NMC Card can be easily installed while the UPS is online, maintaining the highest system
availability
The user can configure the card with one of the following means:
• Web browser
• Telnet/SSH/CLI
• Local serial link (network parameters)
• BOOTP/DHCP (network parameters).
Network
Management Card
(Network-MS)
User Manual
1.3.4 Administration
• NEW features:
o External User Authentication from RADIUS or LDAP
• Up to 35 workstations (in TCP connected mode) or up to 100(in UDP broadcasted mode) protected by
Intelligent Power Protector.
• Up to 5 browsers connected at the same time (3 in SSL).
• Minimum recommended browser versions: Internet Explorer 8, Mozilla Firefox 3.6, Chrome.
• E-mail sending configurable according to UPS alarms and transmission of a periodical report.
• Control of UPS on/off switching via the HTML interface.
• Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the
installation and optimisation of backup time by shutting down non-priority systems.
• Automatic data and time adjustment via NTP server.
• Protection by encrypted password.
• Protection by secure SSL connection.
• Backup logs in the non-volatile memory.
• Languages available: English / French/ Spanish / German / Italian / Chinese Traditional / Chinese
Simplified / Japanese / Portuguese / Russian / Korean / Czech.
• On-line help in English available for each page.
• Card firmware update via the network.
• Card Mass settings via the network with Intelligent Power Manager.
• Firmware Mass Upgrade via the network with Intelligent Power Manager.
• Ability to change the SMTP, SNMP and TRAP ports.
1.3.5 Network
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet.
Compatible with 1Gbits networks in 100 Mbits mode
Network
Management Card
(Network-MS)
User Manual
IPP in connected mode in/out TCP 5000
IPP in UDP broadcast mode in/out UDP 4679, 4680R
RADIUS out UDP 1812*
LDAP out TCP 389*
* These ports can be changed by the user, the values shown are the defaults defined by the standards.
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
SNMP Community name read public 32 characters maximum
SNMP port 161 1 to 65535
Trap port 162 1 to 65535
SNMP Version V1&V3 Disabled,V1,V3,V1&V3
Read-Only User readuser 1 character minimum,
32 characters maximum
Read-Only Security Level Authentification None, Authentification,
Authentification&Privacy
Read-Only Password readuser 8 characters minimum,
24 characters maximum
Read-Write User wirteuser 1 character minimum,
32 characters maximum
Read-Write Security Level Authentification&Privacy None, Authentification,
Authentification&Privacy
Read-Write Password writeuser 8 characters minimum,
24 characters maximum
Notification Username notifuser 8 characters minimum,
24 characters maximum
Date and time Date and time adjustment Accept automatic update Synchronise with an NTP
from IPP or IPM server
Accept automatic update from
NSM or EPM
Synchronise manually
NTP server ntpserver 49 characters maximum
Serial link Speed 9600 baud Not configurable
Data bits 8 Not configurable
Stop bits 1 Not configurable
Parity without Not configurable
Flow control without Not configurable
Network
Management Card
(Network-MS)
User Manual
2 Installation
2.2 Indications
Network
Management Card
(Network-MS)
User Manual
Ethernet Port
LED Colour Activity Description
ACT Green • Off • Card not connected to the network.
• Card connected to the network but without
• On
activity
• Flashing • Port is active in receiving / transmission
Settings/Sensor Port
LED Colour Activity Description
UPS Green • Off • Card startup in progress.
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
3 Configuration
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
Network settings
-----------------------------------------------------------------------------
1 : Read Network settings
2 : Modify Network settings
3 : Set Ethernet speed
0 : Exit
-----------------------------------------------------------------------------
Network configuration :
MAC address : 00:20:85:FD:1C:07
Mode : Static IP
IP address : xxx.xxx.xxx.xxx
Subnet mask : xxx.xxx.xxx.xxx
Gateway : xxx.xxx.xxx.xxx
Link Local IPv6 address : xxxx::xxxx:xxxx:xxxx:xxxx /xx
Global IPv6 address : xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx /xx
Global IPv6 address : xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx /xx
Network
Management Card
(Network-MS)
User Manual
The IPv6 parameters are read only through the serial line configuration menu. If IPv6 is enabled, all IPv6
addresses of the card can be read from the HyperTerminal™. The “Your network is equipped with a DHCPv4
server” chapter describes the steps to follow to display this addresses.
Network
Management Card
(Network-MS)
User Manual
• On a computer equipped with a Web browser (Internet Explorer, FireFox, Google chrome or Opera
recommended), enter the address initialised previously in the Installation chapter.
• The "UPS properties" home page is displayed.
Network
Management Card
(Network-MS)
User Manual
4.2 UPS
4.2.1 UPS properties page
• Essential information about the UPS status is available on the UPS Properties page (see Figure), which
refreshes automatically every ten seconds.
• The UPS Properties page shows an image and generic name of the UPS range. You can customize
Computer Room to name the location of your system (see “System Settings”).
• An animated diagram displays for online UPSs showing an overview of the current UPS operating mode.
Network
Management Card
(Network-MS)
User Manual
Animated synoptic: An animated synoptic gives a global overview of the UPS current operating mode.
This synoptic is available on all On-Line UPS.
The synoptic drawing depends on the UPS topology. The different drawings are described in the table below.
Note: In case of loss of communication with the UPS, all the elements of the synoptic are grey.
Network
Management Card
(Network-MS)
User Manual
• AC Normal Flow:
Yellow AC to DC converter powered by AC Normal
Gray AC to DC converter not powered by AC Normal
• AC to DC Converter:
Green Powered
• Battery:
Green Remaining capacity > 50%
Network
Management Card
(Network-MS)
User Manual
• DC to AC Converter :
Green Powered
• DC to AC Converter Output:
Yellow Energy flow present
Gray No energy flow
• AC Bypass Input:
Green In tolerances
•
• AC Automatic Bypass Flow :
Yellow Energy flow present
Gray No energy flow
Network
Management Card
(Network-MS)
User Manual
• AC Output Flow:
Yellow Energy flow present
Gray No energy flow (or Load = 0%)
• AC Output:
Green Load protected
Network
Management Card
(Network-MS)
User Manual
• UPS measurements :
Place the cursor over an element in the diagram to display the UPS measurement detail (see Figure). These
measurements are available for Input, Battery, Output, and Bypass mode. The available measurements depend
on the UPS range.
Network
Management Card
(Network-MS)
User Manual
The various icons showing the status of the UPS outputs are:
Outlet powered
(green outlet)
Outlet not powered or not protected
(red outlet)
Battery Information:
• Battery load level: remaining battery charge (in percent).
The information is completed with the 3 following labels:
- Charging: if the utility power is present and the battery charge is in progress.
- Discharging: if the UPS operates on battery.
- Fault: if the battery is faulty.
• Remaining backup time: Estimation of the battery's maximum backup time remaining before UPS
shutdown
• Battery status: Result of the last automatic battery test carried out by the UPS
Possible values are:
- OK: the test was completed correctly.
- NOK: the battery needs to be checked.
- Deactivated: the automatic battery test is not validated on the UPS.
Network
Management Card
(Network-MS)
User Manual
• Click on UPS Modules scroll list to view the information about the UPS modules.
• Active sources:
x UPS + y UPS redundant : x indicates the minimal number of UPS necessary to power the load,
y indicates the number of UPS in redundancy.
The addition of these 2 values is the total number of available UPS.
• The Minimum redundant UPS modules to trigger alarm can be configured from this page. The button
Save makes the card setting the parameter into the UPS. A warning message informs the user about the
consequences of this parameters modification.
The redundancy lost can generate Email notification (if set in the email notification page) and SNMP
trap. It can also be used by IPP for server protection criteria.
Network
Management Card
(Network-MS)
User Manual
• The Status can take the next forms:
when the module has at least one alarm (level Warning) active.
when the module has at least one alarm (level Critical) active.
When the module is working properly with no alarms, the icon is not reactive, otherwise it is reactive and clicking
on it makes the page Alarm Table appear.
Network
Management Card
(Network-MS)
User Manual
Click on Power usage scroll list to view the information about the consumptions.
• Average power usage: indicates the average consumption on the last hour of each output. The sum of
these 3 consumptions is also given.
• Cumulative power usage: indicates the consumption cumulated of each output since the last reset. The
sum of these 3 consumptions is also given.
Note: The consumptions are only available with UPS Eaton 5PX, 5P, 9PX and 9SX. The consumption of each
output is only available with UPS Eaton 5PX.
Network
Management Card
(Network-MS)
User Manual
Click on "Alarm Table" scroll list to view the list of current alarms. The table of managed alarms is included in
the appendix.
Critical
Warning
Unknown
Network
Management Card
(Network-MS)
User Manual
• Alarm table for modular UPS:
Network
Management Card
(Network-MS)
User Manual
Click on About your UPS scroll list to view the information about the UPS and the card.
Network
Management Card
(Network-MS)
User Manual
On-line contextual help in English is available at the top of each page by clicking on the Help link, which is always
located on the top right corner. The navigation menu of the on-line help is identical to that of the card's pages.
Network
Management Card
(Network-MS)
User Manual
4.2.3 Logging In
By default, the user name and password are both admin for the local account (see Figure). If an external
authentication is used, the username and password will be those defined in LDAP or RADIUS authentication
depending on the type chosen.
Both the user name and password fields accept up to a maximum of ten characters. After five minutes have
elapsed, or if the browser is closed and reopened, you must re-enter the user name and password.
An error in either field results in rejection of the requested action (such as save, page access, or card reboot).
After three unsuccessful login attempts, you must refresh the browser. Both the user name and password fields
are encrypted with an MD5 type algorithm, ensuring total security.
See “Set Login Password to Default” to reset the password (from RS232 serial link).
Network
Management Card
(Network-MS)
User Manual
UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user
manual for more information.
This page enables triggering of startup and shutdown sequences for the UPS main output and controlled outlets.
• The status of each output is displayed by a symbol associated with the Off label (red symbol) or On
(green symbol).
• The shutdown sequences take into account the time required for the registered servers to shut down
without losing data (see shutdown parameters).
• The main outlet has priority over the controlled outlets. Shutdown of the main outlet causes the
controlled outlets to shut down. Controlled outlets can only be started if the master outlet is on.
The system proposes six different commands, and a command is only actually started after clicking on Execute:
• Safe power down: A sequence to switch off output power is launched immediately. The systems
supplied are shut down correctly while the shutdown sequence is running, then the output is cut.
• Safe power down & reboot: A sequence to switch off then restore output power is launched
immediately. The powered systems are shut down correctly during the shutdown sequence, then the
output is switched off.
• Finally, the restart sequence is launched at the end of the time delay specified in the "Toggle duration"
parameter. The output status is updated.
Network
Management Card
(Network-MS)
User Manual
• Immediate On: A sequence to switch on output power is launched immediately. The output is re-
powered and the systems supplied start up correctly.
• Delayed, safe power down: This is the same switch off sequence as for the "Safe power down"
command, but postponed by the number of seconds programmed in the "Off Delay" parameter.
• Delayed, safe power down & reboot: This is the same switch off then on sequence as for the "Safe
power down & reboot" command, but postponed by the number of seconds programmed in the "Off
Delay" parameter.
• Delayed On: This is the same switch on sequence as for the "Immediate On" command, but postponed
by the number of seconds programmed in the "On Delay" parameter.
The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card.
Network
Management Card
(Network-MS)
User Manual
UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user
manual for more information.
The weekly schedule enables the administrator to optimise power consumption or program a reboot of the
protected equipment at a set time.
In a shutdown sequence, the Intelligent Power Protector connected to the card are informed and ensure that
each machine is shut down correctly before the UPS output is switched off. Up to 7 UPS shutdown sequences
can be programmed in one week, with a minimum shutdown delay of 30 minutes.
The On / Off sequences are valid only if the card's time has been properly set.
Network
Management Card
(Network-MS)
User Manual
This page enables viewing and configuration of UPS operating parameters in battery mode and for power
restoration.
Click on the Shutdown parameters section in the menu to see the list of parameters.
Note
As priority is given to the main outlet, the card cannot supply the controlled outlets when main outlet power is off.
Network
Management Card
(Network-MS)
User Manual
For the main outlet ("Master" by default)
The first shutdown criteria initiates the restart of the shutdown sequence.
• If remaining time is under (0 to 99999 seconds, 180 by default) is the minimum remaining backup time
from which the shutdown sequence is launched.
• If battery capacity is under (0 to 100%); this value cannot be less than that of the UPS and is the
minimum remaining battery capacity level from which the shutdown sequence is launched.
• Shutdown after (0 to 99999 minutes, not validated by default) is the operating time in minutes left for
users after a switch to backup before starting the shutdown sequence.
• Shutdown duration (120 seconds by default) is the time required for complete shutdown of systems
when a switch to backup time is long enough to trigger the shutdown sequences. It is calculated
automatically at the maximum of Shutdown duration of subscribed clients but can be modified in the
Advanced mode.
• If battery capacity exceeds Minimum battery level to reach before restarting the UPS after utility
restoration
Important: Certain UPSs do not support this option
• Turn off UPS after sequential shutdown
On Disable mode, the card doesn’t send the Shutoff command to the UPS.
On Enable mode, the card sends the Shutoff command to the UPS on the shutdown criteria.
Important: By default, this option is set to Disable. But if the card detects that an IPP is connected to
the card, then the option goes automatically to Enable, and stays in this state. At this time, only the user
can modify this setting.
The page enables programming of operation time and level in backup mode to manage outlet load shedding in
the event of electric power failure:
• Switch Off after (from 0 to 99999, 65535 by default) defines the time during which the outlet is supplied
starting from the moment of utility failure. Caution, this time includes the outlet shutdown duration.
• Switch Off if battery capacity under (0 by default) is an extra condition for outlet shutdown that can
trigger the shutdown sequence before the shutdown duration runs out.
• Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet
when an outlet shutdown sequence is launched.
It is calculated automatically using the maximum shutdown durations of notified applications on the
outlets.
• Switch On after (from 0 to 99999, default 65535) is the period between main output startup and startup
of the relevant programmable outlet, therefore outlet startup can be delayed in relation to the main
output.
Important: Certain UPSs do not support this option
Network
Management Card
(Network-MS)
User Manual
4.2.7 Measurements
Network
Management Card
(Network-MS)
User Manual
• Save log enables all saved values to be opened or saved in CSV format. (compatible with Excel type
spread sheets)
• Clear log enables deletion of all records. The administrator must enter his/her login / password to
validate this action.
The card can save 435 events. The table of managed alarms is included in the appendix.
Network
Management Card
(Network-MS)
User Manual
• Save log enables all saved values to be opened or saved in CSV format. (compatible with Excel type
spread sheets)
• Clear log enables deletion of all records. The administrator must enter his/her login / password to
validate this action.
The card can save 435 events. The table of managed alarms is included in the appendix.
Network
Management Card
(Network-MS)
User Manual
4.3 Notification
4.3.1 Email Notification
The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is
compatible with mobile telephone transfer systems using text messages (SMS).
SMS notification requires the use of a third-party application that converts emails to SMS.
• Recipient List:
On the left side of this page, up to four recipients can be configured to receive e-mails from the card.
Each addressee has its own trigger events, selected from the right side of the page, for which an e-mail
is sent. The card’s log indicates e-mail transmission errors.
Each recipient is configured with the following parameters:
◗ Recipient: (Field is limited to 99 characters) this is the e-mail address of the person
or department to receive the e-mail.
The default value is : [email protected]
◗ eNotify: This parameter enables communications to the Eaton eNotify Monitoring
and Diagnostics Service. NOTE: Available only for customers with a valid eNotify
Service Contract.
◗ Attached files: The files selected (Measurements, Event log, System log,
Environment measurements) are enclosed with each e-mail sent. The files are sent
Network
Management Card
(Network-MS)
User Manual
in CSV format
◗ Periodic report: In addition to the e-mails sent when events occur, a periodic e-mail
containing the 3 log files (or 4 when the optional Sensor is connected) can be sent
to the recipient every x days at the time specified by the user.
To configure the first transmission, specify the day, time and frequency of the next
transmission in the "next report" box. After this date, the page will show the date
and time of the next transmission.
Data are sent in CSV format.
Network
Management Card
(Network-MS)
User Manual
This page enables customisation of the content of the messages received by recipients of e-mails sent by the
card.
Customisation is common to the four recipients that can be notified (see E-mail notification).
• Sender: (59 characters maximum) identifies the source of the message. The default value is
[email protected].
This field is free. However, depending on the type of SMTP server configuration, it is possible that the
server checks that the domain name contained in the Sender address exists, and even that the user in
the Sender address belongs to this domain.
• Subject: enables the user to specify the subject of the e-mail to be sent. By entering some free text and
selecting from several optional fields, if desired, the message subject is built:
- UPS name recalls the name of the UPS; it may or may not be selected.
- UPS location recalls the geographic location of the UPS (see System Settings); it may or may not be
selected.
- Event message identifies the event generating the e-mail; it may or may not be selected.
• Message text is a free zone long of 255 characters maximum.
The body of the e-mail sent is composed of:
- Message text, which is free text.
- The date and time of the event, as saved in the log.
- URL of the card, enabling a direct link with the card to be established.
- Attachments, as configured for the e-mail recipients.
- Duplication of the subject, as configured.
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
4.4 Configuration
4.4.1 Network settings
This menu enables the administrator to configure the network parameters of the card and authorisation of the
remote upgrade of the embedded system.
Network
Management Card
(Network-MS)
User Manual
Sequence with BootP/DHCP server: After each startup, the card makes 3 attempts to recover the
network parameters. If no response is received from the server, the card boots with the last saved
parameters from the previous start. These parameters are those shown on the page.
The default value for this parameter is "Enable"
Note 1:
If the hostname is not used, the IP address supplied by the DHCP server must be fixed to maintain
connection with the clients installed on the stations to be protected.
Note 2:
During the first connection, if the DHCP query is not successful, the NMC starts with the following IP
configuration:
Default IP address: 192.168.1.2
Subnet mask: 255.255.255.0
Gateway Address: 0.0.0.0
Network
Management Card
(Network-MS)
User Manual
not editable. Always available when the IPV6 is enabled.
• IPv6 Address 2:
• If Auto Config is enabled: this field displays the second IPv6 address built from the IPv6 router (not
editable).
• If Auto Config is not enabled, this field is empty and not editable.
• Firmware Upload: Authorise (chose "Enabled") remote updating of the card's embedded software.
The default value for this parameter is "Enabled".
• Primary DNS Server: contains the IPv4 or IPv6 address of the main DNS server ensuring conversion of
the domain name to IP address.
• Secondary DNS Server: contains the IPv4 or IPv6 address of the secondary DNS server ensuring
conversion of the domain name to IP address if the primary DNS server is not available.
• SMTP Port: contains the port number of the SMTP server.
• SMTP Server: contains the name or IP address of the local server with which the card connects to send
e-mails.
It may be filled in either as host + domain name (DNS resolution), or directly with the IP address.
The default value is smtpserver. The card uses the standard port (25) for sending e-mails.
• SMTP Server Authentication: Displays login and password fields in order to connect the NMC card to
a SMTP Server that requires an authentication.
Important note:
The card must be rebooted after any changes to these IP parameters. See "System" page
Network
Management Card
(Network-MS)
User Manual
4.4.2 RADIUS
This menu allows the administrator to configure RADIUS settings on the card. They are editable only if the
parameter of the External Authentication on the Access control Access controlpage is set to RADIUS.
Two RADIUS servers can be registered. The secondary server is used when the primary does not respond in the
delay (time out) and after the number of retry set.
The button “Modify Server” allows to edit and to modify the server configuration selected.
Network
Management Card
(Network-MS)
User Manual
• Enable Configuration: If enabled, this server will be used during radius authentication process.
• Primary/Secondary: identifies the priority order between Radius servers. The primary is used in first (if
enabled) , if it is unreachable, the secondary is used.
• Radius Server: identifies the name or the IP (IPv4 or IPv6) address of the server.
• Secret:identifies the secret shared between the card and the Radius Server
• NAS IP Address: identifies the IP address of the NAS (the Network Management Card) to use. The
possible values in the GUI list are based on the IPv4 and IPv6(s) addresses of the card.
• Auth. Port: identifies the remote radius server port.
• Time Out: identifies the delay to wait before to send another radius request.
• Retry Number: identifies the number of request to send before testing another Radius server (if
available).
After an authentication success, the card must check if the user has the permission to open a (admin) session.
Two radius attributes are used to manage admin authorization:
• An IETF attribute: Service-Type (6)
• An Eaton Vendor Specific Attribute (534): Eaton-UserLevel (28)
If one of these attribute is present with the value as defined in the following table the access of the card is
allowed, else the access is refused:
Network
Management Card
(Network-MS)
User Manual
.
4.4.3 LDAP
This menu allows the administrator to configure LDAP settings on the card. The settings on this page are editable
only if the parameter of the External Authentication on the Access control page is set to LDAP.
• Authentication Mechanism: identifies the binding type used. The card supports simple and Digest MD5
(SASL) mechanisms. For Digest MD5, your DNS server MUST support the reverse lookup on the IP
address of your LDAP server.
• User Search Bind: identifies the binding type used to search user. The card supports anonymous bind
and a bind with an accredited user. When an accredited user is used, the Mechanism used is the
Mechanism set in the Authentication Mechanism field.
• Search User: identifies the User which is used to search user information during login step. This
attribute is a Distinguished Name when the Authentication Mechanism is set to simple, and a SASL
username when the Authentication Mechanism is set to Digest MD5.
• Search User Password: identifies the password of the Search User.
Network
Management Card
(Network-MS)
User Manual
• User Base DN: identifies the database entry from which the user search is started.
• User Object: identifies the LDAP class of the user object.
• User Attribute: identifies the attribute name where the login identifier is stored.
• Authorization Mode: identifies the method to use for authorization:
o None: all authenticated users are authorized.
o By User Attribute: the authorization credential (UPSAdministrators value) is stored in the Group
Name Attribute of the LDAP user.
o By Group: the authorization credential is stored in LDAP Groups.
• UPS Group Base DN: identifies the database entry from which the UPS group search is started.
• Group Name Attribute: identifies the attribute name where the UPS group identifier
("UPSAdministrators" value) is stored.
• User Name Attribute: identifies the attribute name in the object group where the user identifier is stored.
Two LDAP servers can be registered. The secondary server is used when the primary does not respond in the
delay (time out).
The button Modify Server' allows to edit and to modify the server configuration selected.
• Enable Configuration: If enabled, this server will be used during LDAP authentication process.
• Primary/Secondary: identifies the priority order between LDAP servers. The primary is used in first (if
enabled) , if it is unreachable, the secondary is used.
• LDAP Server: Server Name or IP Address of the server.
• Port: identifies the remote LDAP server port.
Network
Management Card
(Network-MS)
User Manual
4.4.3.2 Authorization management
When an authorization mode is set, the “UPSAdministrators” string is searched in the LDAP Directory.
Consequently, the LDAP Directory must be updated in the following way to allow users to open Web session in
the NCM card:
• If the mode is “By User Attribute”: the administrator must set the LDAP attribute defined by the "Group
Name Attribute" with the “UPSAdministrators” value. This update must be done for all allowed users.
• If the mode is “By Group”: the LDAP administrator must create a group with the following properties :
o The location of this group in the LDAP directory must set under the DN path set in the UPS
Group Base DN value.
o The attribute defined in the Group Name Attribute must be set with the “UPSAdministrators”
value.
o All allowed users must be declared as member of this group: the multi valued attribute defined
in the User Name Attribute must be set with all allowed users DN .
When MD5 is set as Authentication Mechanism, the following rule must be applied:
• A DNS server must be registered in the Network Configuration of the card.
• A DNS reverse lookup must be possible for the LDAP IP server.
• If an Accredited User is used for the LDAP search, its name is no longer a DN but a SASL name.
• The user login must be compliant with the SASL name rules of the LDAP server used.
If the LDAP server is Active Directory, the following values are usually employed:
Network
Management Card
(Network-MS)
User Manual
4.4.4 System
This menu enables the customisation of the information on the UPS properties pages.
• UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for
UPS administration at IT network level and/or electrical maintenance. This field does not appear on any
other Web page. By default, its value is "Computer Room Manager".
• UPS Location: Enter a description (limited to 31 characters) of the location of the UPS in your
installation (e.g. Computer room E1-C066). This text is displayed in the home page and in the title of the
page. By default, its value is "Computer Room".
• Default Language: Enables initialisation of the browser language at card connection.
Choice of one of the available languages: English, French, German, Spanish, Italian, Chinese
Traditional, Chinese simplified, Japanese, Portuguese, Russian, Korean, Czech changes the language
of the html interface pages (Refresh the web page <F5> after modification).
• History log interval: [from 5 to 99999 sec., 60 by default]. Measurement save period.
• Environment log interval: [from 60 to 99999 sec., 300 by default]. Temperature and humidity
measurement save period.
• Reset Communication button: performs a remote reboot of the card without modifying the
configuration. This action is compulsory for consideration of any changes made on the "Network
Settings" page.
• Factory Reset button: enables restoration of the default configuration of all the card’s parameters.
TCP/IP parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the
"Keep TCP/IP parameters" option is selected.
Network
Management Card
(Network-MS)
User Manual
4.4.5 Notified Applications
Important note: It is not necessary to add the Intelligent Power Protector protecting your servers in this list. These
modules subscribe and unsubscribe themselves automatically.
Select an entry in the list to modify the values in the edit zone at the bottom of the page. The table displays the
following information:
• All: selects all the lines.
• Nr: the index where the application is stored into the table.
• Hostname or Address IP: By priority, the hostname of the computer is displayed when the IP address
can be converted into a hostname by a DNS server or if the application has been entered as a
hostname.
Network
Management Card
(Network-MS)
User Manual
• Application Name: Given by the application at subscription time.
• Output: number of the UPS output from which the client is powered.
• Configuration: shows where the parameters of the Intelligent Power Protector come from: Local
(coming from the application) or Central (coming from the card).
The Central shutdown configuration is available by clicking on the Configuration link.
• Shutdown duration: the shutdown duration necessary to properly shutdown the computer.
• Shutdown after: the time available to the user from the power failure until the launch of the shutoff
sequence of the UPS and equipment.
• Connected: This value is set to YES if the notified application connects through TCP protocol.
WARNING!
- This test will generate a REAL shutdown sequence of the selected servers on which the Intelligent Power
Protector application is running.
• Add NMS: allows an SNMP trap receiver to be added such as a Network Management System.
• Modify NMS: allows an SNMP trap receiver to be modified.
Both buttons open a new window where it is possible to enter the Application name, the Hostname or IP
Address, the trap port, the protocol version needed: V1, V3 or both, the Trap community (only used in
V1) and the filter on the several implemented MIBs.
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
Note: Intelligent Power® Manager provides more advanced configuration management features
Click on Notified Applications in the menu, then Configuration.
This page is used to define either the "shutdown" or the "notification" settings used by the Intelligent Power
Protector that connects to Network Management Card. These settings are used by the Intelligent Power Protector
if they are in central-configuration mode or if their configuration is not valid.
• Shutdown duration: the shutdown duration necessary to properly shutdown the computer.
• Shutdown after: the time available to the user from the power failure until the launch of the shutoff
sequence of the UPS and equipment. This parameter is optional. Uncheck the box if you wish not to use
this parameter.
• Broadcast : Sends network notifications to the Administrators and Users groups on events declared in
the server hosting the NSM
If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration
mode", proceed as follows:
• Change the IPP parameters in the "Notified Applications" page.
• Click the "Save" button.
• In this page, select the IPPs for which you want to apply the new configuration.
• Press the "Remove" button.
• The IPPs selected will disconnect then reconnect and use the new configuration.
Network
Management Card
(Network-MS)
User Manual
This menu enables configuration of the different parameters enabling secure access to the card via a browser.
• Enter New Manager Login: The login user name. This text field (limited to thirty characters) enables
secure access and modification of pages. Default value is admin.
• Enter New Password: This text field (limited to thirty characters) enables secure access to
Configuration menu pages. Default value is admin.
• Confirm New Password: Re-enter the new password.
• External Authentication: identifies the type of authentication used between LDAP and Radius. If None
is chosen, the local user database is used.
• Authentication Order: identifies the priority order used between local and external authentication.
• Session Time expiration after inactivity (s): identifies the time after which the session is closed if no
activity is detected.
• Maximum Session Time (s): identifies the maximum time of a session whatever activity.
• Security mode: Manages the various authentication methods for page access:
Authentication for configuration: Only the configuration pages are protected by login / password
Full authentication: All pages are protected by login / password
SSL and full authentication: All pages are protected by login / password and are only accessible in
SSL
SSL Access: When selected, access to the Web interface is made in secure mode (https).
Network
Management Card
(Network-MS)
User Manual
Connections with Intelligent Power Protector stay in standard mode (secure TCP)
SSL Security Implementation:
SSL version 3.0
TLS version 1.0
Method TLS_RSA_WITH_512_MD5
Certificate 1024 bits
Auth RSA
Key Exchange RSA
Encryption RC4_512
Digest MD5
Changes take effect after a card reboot
• Telnet access: This parameter enables the access to the setting parameters interface via a Telnet/SSHI
connection.
• Telnet security: This parameter defines the protocol for the access to the setting parameters interface.
These 2 values are mutually exclusive.
• TELNET: The data are read or written via an unsecured access.
• SSH: The data are read or written via a secured access.
• Console interface: This parameter defines the way to access the setting parameters. The 2 values are
mutually exclusive. The selected HMI (Human Machine Interface?) is available for the TCP/IP
connection (RS232 not concerned) and for the 2 protocols (Telnet, SSH). The new value will be taken
into account after a manual reset of the NMC.
• MENU: The HMI is a menu interface and the parameters are accessible via some pre-defined menus.
• CLI: The access to the parameters is done independently of each other using the command line
interface.
• Save: Saves any modifications.
Network
Management Card
(Network-MS)
User Manual
• SNMP Version: This field allows the user to select the snmp protocol version: {Disabled, V1, V3 are
supported by the card}.
• SNMP Port: Allows the user to select and modify the port number of the SNMP server.
• SNMP Community Read-Only: The SNMPv1 Read community name that identifies a sub-group
attached to a network manager or a logical entity. The card and the clients must share the same
community name to communicate.
• SNMP Write Enabled: Enables SNMP write function.
SNMP Community Write: Displays only if SNMP Write is enabled. The SNMPv1 Write community name
that identifies a sub-group attached to a network manager or a logical entity. The card and the clients
must share the same community name to communicate.
• Read-Only User: identifies the login of the user in the SNMPv3 version which is authorized to read only
SNMP variables.
• The Read-Only Security Level: selects the security level
• No Auth No Priv: the user must not use authentication and privacy to access to SNMP variables.
Network
Management Card
(Network-MS)
User Manual
• Auth No Priv: the user must use authentication and NOT privacy to access to SNMP variables.
• Auth Priv: the user must use authentication and privacy to access to SNMP variables.
• The Read-Only Authentication Password: allows administrator to specify a new authentication
password for the Read-Only User. Its length must be ranging between 8 and 24 characters and using
only letters, numbers and <>&@#%_=:;,./?|$*()-~ symbols.
• The Read-Only Privacy Password: allows administrator to specify a new privacy password for the
Read-Only User. Its length must be ranging between 8 and 24 characters and using only letters,
numbers and <>&@#%_=:;,./?|$*()-~ symbols.
• The Read-Write User: identifies the user in the SNMPv3 version which is authorized to read and write
SNMP variables.
• The Read-Write Security Level: selects the security level:
• No Auth No Priv: the user must not use authentication and privacy to access to SNMP variables.
• Auth No Priv: the user must use authentication and NOT privacy to access to SNMP variables.
• Auth Priv: the user must use authentication and privacy to access to SNMP variables.
• The Read-Write Authentication Password: allows administrator to specify a new authentication
password for the Read-Write User. Its length must be ranging between 8 and 24 characters and using
only letters, numbers and <>&@#%_=:;,./?|$*()-~ symbols.
• The Read-Write Privacy Password: allows administrator to specify a new privacy password for the
Read-Write User. Its length must be ranging between 8 and 24 characters and using only letters,
numbers and <>&@#%_=:;,./?|$*()-~ symbols.
• The Notification username: allows administrator to specify the “username” field for SNMPV3
notifications. This field has to also be defined in the applications that received those notifications.
• Save: Saves any modifications.
Network
Management Card
(Network-MS)
User Manual
This menu enables initialisation of the date and time of the card in three different ways.
The date format is always of year/month/day type
• Set manually: Enables initialisation of the date and time of the card, with the values entered in the Date
and Time fields. This update is made after clicking on the Save button.
Maximum drift is +/- 2 min./month
• Accept automatic update from IPP or IPM: Enables initialisation of the date and time of the card, with
the values provide by the Intelligent Power Protector or the Intelligent Power Manager.
• Synchronize with NTP server: Enables connection with a time server, either available on the
company’s internal network or on the Web. This server communicates GMT time. The IP address or
hostname of the time server must be entered, and the time zone of your geographic area must then be
selected from the list. Connection is made with the server and the date and time are set after clicking on
the "Save" button. Time is updated every five hours, thus preventing any drift in the time. After two
attempts, if the NTP server is not accessible, the card resends periodic requests.
The card uses the NTP protocol (UDP 123 port). The "firewall" must be configured to transmit queries
outside the intranet. When ntp could not be contacted, an error message is issued at the top of the web
page.
Daylight Savings Time: Enable the time adjustment for daylight saving time.
Network
Management Card
(Network-MS)
User Manual
1. Select the Week number, Day, Month, and Time for which daylight saving time should start. For
example, if daylight saving time starts the second Sunday of March at 2:00 am, select Second Sunday
and March, and then enter 02:00.
2. Select the Week number, Day, Month, and Time for which daylight saving time should end. For
example, if daylight saving time ends the first Sunday of November at 3:00 am, select First Sunday, and
November, and then enter 03:00
Note 1:
The even the card is used in a UPS supporting time-stamping, the card's time is automatically synchronized with
that of the UPS.
Note 2:
After start-up, if the card is in manual mode or if no NTP server was reached, the card initializes at 01/01/1970.
Network
Management Card
(Network-MS)
User Manual
To upload a new version of the card's firmware, select the file to be loaded using the Browse… button and click
Upload.
Do not interrupt the operation before the card displays the following screen:
Network
Management Card
(Network-MS)
User Manual
Important note: To switch the serial port to the configuration mode, just disconnect the cable and reset the card.
4.5.1 Characteristics
Network
Management Card
(Network-MS)
User Manual
4.5.2 Environment Status
Network
Management Card
(Network-MS)
User Manual
The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door,
alarms or generator unit).
The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the
protected system.
The Sensor name is the function name given to the sensor, usually it enables location of the sensor.
Temperature: Choose the temperature unit (°C or °F) from the selection box.
Note: Changing the temperature unit clear the log file.
High threshold: if this value is exceeded, a notification if enabled. The default value is 40 °C / 104 °F.
Low threshold: If this value is exceeded, a notification if enabled. The default value is 5 °C / 41 °F.
Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold.
The default value is 2 °C / -3.6 °F.
The high alarm disappears when the value drops below the High threshold - Hysteresis value
The low alarm disappears when the value returns above the Low threshold + Hysteresis value
Humidity
High threshold: If this value is exceeded, a notification is sent if this is validated. The default value is 90%.
Low threshold: If this value is exceeded, a notification is sent if this is validated. The default value is 5%.
Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. The default
value is 5%.
Network
Management Card
(Network-MS)
User Manual
The high alarm disappears when the value drops below the High threshold - Hysteresis value
The low alarm disappears when the value returns above the Low threshold + Hysteresis value
Input #1 and Input #2: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning,
generator unit, etc.). Max. length is 28 characters.
When closed and when open: are the names associated to the two contact positions. (e.g.: "open" and "closed"
for a door, "On" and "Off" for a generator).
Each status change triggers a notification if enabled.
When the Notification box is enabled, the following functions are activated for each event selected:
• display in the list of current alarms
• Consideration in the UPS log
• SNMP trap generation
• notification by e-mail (if the Environment sensor notification option is enabled in the e-mail notification
page)
System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the
Shutdown option cannot be used.
Network
Management Card
(Network-MS)
User Manual
4.5.4 Log
The two environment sensor measurements: Temperature and Humidity are recorded at an interval defined by
the Environment log interval in the System settings page.
By default, this period is 300 seconds.
Each measurement is dated and stored in the log of the UPS’s communication card.
The size of log files is limited by a time indexing system.
The user can Save the log on his/her workstation at any time, in a CSV format file.
The user can also Clear the files contained in the card to reset the log.
Network
Management Card
(Network-MS)
User Manual
5 Server protection
• IP Address or hostname of the server on which it is installed: So that the card can inform it of power
events.
• Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each
IPP): The card takes into account the longest shutdown time of all the Intelligent Power Protector
subscribed (This is the Shutdown duration of the Shutdown parameters) page to manage UPS
shutdowns without affecting any of IPP connected.
During normal operation, the protection application periodically checks its connection with the card.
In case of a major power event, the card sends information to the protection application which reacts according to
the situation. (shutdown order, programmed actions, messages to the administrator and to users via the network)
When the server shuts down, the protection application unsubscribes itself from the notified applications.
During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If
several criteria are selected, (See page Shutdown parameters), the first criterion encountered will launch the
shutdown procedure.
At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid
unnecessary discharge of its batteries, depending on its configuration.
Network
Management Card
(Network-MS)
User Manual
Shutdown after :
Battery
capacity
Delay before
shutdown
100%
Remaining autonomy
t
0%
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and
launches the system shutdown procedure at the end of the countdown.
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding
battery backup time.
Note 1:
The Intelligent Power Protector can also manage its own Shutdown Timer (configurable in the Shutdown
Module"set-up" menu of each Intelligent Power Protector) launched when the UPS switches to battery.
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored
is not guaranteed (e.g. power restoration if only this system was shut down).
5.1.1.2 Initiating the shutdown procedure when the battery level is lower than:
(If Capacity under)
When the card detects that the remaining backup time percentage is less than the configured level, the shutdown
sequence is started.
By default, this value is set at 20%.
Note:
The UPS already manages an equivalent parameter for the end of backup pre-alarm.
Network
Management Card
(Network-MS)
User Manual
The card does not accept values less than that programmed in the UPS.
Check the UPS documentation.
When the Network Management Card detects that the percentage of backup time remaining is less than the value
set, the shutdown sequence is started.
Duration (in seconds) required for the system protected by the protection application to shut down.
The protection applications send their own "Shutdown duration" to the Network Management Card.
Based on these values (maximum Shutdown duration of all subscribed customer systems) that the card will send
to the delayed shutdown order to the UPS.
Network
Management Card
(Network-MS)
User Manual
Certain UPS models are equipped with controlled outlets (generally 2) which are always dependant on the UPS's
main outlet.
Shutdown of the main outlet systematically causes shutdown of the programmable outlets.
Warning: Some inverters have only 2 programmable plugs without mains plug (Powerware). With this type of
UPS, stopping a programmable outlet causes the UPS shutdown.
Utility
Main output
Shutdown duration
main output
Outlet 1
Shutdown
duration outlet
1 Shutdown duration 1
NSM 1 on main
output
Shutdown
duration 2
NSM 2 on outlet 1
Intelligent Power Protector (IPP) starting with version 3.0 are compatible with the controlled outlets.
After connecting the server electrically to one of the controlled outlets, the IPP must be informed of the outlet
number to which it is connected.
Refer to the documentation of the IPP available on the internet site www.eaton.com
It is possible to optimise backup time by shutting down non-priority equipment or sequencing the shutdown of
several devices.
Network
Management Card
(Network-MS)
User Manual
Two shutdown criteria are possible:
• Shutdown of outlets after a set battery back-up time (After)
• Shutdown of outlets at a given battery discharge level (if battery capacity under)
It is possible to specify values for both criteria. The first criterion reached will initiate server shutdown.
It is possible to delay outlet power-on to reduce inrush currents on startup or to sequence the startup of several
devices.
Controlled outlet startup after a given time is based on startup of the main outlet.
Network
Management Card
(Network-MS)
User Manual
During battery backup time, the Shutdown Timer of the Network Management Card is reached: After a user-
defined backup time period (Shutdown parameters page), the shutdown of all servers is initiated, followed by the
UPS shutdown (depending on its configuration). The UPS restarts when utility power is restored (depending on its
configuration)
Shutdown duration: Maximum value of shutdown times of protection application subscribed to the card. This value
is updated each time a client subscribes/ unsubscribes.
Utility
Main output
Shutdown duration
Shutdown after: main output
NSM 1 on main
output
Shutdown after 1:
Output 1
Shutdown
duration output 1
NSM 2 on output 1
5.2.2 Extended power outage, shutdown initiated by the "Low battery power"
message
When the "Low battery power" criterion is displayed, the UPS is shut off after taking into account the shutdown
duration of the servers.
"Low battery power": The message appears if either of the two following criteria is reached:
- Low Battery Level
- Low Battery Delay
Network
Management Card
(Network-MS)
User Manual
Start shutdown Start shutdown main
Utility failure output 1 output Utility restore
Utility
Shutdown duration
Main output
Battery capacity
under:
NSM 1 on main
output
Shutdown
duration output 1
Output 1
Battery capacity
under: (output 1)
NSM 2 on output 1
5.2.3 Case of power restoration before the end of the "shutdown duration" counter
If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for
a time equal to the forced reboot delay (10 seconds)
Utility
Shutdown
duration Forced Reboot
Main output
Shutdown
duration output 1
Output 1
Battery capacity
under: (output 1)
NSM 2 on output 1
Network
Management Card
(Network-MS)
User Manual
As described in the 5.1.1.4 paragraph, the protection application transmit their own "Shutdown duration" to the
Network Management Card. Based on these values (maximum Shutdown duration of all subscribed customer
systems) that the card will send to the delayed shutdown order to the UPS.
If the UPS have two NMC cards, the maximum shutdown duration of the two groups of protected systems will be
used for the delayed shutdown order.
Example: If the subscribed customers of the first NMC card have a maximum Shutdown duration of 60s and the
ones of the second NMC card of 120s, the servers shutdown will be launched 120s before the UPS shutoff..
5.3.2 Settings
Set-up shutdown parameters to the same value on the 2 cards are highly recommended (for the main output and
the controlled outlets).
If the settings are not the same, the first criteria reached on one the 2 cards will launch the secure shutdown of all
servers
Please, note that in any case the shutdown of the protected servers will be executed safely.
Network
Management Card
(Network-MS)
User Manual
6 TELNET/SSH/CLI interfaces
6.1 Introduction
This chapter describes how to use the Telnet/SSH/CLI interfaces of the IBM Network Management Card.
These settings enable the administrator to configure the network parameters of the card and authorisation of the
remote upgrade of the embedded system.
The parameter list is the following:
• MAC address (read only)
• IP address
• Subnet mask
• Gateway address
• Host name
• Domain name
• BOOTP/DHCP
• IPv6
• IPv6 autoConfig
• IPv6 address 1
• IPv6 prefix length
• IPv6 Gateway address
• IPv6 local address (read only)
• IPv6 address 2 (read only)
• Updating software
• Primary DNS server
• Secondary DNS server
• SMTP server
• SMTP port
• SMTP server authentication
• SMTP login
• SMTP password
Network
Management Card
(Network-MS)
User Manual
6.2.2 System settings
These settings enable the customisation of the information on the UPS properties pages.
The parameter list is the following:
• UPS contact
• UPS location
• History log interval
• Environment log interval
• Default language
This is the list of the supervision stations receiving traps. There is a maximum of 3 trap receivers.
The parameter list is the following:
• Receiver 1, 2 or 3 :
• Application name
• Host name
• Trap port
• Protocol
• Trap community
• MIB filter
These settings enable the configuration for secure access to the card via a web browser or SNMP. This menu can
also define Telnet/SSH/CLI procedure to access to the card.
The parameter list is the following:
• Login
• Password
• Security mode
• Telnet access
• Telnet security
• Console interface
These settings are used to define the behaviour of the UPS during a shutdown.
The parameter list is the following:
• Outlet 1 (main):
• Name
• Remaining time limit
• Remaining capacity limit
• Shutdown after
Network
Management Card
(Network-MS)
User Manual
• Shutdown timer selected
• Shutdown duration
• Battery capacity exceeds
• Outlet 2 & 3:
• Name
• Switch off after
• Remaining capacity limit
• Shutdown duration
• Switch on after
Network
Management Card
(Network-MS)
User Manual
• Port
• Time Out
These settings enable the initialisation of the date and time of the card in three different ways.
The parameter list is the following:
• Date & Time
• Type of synchronisation
• NTP host name
• Time-Zone
• Daylight saving time
These settings enable the configuration of the environment sensor. If not present, this menu is not available.
The parameter list is the following:
• Sensor name
• Temperature:
• Unity
• High threshold
• Low threshold
• Hysteresis
• Offset
• High notify
Network
Management Card
(Network-MS)
User Manual
• Low notify
• High shutdown
• Low shutdown
• Humidity:
• High threshold
• Low threshold
• Hysteresis
• Offset
• High notify
• Low notify
• High shutdown
• Low shutdown
• Input#1:
• Identifier
• Close label
• Close notify
• Close shutdown
• Open label
• Open notify
• Open shutdown
• Input#2:
• Identifier
• Close label
• Close notify
• Close shutdown
• Open label
• Open notify
• Open shutdown
Network
Management Card
(Network-MS)
User Manual
• Settings in read-only mode: yellow.
• Warning message: green.
• Error message: light red.
Network
Management Card
(Network-MS)
User Manual
Session Time
Max Session Time
Radius Menu Primary Server: Enable
Radius Menu Primary Server: Name
Radius Menu Primary Server: Secret
Radius Menu Primary Server: Port
Radius Menu Primary Server: NAS
Radius Menu Primary Server: Retry
Radius Menu Primary Server: TimeOut
Radius Menu Secondary Server: Enable
Radius Menu Secondary Server: Name
Radius Menu Secondary Server: Secret
Radius Menu Secondary Server: Port
Radius Menu Secondary Server: NAS
Radius Menu Secondary Server: Retry
Radius Menu Secondary Server: TimeOut
LDAP Menu Primary Server: Enable
LDAP Menu Primary Server: Name
LDAP Menu Primary Server: Port
LDAP Menu Secondary Server: Enable
LDAP Menu Secondary Server: Name
LDAP Menu Secondary Server: Port
LDAP Menu Mechanism
LDAP Menu Search Mode
LDAP Menu Search User Distinguished Name
LDAP Menu Search User Password
Login password to default
Default Configuration
This screen is the main screen displayed when the connection is established.
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Main menu
------------------------------------------------------------------------
1 : Reset
2 : Network settings
3 : Trap receivers
4 : System settings
5 : Shutdown settings
6 : Access control
7 : Date and Time
8 : Environment settings
9 : Item not available
10 : Authentication settings
11 : Set login password to default
12 : Default configuration
This menu item is used to reset the card. It is not possible to reset the card when a flash write process is in
progress. When a reset operation is completed, a prompt is displayed to confirm the reset.
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Network settings
------------------------------------------------------------------------
: MAC address [00:20:85:FD:1C:07] (3)
1 : BootP/DHCP (0=Disabled, 1=Enabled) [1]
(1)
2 : IP Address [xxx.xxx.xxx.xxx]
3 : Subnet Mask [xxx.xxx.xxx.xxx] (1)
4 : Gateway Address [xxx.xxx.xxx.xxx] (1)
5 : Host Name [ups1]
6 : UPS Domain Name [ups.domain.com]
7 : IPv6 (0=No, 1=Yes) [0]
8 : IPv6 Auto-config (0=No, 1=Yes) [0] (2)
9 : IPv6 add.1/prefix len. [ ] (3)(5)
10 : IPv6 gateway address [ ] (3)
11 : IPv6 local address (4)
12 : IPv6 address 2 (4)
13 : Firmware upgradable (0=No, 1=Yes) [1]
14 : Primary DNS Server (IPv4 or IPv6) [xxx.xxx.xxx.xxx]
15 : Secondary DNS Server [xxx.xxx.xxx.xxx]
16 : SMTP menu
17 : SNMP menu
0 : Exit
----------------------------------------------------------------------
(1) Read-only or read-write according to “BootP/DHCP” status
(2) Read-only or read-write according to “IPv6 enabled” status
(3) Read-only or read-write according to “IPv6 enabled” and “IPv6 auto-config” status
(4) Read-only
(5) The value is a concatenation of the IPv6 address 1 and of the prefix length.
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Network settings - SMTP
------------------------------------------------------------------------
1 : Hostname (for Email notification) [smtpserver]
2 : SMTP Port (Default Value: 25) [25]
3 : Authentication (0=No, 1=Yes) [1]
4 : Login [smtplogin] (1)
5 : Password [*************] (2)
0 : Exit
----------------------------------------------------------------------
(1) Read-only or read-write according to “Authentication” status
(2) Write-only or hidden according to “Authentication” status
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Network settings - SNMP
------------------------------------------------------------------------
1 : Version (Disabled, V1, V3, V1V3) [V1V3]
2 : SNMP port (Default value: 161) [161]
** About V1 **
3 : Community read-only [publicuser]
4 : SNMP write (0=No, 2=Yes) [2]
5 : Community write [privateuser] (1)
** About V3 **
6 : Read-only user [readuser]
7 : R/O security (1=No Auth, 2=Auth NoPriv, 3=Auth Priv) [2]
8 : Read-only password [***********] (2)
9 : Read-Write user [writeuser]
10 : R/W security (1=No Auth, 2=Auth NoPriv, 3=Auth Priv) [2]
11 : Read-Write password [***********] (3)
12 : Notification user name [notifuser]
0 : Exit
----------------------------------------------------------------------
All items from 3 to 11 are read-write or masqued according to “Version” status.
(1) Read-write or read-only according to “SNMP write” status;
(2) Write-only or hidden according to “R/O security” status; the length has to be 8 characters at least;
(3) Write-only or hidden according to “R/W security” status; the length has to be 8 characters at least.
This menu is used to view or modify the applications receiving traps and to configure trap type.
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Trap receiver
------------------------------------------------------------------------
1 : Receiver 1
2 : Receiver 2
3 : Receiver 3
0 : Exit
------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Trap receiver X
------------------------------------------------------------------------
1 : Hostname or IP address [xxx. xxx. xxx. xxx]
2 : Application mane [MyTrap]
3 : Trap Port (Default value: 162) [162 ]
3 : Trap community [ ]
4 : Protocol (Disabled, V1, V3, V1V3) [Disabled]
5 : MIB filter (b0=Pulsar, bit1=Power MIB, bit2=IETF) [2] (1)
0 : Exit
----------------------------------------------------------------------
(1) Only the 3 less significant bits are used (b0 to b2). The possible value are from 0 to 7 (3 bits used set to 1).
0 : Exit
----------------------------------------------------------------------
This menu is used to view or modify the shutdown settings for the 3 outlets.
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings
------------------------------------------------------------------------
1 : Master
2 : Outlet 2
3 : Outlet 3
0 : Exit
------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings - Master
------------------------------------------------------------------------
1 : Name [Master]
2 : Shutdown if remaining time under (sec) [180]
3 : Shutdown if capacity under (%) [20]
4 : Shutdown timer enabled (0=No, 1=Yes) [0]
5 : Shutdown timer (sec) [1800]
6 : Shutdown duration (sec) [120]
7 : Restart if capacity exceed (%) [0]
0 : Exit
------------------------------------------------------------------------
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings – Outlet 1
------------------------------------------------------------------------
1 : Name [Group1]
2 : Switch off after (sec) [2147483647]
3 : Switch off if capacity under (%) [0]
4 : Shutdown duration (sec) [120]
5 : Switch on after (sec) [0]
0 : Exit
------------------------------------------------------------------------
0 : Exit
----------------------------------------------------------------------
(1) Write-only and encrypted
(2) Read-write or read-only according to “Telnet access enabled” status.
Network
Management Card
(Network-MS)
User Manual
6.3.9 Date and time menu
0 : Exit
----------------------------------------------------------------------
(1) Read-write or read-only according to “Type of synchronization” status
(2) Setting resolves to the nearest half hour; for example, sending +02:36 results in +02:30, and sending +02:46
results in +03:00.
0 : Exit
------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Environment settings - Temperature
------------------------------------------------------------------------
1 : Unity (C=Celsius, F=Farenheit) [C]
2 : High Threshold [40 ]
3 : Low Threshold [5]
4 : Hysteresis [2]
5 : Offset [0.0]
6 : High notify (0=No, 1=Yes) [0]
7 : Low notify (0=No, 1=Yes) [0]
8 : High shutdown (0=No, 1=Yes) [0]
9 : Low shutdown (0=No, 1=Yes) [0]
0 : Exit
------------------------------------------------------------------------
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Environment settings - Humidity
------------------------------------------------------------------------
1 : High Threshold [90 ]
2 : Low Threshold [5]
3 : Hysteresis [5]
4 : Offset [0.0]
5 : High notify (0=No, 1=Yes) [0]
6 : Low notify (0=No, 1=Yes) [0]
7 : High shutdown (0=No, 1=Yes) [0]
8 : Low shutdown (0=No, 1=Yes) [0]
0 : Exit
------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Environment settings – Input #1
------------------------------------------------------------------------
1 : Identifier [Fan1]
0 : Exit
------------------------------------------------------------------------
0 : Exit
-----------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
Radius settings (1)
-----------------------------------------------------------------------------
0 : Exit
-----------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
LDAP settings(1)
-----------------------------------------------------------------------------
0 : Exit
-----------------------------------------------------------------------------
(1) Read-write or read-only according to “Authentication Method” status
(2) Read-write or read-only according to “Enable” status of the Primary Server
(3) Read-write or read-only according to “Enable” status of the Secondary Server
(4) Read-write or read-only according to “Search Mode” status
If the login or password is lost, select this option to enable the return to the default Login/Password.
This item is used to return to default configuration which is described in this document.
The NMC card is automatically restarted after returns to default configuration.
Network
Management Card
(Network-MS)
User Manual
not allowed in command arguments except for the strings. The strings are in double quotes (“”).
The recognized commands are given in the following chapters and may be updated later.
6.4.1.2 “setEcho”
Purpose Hide, or not, all characters. If hidden, each character entered is replaced by an ‘*’
Syntax setEcho [option]
option :
ON
OFF
Examples #> setEcho ON
6.4.1.3 “quit”
6.4.1.4 “reset”
6.4.1.5 “version”
Network
Management Card
(Network-MS)
User Manual
6.4.1.6 “defaultPass”
6.4.1.7 “defaultConf”
6.4.2.1 “getNetwork”
6.4.2.2 “setNetwork”
Network
Management Card
(Network-MS)
User Manual
(1)
IPMask = “xxx.xxx.xxx.xxx”
(1)
IPGateway = “xxx.xxx.xxx.xxx”
HostName = “xx..xx”
DomainName = “xx..xx”
IPv6Enable = 0|1 (0=No, 1=Yes)
(2)
IPv6AutoConf = 0|1 (0=No, 1=Yes)
(3)(4)
IPv6Address1 = “xx.xx/xxx”
(3)
PrefixLength = xx
(3)
IPv6DefaultGateway [= ]
PrimaryDNS = “xx..xx”
SecondaryDNS = “xx..xx”
FirmwareUpgrade = 0|1 (0=No, 1=Yes)
Examples #> setNetwork IPAddress=xxx.xxx.xxx.xxx IPMask= xxx.xxx.xxx.xxx
(1)
Comments : Writing enabled according to “DHCP” status
(2)
: Writing enabled according to “IPv6Enable” status
(3)
: Writing enabled according to “IPv6AutoConf” status
(4)
: The value is a concatenation of IPv6 address 1 and prefix length
6.4.2.3 “getSMTP”
6.4.2.4 “setSMTP”
Network
Management Card
(Network-MS)
User Manual
Examples #> setSMTP HostName = “Smtp Server”
(1)
Comments : Writing enabled according to “Authentication” status
(2)
: Don’t forget to set echo off
6.4.2.5 “getSNMP”
6.4.2.6 “setSNMP”
Network
Management Card
(Network-MS)
User Manual
NotificationUserName = “xx.xx”
FirmwareUpgrade = 0|1 (0=No, 1=Yes)
Examples #> setSNMP User = “readuser”
(1)
Comments : Writing enabled according to “snmpVersion” status
(2)
: Writing enabled according to “WriteCommunitySecurityLevel” status
(3)
: Writing enabled according to “UserSecurityLevel” status
(4)
: Writing enabled according to “AdminSecurityLevel” status
(5)
: Don’t forget to set echo off
(6)
: The length has to be 8 characters at least.
6.4.3.1 “getTrap”
6.4.3.2 “SetTrap”
Network
Management Card
(Network-MS)
User Manual
bit2 = 1 : MIB IETF enabled
6.4.4.1 “getSystem”
6.4.4.2 “setSystem”
6.4.4.3 “getHistSyst”
6.4.4.4 “setHistSyst”
Network
Management Card
(Network-MS)
User Manual
Examples #> setHistSyst Interval=12
Comments
6.4.4.5 “getEnvSyst”
6.4.4.6 “setEnvSyst”
6.4.5.1 “getShutdown”
Network
Management Card
(Network-MS)
User Manual
StartupTimer
Examples #> getShutdown 1 ShutdownDuration
Comments
6.4.5.2 “setShutdown”
6.4.6.1 “getAccess”
6.4.6.2 “setAccess”
Network
Management Card
(Network-MS)
User Manual
options :
Login = “xx..xx”
(1)(2)
Password = “**..**”
(1)(2)
ConfirmPass = “**..**”
Security = 1|2|3 (1=conf., 2=full auth.,
3=full auth. & SSL)
Examples #> setAccess Security=3
(1)
Comments : Don’t forget to set echo off
(2)
: The 2 passwords entered must be the same for to be taken into account
6.4.6.3 “getTelnet”
6.4.6.4 “setTelnet”
6.4.7.1 ”getAuth”
Network
Management Card
(Network-MS)
User Manual
Examples #> getAuth SessionTime
Comments
6.4.7.2 “setAuth”
6.4.7.3 ”getRadPrimSrv”
6.4.7.4 “setRadPrimSrv”
Network
Management Card
(Network-MS)
User Manual
(1)
Comments : Writing enabled according to “AuthMethod” status
(2)
: Writing enabled according to “Enable” status
6.4.7.5 ”getRadSecondSrv”
6.4.7.6 “setRadSecondSrv”
(1)
Purpose To modify an Radius secondary server setting
Syntax syntax: setRadSecondSrv [options...]
options:
Server Enable <-- 0=No, 1=Yes -->(1)
Server ServerName="Server Name"(1) (2)
Server SharedSecret="Shared Secret"(1) (2)
Server Port=xx <-- 1..65535 -->(1) (2)
Server NasIdentiferType=IPV4|IPV6_1|IPV6_2|IPV6_LOCAL(1) (2)
Server Retry=xx <-- 1..9999 -->(1) (2)
Server Timeout=xx <-- 1..9999 -->(1) (2)
Examples #> setRadSecondSrv Port =1812
(1)
Comments : Writing enabled according to “AuthMethod” status
(2)
: Writing enabled according to “Enable” status
6.4.7.7 ”getLDAPPrimSrv”
Network
Management Card
(Network-MS)
User Manual
Comments
6.4.7.8 “setLDAPPrimSrv”
6.4.7.9 ”getLDAPSecondSrv”
6.4.7.10 “setLDAPSecondSrv”
6.4.7.11 ”getLDAPSearch”
Network
Management Card
(Network-MS)
User Manual
SearchUser
SearchUserPassword
UserBaseSearchDn
UserObject
UserAttr
AuthzMode
UPSGroupNameAttr
UserNameAttr
GroupBaseSearchDn
Examples #> getLDAPSearch AuthMechanism
Comments
6.4.7.12 ” setLDAPSearch”
6.4.8.1 “getDate”
Network
Management Card
(Network-MS)
User Manual
Time
TimeSync
TimeNtp
TimeZone
TimeDaylight
Examples #> getDate timeSync
Comments
6.4.8.2 “setDate”
6.4.9.1 “getEnv”
6.4.9.2 “setEnv”
Network
Management Card
(Network-MS)
User Manual
6.4.9.3 “getTemp”
6.4.9.4 “setTemp”
6.4.9.5 “getHum”
Network
Management Card
(Network-MS)
User Manual
HighNotify
LowNotify
HighShutdown
LowShutdown
Examples #> getHum Offset
Comments
6.4.9.6 “setHum”
Network
Management Card
(Network-MS)
User Manual
iName = “xx..xx”
State[0].Description = “xx..xx”
State[0].Notify = 0|1 (0=No, 1=Yes)
State[0].Shutdown = 0|1 (0=No, 1=Yes)
State[1].Description = “xx..xx”
(1)
State[1].Notify = 0|1 (0=No, 1=Yes)
(1)
State[1].Shutdown = 0|1 (0=No, 1=Yes)
Examples #> setInput1 State[0].Label = “Door open” State[0].Notify = 1
(1)
Comments : Writing enabled only if the notification is enabled
6.5 Constraints/Limitations
1. It is not possible to open sessions with different protocols (see table below).
2. The maximum number of sessions opened at same time is 5.
3. Email recipients can not be configured through Telnet/SSH/CLI.
Table of compatibility:
TELNET & MENU TELNET & CLI SSH & MENU SSH & CLI
TELNET & MENU
TELNET & CLI
SSH & MENU
SSH & CLI
Network
Management Card
(Network-MS)
User Manual
• Use the cord supplied with the card (only with reference 34003918 or CAB-00010 or 720-C2270-00).
• Connect the card to a computer equipped with a hyperterminal type emulator. The serial link must be set
at 9600 baud, 8 bits, no parity, 1 stop bit, and without flow control.
• Check that UPS power is on.
• Enter admin as password (not modifiable).
• The menu is in English only.
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
Reset
-----------------------------------------------------------------------------
1 : Restart the card from the boot
0 : Exit
-----------------------------------------------------------------------------
-----------------------------------------------------------------------------
Network settings
-----------------------------------------------------------------------------
1 : Read Network settings
2 : Modify Network settings
3 : Set Ethernet speed
0 : Exit
-----------------------------------------------------------------------------
Network configuration :
MAC address : 00:20:85:FD:1C:07
Mode : Static IP
IP address : xxx.xxx.xxx.xxx
Subnet mask : xxx.xxx.xxx.xxx
Gateway : xxx.xxx.xxx.xxx
Link Local IPv6 address : xxxx::xxxx:xxxx:xxxx:xxxx /xx
Global IPv6 address : xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx /xx
Global IPv6 address : xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx:xxxx /xx
Network
Management Card
(Network-MS)
User Manual
For each of the following questions, you can press <Return> to select the
value
shown in braces, or you can enter a new value.
Should this target obtain IP settings from the network?[N]
Static IP address [xxx.xxx.xxx.xxx]?
Subnet Mask [xxx.xxx.xxx.xxx]?
Gateway IP address [xxx.xxx.xxx.xxx]?
Wait during your new configuration is saved ...
Reset the card to take into account the new configuration.
In DHCP mode, the card can receive the following parameters according to the DHCP server settings
• IPv4 address
• Subnet Mask
• IPv4 Gateway address
• Primary DNS server
• Secondary DNS server
The card must be restarted in order for the new parameters to be taken into account.
The card must be restarted in order for the new parameters to be taken into account.
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------
Wait during Login Password return to default ...
The card is now accessible via the Web with the password admin.
The card must be restarted in order for the new parameters to be taken into account.
Network
Management Card
(Network-MS)
User Manual
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------
Wait during configuration returns to default ...
The card must be restarted in order for the new parameters to be taken into account.
Network
Management Card
(Network-MS)
User Manual
8 Appendix
Network
Management Card
(Network-MS)
User Manual
Positive DC bus too high Positive DC bus OK
Negative DC bus too low Negative DC bus OK
Positive DC bus too low Positive DC bus OK
Inverter limitation Inverter end of limitation
Inverter fuses blown Input fuses OK
Inverter fault Inverter OK
Inverter overload Inverter load OK
Inverter over temperature Inverter temperature OK
Inverter short circuit Inverter OK
Inverter thermal overload Inverter load OK
Load not protected - On Automatic Bypass Load protected - Return from Bypass
Load short circuit Load OK
Load not powered Load powered
Protection Lost Protection OK
Emergency button ON Emergency button OFF
Fan fault Fan OK
Redundancy Lost Redundancy OK
Low battery Battery OK
UPS communication failed UPS communication restored
UPS data base not available UPS data base OK
UPS on battery UPS on normal AC
UPS internal fault UPS OK
UPS overload UPS returns to normal load
UPS overtemperature UPS temperature OK
Imminent UPS shutoff UPS OK
<Sensor name>: <Sensor name>:
Temperature is above high threshold xx °C Temperature is in normal range
<Sensor name>: <Sensor name>:
Humidity is above high threshold xx % Humidity is in normal range
<Sensor name>: <Sensor name>:
Temperature is below low threshold xx °C Temperature is in normal range
<Sensor name>: <Sensor name>:
Humidity is below low threshold xx % Humidity is in normal range
<Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when closed label>
<Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #1 label> <when open label>
<Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when closed label>
<Sensor name>: <Input #2 label> <when open label> <Sensor name>: <Input #2 label> <when open label>
Network
Management Card
(Network-MS)
User Manual
If the UPS is modular UPS, for each module:
Network
Management Card
(Network-MS)
User Manual
Inverter limitation Inverter end of limitation
Inverter overload Inverter load OK
Inverter over temperature Inverter temperature OK
Inverter thermal overload Inverter load OK
Negative DC bus too high Negative DC bus OK
Positive DC bus too high Positive DC bus OK
Negative DC bus too low Negative DC bus OK
Positive DC bus too low Positive DC bus OK
Output switch (Q5N) open Output switch (Q5N) closed
Normal AC NOK Normal AC OK
UPS on battery UPS on normal AC
UPS overload UPS returns to normal load
UPS over temperature UPS temperature OK
Fan fault Fan OK
UPS communication failed UPS communication restored
Network
Management Card
(Network-MS)
User Manual
Automatic Bypass switch (Q4S) open Automatic Bypass switch (Q4S) closed
Bypass AC frequency out of tolerance Bypass AC frequency OK
Automatic Bypass fault Automatic Bypass OK
Automatic Bypass overload Automatic Bypass load OK
Automatic Bypass over temperature Automatic Bypass temperature OK
Bypass AC phase out of tolerance Bypass AC phase OK
Automatic Bypass thermal overload Automatic Bypass load OK
Load not protected - On Automatic Bypass Load protected - Return from Bypass
Bypass AC voltage out of tolerance Bypass AC voltage OK
Battery switch (QF1) open Battery switch (QF1) closed
Manual Bypass switch (Q3BP) closed Manual Bypass switch (Q3BP) open
UPS on manual bypass
Inverter limitation Inverter end of limitation
Inverter fuses blown Input fuses OK
Inverter fault Inverter OK
Inverter overload Inverter load OK
Inverter overtemperature Inverter temperature OK
Inverter short circuit Inverter OK
Inverter thermal overload Inverter load OK
Output switch (Q5N) open Output switch (Q5N) closed
Load short circuit Load OK
Single wave load fault Load OK
Negative DC bus too high Negative DC bus OK
Positive DC bus too high Positive DC bus OK
Rectifier fault Rectifier OK
Negative DC bus too low Negative DC bus OK
Positive DC bus too low Positive DC bus OK
Protection Lost Protection OK
Redundancy Lost Redundancy OK
Normal AC NOK Normal AC OK
Low battery Battery OK
UPS communication failed UPS communication restored
UPS data base not available UPS data base OK
UPS on battery UPS on normal AC
Emergency button ON Emergency button OFF
Fan fault Fan OK
Load not powered Load powered
UPS internal fault UPS OK
Battery fault Battery OK
UPS overload UPS returns to normal load
UPS over temperature UPS temperature OK
Network
Management Card
(Network-MS)
User Manual
Imminent UPS shutoff UPS OK
< Sensor Name> : Temperature is above high <Sensor Name> : Temperature is in normal
threshold <xx> (°C) or (°F) range
< Sensor Name> : Humidity is above high threshold <Sensor Name> : Temperature is in normal
<xx> (%) range
< Sensor Name> : Temperature is below low threshold <Sensor Name> : Temperature is in normal
<xx> °C or (°F) range
< Sensor Name> : Humidity is below high threshold <Sensor Name> : Temperature is in normal
<xx> (%) range
<Sensor name>: <Input #1 label> <when closed
label>
<Sensor name>: <Input #1 label> <when open label>
<Sensor name>: <Input #2 label> <when closed
label>
<Sensor name>: <Input #2 label> <when open label>>
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
The Card implements the full IETF standard UPS MIB (RFC 1628), including the IETF alarm table and traps. Visit
http://tools.ietf.org for a description of the MIB. The UPS MIB access path is 1.3.6.1.2.1.33
This section contains an overview of MIB definitions for each of the MIB files:
Eaton Pulsar MIB (MGE MIB)
Eaton Pulsar MIB (MGE MIB) for environmental sensors
The NMC implements the reduced Eaton Pulsar MIB (MGE MIB), only the objects listed in the following tables are
managed. The entire MIB description is available at http://download.mgeops.com
Network
Management Card
(Network-MS)
User Manual
mginputFrequency_1 DeciHz {6.2.1.3.1.0}
mginputFrequency_2 DeciHz {6.2.1.3.2.0}
mginputFrequency_3 DeciHz {6.2.1.3.3.0}
mginputMinimumVoltage {6.2.1.4.0}
mginputMaximumVoltage {6.2.1.5.0}
mginputCurrent_1 DeciAmps {6.2.1.6.1.0}
mginputCurrent_2 DeciAmps {6.2.1.6.2.0}
mginputCurrent_3 DeciAmps {6.2.1.6.3.0}
upsmgInputBadStatus {6.3.0}
upsmgInputLineFailCause {6.4.0}
upsmgOutputPhaseNum {7.1.0}
mgoutputPhaseIndex_1 {7.2.1.1.1.0}
mgoutputPhaseIndex_2 {7.2.1.1.2.0}
mgoutputPhaseIndex_3 {7.2.1.1.3.0}
mgoutputVoltage_1 deciVolts {7.2.1.2.1.0}
mgoutputVoltage_2 deciVolts {7.2.1.2.2.0}
mgoutputVoltage_3 deciVolts {7.2.1.2.3.0}
mgoutputFrequency_1 deciHz {7.2.1.3.1.0}
mgoutputFrequency_2 deciHz {7.2.1.3.2.0}
mgoutputFrequency_3 deciHz {7.2.1.3.3.0}
mgoutputLoadPerPhase_1 % {7.2.1.4.1.0}
mgoutputLoadPerPhase_2 % {7.2.1.4.2.0}
mgoutputLoadPerPhase_3 % {7.2.1.4.3.0}
mgoutputCurrent_1 deciAmps {7.2.1.5.1.0}
mgoutputCurrent_2 deciAmps {7.2.1.5.2.0}
mgoutputCurrent_3 deciAmps {7.2.1.5.3.0}
upsmgOutputOnBattery 1(yes) 2(no) {7.3.0}
upsmgOutputOnByPass 1(yes) 2(no) {7.4.0}
upsmgOutputUtilityOff 1(yes) 2(no) {7.7.0}
upsmgOutputInverterOff 1(yes) 2(no) {7.9.0}
upsmgOutputOverLoad 1(yes) 2(no) {7.10.0}
upsmgOutputOverTemp 1(yes) 2(no) {7.11.0}
upsmgAgentIpAddress {12.1.0}
upsmgAgentSubnetMask {12.2.0}
upsmgAgentDefGateway {12.3.0}
upsmgAgentType {12.6.0}
upsmgAgentMibVersion {12.11.0}
upsmgAgentFirmwareVersion {12.12.0}
upsmgAgentCommUPS 1(yes) 2(no) {12.13.0}
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
This table lists objects that are managed if there is an optional Sensor / Environmental
Monitoring Probe (EMP) installed. The Eaton Pulsar MIB access path is
1.3.6.1.4.1.705.1.
Network
Management Card
(Network-MS)
User Manual
Network
Management Card
(Network-MS)
User Manual
upsEnvironmentHumidityOK Trap 60 Level 2
upsEnvironmentInput1Closed Trap 61 Level 2
upsEnvironmentInput1Open Trap 62 Level 2
upsEnvironmentInput2Open Trap 64 Level 2
upsEnvironmentInput2Closed Trap 63 Level 2
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified
applications” page
The Card implements the full Eaton Powerware MIB (PowerMIB), including alarm tables. The Eaton traps are
sent. The Eaton Powerware MIB access path is 1.3.6.1.4.1.534.
Table is an abbreviated list of objects from the PowerMIB. The UPS output/load segment controls objects and the
entire MIB description is available at http://powerquality.eaton.com/Support/SoftwareDrivers.
Network
Management Card
(Network-MS)
User Manual
xupsSecondaryInputWatch Integer {3.7.0}
Network
Management Card
(Network-MS)
User Manual
xupsOnBattery {7.3.0}
xupsLowBattery {7.4.0}
xupsUtilityPowerRestored {7.5.0}
xupsReturnFromLowBattery {7.6.0}
upsOutputOverload {7.7.0}
xupsInternalFailure {7.8.0}
xupsBatteryDischarged {7.9.0}
xupsInverterFailure {7.10.0}
xupsOnBypass {7.11.0}
xupsBypassNotAvailable {7.12.0}
xupsOutputOff {7.13.0}
xupsInputFailure {7.14.0}
xupsBuildingAlarm {7.15.0}
xupsShutdownImminent {7.16.0}
xupsOnInverter {7.17.0}
xupsBreakerOpen {7.20.0}
xupsAlarmBatteryBad {7.23.0}
xupsOutputOffAsRequested {7.24.0}
xupsDiagnosticTestFailed {7.25.0}
xupsCommunicationsLost {7.26.0]
xupsUpsShutdownPending {7.27.0}
xupsAlarmTestInProgress {7.28.0}
xupsAmbientTempBad {7.29.0}
xupsLossOfRedundancy {7.30.0}
xupsAlarmTempBad {7.31.0}
xupsAlarmChargerFailed {7.32.0}
xupsAlarmFanFailure {7.33.0}
xupsAlarmFuseFailure {7.34.0}
xupsPowerSwitchBad {7.35.0}
xupsModuleFailure {7.36.0}
xupsOnAlternatePowerSource {7.37.0}
xupsAltPowerNotAvailable {7.38.0}
xupsNoticeCondition {7.39.0}
xupsRemoteTempBad {7.40.0}
xupsRemoteHumidityBad {7.41.0}
xupsAlarmOutputBad {7.42.0}
xupsAlarmAwaitingPower {7.43.0}
xupsOnMaintenanceBypass {7.44.0}
Network
Management Card
(Network-MS)
User Manual
xupsTestBatteryStatus Integer {8.2.0}
xupsLastGeneralTest Integer {8.3.0}
xupsLastGeneralTestResult Integer {8.4.0}
• clients.conf file: allows NAS (NMC card) with an address in the 166.99.224/8 network to send requests
to the server (shared secret between the server and the NMC cards: eaton123)
client 166.99.224.0/8{
secret = eaton123
shortname = nmc
require_message_authenticator = no
}
• users.conf file: allows (with Service-Type attribute) the access to the NMC cards as an administrator
for the user:
o name: “admin”,
o password "myPassword "
Network
Management Card
(Network-MS)
User Manual
admin Cleartext-Password := "myPassword"
Service-Type = Administrative-User
The following RADIUS configuration must be apply( value of the masked field secret: eaton123):
8.3.2 LDAP
Network
Management Card
(Network-MS)
User Manual
• Password: eaton
The following LDAP configuration must be apply(value of the masked field “Search User Password”: eaton):
Network
Management Card
(Network-MS)
User Manual
9 Glossary
Bootp:
Protocol based on UDP used to allocate an IP address corresponding to an Ethernet card during the startup
phase. Defined by the RCF 951
Community name:
Access key to access SNMP agent information
DN Distinguished Name
An LDAP object is referenced by its distinguished name (DN). A DN is a sequence of relative distinguished
names (RDN) connected by commas.
Gateway
Interconnection equipment between networks with different conventions, to enable communication between them
HTTPS
Secure version of HTTP, the communication protocol of the World Wide Web. It was invented by Netscape
Communications Corporation to provide authentication and encrypted communication and is used in electronic
commerce.
Network
Management Card
(Network-MS)
User Manual
RFC
Request for Comments. All documents defining internal Internet operation.
Network
Management Card
(Network-MS)
User Manual
Telnet is not a secure protocol, but it is possible to secure the connection using SSH
SSL (Secure Sockets Layers) is a protocol developed by Netscape Communications Corporation for securing
data transmission in commercial transactions on the Internet. Using public-key cryptography, SSL provides server
authentication, data encryption, and data integrity for client/server communications
Subnet mask
Mask of bits used to identify and differentiate the network address and the equipment address in an IP address.
Normally, the mask is automatically determined by the class of address, which defines in a unique manner the
network part/equipment part division of the IP address.
- Class A: internet address: 255.0.0.0.
- Class B: internet address: 255.255.0.0.
- Class C: internet address: 255.255.255.0.
Trap (SNMP): This term describes an event that affects a MIB variable. Traps are sent to the manager, which is
programmed to perform specific tasks upon reception of the traps.