Cooling Load Calculation 2016
Cooling Load Calculation 2016
3
Source: komuves.blog.hu, gammert.de,
Introduction
The Purpose of COOLING LOAD CALCULATION to define sizing values
for the…
5
Source: pelletofenservice.at
Sources of Heat Gain
6
Source: alex-plank.de
Sources of Heat Gain
7
Source: holidaycheck.de
Components of Heat Gain
Source: www.slideshare.net 8
Components of Heat Gain
Definition
9
Definitions
Heat gain is classified
Radiant energy first must be absorbed by surfaces that enclose the space
(walls, floor, and ceiling) and the objects in the space (furniture, etc.).
When these surfaces and objects become warmer than the surrounding air,
some of them transfers heat to the air by convection.
The heat storage capacity of these surfaces and objects determines the
heat gain.
The sum of all space instantaneous heat gains in any given time does not
necessary (or even frequently) equal the cooling load for the space at that
same time. Source: spiegel.de 12
Heat Gain Through Building Envelpoe
Radiation: movements of infra red
rays through the glass, striking factor
of heat gain in summer.
RADIATION THROUGH
GLAZING
Sol-air temperature is the outdoor air temperature which gives the same rate
of heat entry into the surface as would the combination of incident solar
radiation, radiant energy exchange with the sky and other outdoor
surroundings, and convective heat exchange with outdoor air. 15
Source: solebich.de
Heat Gain Through Building Envelpoe
Heat Flow into Sunlit Surfaces of the Building Envelope
The heat balance at a sunlit surface gives the heat flow into the surface:
Q
= αE t + ho (to − ts ) − ε∆R
A
where
α – absorptance of surface for solar radiation;
Et – total solar radiation incident on surface, W/(m2·K) ;
ho – coefficient of heat transfer by long-wave radiation
and convection at outer surface, W/(m2·K);
to – outdoor air temperature, °C;
ts – surface temperature, °C;
ε – hemispherical emittance of surface;
∆R – difference between long-wave radiation incident on
surface from sky and surroundings and radiation
emitted by blackbody at outdoor air temperature, W/m2 16
Heat Gain Through Building Envelpoe
The rate of heat transfer can be expressed
Q
= ho (to − ts )
A
Vertical surfaces: they receive long-wave radiation from the ground and
surrounding buildings as well as from the sky, ∆R values are difficult to
determine. When solar radiation intensity is high, surfaces have a higher
temperature than the outdoor air, thus their long-wave radiation
compensates to the sky’s low emittance. This means ε∆R = 0 17
Fenestration Heat Gain
Total Fenestration Heat Gain
18
Fenestration Heat Gain
Parts of Fenestration Heat Gain: Direct Solar Heat Gain
Source: skymosity.com
Qc = U ⋅ A ⋅ (to − ti )
A – window area, m2
U – overall U-factor, W/m2K
to – outside temperature, °C
ti – inside temperature, °C
21
Fenestration Heat Gain
22
Shading
Internal Shading
23
Source: ambitionblinds.co.uk, caribbeancoshutters.com,
Shading
External Shading
24
Source: en.wikipedia.org
External Shading
External venetians
Louvres
Shading
Overhang 25
where
Q – heat transfer rate, W
U – coefficient of overall heat transfer between adjacent and
conditioned space, W/(m2·K)
A – area of separating section concerned, m2
tb – average air temperature in adjacent space, °C
ti – air temperature in conditioned space, °C 27
Sources of Internal Heat Gain
Occupants
Occupants:
• heat and
• moisture
are emitted by humans in
different states of activity.
Source: alfanyelvstudio.hu
Sensible and latent heat gains often comprise a large fraction of the total load.
The conversion of sensible heat gain from people to space cooling load is
affected by the thermal storage characteristics of that space because some
percentage of the sensible load is radiant energy.
Latent heat gains are considered instantaneous.
28
Sources of Internal Heat Gain
Occupants
29
Sources of Internal Heat Gain
Lighting
The primary source of heat from lighting comes from light-emitting elements,
or lamps, significant additional heat may be generated from associated parts
of light fixtures, house of lamps.
where
Qel – heat gain from electric lighting, W
W – total light wattage, W
Ful – lighting use factor
Fsa – lighting special allowance factor 30
Source: ipon.hu, meteonline.hu, toparuk.hu, webaruhaz.hu
Sources of Internal Heat Gain
Lighting Qel = W ⋅ Ful ⋅ Fsa
The total light wattage is obtained from the ratings of all lamps installed, both
for general illumination and for display use.
The lighting use factor is the ratio of wattage in use to total installed wattage.
For commercial applications such as stores, the use factor is generally 1.0.
The special allowance factor is for fluorescent fixtures and/or fixtures that are
either ventilated or installed so that only part of their heat goes to the
conditioned space.
31
Sources of Internal Heat Gain
Electric Motors
The motor use factor may be applied when motor use is known to be
intermittent with significant nonuse during all hours of operation (e.g.,
overhead door operator).
The motor load factor is the fraction of the rated load being delivered under
32
the conditions of the cooling load estimate
Sources of Internal Heat Gain
Electric Appliances
In a cooling load estimate, heat gain from all appliances (electrical, gas, or
steam) should be taken into account.
Because of the variety of appliances, applications, schedules, use, and
installations, estimates can be very subjective.
Often, the only information available about heat gain from equipment is that
on its nameplate.
The sensible heat gain of an electric appliance is
Qs = qinput ⋅ FL
where
qinput – energy input
FL – ratio of sensible heat gain to the manufacturer’s
rated energy input.
33
Sources of Internal Heat Gain
Infiltration Heat Gain
1. Total heat
= 1.2 ∙ ∙ ∆ℎ
where
34
Sources of Internal Heat Gain
Infiltration Heat Gain
2. Sensible heat
3. Latent heat
= 1.2 ∙ 2500 ∙ ∙∆
where
2500 kJ/kg is the approximate heat content of 50% relative
humidity vapour,
∆x – the change of humidity ratio
∆t – change of dry-bulb temperature, K
36
Latent Heat Gain from Moisture Diffusion
37
Cooling Load Calculation Methods
38
Cooling Load Calculation Methods
39
Cooling Load Calculation Methods
The heat balance (HB) method in which the calculation
procedures and scientific principles are explained in equation
format. These equations are coded in a generic computer program
named Hbfort, released with Cooling and Heating Load Calculation
Principles (Pedersen et al. 1998), and linked to a user interface
program to allow input and output in either inch-pound or SI units.
40
EN STANDARDS
41
Sensible load calculation of a space
(MSZ EN 15255)
The heat flow due to the solar radiation absorbed and the vault sky losses by the light
components (opaque and transparent; thickness ≤ 120 mm) :
l w
Φ sl = ∑ [ A ⋅ ( S f ⋅ I sr + qer ⋅ U / he )]k + ∑ [ A ⋅ ( S f 2 ⋅ lsr + qer ⋅ U / he )] j
k =1 j =1
where:
A - Area of surfaces [m2],
42
Sensible load calculation of a space
(MSZ EN 15255)
The heat flow due to the solar radiation absorbed and the vault sky losses by the opaque heavy
component ( thickness >120 mm) is given by:
h
Φ sh = ∑ [ A ⋅ ( S f ⋅ I sr + q er ⋅ U / he )] y
y =1
The solar radiation reaching the surface of the building envelope components is given by:
I sr = f s ⋅ I D + I d + I r
where
fs - the sunlit factor due to external obstructions, derived from EN ISO 13791;
ID - the direct component of the solar radiation reaching the surface;
Id - the diffuse component of the solar radiation reaching the surface;
Ir - the reflected component of the solar radiation reaching the surface.
43
Sensible load calculation of a space
(MSZ EN 15255)
Example to the instantaneous total solar radiation on the exposure of the wall (W/m2):
44
Latent load calculation of a space
(MSZ EN 15243)
For the cooling coil condensation, a simple model is used. It assumes that one part of the air
passing through the coil is not treated, and that the other part leaves at the dew point
characteristics of the cooling coil temperature. This latter air flow is called here recirculated
air flow. The caculation of recirculated air flow requirements depend on the type of the water
control.
45
Latent load calculation of a space
(MSZ EN 15243)
Recirculated air flow
Control 1. Nonvariable water flow:
In this case the cooled coil temperature is equal to the water inlet + 2K. The required
recirculated air flow depends on the sensible cooling need and the cooling coil temperature.
Qsens
q m, recirc =
c pa ⋅ ( 26 − θ sat )
where:
q m ,recirc = A f ⋅ 15 ⋅ ρ ai
where:
1. At the start of the hour, the indoor humidity is higher than the saturation humidity for the
cooling coil. The condensation will occur, either during the whole hour either during one
part of it.
2. At the beginning of the hour, the indoor humidity is lower than the saturation humidity for
the cooling coil. The cooling coil will be dry at the beginning, but condensation can occur
before the end of the hour.
47
Latent load calculation of a space
(MSZ EN 15243)
For a duration of t, indoor air humidity (at the end):
xi,moy is proportional with xi,fin according to the fact that the cooling coil is wet or dry at the
end of the hour.
49
Hungarian Standard for calculation of cooling load
(MSZ-04.140/4)
Calculation of outdoor heat load:
Components of outdoor heat load:
where:
Q& F - solar heat load through exterior building structures (wall, roof) into
the space,
where:
W
k - thermal transmittance of the wall or roof 2
m K
ahol
AÜ - surface of windows [m 2 ]
Z - reduction factor [-] (takes into account the heating capacity of building
envelope )
W
kÜ - thermal transmittance of the window 2
m K
51
THANK YOU
FOR
YOUR ATTENTION
Department of Building Service and Process Engineering
Miklos Kassai PhD., assistant professor
Building ”D”, Room 124
Tel: 463-2024; e-mail: [email protected] 52