Cooling Load Estimation Project: Lecturer: MR - Badran

1) The document estimates the cooling load of a 149m2 house with various rooms. It calculates load from the roof, walls, windows, lights, occupants, appliances, ventilation, and infiltration. 2) The total cooling load is estimated to be 4252.76W from the roof, over 20,000W from the walls, over 2500W from windows, 558W from lights, 738.75W from occupants, 5015W from appliances, 636.1W from ventilation, and 2522W from infiltration. 3) The document provides detailed calculations for estimating cooling load from each source using common formulas that take into account factors like U-value, surface area, temperature difference

Uploaded by

Edris Salam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views

Cooling Load Estimation Project: Lecturer: MR - Badran

1) The document estimates the cooling load of a 149m2 house with various rooms. It calculates load from the roof, walls, windows, lights, occupants, appliances, ventilation, and infiltration. 2) The total cooling load is estimated to be 4252.76W from the roof, over 20,000W from the walls, over 2500W from windows, 558W from lights, 738.75W from occupants, 5015W from appliances, 636.1W from ventilation, and 2522W from infiltration. 3) The document provides detailed calculations for estimating cooling load from each source using common formulas that take into account factors like U-value, surface area, temperature difference

Uploaded by

Edris Salam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 12

Duhok Polytechnic University

Technical College of Engineering


Refrigeration and Air-Conditioning Engineering Department

Refrigeration and Air-Conditioning Engineering

Cooling Load Estimation


Project
Students:Ajin Nawfal
Edris Salam
Lecturer: Mr.Badran
Date: 5-May-2018
Q/ Estimate the Cooling load capacity of a House of
149 m² showing in a figure below.

Page 1 of 11
located in Duhok /Kurdistan-Iraq

Plan Details

Livingroom: 33 m² Bathroom: 7 m²
Bedroom: 15 m² Bathroom: 4 m²
Bedroom: 17 m² Kitchen: 18 m²
Bedroom: 13 m² Hall: 14 m²
Porch: 9 m²

Page 2 of 11
1-ROOF CONSTRUCTION
𝐐 = 𝐔 ∗ 𝐀 ∗ (𝐂𝐋𝐓𝐃)𝐜𝐨𝐫𝐫𝐞𝐜𝐭𝐢𝐨𝐧

(CLTD)correction = [CLTD + LM] ∗ K + (25.5 − Tr) + (To − 29.4)


CLTD =19 -- From Table @152.4mm h.w concrete with25.4 insulation with suspended ceiling

U=0.71 -- From Table @152.4mm h.w concrete with25.4 insulation with suspended ceiling

LM=1.1 --From Table @32 latitude

K=1

Tr=22 -- minimum temperature

To=46 – maximum temperature

(CLTD)correction = [19 + 1.1] ∗ 1 + (25.5 − 22) + (46 − 29.4)

(CLTD)correction = 40.2

Q = 0.71 ∗ 149 ∗ 40.2

𝑸 = 𝟒𝟐𝟓𝟐. 𝟕𝟓𝟖 𝑾

Page 3 of 11
2-WALLS
A- not partition wall ( exposure wall)

Q = U ∗ A ∗ (CLTD)correction

(CLTD)correction = [CLTD + LM] ∗ K + (25.5 − Tr) + (To − 29.4)


LM from Table @32latitute
CLTD from table @ Group E WALLS
U =3.32 from Table @ H.W. concrete wall + finish .. 101.6 mm concrete

Direction wall Area CLTD LM


NORTH WALL 13.85*3 12 0.5
South WALL 13.85*3 19 6.6
EAST WALL 12.02*3 21 0
West WALL 12.02*3 27 0

I) NORTH WALL
(CLTD)correction = [12 + 0.5] ∗ 1 + (25.5 − 22) + (46 − 29.4)

(CLTD)correction = 32.6

Q = 3.32 ∗ (13.85 ∗ 3) ∗ 32.6

𝑸 = 𝟒𝟒𝟗𝟕. 𝟎𝟑𝟗𝟔 𝑾

II) SOUTH WALL


(CLTD)correction = [19 + 6.6] ∗ 1 + (25.5 − 22) + (46 − 29.4)
(CLTD)correction = 45.7
Q = 3.32 ∗ (13.85 ∗ 3) ∗ 45.7
𝑸 = 𝟔𝟑𝟎𝟒. 𝟏𝟑𝟐𝟐 𝑾

III) EAST WALL


(CLTD)correction = [21 + 0] ∗ 1 + (25.5 − 22) + (46 − 29.4)

(CLTD)correction = 41.1

Q = 3.32 ∗ (12.02 ∗ 3) ∗ 41.1

𝑸 = 𝟒𝟗𝟐𝟎. 𝟒𝟓𝟗𝟏𝟐 𝑾

Page 4 of 11
IV) West WALL
(CLTD)correction = [27 + 0] ∗ 1 + (25.5 − 22) + (46 − 29.4)

(CLTD)correction = 47.1

Q = 3.32 ∗ (12.02 ∗ 3) ∗ 47.1

𝑸 = 𝟓𝟔𝟑𝟖. 𝟕𝟕𝟒𝟑𝟐 𝑾

3-GLASSES
A- Conduction

𝐐 = 𝐔 ∗ 𝐀 ∗ 𝐂𝐋𝐓𝐃
CLTD=8 From Table
U=1

4 windows 1.5*1.5

Q = 1 ∗ (1.5 ∗ 1.5) ∗ 8

𝑸𝟏 = 𝟏𝟖 𝑾for each window *4 windows

𝑸𝟏 = 𝟏𝟖 ∗ 𝟒 = 𝟕𝟐 𝑾
3 windows 1.5*1.1

Q = 1 ∗ (1.5 ∗ 1.1) ∗ 8

𝑸𝟐 = 𝟏𝟑. 𝟐 𝑾for each window *3 windows

𝑸𝟐 = 𝟏𝟑. 𝟐 ∗ 𝟑 = 𝟑𝟗. 𝟔 𝑾
3 windows 1.5*0.5
Q = 1 ∗ (1.5 ∗ 0.5) ∗ 8

𝑸𝟑 = 𝟔 𝑾for each window *3 windows

𝑸𝟑 = 𝟔 ∗ 𝟑 = 𝟏𝟖 𝑾

QTotal = Q1 + Q2 + Q3

𝑸𝑻𝒐𝒕𝒂𝒍 = 𝟕𝟐 + 𝟑𝟗. 𝟔 + 𝟏𝟖 = 𝟏𝟐𝟖. 𝟔 𝑾

Page 5 of 11
B-Solar:
Q = A ∗ SC ∗ SHFG ∗ CLF
SC=0.92From Table @ 10mm Clear
SHFG From Table
CLF From Table

Direction OF GLASSES Area SHFG CLF


NORTH GLASSES 2(1.5*1.5)+(1.1*1.5) 148 0.91
EAST GLASSES 2(1.1*1.5) 710 0.8
South GLASSES 2(1.5*1.5)+2(0.5*1.5) 801 0.83

I) NORTH GLASSES

Q = (No. of windows ∗ A) ∗ SC ∗ SHFG ∗ CLF

Q = {(1.1 ∗ 1.5) + (2 ∗ 1.5 ∗ 1.5 )} ∗ 0.92 ∗ 148 ∗ 0.91

𝑸 = 𝟕𝟔𝟐. 𝟎𝟏𝟗𝟒𝟒 𝑾
II) EAST GLASSES

Q = A ∗ SC ∗ SHFG ∗ CLF *NO.OF WINDOWS

Q = (2 ∗ 1.1 ∗ 1.5) ∗ 0.92 ∗ 710 ∗ 0.8

𝑸 = 𝟏𝟕𝟐𝟒. 𝟒𝟒𝟖 𝑾
III) SOUTH GLASSES

Q = A ∗ SC ∗ SHFG ∗ CLF *NO.OF WINDOWS

Q = ((2 ∗ 1.5 ∗ 1.5) + (2 ∗ 0.5 ∗ 1.5)) ∗ 0.92 ∗ 801 ∗ 0.83

𝑸 = 𝟑𝟔𝟔𝟗. 𝟖𝟔𝟏𝟔 𝑾

Page 6 of 11
4-LIGHTS:
𝑄 = 𝑁𝑂. 𝑂𝐹𝐿𝐼𝐺𝐻𝑇𝑆 ∗ 𝑊𝐴𝑇𝑇𝐴𝐺𝐸 ∗ 𝐶𝐿𝐹
No.of light=15

CLF=0.93 From Table 17A

𝑄 = 15 ∗ 40 ∗ 0.93

𝑸 = 𝟓𝟓𝟖 𝑾

5-PEOPLE :
I) Sensible heat

𝑄𝑠 = 𝑁𝑂. 𝑂𝐹𝑃𝐸𝑂𝑃𝐿𝐸 ∗ 𝑆𝑒𝑛𝑠. 𝐻𝐺 ∗ 𝐶𝐿𝐹


No. of People=5
Sens.HG=75 From Table 18
CLF=0.97 From Table 19

𝑄𝑠 = 5 ∗ 75 ∗ (0.97)

𝑸𝒔 = 𝟑𝟔𝟑. 𝟕𝟓 𝑾
II) Latent heat

𝑄𝑙 = 𝑁𝑂. 𝑂𝐹𝑃𝐸𝑂𝑃𝐿𝐸 ∗ 𝐿𝑎𝑡𝑒𝑛𝑡. 𝐻𝐺


No. of people=5

Latent.HG=75 From Table 19

𝑄𝑙 = 5 ∗ 75

𝑸𝒍 = 𝟑𝟕𝟓 𝑾

Page 7 of 11
6-APPLIANCE:
I) Sensible heat

𝑄𝑠 = 𝑁𝑂. 𝑂𝐹𝐴𝑃𝑃𝐴𝑅𝐴𝑇𝑈𝑆 ∗ 𝑆𝑒𝑛𝑠. 𝐻𝐺 ∗ 𝐶𝐿𝐹


NO.of App=10
Sens.HG=550 From Table 21
CLF=0.73 From Table 22

𝑄𝑠 = 10 ∗ 550 ∗ (0.73)

𝑸𝒔 = 𝟒𝟎𝟏𝟓 𝑾
II) Latent heat

𝑄𝑙 = N𝑂. 𝑂𝐹𝐴𝑃𝑃𝐴𝑅𝐴𝑇𝑈𝑆 ∗ 𝐿𝑎𝑡𝑒𝑛𝑡. 𝐻𝐺


NO.of App=10
Latent.HG=100 From Table 21

𝑄𝑠 = 10 ∗ 100

𝑸𝒔 = 𝟏𝟎𝟎𝟎 𝑾

Page 8 of 11
7-VENTILATION
L/S/PERSON

𝐋/𝐬
𝑽̇𝒇 = 𝑵𝑶. 𝑶𝑭𝑷𝑬𝑹𝑺𝑶𝑵 ∗
𝑷𝑬𝑹𝑺𝑶𝑵
ṁ𝒇 = 𝑽̇ ∗ 𝝆

No.of Person=5
L/s/Person =3.5 from Table 6.1
Ρ=1.2 Kg/m3
Cp=1.022 Kj/Kg*C

𝑳 𝒎𝟑
𝑽̇𝒇 = 𝟓 ∗ 𝟑. 𝟓 = 𝟏𝟕. 𝟓 = 𝟎. 𝟎𝟏𝟕𝟓
𝑺 𝒔
𝒌𝒈
ṁ𝒇 = 𝟎. 𝟎𝟏𝟕𝟓 ∗ 𝟏. 𝟐 = 𝟎. 𝟎𝟐𝟏
𝒔

1) Sensible heat

𝑄𝑠 = ṁ𝒇 ∗ 𝐶𝑃𝑚 ∗ ∆𝑇

𝑄𝑠 = 𝟎. 𝟎𝟐𝟏 ∗ 1.022 ∗ (46 − 22)

𝑸𝒔 = 𝟎. 𝟓𝟏𝟓𝟏 𝑲𝑾 = 𝟓𝟏𝟓. 𝟏𝑾
2) Latent heat

𝑄𝑙 = ṁ𝒇 ∗ ℎ𝑓𝑔 ∗ ∆𝑊

Hfg=2500 kj/kg
w2=0.011 from psychrometric chart
w1=0.0087 from psychrometric chart

𝑄𝑙 = 𝟎. 𝟎𝟐𝟏 ∗ 2500 ∗ (0.011 − 0.0087)

𝑸𝒍 = 𝟎. 𝟏𝟐𝟏 𝑲𝑾 = 𝟏𝟐𝟏 𝑾
3) Total

𝑄𝑡 = 𝑄𝑠 + 𝑄𝑙
𝑄𝑡 = 515.1 + 121

𝑸𝒕 = 𝟔𝟑𝟔. 𝟏 𝑾
Page 9 of 11
8-INFILTRATION
ACH (AIR CHANGE PER HOUR)

𝑽̇𝒇 = 𝑨𝑪𝑯 ∗ 𝑽𝑶𝑳𝑼𝑴𝑬

ṁ𝒇 = 𝑽̇ ∗ 𝝆

ACH=0.69 From Table 62

Volume=Area*L=149*3

Ρ=1.2 Kg/m3

Cp=1.022 Kj/Kg*C

𝟏𝟒𝟗 ∗ 𝟑 𝐦𝟑
𝑽̇𝒇 = 𝟎. 𝟔𝟗 ∗ ( ) = 𝟎. 𝟎𝟖𝟓𝟕 = 𝟖𝟓. 𝟕 𝐋/𝐬
𝟑𝟔𝟎𝟎 𝐬

ṁ𝐟 = 𝟎. 𝟎𝟖𝟓𝟕 ∗ 𝟏. 𝟐 = 𝟎. 𝟏𝟎𝟑 𝐤𝐠/𝐬

I) Sensible heat

Qs = ṁ𝐟 ∗ CPm ∗ ∆T
Qs = 𝟎. 𝟏𝟎𝟑 ∗ 1.022 ∗ (46 − 22)

𝑸𝒔 = 𝟐. 𝟓𝟐𝟐 𝑲𝑾 = 𝟐𝟓𝟐𝟐𝑾
II) Latent heat

Ql = ṁ𝐟 ∗ hfg ∗ ∆W
Ql = 𝟎. 𝟏𝟎𝟑 ∗ 2500 ∗ (0.011 − 0.0087)

𝑸𝒍 = 𝟎. 𝟓𝟗𝟐𝟐 𝑲𝑾 = 𝟓𝟗𝟐. 𝟐 𝑾
III) Total
Qt = Qs + Ql

Qt = 2522 + 592.2

𝑸𝒕 = 𝟑𝟏𝟏𝟒. 𝟐 𝑾

Page 10 of 11
Results Table

add 8%
Total Total Total heat gain
Q sensible Q latent for factor
ITEM heat heat gain Refrigeration
(W) (W) of safity
gain (W) (KW) Tons (RT)
(R.T)

Roof 4253 0 4253 4.253 1.209321 1.30607


Wall north 4497 0 4497 4.497 1.278701 1.381
Wall east 4921 0 4921 4.921 1.399264 1.5112
Wall south 6305 0 6305 6.305 1.792798 1.93622
Wall west 5639 0 5639 5.639 1.603424 1.7317
Glass conduction 129 0 129 0.129 0.03685 0.03808
Glass solar north 762 0 762 0.762 0.216671 0.234
Glass solar east 1725 0 1725 1.725 0.490496 0.52974
Glass solar south 3700 0 3700 3.7 1.052078 1.13624
Lights 558 0 558 0.558 0.158665 0.17136
People 364 375 739 0.739 0.210131 0.22694
Appliance 4015 1000 5015 5.015 1.425992 1.54007
Ventilation (L/s) 515 121 636 0.636 0.180844 0.19531
Infiltration 2522 593 3115 3.115 0.885736 0.95659
TOTAL 39900 2089 41989 41.989 11.9394 12.8945