SCM-SCC Operations Manual
SCM-SCC Operations Manual
SCM2500
SCC3500
When using this instrument, basic safety precautions shall always be followed to
reduce the risk of fire, electrical shocks and injury to persons, including the
following:
SAFETY PRECAUTIONS
In order to provide maximum user safety this instrument was designed with all electrical
circuitry enclosed within a protective non-conductive housing. The label below will be
visible at any location where high voltage is present.
Chemtrac, Inc
6991 Peachtree Industrial Blvd., Building 600
Norcross, GA 30092
The treated water sample flows into the sample cell where it is drawn into the bore
during the upstroke of the piston cycle and is expelled from the bore on the piston down
stroke. Particles contained in the water are temporarily immobilized on the piston and
cylinder surfaces. As the water is moved back and forth by the piston, charges
surrounding these particles (+ and -) are moved downstream to the electrodes. This
movement of like charges causes an alternating current to be generated, defined as
"streaming current." A signal gain selector, accessed through the menu screen, is used
to select the best signal amplification. The signal amplification should be set where a
normal change in dosage results in a desired deviation in streaming current (normally 30
units). The displayed streaming current value (SCV) should be considered as a relative
reading due to amplification of the primary signal.
The streaming current amplitude and polarity is a function of sampling location in the
treatment process. It is important to understand why the streaming current varies at
different points in the system to properly interpret the readings, therefore, Section 2.2
should be read very carefully.
The sample must be taken at a point where uniform distribution and mixing of coagulant
is obtained for all flow rate conditions, and at a point that allows for a quick response to
chemical feed changes as measured by the monitor (i.e. after the rapid mixer or static
mixer, and before the slow mixer or flocculation basin). The lag time, or the amount of
time it takes the water to travel from the point of chemical addition to the sensor, should
be no greater than 3 minutes (30 seconds to 1.5 minutes are typical lag times). If
uniform distribution and mixing is not being obtained at a selected sample point, the
streaming current reading will oscillate. If the chemical is not being properly mixed
(indicated by an oscillating monitor reading), the sample point needs to be moved
further downstream away from the mixing device to allow the chemical more time to mix
in with the water. Under rare circumstances, moving the sample point further
downstream in order to obtain a more stable reading may result in a lag time longer than
3 minutes. Steps should be taken to improve chemical mixing under these conditions.
When possible, avoid sampling from places where sludge, grit, etc., will be drawn into
the sensor sample cell. Sample lines must be sized to provide velocities that will
prevent floc/sludge accumulation. Keep sample lines as short as possible to minimize
delay in response time.
Figure 1, Streaming Current Profile, normally observed in a typical water plant. When
coagulant is added to raw water, the charge neutralization process begins immediately.
The time required for this neutralization process to go to completion is primarily a
function of mixing, time, raw water characteristics, type of coagulant, and to a lesser
degree, temperature. Untreated raw water has a net negative charge. Cationic
Based upon the above discussion, the proper sample point for a specific plant depends
upon the following conditions:
1. Point or points of coagulant feed.
2. Mixing efficiency of raw water and coagulant.
3. Magnitude of raw water flow swings.
4. Type and quantity of coagulants used.
In order for the monitor to be used for automatically controlling the coagulant feed
(alum, polymer, ferric chloride), the following guidelines must be followed:
1. The coagulant must be thoroughly mixed with the raw water by the time the
sample is taken.
2. “Lag time” (i.e., the time it takes for the monitor to see a change in coagulant
feed) should be no greater than 5 minutes.
3. Variability in sample flow rates should be no greater than +/- 10 % of the initial
rate.
4. Coagulant pumps must be kept in good mechanical condition to respond quickly
and accurately to process changes.
5. Raw water quality should be in a stable condition (turbidity, pH, color, etc. should
not change rapidly or widely) when setting up the system.
The monitor should be operated a few days in manual control to observe how it
responds to normal process operation. Recording streaming current changes on a strip
chart recorder is very helpful in anticipating factors that may have to be dealt with when
automatic control is started. This period, if using the monitor with a recorder for
monitoring, is also a good time to determine the optimum coagulant dosage and
establish the operating “setpoint”. This enables the system to be put on automatic
control very simply.
D URA-TRAC TM
DU RA -TRAC TM
DURA-TRAC TM
II
PAT ENTED MA DE IN U .S.A.
OPERATOR
MANUAL
DU RA -TRA C TM
II
PAT ENTE D MADE IN U.S.A .
MONITOR/CONTROLLER
Power ...................................... 85-264 VAC, 47–63 Hz
Current Load ........................... 110 VAC @ 0.5A Max
220 VAC @ 0.25A Max
User Interface.......................... Backlit Liquid Crystal Display, Menu Driven Functions,
Keypad Interface
SCV Readout .......................... -1000 to +1000
Resolution ............................... Streaming Current Units
Signal Gain .............................. User Adjustable 1X to 20X
Zero Offset .............................. Automatic, Full Scale All Ranges
Accuracy ................................. 0.5% of Full Scale
Response Time ....................... 1 Second
SCV Output Signal .................. Standard 4-20 mA (300 ohm Load)
Optional 0-10 VDC
Alarm Output ........................... 24 VDC (Solid State Relay Optional) and Auditable
Alarm for Sensor Status, High/Low Streaming Current
Value and High/Low Pump Output - SC3500XRD Only
Digital Input ............................ Dry Contacts
Enclosure Type ....................... NEMA 250 Type 4X, Reinforced Fiberglass
Enclosure Size ........................ 9.2”W, 11.2”H, 6.3”D (234mm W, 285mm H, 161mm D)
Mounting Holes ....................... 11.25”W, 7.4”H (286mm W, 188mm H)
Weight ..................................... 6 Pounds (2.72 kg)
Control Output Alarms ............. Adjustable High/Low Alarms
Operating Temperature ........... 32° F to 120° F (0° C to 49° C)
The sensor can be located several hundred feet from the monitor. The sensor must be
mounted in a vertical position with the sample flowing into the inlet (3/4” barb fitting) and
exiting from the outlet (PVC elbow). Typically, the sensor is mounted as closely as
possible to the sampling point. Minimizing sample line lengths provides quicker
response to process changes. Sample may be obtained by using a sample pump,
tapping off a pressurized line, or using gravity feed system to get sample to the sensor.
The sample flow rate should not exceed 5.0 GPM for Dura-Trac sensor and 10.0 GPM
for Dura-Trac II sensor. Draining to atmosphere (unobstructed) is required; a
closed pipe (pressurized) drain is not recommended.
The Monitor/Controller module should be installed in a location, which will allow regular
viewing of the display as well as easy access to the front panel menu keys. See
Mounting Dimension Diagrams at end of Manual.
FUSE
FUSE: AGC-1.5A
WARNING TURN POWER OFF BEFORE MAKING ANY WIRE CONNECTIONS 17 18 19 20
OFF TO AVOID DAMAGING THE ELECTRONIC CIRCUIT.
SMM | Sensor
*
*
ON *
* *
L G N
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
GND
N
L
POWER CORD
High
Cond.
Opto (W)
N
Opto (B)
Opto (O)
8
L1
- Probe
7
+ Probe
6
Shield
5
Opto
4
Signal
3
Vdc Gnd
2
+24 Vdc
1
9 10 11 12
High
Cond.
Opto (W)
Opto (B)
Opto (O)
8
- Probe
7
+ Probe
6
Shield
5
Opto
4
Signal
3
Vdc Gnd
2
+24 Vdc
Chemtrac, Inc.
L1
N
9 10 11 12
High
Cond.
Opto (W)
Opto (B)
Opto (O)
8
- Probe
7
+ Probe
6
Shield
5
Opto
4
Signal
3
Vdc Gnd
2
+24 Vdc
1
CAUTIONS
Make sure the monitor’s power switch is turn to off position before making any
signal wiring connections.
FUSE
FUSE: AGC-1.5A
WARNING TURN POWER OFF BEFORE MAKING ANY WIRE CONNECTIONS 17 18 19 20
OFF TO AVOID DAMAGING THE ELECTRONIC CIRCUIT.
1 9 17
SMM | Sensor
2 10 18
3 11 19
4 12 20
5 13
6 14
7 15
ON 8 16
L G N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
GND
N
L
(WHITE)
(BLACK)
(BLUE)
(RED)
1 2 3 4 5 6 7 8 9 10
Opto (W)
Opto (O)
Opto (B)
+24 Vdc
Vdc Gnd
Signal +
+ Probe
Signal -
- Probe
Shield
Sample shall be connected to the sample cell inlet side. A 3/4" barbed fitting connection
is provided for hose connection. The PVC elbow opposite the inlet is the outlet. The
outlet sample must flow to an open drain (sample receiver). The cell cannot operate
properly if pressurized. Do not replace either fitting with any other type of fitting.
Start treated water sample through the cell at a rate of between 1 to 5 GPM. Make sure
the outlet is free of obstructions. Continuous reliability of the sample flow is essential.
Interruption of the sample flow will result in erroneous readings on the
Monitor/Controller. For Controller model SCC3500XRD operating in AUTO mode, loss
of flow to the Dura-Trac sensor will result in improper coagulant dosing. A suitable flow
alarm is recommended for maximum reliability.
IMPORTANT
On the SCC3500XRD, the pump control output of the controller must be set in the
MANUAL mode if the sensor is flushed or cleaned or if power to the sensor is
interrupted for any reason. The controller can be placed back in AUTO once power
and sample flow is restored. For system with Dura-Trac with flush with Sensor
Maintenance Module (SMM), during Automatic Flushing cycles, the pump control
output signal is maintained at a constant value (see Flush Menu).
DURA-TRAC TM
SAMPLE OUTLET
SAMPLE INLET
3/4" BARB FITTING
2" Line
DURA-TRAC TM
II
PATENTED MADE IN U.S.A.
SAMPLE OUTLET
45 DEGREE ELBOW
SAMPLE INLET
3/4" BARB FITTING
2" Line
The SCM2500XRD and SCC3500XRD are available with one of two options for
automatic sensor flushing/cleaning. The first option is the Dura-Trac with flush and is
composed of a valve mounted onto the Dura-Trac sensor, which is connected to flush
water. The second option is the SMM and is composed of a flush valve, sample
isolation valve, and chemical injection pump. The Dura-Trac with flush is recommended
for Drinking Water applications where high turbidity is often experienced. The SMM is
recommended for Waste Water applications. These options are only supplied if
specified at the time of purchase. The line of monitors offered by Chemtrac® can be
upgraded to include one of these two options. To upgrade to the Dura-Trac with either
options, the Dura-Trac sensor will need to be returned to the factory.
Potable water or the best quality plant water available shall be used for the flush water
supply. If potable water is used for flush water, a backflow prevention device should be
installed on the flush water line to prevent contamination of the potable water source.
The flush water needs to maintain a pressure of 35 PSI min to 80 PSI max.
3.5.1 Dura-Trac with Flush
Connect the male NPT end of the ¼’’ MNPT to ¼’’ Quick Connect Tube adapter fitting
(supplied with the unit) to the flush water supply. Connect a sufficient length of ¼’’
Teflon tubing between the flush water supply (¼’’ Quick Connect Tube adapter fitting)
and the valve’s ¼” quick connect fitting (see Figure 10 on the next page). The flush
valve’s outlet should already be connected to the probe flush assembly. The third valve
outlet (located on the bottom of the valve and pointed towards the ground) is the drain
outlet. Run this outlet to an appropriate drain using ¼’’ semi-rigid tubing. A manual
control valve should be installed on the flush water line in close proximity of the unit so
CHEMTRAC
SYSTEMS, INC.
DURA-TRAC TM
FLUSH WATER
CONNECTION
1/8" NPT TO 1/4"
COMPRESSION
FLUSH VALVE
25 PSI
CHECK
VALVE
Figure 10 shows tubing connections for the Dura-Trac II sensor maintenance features.
Semi-rigid Teflon tubing (1/4” OD) should be used for making the connections. .
Note: A manual control valve should be installed on the flush water line in close
proximity of the unit so that the flush water may be shut off during sensor maintenance.
Do not open flush water supply valve until all connections have been made.
Connect an appropriate length of ¼’’ semi-rigid Teflon tubing between the flush
water supply line and the PINCH VALVE assembly quick connect fitting (located
on the valve port marked “P”).
Connect an appropriate length of ¼’’ semi-rigid Teflon tubing between the flush
water supply line and the SENSOR FLUSH VALVE inlet quick connect fitting
(located on the valve port marked “P”).
Connect an appropriate length of ¼’’ semi-rigid Teflon tubing between the
SENSOR FLUSH VALVE outlet quick-connect fitting (located on the valve port
marked “A”) and quick-connected fitting on probe flush assembly (located on the
bottom of the probe assembly).
Connect an appropriate length ¼’’ semi-rigid Teflon tubing between the
“Chemical Wash” PUMP INLET quick connect fitting (Marked “IN”) on the bottom
of the DuraTrac II sensor and the chemical carboy.
During the automatic flush/cleaning cycle, the chemical pump injects a cleaning solution
into the sensor. This cleaning solution helps prevent the buildup of fouling agents,
which can overtime affect the sensitivity and response of the instrument. Periodic
checks of the chemical carboy should be made to ensure the chemical storage tank is at
least 1/4 full.
Flush Water
DURA-TRAC TM
II
PATENTED MADE IN U.S.A.
CARBOY
TANK
The Monitor/Controller is equipped with user interface keys, LED indicators, and audible
beeps. The interface keys are up (), down (), left (), right (), and function keys.
= UP key
= DOWN key
There are four LED lights to the left of the graphical display. These are:
Power –Green LED that illuminates when there is power to the unit.
Service - Yellow LED displays the status of the electronics.
Diag. – Green LED that blinks to give a diagnostic status of the remote sensor.
When this LED stops blinking, the remote sensor diagnostic alarm is in alarm
condition.
Alarm – Red LED that illuminates when the Monitor/Controller is in alarm condition.
The Monitor/Controller provides the user with an audible beep feedback every time a
button is pressed.
The menu navigation of the Monitor/Controller is by using buttons at the front panel.
The following steps explain general menu navigations.
1. From the MAIN screen, pressing any function key will gain access to other
menu screens.
2. At the menu screen, on the far left hand side of the text there is a text cursor ()
that indicates the active line on the menu. By pressing the or key, the text
cursor will move to a different menu text line.
3. To modify the parameter setting on the active menu text, first press the key
to gain access to the parameter and then press the or key to scroll
through the parameter range. By holding down the or key, the number will
increased or decreased with larger unit changes.
4. When finished making the parameter change, press key to store the value.
At this point, the new parameter has not been saved. After all parameters
modification are completed, press the SAVE function key to accept the change
or press the MAIN function key to discard the changes.
The menu system for the SCM2500XRD is simple to navigate, below you will find the
different screens accessible through the function keys (SETUP, ALARM, and FLUSH):
The MAIN screen on the SCM2500XRD is the screen used under normal operation of
the instrument. From this screen, all other features and menus can be accessed. The
menu screen shows with Flush option.
Definitions
Streaming Current Value (SCV) ranges from –1000 to +1000
Gain, signal amplification factor, adjustable from 1X to 20X
Next Flushing Cycle (optional): If the unit include sensor flush feature, the
menu display the time when the next flush will occur in days, hours, and minutes.
Zero Offset Conditions
Offset: OUT Offset condition OUT, actual SCV is display
Offset: IN Offset condition IN, adjusted SCV is displayed and the actual
SCV value will be display to the right of OUT.
Offset Value: -1000 to +1000
The Offset function is used to automatically zero the current reading. Once an
optimum chemical dosage has been obtained, the user can null the reading so
that the setpoint becomes referenced to zero for easier interpretation (see Setup
Screen Menu).
Function Keys – There are four main menu selections across the bottom for the
four buttons below. The four menus are:
SETUP – SCV Setup Menu
ALARM – Alarms Status
FLUSH – Sensor Flush Control Menu
Pressing one of these keys directly below these menu selections accesses the
functions within that menu.
From the MAIN screen, press SETUP function key, the SETUP screen will display.
Within the SETUP screen menu, the GAIN, OFFSET, and SCV ALARMS settings can
be modified.
Definitions
Sensor Gain: Signal amplification factor, adjustable from 1X to 20X. The gain
should be adjusted so that a regular change in dosage results in a noticeable
deviation (e.g. 20 to 30 units). To select the proper gain setting let the reading
stabilize for 10 minutes and record the reading. Make a normal dosage change
and then allow another 5 to 10 minutes for the reading to fully stabilize. If the
reading did not change noticeably, simply increase the gain setting and repeat
testing. If the reading changed, but did so by more than 50 units, it is suggested
to decrease the gain setting. Ideal change in Streaming Current for a normal
dosage change is anywhere between 20 to 50 units. If the reading seems
unstable when flow, dosage, NTU, and PH are stable, then check to ensure the
probe is clean and that the sensor is getting a well mixed sample.
Offset Mode: Offset mode can be changed to IN or OUT. Changing the Offset
mode to from “OUT” to “IN” will automatically zero or null the current Streaming
Current reading. For example, if the current reading was –150 and the Zero
Offset was changed to “IN”, then the adjusted Streaming Current value is
displayed on the Main Screen would be zero. The reading will not stay exactly at
zero since the reading is always slightly changing as a result of slight changes in
charge. The Offset value will display at the line below. On the Main Display, the
raw Streaming Current value (with offset) will be displayed to the right of the
Zero Offset: IN. The different between the Streaming Current value and the raw
is the offset value. To disengage the Offset, simply change the Offset mode to
“OUT” and the true Streaming Current Reading will be displayed.
Offset Value: The Offset value indicates the amount of offset that has been
applied to the reading in order to offset the reading to zero. So that, at any time
the operator can see what the offset value is and if anyone has changed it from a
previous offset. To disengage the offset, simply change the Offset Mode to
“OUT” and the true Streaming Current Reading will be displayed. This is also
the method used to re-zero the reading if the current offset no longer
corresponds to optimum coagulant feed. To re-zero the reading when Offset
mode is “IN”, increased or decreased the Offset Value then press Enter to
SAVE.
From the SETUP MENU (1), continue pressing the down arrow key until SETUP MENU
(2) menu screen display. SETUP MENU (2) menu screen is a continuation of the
SETUP MENU (1) menu screen.
Definitions
SCV Filter: The filter function activate rolling average of the Streaming Current
value over time. The SCV filter can be set to OFF, 30, 60, 90, or 120 seconds.
The default setting is OFF.
Control: The control function only applies to the SCC3500. It should always be
set for Reverse when the SCC3500 is being used to control cationic
coagulant/polymer. If an anionic coagulant/polymer is being controlled, then the
Control function needs to be changed to Direct.
From the MAIN screen, press ALARM function key, the ALARM STATUS screen will
display. Within the ALARM STATUS menu you can view which Alarm has been
triggered, as well as, turn the Monitor/Controller’s audible alarm feature on and off.
Definitions:
When any alarm is triggered, a +24 Vdc signal will be present on the Monitor’s digital
alarm output terminals. This signal can be connected to a SCADA/DCS system to alert
the operators to an Alarm condition. In lieu of a +24VDC signal, an optional solid state
relay output is available (must be specified with order).
After being properly adjusted by the operator to match up with the upper and lower SCV
readings that typically correlate to the acceptable window of process performance, the
Hi and Lo Alarms alert the operator as to whether the SCV has exceeded acceptable
limits. A Lo Alarm signify an underfeed of chemical (even possible loss of chemical
feed) and a Hi Alarm signify an overfeed.
This flush feature is an option that is available for both the SCM2500XRD and the
SCC3500XRD. See Section 3.3.7 for detailed description.
The menu system for the SCC3500XRD is simple to navigate; below you will find the
different screens accessible through the function keys (SETUP, ALARM, FLUSH, and
CTRL). The menu screen shows with Flush option.
Definitions
Streaming Current Value (SCV) ranges from –1000 to +1000
Gain, signal amplification factor, adjustable from 1X to 20X
Next Flushing Cycle (optional): If the unit include sensor flush feature, the
menu display the time when the next flush will occur in days, hours, and minutes.
Zero Offset Conditions
Offset: OUT Offset condition OUT, actual SCV is display
Offset: IN Offset condition IN, adjusted SCV is displayed and the actual
SCV value will be display to the right of OUT.
From the MAIN screen, press SETUP function key, the SETUP screen will display.
Within the SETUP screen menu, the GAIN, OFFSET, SCV ALARMS, and SCV Filter
settings can be modified. The SETUP Menus are the same for SCM2500XRD and
SCC3500XRD see Sections 3.2.2 and 3.2.3 for detail descriptions.
Note: See the Addendum section if your SCC3500 has the Remote Control Option.
From the MAIN screen, press ALARM function key, the ALARM STATUS screen will
display. Within the ALARM STATUS menu you can view which Alarm has been
triggered, as well as, turn the Monitor/Controller’s audible alarm feature on and off.
Definitions:
When any alarm is triggered, a +24 Vdc signal will be present on the Monitor’s
alarm terminals 13 (+) and 14 (-). This signal can be connected to a
SCADA/DCS system to alert the operators to an Alarm condition. In lieu of a
+24VDC signal, an optional solid-state relay output is available (must be
specified with order).
After being properly adjusted by the operator to match up with the upper and
lower Streaming Current readings that typically correlate to the acceptable
window of process performance, the Streaming Current Value (SCV) Hi and Lo
Alarms alert the operator as to whether the streaming current value has
exceeded acceptable limits. A Lo Alarm will signify an underfeed of chemical
(even possible loss of chemical feed) and a Hi Alarm will signify an overfeed.
4.3.4 SCC3500XRD Pump Control (1) Menu
From the MAIN screen, press CTRL function key, the PUMP CONTROL (1) Menu
screen will display. There are PUMP CONTROL (1), PUMP CONTROL (2), and FLOW
CONTROL (3) menus under CTRL function key. Use up or down arrow key to navigate
between menus. Within the PUMP CONTROL (1) Menu screen, the PID tuning
parameters can be adjusted.
Definitions
Pump Ctrl: The Controller’s pump output control has two mode of operation;
AUTO or Manual. In AUTO mode, the pump output percent will increased or
decreased automatically in response to deviations from the setpoint. In MAN
mode, the pump output percent can be increased or decreased manually by
setting the Man Output. The two mode can be toggle by pressing the or
key.
Man Output: In MAN mode, the pump output percent % can be increased or
decreased by pressing the or key. The Man Output value can be changed
from 0 to 100% at 0.1% increment. This parameter is saved in non-volatile
memory. When running in Automatic mode, the Man Output setting is ignored.
When switching from AUTO to MAN, the pump output will be locked into
whatever output % it was at when the control was set to Man. In other words,
From the PUMP CONTROL (1) menu screen, continue pressing the down arrow key
until PUMP CONTROL (2) menu screen display appears. PUMP CONTROL (2) menu
screen is a continuation of the Pump Control (1) menu screen.
Definitions
Pump Out Min: This setting is used to prevent the pump control signal from
dropping below a user defined limit. The minimum percent (%) value can be
increased or decreased by pressing the or key. The minimum percent (%)
value can be changed from 0 to 100% at 0.1% increment.
Pump Out Max: This setting is used to prevent the pump control signal from
going above a user defined limit. The maximum percent (%) value can be
increased or decreased by pressing the or key. The maximum percent (%)
value can be changed from 0 to 100% at 0.1% increment.
Output Lo: This setting defines the low alarm value of the pump control output
signal. The low alarm percent (%) value can be increased or decreased by
pressing the or key. The low alarm percent (%) value can be changed
from 0 to 100% at 0.1% increment. When the pump control output signal fall
below the low alarm value, alarm condition will occur.
Output Hi: This setting defines the high alarm value of the pump control output
signal. The low alarm percent (%) value can be increased or decreased by
pressing the or key. The high alarm percent (%) value can be changed
from 0 to 100% at 0.1% increment. When the pump control output signal rise
above the high alarm value, alarm condition will occur.
MAIN Function Key: Pressing this key will ignore any setting modifications on
this screen and brings up the MAIN screen.
SAVE Function Key: Pressing this key will save current setting modifications
and brings up the MAIN screen.
4.3.6 SCC3500XRD Flow Control (3) Menu
From the PUMP CONTROL (2) menu screen, continue pressing the down arrow key
until FLOW CONTROL (3) menu screen display appears. FLOW CONTROL (3) menu
screen is a continuation of the Pump Control (2) menu screen.
When ENABLED, the FLOW CONTROL function allows the user to control the chemical
feed based on the process FLOW rate and the Streaming Current Value PID control
output. The flow control is a proportional pump output control base on the process flow
Flow control is a feature that allows the Controller to perform coagulant pump control in
the process that is varying their process flow. During large process flow variation, the
PID control alone may not be able to response to the flow changes. The Controller
monitors the process flow and uses it in the flow control calculation. The Controller is
equipped with auxiliary analog input (4-20mA). When the flow control is enabled, the
pump control output is proportionally changed by the amount of process flow changes in
conjunction with the PID loop based on the SCV setpoint. The following are parameters
used in the flow control:
Definitions
Flow Ctrl: The flow control modes are ENABLED or DISABLED. When the
flow control is ENABLED, pump output percent % will increase or decrease
automatically in response to process flow changes and SCV deviation from the
setpoint. When the flow control is DISABLED, the pump output percent will
increase or decrease automatically in response PID control only and not to
changes in the flow signal. Switch between ENABLED or DISABLED control
mode by pressing either or key.
Band: The Band setting determines how much the PID can adjust above or
below the pump output value that is determined by the Flow Control settings (see
Flow Min/Max, Pump Output Min/Max). This allows the user to limit the range in
which the SCM PID can operate within. The graph on the following page
provides an example of how the + and – Band settings are used. The SCV
control band percent (%) value can be increased or decreased by pressing the
or key. The SCV control band percent (%) value can be changed from 0 to
100% at 1% increment.
Flow Min: Minimum process flow input signal (in percent) that will result in the
minimum pump control output signal (as determined by Pump Output Min). The
percent (%) value can be increased or decreased by pressing the or key.
The percent (%) value can be changed from 0 to 100% at 0.1% increment.
NOTE: When the Flow signal drops below the Flow Min setting, the
Pump Output will go to 0% (4mA) and the PID control goes into a Hold
status. So, when setting the Flow Min, keep in mind that it should be set to
a value that will always be higher than the actual flow signals produced
when the process is running.
The above graph illustrates how the Flow Control settings work together to determine the Pump
Output. The solid line represents the Pump Output as determined by the Flow Control settings
(Flow Min, Flow Max, PO Min, PO Max) and the two dashed lines represent the upper and
lower limits that the SCC PID must operate within as determined by the +Band and –Band
settings.
The first step in establishing the proper flow control settings is to determine the % Flow Min
and % PO Min settings. Generally, these can both be set for 0%. The %Flow Max should be
set for whatever is the maximum flow signal the SCM will see when the plant is operating at
higher flows. And the %PO Max would be set to equal the Pump Output that produces near
optimum quality finished water at the higher flow rate during normal turbidity conditions.
Once the Flow and PO Min/Max settings are determined, the next thing to determine is the +
and – Band settings. If the % PO Max setting was established under “normal” turbidity
conditions, and assuming the turbidity doesn’t generally go much lower than what is considered
“Normal”, then the – Band setting can be set to something like 5 to 10% because it can be
assumed the SCC doesn’t typically need to reduce the coagulant dosage by very much from
what is considered normal. The + Band setting on the other hand needs to be set to a value
large enough to allow the SCC to increase the Pump Output by large enough % in order to
handle the larger turbidity/organics excursions.
Since there are several variables and situations to consider when using the flow pacing feature,
it is recommended to contact Chemtrac, Inc. (770-449-6233) to discuss your unique application
requirements so that you can be better advised on what settings to use.
4.3.7 SCC3500XRD Optional Flush and/or Sensor Maintenance Control Menu
Sensor Flush is only available with the optional Dura-Trac Flush feature or Sensor Maintenance
Features added to the Dura-Trac II Sensor
From the MAIN screen, press FLUSH function key, the FLUSH CTRL MENU screen will
display. The goal of the sensor flush is to minimize the need for operator involvement for
maintenance purposes. This feature greatly enhances the reliable operation of the Streaming
Current Monitor. Within the FLUSH CTRL MENU screen, the flush parameter settings can be
modified.
Definitions
Auto Flush: The Sensor Maintenance option or Dura-Trac with Flush runs
an automatic flushing/cleaning sequence and will continue to flush according
to the flush parameter settings. The Auto Flush can be set to ENABLED or
ON
PUMP OUTPUT HOLD
HOLD PERIOD
OFF
ON
SAMPLE ISOLATION
OFF
ON
SENSOR FLUSH FLUSH RINSE
AND RINSE
OFF
ON
CHEMICAL PUMP WASH PERIOD
OFF
TIME (SECONDS)
NOTES
Sample Isolation and Chemical Wash only apply to instruments with the optional
Dura-Trac II with Sensor Maintenance Features. The Dura-Trac with flush option
does not include the sample isolation or chemical pump feature; however, there
will still be a delay between sensor flush and rinse.
After sample flow is established and power has been applied to the sensor and
streaming current monitor, allow 10-15 minutes or longer for the reading to stabilize.
The reading may fluctuate 5 to 10 units, even under stable conditions due to the
chemical not being thoroughly mixed. If readings fluctuate widely, refer to
Troubleshooting Guide. The monitor’s reading may be negative, zero, or positive. The
monitor is simply indicating the streaming current value of the sample. In most
applications, the reading will be slightly negative (anionic).
Next, a test should be performed to determine the Raw SCV reading. This will help
determine the Proportional Band setting, LO SCV Alarm setting, and give a better
understanding of instrument response. To determine the Raw SCV reading, shut off
sample flow to the sensor and turn the outlet fitting up. Slowly pour a 2 liter sample of
raw untreated water into the sensor and allow the reading to stabilize and then record
the reading. This reading should serve as an absolute alarm value, which if measured
by the monitor will indicate a loss of chemical feed. It is recommended to set the Lo
SCV Alarm value (see Alarm setup menu) between the Raw SCV measurement and the
setpoint value. Further testing will help to determine the best ideal alarm value. The HI
Alarm value should be set above the setpoint value and at a point where testing shows
an unacceptable amount of overfeed.
After verifying proper response, the next step should be to optimize the process to
establish an SCV setpoint. The SCV setpoint can then be zero’d so that the setpoint will
be adjusted to a reading of zero (0). This is done by entering the Setup menu and
changing the Offset mode to “IN”. Offsetting the SCV is not necessary for normal
monitor operation as it is only provided so that an easier reference of zero can be used
for monitoring changes in the process. For example, if the true SCV setpoint reading
was –150, and the user switched the Offset Mode to “IN”, then a value of +150 will be
added to whatever the true SCV reading is. For example, if the true SCV reading goes
from -150 to -145, then the offset reading would go from 0 to +5 because -145 + 150 =
+5. Once the setpoint has been zero’d, it is easier to determine whether chemical is
being under or overdosed since going negative (anionic) from 0 would be an under-dose
and going positive (cationic) would be an overdose. A setpoint of zero (0) is also easier
for multiple operators (night and day shift) to remember. Since the setpoint will change
seasonally, adjusting the setpoint so that it equals zero (0) helps to avoid confusion.
The treatment optimization process should be done slowly and stepwise. Assuming that
the plant is producing acceptable water with present chemical dosages, trim
approximately 10%, wait for the reading to stabilize, and record the reading as the
setpoint. You may need to change GAIN setting to increase magnitude of response. If
the settled and finished water quality is still acceptable at the reduced dosages, trim
another increment, wait for the reading to stabilize, and record the reading as the new
setpoint. Continue this process, being sure to wait long enough each time to see the full
effect of the chemical feed changes on the process (i.e. settled water turbidity,
If the Offset function is being used, re-zero the monitor reading as described in section
4.2.2 after each reduction in chemical feed. If a cationic coagulant is being used, the
streaming current value will become more negative with each reduction in dosage. The
"optimum setpoint" is obtained when a minimum dosage of coagulant is being fed and
produces desired results for the particular treatment process. This setpoint will remain
very close to the same reading even when raw water turbidities increase or decrease.
Simply adjust the coagulant dosage to maintain this setpoint reading on the monitor.
This procedure may need to be repeated on a monthly to seasonal basis to ensure the
setpoint remains representative of optimum process performance.
Make electrical connections between Streaming Current Controller and the chemical
feed pump. The AUTO or Manual control mode is indicated on the MAIN screen. To
switch between AUTO or Manual control mode can be done by pressing both and
keys from the MAIN screen. Once in Manual control mode, the pump control output
percentage can be increased or decreased by pressing the or key.
The AUTO or Manual control mode can also be change from the Pump Control (1)
menu. Once Pump Control (1) menu is display, move the text cursor on the far left hand
side of the screen () to “Pump Ctrl:” then press the control text will blink. The
control mode can be set by pressing the pressing or key, this will toggle between
AUTO and MAN mode. Set the controller to MAN. Once completed, press key then
press or key to get to next parameters on that screen. Next press key to “Man
Output:” then press the control number will blink. The percent (%) number will blink,
the manual chemical feed control value output can now be increased or decreased the
by pressing or key to the desire manual control value. When completed, press
key to get to other parameters on that screen. The SAVE Function Key must be
pressed to save current setting modifications and brings up the MAIN screen.
Automatically controlling the treatment process with the Streaming Current Controller
(SCC3500XRD) is a very simple operation, once you know how the controller works.
Most controller manuals do not explain, in simple terms, the purpose of so-called "tuning
constants" termed Proportional Band, Integral Time, and Rate. Controllers with these
three functions are sometimes called "3-mode controllers," or "PID controllers". In
order to explain the purpose of these functions, a brief review of how a simple
proportional controller works may be helpful.
Since the SCV is taking its sample downstream of the coagulant feed point, there will be
some "lag time" before it can sense a change in turbidity, alum feed, raw water flow, etc.
Because this “lag time” exist, the controller must have a way to account for it, otherwise
the result would be continuous cycling above and below the setpoint,. The Proportional
Band, Integral Time, and PID Rate functions provide a way to eliminate cycling due to
the lag time between coagulant additions and streaming current sensing.
The following are description of parameters used in the PID control loop algorithm:
Process Variable: This is the Streaming Current Value (SCV), and it is what the
controller is constantly comparing to the Setpoint to determine what changes in
PID Output are required.
Setpoint: The process variable “target” that the controller is trying to maintain.
PID Output: The 4-20mA output signal produced by the controller. The output is
used to control the coagulant pump in an effort to keep the process variable near
the setpoint..
Proportional Band: This setting determines the controller’s response to changes
that occur in the SCV. Raise this value and the controller will make a smaller
adjustment when the SCV drifts away from setpoint.
Integral Time: This setting accounts for the lag time in the process between
coagulant injection point and the sample point for the SCM. If lag time is 60
seconds, the Integral Time should be set for 60.
PID Rate: The value is a function design to improve the PID response in
applications with exceedingly long lag times.
Maximum Output: Defines the maximum value for the output signal to the
coagulant pump.
Minimum Output: Defines the minimum value for the output signal to the
coagulant pump.
The Controller’s PID loop is designed for reverse acting; process variable goes down will
cause the output to go up. To set the loop to be direct acting, go to the second page of
the Setup menu and change the setting to Direct.
PID Rate
The PID Rate setting is usually left at 1 for most applications. The PID Rate
function serves to improve the controllers response when higher Proportional Band and
Integral Time settings appear to still be too responsive for the application. The PID
Rate setting should not exceed 10.
The AUTO or Manual control mode is indicated on the MAIN screen. To switch between
AUTO or Manual control mode can be done by pressing both and keys from the
MAIN screen. When in AUTO control mode, the pump output percent will increase or
decrease automatically in response to deviations from the setpoint.
The AUTO or Manual control mode can also be changed from the Pump Control (1)
menu. When Pump Control (1) menu is displayed, move the text cursor on the far left
hand side of the screen () to “Pump Ctrl:” then press key, the control text will blink.
The controller mode can be set by pressing or key, this will toggle between AUTO
and MAN modes. Set the controller to AUTO. When completed the change, press the
key then press or key to get to other parameters on that screen. The
Proportional Band, Integral Time, and PID Rate can be changed by following the same
procedures. The SAVE Function Key must be pressed save current setting
modifications and brings up the MAIN screen. The MAIN Function Key can be used to
discard any new modification made to this screen and brings up the MAIN screen.
Tuning constants are stored digitally in non-volatile memory and can be changed by
front panel keys. Table below shows default PID Parameters preset by Chemtrac®.
Caused by:
Decrease in pH
Decrease in raw H20 flow
Decrease in color
Decrease in raw water turbidity
Decrease in lime
Decrease in caustic
Decrease in anionic polymers Increase in aluminum sulfate, or PAC
Increase in cationic polymers Increase in chlorine
Caused by:
Increase in pH
Increase in H20 flow
Increase in color
Increase in raw water turbidity
Increase in lime
Increase in caustic
Increase in anionic polymers
Decrease in aluminum sulfate, or PAC
Decrease in cationic polymers
Decrease in chlorine
NOTES
Potassium Permanganate usually has no appreciable effect on the SCV (at
normal dosages of 1-2ppm).
Increasing conductivity will drive the SCV toward zero.
Change in lag time may affect the SCV.
Introduction
It can take several days, weeks, or possibly even a few months for an operator
who has come to rely on Jar test, eye-balling, turbidity readings, or any other
method for determining coagulant dosage to become comfortable using the
Streaming Current Monitor as a tool for controlling coagulant feed. Very few
plants install an SCM and start controlling in Automatic mode in the first few
weeks. Monitoring the response and repeatability of the monitor through several
different turbidity excursions is the way most operators prove to themselves the
capabilities and reliability of Streaming Current technology.
Eventually the moving parts of the monitor will wear. Most notably, the probe
and piston will wear the fastest and require replacement once every two years on
average (sooner if there is too much in the way of abrasive solids in the
sample). The Gain setting is provided as a way to compensate for wear that
occurs, but eventual these parts will need replacing. To determine if the probe
and piston need to be replaced simply make small chemical feed adjustments. If
the probe is unresponsive and cleaning and/or adjusting the Gain setting does
not improve the result, the probe and piston most likely need to be replaced.
Having a new set on hand to compare against is the best method of determining
if the parts need to be replaced. Sensor maintenance will also include replacing
other mechanical parts like the linkage between the motor and piston, and the
motor itself. When these parts start to develop noticeable loose motion, they
can cause the reading to become less stable. If the reading starts to become
slightly unstable, and cleaning or replacing the probe and piston does not
eliminate the unstable reading, check the linkage and shaft of the motor to see if
it has excessive movement. If so, replace the worn parts.
It may not be necessary to replace both the piston and the probe at the same
time as usually the piston wears faster than the probe. To check this, simply
install a new piston with the old probe and compare those readings to the ones
obtained with the new piston and new probe combination. If the old probe and
new piston combination produce a reading that is within 50% or more of the new
set, then the probe can still be used as long as the new piston is installed. The
same procedure should be followed with a new probe and old piston to
determine if the old piston is still suitable for use. Using this procedure, the
operator can determine which part, if not both, needs to be replaced. Be sure to
order a replacement part(s) to have on hand as a spare once you have installed
the new probe and/or piston to replace the worn part(s).
Sensor Conditioning
It is important to realize that a recently cleaned probe and piston will need time to
condition (or stabilize) after they have been cleaned. In some cases, the
conditioning time can take as little as 15 minutes or up to 1 hour. The time it
takes depends on the type of coagulant and dosage level, as well as other water
quality parameters like NTU, TOC, and alkalinity. Because this conditioning has
to occur after each cleaning, it is advised to avoid cleaning the probe more often
than what proves to be necessary. For example, don’t assume that cleaning
once a day or even once a week is optimum. In this case, cleaning to frequently
can create problems as operators might not wait long enough for the sensor to
fully recondition before putting the unit back into automatic control. One way to
shorten the conditioning time after a cleaning is to temporarily increase the
coagulant dosage by 10 to 20% for 5 to 10 minutes. This will help condition the
probe more rapidly.
2. Display does not A. GAIN setting too low. A. Increase GAIN setting.
change with
B. Wrong sample point or B. Select correct sample point.
change in
insufficient mixing..
coagulant dosage. C. Clean cell (see Cleaning
C. Sample cell dirty. Procedures).
D. Excessive “lag time” D. Move sampling point closer to
between coagulant coagulant feed point and/or
injection point and sensor decrease sample TRANSPORT
sample cell. time (See Selecting Proper
Sample Point).
The Dura-Trac sensor is supplied with two (2) probes and (2) pistons so freshly cleaned parts
can always be on hand.
CAUTIONS
If monitor is being used for automatic dosage control, put the controller into
MANUAL mode before starting replacement procedure.
Depending on the type of contamination, see table below for different cleaning
procedures recommended.
A “soak and brush” method is recommended for any contaminant. Soak only long
enough to dissolve/remove the material. Probe surfaces should be thoroughly washed
with clean water to remove any residual cleaning compound.
CAUTIONS
Do not soak entire probe cartridge, only soak inside the bore. Acid concentration
shall not exceed 15% concentration.
Figure 12 AND 13 illustrates Dura-Trac and Dura-Trac II sensor parts identification with
part numbers. Table below lists recommended replacement parts.
WASHER
(1608)
VITON SEAL
110 CRANK (7701)
ASSEMBLY
(5302) MOUNTING NUT
(1607)
NEOPRENE
110 MOTOR
WASHER
(1301)
(5016)
OPTO
SWITCH 4-40 SET
(1308) SCREW
MOTOR BRACKET
ROD END (3311)
(3707)
DURA NUT
YOKE PIN (4200)
(5720)
EXTENSION
(5611)
YOKE
(5710)
GUIDE
(8711)
PISTON
(1701)
PROBE
WASHER
(7703)
PROBE
(8601)
DURA NUT
(4200)
O-RING
(1605)
DURA PLUG
(8606)
NEOPRENE WASHER
(5016) ROD END
110V MOTOR
OPTO (3707)
(5470)
SWITCH
4-40 SET (1308)
SCREWS
MOTOR YOKE PIN
BRACKET (5720)
(3311)
YOKE
(5710)
DURA NUT
(4200)
WW EXTENSION
(5611)
WW PROBE BLOCK
(5630)
GUIDE
(7720)
PISTON
(1710)
PROBE
WASHER
(7703)
PROBE
(8601)
DURA NUT
(4200)
O-RING
(1605)
DURA PLUG
(8606)
Chemtrac, Inc
6991 Peachtree Industrial Blvd., Building 600
Norcross, GA 30092
The following Figures 14 thru 19 illustrate enclosure and mounting dimensions for Streaming
Current Monitor/Controller, Dura-Trac Sensor, Dura-Trac Sensor with Flush, Dura-Trac II
Sensor, and Sensor Maintenance Module.
SCC3500XRD
13.6" [345mm]
11.2" [285mm]
12.5" [317mm]
Power
Service
Diag.
Alarm
CHEMTRAC
SYSTEMS, INC.
7.71" [196mm]
CHEMTRAC
SYSTEMS, INC.
8.5" [215mm]
7.2" [183mm]
DURA-TRAC TM
14.7" [373mm]
PATENTED MADE IN U.S.A.
11.2" [285mm]
9.7" [247mm] 6.3" [161mm]
10.5" [266mm]
9.2" [234mm]
18.8" [477mm]
DURA-TRAC TM
II
PATENTED MADE IN U.S.A.
CHEMTRAC
SYSTEMS, INC.
8.5" [215mm]
7.2" [183mm]
DURA-TRAC TM
17.6" [447mm]
PATENTED MADE IN U.S.A.
18.8" [477mm]
DURA-TRAC TM
II
PATENTED MADE IN U.S.A.
The Remote Control Feature is an optional and is only supplied on the SCC3500 when
specifically ordered by the customer.
The Remote Control Feature allows certain parameters on the controller to be remotely
set by digital input (relay) and 4-20mA signals which would generally be controlled
through the customer’s DCS/SCADA. The parameters which can be remotely set
include CONTROL MODE, S ETPOINT, and MANUAL PUMP OUTPUT. The below text
explains
From the SETUP MENU (1), continue pressing the down arrow key until SETUP MENU
(2) menu screen display. SETUP MENU (2) menu screen is a continuation of the
SETUP MENU (1) menu screen.
Definitions
SCV Filter: The filter function activate rolling average of the Streaming Current
value over time. The SCV filter can be set to OFF, 30, 60, 90, or 120 seconds.
The default setting is OFF.
Control: The control function only applies to the SCC3500. It should always be
set for Reverse when the SCC3500 is being used to control cationic
coagulant/polymer. If an anionic coagulant/polymer is being controlled, then the
Control function needs to be changed to Direct.
Remote SP Control: This setting must be Enabled in order for the Setpoint to
be controlled remotely via a 4-20mA signal. The 4-20mA signal to control the
Setpoint is connected to Aux 2 terminals 19 (+) and 20 (-). The scaling on the 4-
20mA signal is -1000 to +1000.
In order to remotely change the Control mode from Manual to Auto, either the
Remote SP Control or Manual PO Control must be enabled.
To remotely set the Control mode to Auto, a closed dry contact must be applied
across terminals 15 and 16. Open the contact to switch back to Manual mode.
Frequency: 50-60 Hz WARNING !! TURN POWER OFF BEFORE MAKING ANY WIRE
POWER SWITCH Max Current: 1.5A @ 120V~ CONNECTIONS TO AVOID DAMAGING THE ELECTRONIC CIRCUIT.
25 26 27 28
SMM | Sensor
FUSE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
GND
N
L
Power
Terminals 11 & 12 (Analog Out) - Pump Control Signal (4-20mA)
Terminals 15 & 16 (Digital In) - Control Mode (Relay)
Terminals 17 & 18 (Aux1 Input) - Flow Signal (4-20mA)
Terminals 19 & 20 (Aux2 Input) - Setpoint Value (4-20mA)
Terminals 21 & 22 (Aux3 Input) - Manual Pump Out (4-20mA)
1 2 3 4 5 6 7 8 9 10
Opto (W)
Vdc Gnd
Opto (O)
Opto (B)
+24 Vdc
Signal +
+ Probe
Signal -
- Probe
Shield
An optional feature of the SCM2500XRD is an analog output (4-20mA) representing the Offset
value. On units that have this option, the signal is provided at terminals 11 and 12; see figure
below. Terminal 11 is labeled Offset Value (AO+) and terminal 12 is labeled Offset Value (AO-
). The scaling for the Offset value analog output is from -1000 to +1000 streaming current
value. The two analog outputs are provided to allow the customer to monitor the SCV Signal
and Offset value remotely. The explanation of the Offset mode and Offset value are described
in Section 3.2.2 SCM2500XRD Setup Menu (1).
FUSE
FUSE: AGC-1.5A
WARNING TURN POWER OFF BEFORE MAKING ANY WIRE CONNECTIONS
17 18 19 20
OFF TO AVOID DAMAGING THE ELECTRONIC CIRCUIT.
1 9 17
SMM | Sensor
2 10 18
3
4
11
12
* 19
5 13
* 20
6 14
ON
7 15 *
8 16 * *
L G N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
GND
N
L