As Shown: Rg-6, Coaxial Cable Wire
As Shown: Rg-6, Coaxial Cable Wire
KILOWATT HOUR
NO. OF CB EFF AC METER
CKT. NO. LOAD DESCRIPTION OUTLETS
VA V AMPS
BOLT ON POLES KAIC z
1 LIGHTING OUTLET 10 1,000 220 4.54 20 2 10 5.6 M
2 LIGHTING OUTLET 10 1,000 220 4.54 20 2 10 5.6
3 LIGHTING OUTLET 12 1,200 220 5.45 20 2 10 5.6
4 LIGHTING OUTLET 11 1,100 220 5.00 20 2 10 5.6
5 LIGHTING OUTLET 15 1,500 220 6.81 20 2 10 5.6
6 LIGHTING OUTLET 10 1,000 220 4.54 20 2 10 5.6
7 LIGHTING OUTLET 13 1,300 220 5.90 20 2 10 5.6
8 DUPLEX CONVENIENCE OUTLET,3 PRONG,UNIVERSAL 6 1,080 220 4.90 20 2 10 1 - 2.0(G) 5.6
9 DUPLEX CONVENIENCE OUTLET,3 PRONG,UNIVERSAL 6 1,080 220 4.90 20 2 10 1 - 2.0(G) 5.6
10 DUPLEX CONVENIENCE OUTLET,3 PRONG,UNIVERSAL 6 1,080 220 4.90 20 2 10 1 - 2.0(G) 5.6
11 DUPLEX CONVENIENCE OUTLET,3 PRONG,UNIVERSAL 7 1,260 220 5.72 20 2 10 1 - 2.0(G) 5.6
12 DUPLEX CONVENIENCE OUTLET,3 PRONG,UNIVERSAL 7 1,260 220 5.72 20 2 10 1 - 2.0(G) 5.6
13 1.0 HP WT A.C.U. 1 1,760 220 8.00 20 2 10 1 - 2.0(G) 5.6
14 1.0 HP WT A.C.U. 1 1,760 220 8.00 20 2 10 1 - 2.0(G) 5.6
15 1.0 HP WT A.C.U. 1 1,760 220 8.00 20 2 10 1 - 2.0(G) 5.6
16 1.0 HP WT A.C.U. 1 1,760 220 8.00 20 2 10 1 - 2.0(G) 5.6
17 SMALL COOKING UNIT 1 3,000 220 13.63 30 2 10 1 - 3.5(G) 3.6
18 SPARE - - - - - - - - - -
C
7
DECK
C C C C C SECOND FLOOR
C 2 3 4 5 6
SECOND FLOOR
GROUND FLOOR
PTR NO: 02180505 DATE: JAN. 3, 2017 PLACE ISS.: #7 ANTONIO ST.
.
LOCATION:
SAN SEBASTIAN, TARLAC CITY
DATE: 08 08