The document discusses methods for calculating different capacitance parameters in transformers. It describes how to calculate the ground capacitance Cg, which is the sum of the capacitance C1 between the impulsed winding and grounded low voltage winding, and the capacitance C2 between the impulsed high voltage winding and the grounded tank. It also describes how to calculate the series capacitance Cs, which is the sum of the inter-turn capacitance Ct and the inter-disc capacitance Cd. Formulas are provided for calculating each of these capacitance values based on properties of the transformer windings and dielectric materials.

Uploaded by

Pranjal Verma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views1 page

Capacitance of Transformer

The document discusses methods for calculating different capacitance parameters in transformers. It describes how to calculate the ground capacitance Cg, which is the sum of the capacitance C1 between the impulsed winding and grounded low voltage winding, and the capacitance C2 between the impulsed high voltage winding and the grounded tank. It also describes how to calculate the series capacitance Cs, which is the sum of the inter-turn capacitance Ct and the inter-disc capacitance Cd. Formulas are provided for calculating each of these capacitance values based on properties of the transformer windings and dielectric materials.

Uploaded by

Pranjal Verma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Calculating Capacitance Parameters in transformers:

Ground capacitance calculations:

Ground capacitance Cg = C1 + C2

C1 is the capacitance between impulsed winding and the grounded LV winding on the same
limb.

C2 is capacitance between impulsed HV winding of the side limb and the grounded
transformer tank.

2𝜋𝜀0 𝜀𝑟 𝑙1
𝐶1 = ⁡𝐹
ln⁡(𝐷⁄𝑑)

𝜋𝜀0 𝜀𝑟 𝑙1
𝐶2 = ⁡𝐹
ln(𝐷⁄𝑑 )

‘D’ and ‘d’ are the outer and inner diameter of the high voltage winding respectively.

l1 is the axial height of the discs.

Series Capacitance Calculations:


𝐶 4
The series capacitance 𝐶𝑠 = [ 𝑡 + 𝐶𝑑 ]
𝑁 3

Ct is the inter-turn capacitance


2𝜋𝜀0 𝜀𝑟 𝑙1
𝐶𝑡 = ⁡𝐹
ln⁡(𝐷⁄𝑑 )

𝜀0
Cd is the inter disc capacitance 𝐶𝑑 = 2𝑆𝜀𝑟 ⁡𝐹
𝑑

S = area of disc contributing to the capacitance associated to dielectric of relative permeability.

Refrence:

Transformer engineering design and practice, by S.V.Kulkarni S.A.Khaparde.