C Line Changeover Switches Catalogue

The document discusses Larsen & Toubro's range of onload changeover switches. It provides an overview of the basic function and superior performance of the switches, which offer compactness, high performance, and customer convenience. The product range covers ratings from 63A to 2000A across 6 frame sizes and includes open execution, sheet steel enclosure, fused, and motorized versions.

Uploaded by

ekamjeet singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views48 pages

C Line Changeover Switches Catalogue

The document discusses Larsen & Toubro's range of onload changeover switches. It provides an overview of the basic function and superior performance of the switches, which offer compactness, high performance, and customer convenience. The product range covers ratings from 63A to 2000A across 6 frame sizes and includes open execution, sheet steel enclosure, fused, and motorized versions.

Uploaded by

ekamjeet singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 48

A Spectrum of Benefits ...

Onload Changeover Switch


ABOUT US

Larsen & Toubro is a technology-driven company that infuses engineering


with imagination. The Company offers a wide range of advanced solutions
in the field of Engineering, Construction, Electrical & Automation,
Machinery and Information Technology.

L&T Switchgear, a part of the Electrical & Automation business, is India's


largest manufacturer of low voltage switchgear, with the scale,
sophistication and range to meet global benchmarks. With over seven
decades of experience in this field, the Company today enjoys a leadership
position in the Indian market with a growing international presence.

It offers a complete range of products including powergear, controlgear,


industrial automation, building electricals & automation, reactive power
management, energy meters, and protective relays. These products
conform to Indian and International Standards.
INDEX

Overview 2-5

Product Data 6 - 19

Wiring Diagrams 20- 23

Characteristic Curves 24 - 27

Dimensions 28 - 43
Standards & Approvals

range of Changeover Switches comply with following standards

• IEC 60947-1, EN 60947-1, IS/IEC 60947-1


Low-voltage switchgear and controlgear, Part 1: General Rules

• IEC 60947-3, EN 60947-3, IS/IEC 60947-3


Low-voltage switchgear and controlgear, Part 3: Switches, disconnectors,
switch-disconnectors and fuse combination units

Third party certificates (ERDA / CPRI) available for range of changeover switches

NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005
Standard. Accredited laboratories have the responsibility of satisfying the criteria of
laboratory accreditation at all times, which are verified during Surveillance and
Reassessment visits by NABL. Further the accredited laboratories should prove their
technical competence by satisfactory participation in recognized Proficiency Testing
Programmes.

L&T’s Switchgear Testing Lab is NABL accredited subject to continued satisfactory


compliance to above standard & additional requirements of NABL.

All range of Changeover switches are tested in L&T's NABL accredited Switchgear
Testing Lab.

Marking
A CE marking is a European marking of conformity that indicates a product complies
with the essential requirements of the applicable European laws or directives with
respect to safety, health and environment and consumer protection. Generally, this
conformity to the applicable directives is done through self-declaration and is required
on products in the countries of the European Economic Area (EEA) to facilitate trade
among the member countries. The manufacturer or their authorized representative
established in the EEA is responsible for affixing the CE marking to their product. The
CE marking provides a means for a manufacturer to demonstrate that a product
complies with a common set of laws required by all countries in the EEA to allow free
movement of trade with in the EEA countries.

L&T’s range of Changeover switches conform to the Low voltage directive 73/23/EEC
as amended by directive 93/68/EEC, provided it is used in the application for which it is made
and is installed and maintained in accordance with professional practices with relevant
installation standards and operating instructions.

RoHS Compliance
As a green initiatives, Larsen & Toubro understands the requirements of the RoHS directive.
The directive restricts the use of hazardous substances in electrical and electronic
equipment and bans electrical equipment containing more than permitted levels of lead,
cadmium, mercury, hexavalent chromium, polybrominated biphenyl (PBS) and
polybrominated diphenyl ether (PBDE) flame retardants.

1
Overview
Basic Function
¾ 03
Superior
¾ Performance 04
Product
¾ Range 05
Changeover Switches

C-Line offers you a unique series of changeover Switches combining compactness with high performance
& Customer convenience, thus, making C-line a state-of-the-art product in changeover technology.
The C-line range covers ratings from 63 A to 2000 A in 6 frame sizes. These changeover switches are
available in open execution, Sheet steel enclosure, fused version (suitable for DIN type fuse - link) and
motorised version.

SS Enclosure inclusive of cable gland box

Field-convertible fuse changeover switch

Motorised changeover switch

Basic function of Changeover Switches


Onload Changeover S-D has 3 stable positions as defined below

POSITION l POSITION O POSITION ll


Switch is in ON position Switch is in OFF position and outgoing Switch is in ON position
with normal supply terminals are isolated from both supplies with alternate supply
available at the (normal and alternate supplies) available at the
outgoing terminals. outgoing terminals.

Onload Changeover S-D consists of two separate sets of terminals for incoming supplies and a set of output
terminals to connect the common load. Thus, changeover switch ensures continuity of supply to the load
by alternating between normal and alternate supply.

3
Superior Performance

Higher Contact system is of double break, knife type having self wiping action
short-time with electrodynamic compensation. This ensures reliable performance
during normal as well as short circuit fault conditions, offering higher
withstand
short-time withstand rating.
Capacity

Higher C-line switch offers high electrical and mechanical life in compact frame
sizes. The electrical and mechanical life are two times the requirement of
life
the standard.

Total Factory fitted external shorting links can be easily removed and fitted on
flexibility of the other side as required at site (125 A to 2000 A). This gives more
connection flexibility at the time of installation.

Maximum
termination The C-line range provides generous terminal capacity in its compact size,
capacity facilitating aluminium termination.

Higher Higher ground clearance between terminals and mounting base plate
ground ensures adequate clearance even after connecting cables. This eliminates
clearance the possibility of phase to ground flash over.

Total
C-line Changeover Switch provides complete safety by providing
safety
terminal shrouds, source separator and inter-phase barriers.

4
Product Range

Onload Changeover S-Ds are available from 63 A to 2000 A. The range is covered through 6 frames as
shown below.

Frame No. Ratings (A)


I 63 100

II 125 160 200

III 250 315

IV 400 630

V 630 800 1000

VI 1250 1600 2000*


*Available on request.

Versions C-line Changeovers are available in open execution, Sheet steel


enclosure, fused version and motorised version.

Changeover S-D suitable for open execution


Changeover S-D, which can be commissioned in panels are of open execution
type and provide IP20 protection from front.

Onload changeover S-D in SS enclosures


Onload Changeover S-Ds are available in sheet steel enclosure with adequate
space for cable terminations so that additional cable entry boxes are not
required.
Cable gland plates are also provided with the switch. Enclosure provides IP54
protection.

Changeover S-D suitable for HRC fuses


The Changeover S-Ds for open execution can be easily converted to fused
version at site by using fuse conversion kit. It provides the benefits of overload
and short circuit protection through the fastest switching device-fuse, and is
suitable for cylindrical & knife type (DIN) fuse links. Use of L&T HF & HN fuse
links reduces watt loss.

Motorised Changeover S-D


Onload changeover S-Ds are available in motorised version with control
voltage 240 V ac. The manual changeover S-Ds can also be easily converted to
motorised version at site by using electrically operated mechanism (EOM) kit
without changing panel dimension (125 A to 2000 A).

5
Product Data
Manual
¾ Changeover Product Feature 07
Technical
¾ Specifications of
Manual Changeover 11
Motorised
¾ Changeover Product Features 13
Automatic
¾ Source Transfer Solution 15
Universal
¾ Mounting for
Manual Changeover Range 16
Technical
¾ Specifications of
Motorised Kit 17
Ordering
¾ Information 19
Manual Changeover Product Feature

2 6 4
8

7
9

5
7

1. Mechanism
A single, compact and modular mechanism cassette operates
two Switch-Disconnectors and provides mechanical
interlocking between them.
The use of patented, self interlocked and dual dead center
mechanism in C-line range provides higher reliability for
changeover function.

2. Terminal shroud
These shrouds provide complete touch proof design and
prevent accidental touching of live terminals. They are click
fit type. Due to hinge type design terminal shrouds, it can
be turned by 90 degree, hence terminals can be inspected
without removing these shrouds.

3. Source separator
Source separator is used to isolate two incoming
supplies and to eliminate possibility of flash over
between two supplies due to accidental falling of
external objects.

7
Manual Changeover Product Feature

4. Inter-phase barriers
Inter-phase barriers are provided for additional safety
to eliminate possibility of inter-phase short-circuit.

5. Positive ON / OFF indication of S-Ds

N
O
The C-line Changeover S-D indicates true position of
contacts.

6. Staggered terminals
The C-line Changeover S-Ds are designed to have staggered
terminal arrangement for top and bottom S-Ds. It provides
clear access to all terminals from the front, ensuring ease of
termination.
All terminal joints can be easily inspected without the need
of removing termination of top S-D.

7. Interchangeable dual shaft position


with site convertibility
Patented dual dead center mechanism enables the user to
option between central or side shaft positions for operating
handle. This can be easily converted on site as required
(125 A to 1000 A).

8
Manual Changeover Product Feature

8. Handle
The C-line Changeover Switch has a unique flip-able operating handle for ratings 250 Amp
and above which enables user to operate the switch with two hands. The handle also offers
the following.
features:
• Provision for Padlocking in OFF position with three Padlocks of Ø5 to Ø7
• Defeat feature in both ON states and auto restoration of panel door
• IP54 with extended type operating handle

Two hand type for above One hand type handle Changeover unit pad
400 A rating upto 315 A rating lockable in OFF state by 3 pad locks

9. Auxiliary contact kit


It consists two sets of changeover contacts one for each
S-D. This kit is pre-wired with terminal blocks and can be
fitted at the site without increasing overall dimension.

10. Castell lock


Accessory to lock the Changeover Switch in OFF state
and using this can have interlocking schemes between
multiple Switches.

Sheet steel enclosure


The C-line Changeover Switches are available in sheet
steel enclosure with adequate space for cable
terminations so that additional cable entry boxes are
not required.

9
Manual Changeover Product Feature

Changeover Switch with Direct Handle


Compact direct handle 63 A and 100 A changeover switch suitable for double door DB.
It occupies only 10 Mod space (45 x 140 cut-out).

Fuse Changeover Switch


The C-line Changeover S-Ds for open execution can be easily converted to fused version at
site by using fuse conversion kit with no load line biasing. It provides the benefits of
overload and short circuit protection through the fastest switching device-fuse, and is
suitable for cylindrical & knife type (DIN) fuse links.

+ =

10
Technical Specifications of Manual Changeover

Frame 1 Frame 2

Rating (A) Unit 63 A 100 A 125 A 160 A

Reference Standards

Type designation CO1 - 63 CO1 - 100 CO2 - 125 CO2 - 160


No. of Poles 4 Pole 4 Pole 4 Pole 4 Pole
Rated operational voltage (Ue) (V) 415 415 415 415
Rated frequency (Hz) 50 / 60 50 / 60 50 / 60 50 / 60
Rated impulse withstand voltage (Uimp) (kV) 8 8 12 12
Pollution degree 3 3 3 3
0
Conventional free air thermal current, lth at 40 C (A) 63 100 125 160
0
Conventional enclosed thermal current, lthe at 40 C (A) 63 100 125 160
# #
Rated operational current, le AC-21A / AC-22A / AC-23A (A) 63 100 125 160
Rated operational power for AC-23A* (kW) 37 50 65 85
Rated breaking capacity for AC-23A (A) 504 800 1000 1280
Rated making capacity for AC-23A (A) 630 1000 1250 1600
1 sec (kA rms) 4 5 8 8
Short time withstand, lcw
0.2 sec (kA rms) 7 10 18 18
Short-circuit making capacity, lcm (kA peak) 5.9 7.7 14 14
Mechanical (O-I-O-II-O cycle) 20000 20000 16000 16000
Endurance (category A)
Electrical (O-I-O-II-O cycle) 3000 3000 2000 2000
Type and size of fuse DIN/Cylinæ 14 x 51æ 000 00
NA
Rated fused short-circuit current at 415 V, 50/60 Hz DIN/Cylinæ(kA rms) 80æ 100 100
Termination Capacity
Maximum Al. cable with lug (sq mm) 25 25 95 95
Maximum link width (mm) 16 16 30 30
Maximum link thickness (mm) 2 2.5 5 5
Termination tightening torque (N-m) 4.5 4.5 10 10
Operating torque center / side operating (N-m) 4.5 4.5 10 / 13 10 / 13
Weight (without accessories) (Kg) 2 2.5 4 4

*These values are for 4 pole squirrel cage induction motors and are provided only for guidance and may vary as per the motor manufacturer
# Rated operational current, le AC-21A / AC-22A
æ Type cylindrical fuse

11
Frame 3 Frame 4 Frame 5 Frame 6

200 A 250 A 315 A 400 A 630 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A

IS / IEC 60947-3, EN 60947-3

CO2 - 200 CO3 - 250 CO3 - 315 CO4 - 400 CO4 - 630 CO5 - 630 CO5 - 800 CO5 - 1000 CO6 - 1250 CO6 - 1600 CO6 - 2000
4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole
415 415 415 415 415 415 415 415 415 415 415
50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
12 12 12 12 12 12 12 12 12 12 12
3 3 3 3 3 3 3 3 3 3 3
200 250 315 400 630 630 800 1000 1250 1600 2000
200 250 315 400 630 630 800 1000 1250 1600 2000
200 250 315 400 630 630 800 1000 1250 1600 /1250 2000#/1250
#

100 132 160 225 315 315 400 450 710 710 710
1600 2000 2520 3200 5040 5040 6400 8000 10000 10000 10000
2000 2500 3150 4000 6300 6300 8000 10000 12500 12500 12500
10 16 18 22 26 35 50 50 50 50 50
18 28 28 35 35 70 85 85 85 85 85
17 32 36 46 55 73.5 105 105 105 105 105
16000 16000 16000 10000 10000 10000 10000 10000 10000 10000 10000
2000 2000 2000 2000 2000 2000 1000 1000 1000 1000 500
00 1 1 2 3 3
NA NA NA NA NA
100 100 100 100 100 100

150 185 240 2 x 300 2 x 300 2 x 400 2 x 400 2 x 400 2 x 12 x 63 4 x 8 x 50 3 x 10 x 100


30 40 40 50 50 60 60 60 80 80 100
6 8 8 8 2x8 2 x 10 2 x 10 2 x 10 3 x 12 3 x 12 3 x 12
20 20 20 27 27 35 35 35 55 55 55
10 / 13 20 / 25 20 / 25 28 / 32 28 / 32 30 / 40 30 / 40 30 / 40 55 55 55
4.5 6.5 7 14 14.5 20 22 22 52 57 75

12
Motorised Changeover Product Features

4 1

3
7
6

5 2

1. Site mountable
Motorised kit (EOM) can be mounted over the manual
changeover switch directly at site without any change
in the panel area.

2. Clear termination access


Motorised kit (EOM) fits well within the body of the
manual changeover switch, enabling clear access to the
terminals even after mounting the motorised kit.

3. Manual override
Manual operation of motorised changeover switch is also
feasible through the manual override feature.
As a safety feature, the control supply of motorised kit (EOM)
is automatically cut off during the insertion of handle.

13
Motorised Changeover Product Features

4. Manual and Auto mode selection


The selector switch enables/disables the control supply
to motorised changeover switch. Electrical operation is
possible only in auto mode while manual mode allows
the user to operate the motorised changeover switch
manually using the handle safely by cut-off of control
supply to motorised changeover switch.

5. Auxiliary contacts
It consists two sets of changeover contacts one for each S-D.
It is prewired and prefitted in motorised changeover switch.

6. Pad locking
Provision for padlocking in OFF position with three padlocks
of Ø5 to Ø7. Padlocking possible in both auto and manual
mode.

7. Fuse protection
Inbuilt glass fuse of 5 x 20 size protects the motorised kit
(EOM) during abnormalities. Also, spare fuse holder has
been provided for storage of fuse.

Compact design
No change in H x W x D of motorised changeover switch and manual changeover switch.

14
Automatic Source Transfer System

Illuminated Push button


assembly with Wire harness

UV/OV based AST Controller with Wire Harness


• Option of controlling Motorised Changeover
through Illuminated push button or UV/OV relay
• Sensing of three-phase voltage controls
• Protects against under voltage and over voltage
• Option of programing of minimum voltage,
maximum voltage and time delay

AuxC-1000L Controller with Wire Harness


• Option of sensing : Three-phase, two-phase or single-phase voltage controls
• Option of Measuring : Phase-phase voltage and/or phase-neutral voltage control
• Protects against under voltage, over voltage, phase loss, asymmetry, under
frequency, over frequency, with independent enable and delay Voltage thresholds
with programmable hysteresis
• RS-232 serial interface for set-up, remote control and supervision
• 6 programmable digital inputs & relay outputs (5NO + 1 C/O)

15
Universal Mounting for Manual Changeover Range

C-line manual changeover range also offers a distinctive feature to mount COSD in
different quadrants. This feature aids mounting flexibility.

Operating Quadrant chart (Seen from front of the door)


Sr. Operating Handle (OFF) Switch Shaft Door
No. Quadrant Position Orientation Position Cut-out

ON
N
O

ON
ON

ON

N
O

2
ON
ON

ON

N
O

3
ON
ON

ON

N
O

4
ON
ON

16
Technical Specifications of Motorised Kit

Frame 2

Rating (A) Unit 125 to 200


Reference Standards
Rated frequency (Hz) 50
Rated control voltage (V) 240 V ac
Control voltage range (%) 85% - 110%
Pollution degree 3
Operating temperature (°C) -5 to + 55
Ingress protection (from front) IP30
Max. current at 240 V ac (A) 2

O-I / I-O (sec) 0.5


Operating time (min)
I-II / II-I (sec) 1.4

Black out time (sec) 1.4


Control glass fuse current rating (240 V ac) (A) 1.25
Width (mm) 210

Dimensions of motorised kit Height (mm) 84

Depth (mm) 94

17
Frame 3 Frame 4 Frame 5 Frame 6
250 & 315 400 & 630 630 to 1000 1250 to 2000
IS/IEC 60947-3, IEC 60947- 3, EN60947-3

50 50 50 50

240 V ac 240 V ac 240 V ac 240 V ac

85% - 110% 85% - 110% 85% - 110% 85% - 110%

3 3 3 3

-5 to + 55 -5 to + 55 -5 to + 55 -5 to + 55

IP30 IP30 IP30 IP30

2 2 2 2

0.6 0.7 0.7 0.7

1.4 1.4 1.4 1.4

1.4 1.4 1.4 1.4

1 1.25 1.25 1.25

260 310 380 274

84 84 84 108

94 94 94 118

18
Ordering Information

Inclusive of cable gland box

Rating Manual open Manual SS Fuse Motorised Open Motorised


Frame (A) mountable kit Kit (EOM)
execution version enclosure version Execution Version
Control Voltage – – – 240 V ac 240 V ac

CO10630OOOO
63 A CO10630OSOO CX10630OOCO –
CO10630OOOD*
I –
CO11000OOOO
100 A CO11000OSOO – –
CO11000OOOD*
125 A CO21250OOOO CO21250OSOO CX21250OODO CK90161BOOO

II 160 A CO21600OOOO CO21600OSOO CX21600OODO CK90162BOOO –

200 A CO22000OOOO CO22000OSOO CX22000OODO CK90163BOOO

250 A CO32500OOOO CO32500OSOO CX32500OODO CK90164BOOO


III –
315 A CO33150OOOO CO33150OSOO CX33150OODO CK90165BOOO

400 A CO44000OOOO CO44000OSOO CX44000OODO CK90166BOOO


IV –
630 A CO46300OOOO CO46300OSOO – CK90167BOOO

630 A CO56300OOOO – CX56300OODO CK90168BOOO

V 800 A CO58000OOOO CO58000OSOO CX58000OODO CK90169BOOO –

1000 A CO51000OOOO CO51000OSOO – CK90170BOOO

1250 A CO61250OOOO – – CK90081BOOO

VI 1600 A CO61600OOOO – – CK90082BOOO –

2000 A CO62000OOOO – – CK90083BOOO

* Direct Handle Version t


Center operation Version

Auxiliary contact Operating handle Operating push UV/OV based


suitable for button assembly AST Controller AuXC 1000L
Rating (A) for manual version
Frame (2 sets of changeover with Wire harness with Wire harness controller with
Manual Motorised Wire harness
contact) version version 240 V ac 240 V ac
I 63 A, 100 A CX10002OOOO CX10001OOOO – – – –

II 125 A, 160 A, 200 A CX20002OOOO CX30001OOOO


CK90374OOOO Wire harness
III 250 A, 315 A CX30002OOOO CK90099OOOO
CK90195OOOO CK90192OOOO
IV 400 A, 630 A CX40002OOOO CX40001OOOO#
CK90378OOOO# AuXC 1000L
V 800 A, 100 0A CX50002OOOO CX50001OOOO # controller
ST80024OOOO
#
VI 1250 A, 1600 A, 2000 A CX60002OOOO CX60001OOOO# CK90645OOOO

# Flip-able Operating Handle

19
+ _ _

P N E ON-I OFF ON-II NC-II NO-II C-II C-I NO-I NC-I

Wiring Diagrams
Motorised
¾ Changeover Switch 21
Motorised
¾ Changeover Switch Control
through Supply Monitor - MG73BH 21
Process
¾ for parameter setup of
AuxC-1000L Controller 22
Motorised
¾ Changeover Switch Control
through AuXC-1000L 23
Motorised
¾ Changeover Switch Control
through AuXC-1000 23
Wiring Diagrams

Motorised Changeover Switch


Phase

Neutral
Push to Push to Push to
ON OFF ON
Source I both Source II
Source

Q1 P N E ON-I OFF ON-II NC-II NO-II C-II C-I NO-I NC-I

Auxiliary Contact
Power Supply Opening All
Source I Power

Closing 1 Closing 2
Contacts

Spare
Control
Glass
Fuse
5x20 mm

Q2
Source II Power

Motorised
changeover switch
Contacts

! Do not push source I and source II push button together

Control of Motorised Changeover Switch through


Supply Monitor - MG73BH

DG Phase

18 16 15 28 26 25 18 16 15 28 26 25
NO NC C NO NC C NO NC C NO NC C
}

SET 2 SET 1 SET 2 SET 1

Phase
MG73BH MG73BH LINE 1 {
Neutral

DG EB
Supply Supply Phase
Monitor Monitor LINE 2 {
Neutral

Dual
N L3 L2 P L1 N L3 L2 P L1 Power
Supply

K1 K2
K1 K2 K1 K2
DG Neutral
EB EB
Neutral Phase K2 K1

Output
} ON - II

} OFF

} ON - I
Earth E
Neutral N
Phase P

NC-I NO-I C-I C-II NO-II NC-II

Spare
Control
Glass
Fuse
5x20 mm
Motorised
changeover switch

21
AuxC-1000L Controller

Process for Parameters Setup


• To access parameter setup, starting with the unit in
OFF-RESET mode, press the A and D keys together
for five consecutive seconds. MENU SETUP text will
appear on the display, wait a few seconds or press
A key D to access the menu
• The display will show the code of the first parameter
P1.01, i.e. menu P1, parameter 01
B • Press keys A and B to scroll the parameters of the
same menu
C • Press keys E and F to browse the different menus
• Press keys C to switch between the code and the
value of the parameter
D
• By moving to another parameter or quitting, the
menu the setting will be stored automatically
• Press key D to quit parameters setup
• Press keys E and F simultaneously to go back to the
E F
default setting of the parameter
• If no keys are pressed for more than 2 minutes, the
unit exits setup automatically without storing the
changes

Key parameter to be set as per connection diagram


Compatible Setting
Connection Parameter Default
for C-line Description
Terminal code Setting
Motorised Changeover

Line 1 Changeover switch closed (Feedback 1).


2.1 P5.1.1 Fb.1 Fb.1 Auxiliary contact informing the Auxc1000L of
the open/closed status of line 1 changeover switch.

Line 2 Changeover switch closed (Feedback 2).


2.2 P5.2.1 Fb.2 Fb.2 Auxiliary contact informing the Auxc1000L of the
open/closed status of line 2 changeover switch.

Line 1 Changeover switch close control (Close 1).


AuXC 1000L internal contact which closes to
4.1 P6.1.1 OP.1 CL.1 command the closing of line 1 changeover switch.
It is a Pules and will be released when the operation
is completed.

Open control for both lines (Open All).


4.3 P6.2.1 CL.1 OP.A Used to set Motorised Changeover Switch to neutral
position, with both lines open.

Line 2 Changeover switch close control (Close 2).


AuXC 1000L internal contact which closes to command
5.3 P6.4.1 CL.2 CL.2 the closing of line 2 changeover switch. It is a Pules and
will be released when the operation is completed.

Note: Please refer AuXC-1000L product manual for further programing details.

22
Wiring Diagrams

Control of Motorised Changeover Switch through


AuXC-1000L
K1 K2

K2 K1

Dual
Power
LINE 1 LINE 2 Supply
L1 L2 L3 N L1 L2 L3 N
QF1
6.1 L1
6.2 L2 RS 232
6.3 L3
LINE 1 Parameter setting for the wiring diagram in picture.
6.4 N

QF2
Terminal Parameter code Setting
7.1 L1 AuXC-1000L
7.2 L2
LINE 2 4.1 P6.1.1 CL.1
7.3 L3
7.4 N 4.3 P6.2.1 OP.A
AUX
Q1 Q2 K1 K2 K2 K1 DC
Source I Source II DIGITAL INPUTS SUPPLY
5.3 P6.4.1 CL.2
Power Power _
+
Contacts Contacts
2.1 P5.1.1 Fb.1
4.1
4.2
4.3
5.1
5.2
5.3

2.1
2.2
2.3
2.4
2.5
2.6

1.1
1.2
3.1
3.2
3.3
3.4
3.5

2.2 P5.2.1 Fb.2


L1 L2 L3 N _
+
LOAD DC
Power
Source

Changeover switch
(Q1, Q2)

Contactors
Q1 P N E ON-I OFF ON-II NC-II NO-II C-II C-I NO-I NC-I

Auxiliary Contact
Source I Power

Power Supply Opening All


Mechanical
Closing 1 Closing 2 Interlocking
Contacts

Spare
Control HRC Fuse
Glass
Fuse
5x20 mm
Q2
Source II Power

Motorised
Contacts

changeover switch

Note: Please refer AuXC-1000L product manual for programing details.

Control of Motorised Changeover Switch through


AuXC-1000
K1 K2

K2 K1

Dual
Power
LINE 1 LINE 2 Supply
L1 L2 L3 N L1 L2 L3 N
QF1
8.1
Parameter setting for the wiring diagram in picture.
8.2 RS 232
LINE 1
8.3 Terminal Parameter code Setting
8.4
1.1 P6.01 CL.1
QF2
9.1 AuXC-1000
9.2
LINE 2
1.3 P6.02 OP.A
9.3
9.4 2.1 P6.03 CL.2
Q1 Q2
Source I
K2 K2 K1 K1 DC 4.1 P5.01 Fb.1
Source II DIGITAL INPUTS Supply
Power Power 7.1 + _ _
Contacts Contacts 7.2 4.2 P5.02 Fb.2
1.1
1.2
1.3
2.1
2.2
2.3

3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

5.1
5.2
5.3

L1 L2 L3 N
LOAD

Changeover switch
(Q1, Q2)

Contactors

Q1 P N E ON-I OFF ON-II NC-II NO-II C-II C-I NO-I NC-I Mechanical
Auxiliary Contact Interlocking
Source I Power

Power Supply Opening All


Closing 1 Closing 2
Contacts

HRC Fuse
Spare
Control
Glass
Fuse
5x20 mm
Q2
Source II Power

Motorised
Contacts

changeover switch

Note: Please refer AuXC-1000 product manual for programing details.

23
Characteristic Curves
HRC Fuse-link
¾ Details 25
Time-Current
¾ Characteristics of Type
HF Fuse-links 26
Cut-off
¾ Current Characteristics of Type
HF Fuse-links 26
Time-Current
¾ Characteristics of Type
HN Fuse-links 27
Cut-off
¾ Current Characteristics of Type
HN Fuse-links 27
HRC Fuse-link Details

Features
• Conform to IEC 60269-2, IS 13703 part 2
• Range: 2 A to 800 A, 415 V, AC 50 Hz
• Type: HF Cylindrical (2 A to 63 A) & HN DIN (63 A to 800 A)
• High breaking capacity: 80 kA for type HF and 100 kA for type HN

Fuse Suitable
Rating Fuse-link
Frame mountable fuse-link
(A) Size
kit type
I 63 CO Frame 1 63 A HF 14 x 51 Cylindrical

125 CO Frame 2 125 A Size 000

II 160 CO Frame 2 160 A Size 00

200 CO Frame 2 200 A Size 0

250 CO Frame 3 250 A Size 1


III HN
315 CO Frame 3 315 A Size 1

IV 400 CO Frame 4 400 A Size 2

630 CO Frame 5 630 A Size 3


V
800 CO Frame 5 800 A Size 3

25
Characteristic Curves

HRC Fuse-link Type HF


Time-Current Characteristics

63 A
10 A

16 A
20 A
25 A
32 A
40 A
50 A
8B
2A

4A

6A
4

2
1000

4
2
100
Pre-arcing Time (seconds)

4
2
10

4
2
1

4
2
0.1

4
2
0.01

4
2 3 4 5 10 2 3 4 5 100 2 3 4 5 1000 2 3 4 5
Symmetrical Current (A)

Cut-off Current Characteristics


10
63 A
50 A
40 A
25 A 32 A
20 A
16 A
10 A
8A

6A
4A
(asymmetrical Fault Conditions)

1.0 2A
Cut-off Current-ka (peak)

0.1

2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8
0.01 0.1 1.0 10

Prospective Current - kA (RMS) Symmetrical

26
Characteristic Curves

HRC Fuse-link Type HN


Time-Current Characteristics

100 A
125 A
160 A
200 A
250 A
315 A
400 A
400 A
630 A
800 A
63 A
80 A
10000

4
2
1000

2
100

4
Pre-arcing Time (seconds)

2
10

4
2

2
0.1

2
0.01

4
2 3 4 5 10 2 3 4 5 100 1 2 3 4 5 1000 2 3 4 5 10000 3 4 5

Symmetrical Current (A)

Cut-off Current Characteristics


100

800 A
630 A
5
500 A
600 A
315 A
250 A
200 A
2 160 A
125 A
100 A
80 A
10 63 A
(Asymmetrical Fault Conditions)
Cut-off Current-ka (peak)

0.1
2 5 2 5 2 5 8
0.1 1 10 100

Prospective Current - kA (RMS) Symmetrical

27
Dimensions
Dimensions
¾ of Open Execution Manual
Changeover Switch 29
Dimensions
¾ of Manual Changeover
Switch in Sheet Steel Enclosure 35
Dimensions
¾ of Manual Fuse
Changeover Switch 38
Dimensions
¾ of Motorised
Changeover Switch 41
Dimensions
¾ of Auto Source Transfer Switch
Controller : AuXC-1000 & AuXC-1000L 43
Dimensions

CO1-63/100
Open Execution with Direct Handle Manual Changeover Switch
44 x 140
Cutout Suitable for Mounting In
Distribution Board (Slot for Termination)
4 Nos. Mounting Holes 50.5 74 (Mounting)
44 Suitable for M4 Screws 32 16.5

132.5 (with Shorting Link)


68
59
118 (Mounting)
94.4

64.5
Provision of Mounting on
TH35 - 7.5 Rail As Per IS 11039

37 37 37
140
175
A
81.1
68.1
59.1

Rating Termination Rating A


Bolt
CO1-63 A 2
CO1-63/100 A M6
16 (Terminal with)
34.9
17.3

CO1-100 A 2.5

CO1-63/100
Open Execution with Extended Handle Manual Changeover Switch

(Slot for Termination)


50.5 74 (Mounting)
32 16.5
4 Nos. Mounting Holes
Suitable for M4 Screws
132.5 (with Shorting Link)
68
118 (Mounting)
59

94.4

64.5

* Bushes

37 37 37
140
Panel Door
175
163.6

140.6

Rating Termination
Bolt
A
75.1

CO1-63/100 A M6
68.1
59.1
34.9

5.7

Rating A
17.3

16 (Terminal with) CO1-63 A 2


CO1-100 A 2.5

All dimensions are in mm * Assemble bushes for higher ground clearance.

29
Dimensions

CO2-125/160/200
Open Execution with Extended Handle Manual Changeover Switch

7
Panel Door

88

Maintain Distance Inside of


Phase Barrier

Cubicle to be 241 ± 1
9

190 Mounting
4 Nos. Mounting

Contact Block
267
Holes Suitable

Auxiliary
for M6 Screws
154

211 with Accessories


112
B

120 (Mounting)

L&T
30

A
42

C
L&T
Rating A B C D
CO2-125 22 3 138 121
CO2-160 22 3 138 121 44 44 44 M4 Screws
CO2-200 26 5 150 121 210 for Earthing
(2 Nos.)

CO3-250/315
Open Execution with Extended Handle Manual Changeover Switch
7

Panel Door

113
Maintain Distance Inside of

Phase Barrier 235.4 (Mounting)


11

Cubicle to be 276 ± 1

4 Nos. Mounting
Contact Block

Holes Suitable
Auxiliary
301

for M8 Screws
239 with Accessories
193

159 (Mounting)
138

L&T
B

39

A
54

L&T

Rating A B C D M10 Bolt 56 56 56


CO3-250 29 4.5 182 156 M4 Screws
260 for Earthing
CO3-315 35 5 198 164
(2 Nos.)

All dimensions are in mm

30
Dimensions

CO4-400/630
Open Execution with Extended Handle Manual Changeover Switch

7
Panel Door

130

Maintain Distance Inside of


Phase Barrier
12

Cubicle to be 290 ± 1
286 (Mounting)

316
4 Nos. Mounting

Contact Block
Holes Suitable

Auxiliary
210

for M8 Screws
151
A

329 with Accessories


200 (Mounting)
42

40
58

L&T
202

228
L&T
Rating A
CO4-400 5
CO4-630 6
M12 Bolt 70 70 70
M4 Screws
310 for Earthing
(2 Nos.)

CO5-630/800/1000
Open Execution with Extended Handle Manual Changeover Switch
8

164
Maintain Distance Inside of
12.6

Phase Barrier
Cubicle to be 330 ± 1

380
Terminal
359.8

17.5 345 (Mounting) Shroud


4 Nos. Mounting
247.7

Holes Suitable
for M8 Screws
182
A

351.6 with Accessories

Auxiliary
45
66.7

Contact
220 Mounting

L&T

Block
50
228
264
L&T

Rating A M5 Screws
15

CO5-630 6 for Earthing


(2 Nos.)
CO5-800 8
80 80 80
CO5-1000 8 M16 Bolt

All dimensions are in mm

31
Dimensions

CO6-1250/1600
Open Execution with Extended Handle Manual Changeover Switch
with center operation
4 Nos. Mounting Holes
Suitable for M10 Screws 1250A Terminal Arrangement
317.5 (mounting)
Suitable for M10 Hardware
212.5

19
Housing

55
22
Wall

19
D (with Accessories)

22
265 (mounting)

60
NO NC COM

200

10
A
COM NC NO

Type Terminal Tightening


Designation Screws Torque Panel Door
CO6-1250 M10 Hexagonal 20 N-m
Head Bolt
CO6-1600 M12 Hexagonal 27 N-m
Head Bolt

1600A Terminal Arrangement


105

Maximum:500
105

Minimum:400
Maximum:480
Minimum:380
Suitable for M12 Hardware
108.3
540
22

B
Housing
65
26

Wall

325
E

271
26
22
70

C
F
Cat. No. Rating A B C D E F
CO61250OOOO CO6-1250 310 8 56 339 112 87 Tapped Hole Suitable for M5
Screw for Earthing
CO61600OOOO CO6-1600 330 12 54 347 108 85 (25 Sq. mm Cable Lug)

CO6-1250/1600
Open Execution with Extended Handle Manual Changeover Switch
with side operation
540

105 105 105


D (with Accessories)
265 (mounting)
NO NC COM

200

A
COM NC NO

10

Panel
Door

315 (mounting) 104.3


4 Nos.
Maximum:500

Mounting Holes
Minimum:400

372.9
Maximum:482
Minimum:382

Suitable for
M10 Hardware
325
E

271

Cat. No. Rating A B C D E F


B

CO61250OOSO CO6-1250 310 8 56 339 112 87


C
F

CO61600OOSO CO6-1600 330 12 54 347 108 85


540

Tapped Hole Suitable for M5 Screw


for Earthing (25 Sq. mm Cable Lug) All dimensions are in mm

32
Dimensions

CO6-2000
Open Execution with Extended Handle Manual Changeover Switch
with center operation
317.5 (mounting) 107
Terminal Arrangement
192.1
Suitable for M12 Hardware

Housing

50
Wall

110
456 (with Accessories)

40

26.5
8.5
265 (mounting)
200

25
420.2

40
85

Type Terminal Tightening Panel Door


325

Designation Screws Torque


M12 Hexagonal
CO6-2000 27 N-m
Head Bolt
125.1
4 Nos. Mounting Holes

Maximum:480
540 Suitable for M10 Screws

Minimum:380
15

325
105

271
52.5
83.5
M5 Hardware for Earthing
Lug (25 Sq. mm)

CO6-2000A
Termination of 100 mm Bus Bar

50604
101 Max. Space for
Busbar : 26 mm
Max. Space For Max. Busbar
Busbar : 26mm Thickness: 8 x 2 Nos.
Max. Busbar
Max. Space For
Thickness: 8 X 2 Nos.
Busbar : 38 mm
Max. Busbar
Thickness:12 x 2 Nos.

CK50604
101
>PP-EPDM-FR<

Source 1

(shorting Link Side) CK50604


101
>PP-EPDM-FR<

Source 2

101
>PP-EPDM-FR<

Minimum ground clearance of


Terminal
19 mm is recommended
Max. Space for
Busbar : 38 mm Recommended spacer thickness
Max. Busbar Spacer is the busbar thickness used
Thickness: 12 x 2 Nos.
Minimum inter phase clearance of
Busbar 25 mm is recommended for busbars

*for Recommended Termination Practices, Refer Page number 34


All dimensions are in mm

33
Dimensions

Recommended termination practices for busbar width 60-80 mm


with diagonal hole configuration

Terminal
Spacer
Busbar

Busbar sizes as per standard


Busbar 1250 A 1600 A 2000 A
Cu 80 x 5 x 2nos 100 x 5 x 2nos 100 x 5 x 3nos
Busbar Busbar Busbar Busbar
Configuration 1 Configuartion 2 Configuration 3 Configuartion 4 *Al 63 x 12 x 2nos 50 x 8 x 4nos 100 x 10 x 3nos
(1+1) (1+2) (2+2) (2+3)
*For Aluminium termination as per standard:
1250A: Factory fitted hardware to be used,
1600/2000A: Bolt length of 85 mm to be used.

Note: 1. Different configurations of busbars can be used maintaining minimum cross section areas as specified in the table
2. Factory supplied bolt length caters to the copper bus bar termination as per standard. in case of different configurations & cross section areas,
bolt of higher length may be required.

Termination of 100 mm Bus Bar 1600 A

Busbar cut-out dimensions

27 20 27 20
09

09

25 92.5 25

CO6-2000 A Termination of 100 mm Bus Bar


COM NO NC

25 92.5 25

Direct termination of 100 mm bus bar possible in case of 2000 A.


All dimensions are in mm

34
Dimensions

CO1-63/100
Manual Changeover Switch In Sheet Steel Enclosure
72.4
224.4

152

155
240 (Mounting)
262

310
Ø5.7

75.5 186.5
Termination (Minimum
Rating Hinge Distance)
Bolt
CO1-63/100 A M6
35

31 200 (Mounting)

CO2-125/160/200
Manual Changeover Switch In Sheet Steel Enclosure
97
340

243

215.5
350 (Mounting)

315
431

Ø5.7

157.5 Minimum Hinge


Distance 157.5 mm
4 Nos. Mounting
Holes Suitable
for M8 Screws
40.5

51 213 (Mounting)

All dimensions are in mm

35
Dimensions

CO3-250/315
Manual Changeover Switch In Sheet Steel Enclosure
97.4
378.4

281

285
350 (Mounting)
390

570
Ø5.7

195 Minimum Hinge


Distance 195 mm

4 Nos. Mounting
Holes Suitable
for M8 Screws
110

88.5 213 (Mounting)

CO4-400/630
Manual Changeover Switch In Sheet Steel Enclosure
107.4

4 Nos. Mounting
Holes Suitable
for M8 Screws
399.4

292

366
600 (Mounting)

465
732

Ø5.7

Minimum Hinge 232.5


Distance 232.5 mm
66

59.5 346 (Mounting)

All dimensions are in mm

36
Dimensions

CO5-800/1000
Manual Changeover Switch In Sheet Steel Enclosure
107.6
445

337.1
348.1

4 Nos. Mounting
Holes Suitable
for M10 Screws

102
510

Suitable For Lifting


and Mounting with
M10 Screws 596
600 (Mounting)

804
460

Ø5.7

255
Minimum Hinge
Distance 255 mm

402
560

82 346 (Mounting)

All dimensions are in mm

37
Dimensions

CO1-63
Fuse Changeover Switch (Suitable for Cylindrical Type Fuse Link)

(Slot for Termination)


4 Nos. Mounting Holes 50.5 74 (Mounting)
Suitable for M4 Screws 16.5
32

132.5 (with Shorting Link)


64.5
118 (Mounting)
59

94.4

68
Bushes

Panel Door 37 37 37
175

Note: Assemble bushes for higher ground clearance


163.6
140.6

123.8
115.6

Rating Termination
Bolt
2
75.1
59.1

CO1-63 A M6
34.9
17.3

5.7

16 (Terminal with)

CO2-125/160/200
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
7

Fuse Phase Barrier Panel Door


* Fuse Link
Cubicle to be 276 ± 1 mm.

Neutral
Maintain Distance Inside of

Phase
Barrier Pole
4 Nos. Mounting
Holes Suitable 190 (Mounting)
Contact Block
302

for M6 Screws
255
245

Auxiliary
208 with Accessories
170

120 (Mounting)
112

L&T
30

A
42

C
D

L&T

Rating A B C D
CO2-125 22 3 138 121
CO2-160 22 3 138 121 44 44 44 M4 Screws
CO2-200 26 5 150 121 210 for Earthing
(2 Nos.)

All dimensions are in mm

38
Dimensions

CO3-250/315
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)

7
Fuse Phase Barrier Panel Door
* Fuse Link

Maintain Distance Inside of


Phase Neutral

Cubicle to be 324 ± 1mm


Barrier Pole

351
293
292

4 Nos. Mounting 235.4 (Mounting)


277

Contact Block
Holes Suitable

Auxiliary
for M6 Screws
207
138

239 with Accessories


39

159 (Mounting)
A
54

L&T
D

C
L&T
Rating A B C D
CO3-250 29 4.5 182 156
CO3-315 35 5 198 164

M10 Bolt
56 56 56 M4 Screws
260 for Earthing
(2 Nos.)

CO4-400
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
7

Fuse Phase Barrier Panel Door

* Fuse Link

Neutral
Maintain Distance Inside of

Phase
Cubicle to be 360 ± 1mm.

Pole
Barrier
386
332
320
298
227

286 (Mounting)
4 Nos. Mounting
Contact Block
151

Holes Suitable
5

Auxiliary

for M8 Screws
42

40
58

329 with Accessories


200 (Mounting)

L&T
202

228
L&T

M12 Bolt
70 70 70 M4 Screws
310 for Earthing
(2 Nos.)

All dimensions are in mm

39
Dimensions

CO5-630/800
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)

Fuse
Phase Barrier

8
* Fuse Link

Maintain Distance Inside of


Phase

Cubicle to be 431 ± 1
Barrier
6

459.5
403.6
377
353
263.6

182
A

45
66.7

50

345 (Mounting)
80 80 80
17.5
4 Nos. Mounting
Holes Suitable
for M8 Screws

351.6 with Accessories


Auxiliary
Contact Block
220 (Mounting)

L&T
* Suitable for

228
264
L&T Make
Rating A Fuse Links
CO5-630 6 L&T

CO5-800 8

M5 Screws
15

for Earthing
Suitable (2 Nos.)
for 92 92
M16 Bolt 380

All dimensions are in mm

40
Dimensions

CO2 to CO5 (125-1000A)


Motorised Changeover Switch
G
K (Mounting)
= =
=

NOII OFF
J (Mounting)

L
C
D

M
I NO
MANUAL

AUTO
=

R
N A
P

Mounting Earthing
holes E F F F 10.1
Screws
(4 Nos.) (2 Nos.)

Rating Frame Frame Mounting Earthing


(A) A B C D E F G H J K L M N P R
CO EOM CO EOM Hole Size Screw Size

125 22 3 138 121 28 44 210 211 120 190 CO2 CX2 240.3 234.3 30 42 112 M6 M4
160 CO2 CX2 22 3 138 121 28 44 210 211 120 190 CO3 CX3 277.2 271.2 39 54 138 M8 M4
200 26 5 150 121 28 44 210 211 120 190 CO4 CX4 293.7 287.7 42 58 151 M8 M4
250 29 4.5 182 156 32 56 260 239 159 235.4 CO5 CX5 330.9 324.9 45 66.7 182 M8 M5
CO3 CX3
315 35 5 198 164 32 56 260 239 159 235.4
400 40 5 228 202 32.3 70 310 329 200 286
CO4 CX4
630 40 6 228 202 32.3 70 310 329 200 286
630 50 6 264 228 - 80 380 351.6 220 345
800 CO5 CX5 50 8 264 228 - 80 380 351.6 220 345
1000 50 8 264 228 - 80 380 351.6 220 345

CO6-1250/1600/2000
Motorised Changeover Switch
540
389
108
271 118
>PP-EPDM-FR<

>PP-EPDM-FR<
Ck50604

Ck50604
101

101
=

347

MANUAL AUTO
250.4

ON
274

OFF II
ON
=

= =
70
All dimensions are in mm

41
Dimensions

Panel Cutout
Motorised Changeover Switch

Panel Cutout
B

=
AUTO

MANUAL

88
ON I

OFF NO II
=

Type A B
CO2 with CX2 95 60
52.5 CO3 with CX3 117.7 79.5
88 CO4 with CX4 143 100
CO5 with CX5 172.5 110

Mounting Holes of Respective Changeover Switch

Drilling Plan for Mounting Bezel*


Motorised Changeover Switch

Bezel Assembly

Ø3 x 4
100
Insert this part
into the Bezel
Place Gasket on Bezel
6

Door
100

Self tapping screws


6

6 6

Panel Cutout
*Available with standard product.

All dimensions are in mm

42
Dimensions

AuXC-1000L AuXC-1000L
Rear Terminal Connections Panel cut-out
94,00
82,00

LINE 1 LINE 2
6.1 6.2 6.3 6.4 7.1 7.2 7.3 7.4

96,00
L1 L2 L3 1 NI L2 L3 N

AUX LINE1 LINE 2


RELAY RELAY RELAY
4.1

4.2

4.3

5.1

5.2

5.3

3.1 3.2 3.3 3.4 3.5

92,00 96,00

!
BATTERY
12...48 V= RS 232
+ -- DIGITAL INPUTS

96,00
92,00
1.1

1.2

2.1

2.2

2.3

2.4

2.5

2.6

AuXC-1000 AuXC-1000
Rear Terminal Connections Panel cut-out
94 31

AC SUPPLY
B300
250V 12A 0V ~ 7.1
1.1
AC1
B300 1.2
! 220-240 ~ 7.2
100-690VAC
250V 8A 50/60 Hz
AC1 1.3
7.3
B300
250V 12A 2.1
LINE 1 8.1
AC1 VOLTAGE INPUTS L1
2.2
DC SUPPLY 79
B300 8.2
12...48VDC=
250V 8A 2.3 L2
AC1 + 5.1
8.3
138.5
- 5.2
B300 3.1 L3 144
250V 8A DIGITAL - 5.3
AC1 INPUTS 8.4
3.2
N
4.1
3.3 9.1
B300 4.2 RS 232
250V 8A L1
3.4 4.3
AC1 9.2
3.5 4.4 RS 485 L2
138.5

144

4.5 SG 6.1
3.6 4.6 9.3
B 6.2 L3
B300
250V 8A 4.7 A 6.3
3.7 9.4
AC1 4.8 TR 6.4 N
3.8
LINE 2
VOLTAGE INPUTS

All dimensions are in mm

43
Dimensions

AST Controller
Panel Cutout & Drill Plan for Flush Mounting

198.6±0.5

186±0.5 A1
Hole
Ø5.5 x 4Nos. AST Controller
65±0.5

230±0.5
100±0.5

A2

Mounting Nut / Washers


Provided
Panel Cutout
Panel Door
(Rear side)

44
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND Khairasol, Degaul Avenue L&T Business Park,


HEAD OFFICE Durgapur 713 212 Tower 'B' / 5th Floor
L&T House, Ballard Estate Tel: 2559848, 2559849, 2559844 Saki Vihar Road, Powai
P. O. Box 278 Fax: 0343-2553614 Mumbai 400 072
Mumbai 400 001 e-mail: [email protected] Tel: 022-67052874 / 2737 / 1156
Tel: 022-67525656 Fax: 022-67051112
Fax: 022-67525858 5, Milanpur Road, Bamuni Maidan e-mail: [email protected]
Website: www.Larsentoubro.com Guwahati 781 021
Tel: +91 8876554410 / 8876554417 12, Shivaji Nagar
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 361-2551308 North Ambajhari Road
501, Sakar Complex I e-mail: [email protected] Nagpur 440 010
Opp. Gandhigram Rly. Station Tel: 0712-2260012 / 6606421
Ashram Road II Floor, Vasantha Chambers Fax: 2260030 / 6606434
Ahmedabad 380 009
5-10-173, Fateh Maidan Road e-mail: [email protected]
Tel: 079-66304006-11
Hyderabad 500 004
Fax: 079-66304025
e-mail: [email protected] Tel: 040-67015052 32, Shivaji Marg
Fax: 040-23296468 P. O. Box 6223
38, Cubbon Road, P. O. Box 5098 e-mail: [email protected] New Delhi 110 015
Bangalore 560 001 Tel: 011-41419514 / 5 / 6
Tel: 080-25020100 / 25020324 Monarch Building, 1st Floor Fax: 011-41419600
Fax: 080-25580525 D-236 & 237, Amrapali Marg e-mail: [email protected]
e-mail: [email protected] Vaishali Nagar
Jaipur 302 021 L&T House
131/1, Zone II Tel: 0141-4385914 to 18 P. O. Box 119
Maharana Pratap Nagar Fax: 0141-4385925 191/1, Dhole Patil Road
Bhopal 462 011 e-mail: [email protected] Pune 411 001
Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Tel: 020-66033395 / 66033279
Fax: 0755-3080502 Akashdeep Plaza, 2nd Floor Fax: 020-26164048 / 26164910
e-mail: [email protected] P. O. Golmuri e-mail: [email protected]
Jamshedpur 831 003
Plot No. 559, Annapurna Complex Jharkhand Crystal Tower,
Lewis Road Tel: 0657-2312205 / 38 4th Floor, G. E. Road
Bhubaneswar 751 014 Fax: 0657-2341250 Telibandha
Tel: 0674-6451342, 2436690, 2436696 e-mail: [email protected] Raipur - 492 006
Fax: 0674-2537309 Tel: 0771-4283214
e-mail: [email protected] Skybright Bldg; M. G. Road e-mail: [email protected]
Ravipuram Junction, Ernakulam
Aspire Towers, 4th Floor Kochi 682 016 3rd Floor
Plot No. 55, Phase-I Tel: 0484-4409420 / 4 / 5 / 7 Vishwakarma Chambers
Industrial & Business Park Fax: 0484-4409426 Majura Gate, Ring Road
Chandigarh-160 002
e-mail: [email protected] Surat 395 002
Tel: 0172-4646840 / 41 / 42 / 46 / 53
Fax: 0172-4646802 Tel: 0261-2473726
Email: [email protected] 3-B, Shakespeare Sarani Fax: 0261-2477078
Kolkata 700 071 e-mail: [email protected]
L&T Construction Campus Tel: 033-44002572 / 3 / 4
TC-1 Building, II Floor Fax: 033-22821025 / 7587 Radhadaya Complex
Mount-Poonamallee Road e-mail: [email protected] Old Padra Road
Manapakkam Near Charotar Society
Chennai 600 089 A28, Indira Nagar, Faizabad Road Vadodara 390 007
Tel: 044-2270 6800 Lucknow 226 016 Tel: 0265-6613610 / 1 / 2
Fax: 044-22706940 Tel: 0522-4929905 / 04 Fax: 0265-2336184
e-mail: [email protected] Fax: 0522-2311671 e-mail: [email protected]
e-mail: [email protected]
67, Appuswamy Road Door No. 49-38-14/3/2, 1st floor,
Post Bag 7156 No: 73, Karpaga Nagar, 8th Street NGGO's Colony, Akkayyapalem,
Opp. Nirmala College K. Pudur Visakhapatnam - 530 016
Coimbatore 641 045 Madurai 625 007 Phone : 0891 2791126, 2711125
Tel: 0422-2588120 / 1 / 5 Tel: 0452-2537404, 2521068 Fax.: 0891 2791100
Fax: 0422-2588148 Fax: 0452-2537552 Email: [email protected]
e-mail: [email protected] e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited Electrical Standard Products


Powai Campus, Mumbai 400 072
Customer Interaction Center (CIC)
BSNL / MTNL (toll free) : 1800 233 5858
Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858, Fax : 022 6774 5859
E-mail : [email protected] Website : www.LNTEBG.com

Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA SP 50487 R6