Fluor: Calculation Sheet

This document contains calculations for the foundation of a terminal substation building. It calculates requirements for compression reinforcement, lever arm, required reinforcement area, maximum reinforcement area, minimum reinforcement area, and provided reinforcement spacing for the pile cap. The calculations show that the provided reinforcement spacing of 150 mm is less than the required spacing of 280.73 mm, so reinforcement spacing requirements are satisfied.

Uploaded by

nsureshbabu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views

Fluor: Calculation Sheet

This document contains calculations for the foundation of a terminal substation building. It calculates requirements for compression reinforcement, lever arm, required reinforcement area, maximum reinforcement area, minimum reinforcement area, and provided reinforcement spacing for the pile cap. The calculations show that the provided reinforcement spacing of 150 mm is less than the required spacing of 280.73 mm, so reinforcement spacing requirements are satisfied.

Uploaded by

nsureshbabu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

17-May-16

Page 174 of 3011

FLUOR CONTRACT NO.: A7JJ


REV.: __0__
DATE: 5/5/2016.
.

CALCULATION SHEET BY: JMC CHK'D : _PLA_


Terminal Substation 2 Building DC NO.: P13006-00-CI-EC-0001
Foundation Calculations

persistent & transient / seismic

Mpc.bot If Kpc.bot < K', compression


Kpc.bot   0.03504
d reinforcement is not required
 fck
2
 pc.bot 
CheckK.pc.bot  "Compression reinforcement is NOT required for pile cap."

lever arm;
dpc.bot 1   1  3.53Kpc.bot 
zpc.bot  min
    767.60 mm
Note: Limiting z to 0.95*d is not a
 0.95 dpc.bot  requirement of Ref.1 but is
  considered a good practice, Ref.3
Mpc.bot Fapc.bot 2
mm
As.pc.bot    2193.39 Required area of reinforcement for the
fyd  zpc.bot 2 fyd m whole width of the pile cap
 PT  PT

accidental

Mpc.bot.Acc
Kpc.bot.Acc   0.03438 If Kpc.bot < K', compression
d 2  reinforcement is not required
 pc.bot  fck
CheckK.pc.bot.Acc  "Compression reinforcement is NOT required for pile cap."

lever arm;
dpc.bot 1   1  3.53Kpc.bot.Acc 
zpc.bot.Acc  min
    767.60 mm
Note: Limiting z to 0.95*d is not a
 0.95 d pc.bot  requirement of Ref.1 but is
  considered a good practice, Ref.3

Mpc.bot.Acc Fapc.bot.Acc 2
mm
As.pc.bot.Acc    1973.39 Required area of reinforcement for the
fyd  zpc.bot.Acc 2  fyd m whole width of the pile cap
 Acc  Acc

4 h pc 2
mm Maximum area of reinforcement
As.pc.max   40000.00 (Section 9.2.1.1 (3)), Ref.1
100 m

CheckAs.pc.bot  "Required area of reinforcement is less than the maximum. OK!"

 0.26 fctm  mm
2
As.pc.min  max 0.0013  d
pc.bot  1270.48 Minimum area of reinforcement, sec.9.2.1.1 (1),
 fyk  m Ref.1
 
2
mm

As.pc.bot.reqd  max As.pc.bot As.pc.bot.Acc As.pc.min  2193.39
m
 Required area of reinforcement

2
π ϕpc.b
2
As.ϕ.pc   615.75 mm Area of reinforcing bar provided
4
As.ϕ.pc
spc.bot.reqd   280.73 mm Required pile cap reinforcement spacing
As.pc.bot.reqd

spc.b  150.00 mm Pile cap reinforcement spacing provided


if spc.b  spc.bot.reqd "OK" "NG"  "OK" 

P13006-00-CI-EC-0001-07 Rev 0.xmcd PC3 - Pile Cap