00 Hvac Calc
00 Hvac Calc
WARNING: This spreadsheet contains rules of thumb and should be used for estimating only
Press Ventilation Rate, Sizing of Heating & Cooling Loads Press Psychrometric Chart
Press Duct Sizing & Estimation of System Pressure Loss Press Psychrometric Calcs
Press Fan Laws, Changes to Fan Duty Press Conversions
Press Sizing Pressure Relief Outlets, Door Air Loss Press Natural Ventilation by Temp Diff.
Press Duct Weight & Flange Drilling Press Load Estimate Sheet
Press Pressure Loss Spreadsheet Press Date Plan Set Up
Press Sound Attenuation Spreadsheet Press U Values
Press Preliminary Pipe Sizing Press Hygrometric Sheet
Press Air Leakage Test Sheet Press Process
Press Module Temperature Press Noise Addition
<<<Back
ENTER ANSWER
ENTER
Velocity Pressure
ENTER
1768 x 1768
1995 Dia.
38.4 Pa
0 Pa
9615 Pa
ANSWER
2406 mm dia.
<<<Back
ENTER
Original System Data
Fan Volume 2.78 m3/s (If you don't know the fan power, it should
Fan Pressure 600 Pa be around………. 2.1 kW)
Fan Speed 1350 rpm
Fan Power 2 kW Fan Effy.% = {Vol (m3/s) x Total Press. (Pa)} ÷ (Abs. Power (W) x 10)
78.0
CHANGE NEW
Supply
Plenum Exit 250 x 250 282 0.350 5.60 18.8 4.30 80.9
Duct 400 x 400 451 0.525 3.28 6.5 15.0 3.4
Fire Damper 400 x 400 451 0.525 3.28 6.5 0.50 3.2
Bend 400 x 400 451 0.525 3.28 6.5 0.35 2.3
Bend 400 x 400 451 0.525 3.28 6.5 0.35 2.3
Bend 400 x 400 451 0.525 3.28 6.5 0.35 2.3
Bend 400 x 400 451 0.525 3.28 6.5 0.35 2.3
Bend 400 x 400 451 0.525 3.28 6.5 0.35 2.3
VCD 400 x 400 451 0.525 3.28 6.5 0.27 1.7
Supply Grille OBD 400 x 400 451 0.525 3.28 6.5 0.52 3.4
Supply Grille 400 x 400 451 0.525 3.28 6.5 1.50 9.7
x
Supply Total 113.7
Margin 10% 11.4
Total 125
Exhaust
Exhaust EC Grille 400 x 400 451 0.525 3.28 6.5 2.00 12.9
Duct 300 x 300 339 0.525 5.83 20.4 4.2 4.0
Pressure Relief Damper 300 x 300 339 0.525 5.83 20.4 2.30 47.0
Fire Damper 300 x 300 339 0.525 5.83 20.4 0.20 4.1
Bend 300 x 300 339 0.525 5.83 20.4 1.0 1.0
Bend 300 x 300 339 0.525 5.83 20.4 1.0 1.0
Bend 300 x 300 339 0.525 5.83 20.4 1.0 1.0
Fire Damper 300 x 300 339 0.525 5.83 20.4 0.20 4.1
Plenum Entry 300 x 300 339 0.525 5.83 20.4 0.33 6.7
Plenum Outlet 450 x 200 339 0.525 5.83 20.4 0.23 4.7
Duct 450 x 200 339 0.525 5.83 20.4 6.9 6.7
30o Bend 450 x 200 339 0.525 5.83 20.4 0.41 8.4
30o Bend 450 x 200 339 0.525 5.83 20.4 0.41 8.4
Duct 350 x 250 334 0.525 6.00 21.6 11.9 12.4
C/S (450x200) x (350x250) 350 x 250 334 0.525 6.00 21.6 0.02 0.4
Bend 350 x 250 334 0.525 6.00 21.6 0.35 7.6
Bend 350 x 250 334 0.525 6.00 21.6 0.35 7.6
45o Bend 350 x 250 334 0.525 6.00 21.6 0.18 3.9
45o Bend 350 x 250 334 0.525 6.00 21.6 0.18 3.9
TEXACO CAPTAIN
ADDITIONAL ESP DRIVES FOR ESP SWITCHROOM
CIBSE
OPTION 1 - USING
SEAWATER COOLING COIL
COOLING LOAD =
5.25 x (51.5 - 39.3)/0.8255 = 77.6kW
EXISTING PRE-COOLER
AIR ON AT 23OC/75%rh
OFF AT 18OC/95%rh
DISCHARGE TO
ATMOSPHERE
DUCT GAIN =1OC. TEMP. RISE DUE TO TEMP. RISE DUE TO NEW TEMP. RISE DUE TO EXISTING PANELS' 102kW HEAT
SUPPLY TO ROOM AT 15OC. EQUIPMENT 22kW PANELS' 52.22kW GAIN = 16.68OC.
HEAT GAIN = 3.46OC. HEAT GAIN = 8.22OC.
<<<Back
ENTER
Flange Drilling
Duct Width 150 Duct Backmark
Duct Height 150 mm Side See Note
OR Duct Dia. 200 mm 150 40
Metal Thickness 3 mm 150 40
Spool Length 60 m Backmark: Distance from the outer edge of flange to corn
Remnant: Distance between corner hole and first pitch ho
Flanges: 12 No
Angle size 80 mm Duct Weight (Rectangular)
Flg. Thickness 5 mm Item Material
m3
Duct 0.108
Density of Material 7840 kg/m3 Flanges 0.0096
(Mild Steel 7840 kg/m3) Duct Weight (Circular)
(St/St 7900 kg/m3) Duct Dia. Area m2
200 1.88571429
150mm pitches 1 1
covering 150 150
fill 40 40
M8
Amended 150 pitches 0 0 M10
Amended covering 0 0 M12
Amended fill 115 115
Holes 4 4
Remnant Pitches @ Holes /
See Note 150mm Bolts
115 0 8
115 0 M12
t (Rectangular)
Weight Total
kg kg
846.7
75.3 922.0
Vol. m3 Weight kg
0.00565714 44.4
<<< Back
Air Mix
Heatin 1 Q1 Q2 Q3
Cooling
g
in Airflow 3.433 2.456 5.889 m3/s
Airflow 5.889 m3/s Mix % 58.30 41.l7 100 %
Sp Vol 0.85 m3/kg Sp Enthalpy 46.00 59.80 #VALUE! KJ/kg
High Low M.Content 0.0115 0.0100 #VALUE! kg/kg
Specific Enthalpy 129.40 99.98 KJ/kg Temperature 23.00 23.00 #VALUE! O
C
Moisture Content 0.0367 0.0273 kg/kg
HEATING
Sensible Heating 56.46 kW
Humidification 147.37 kW
Total Change 203.83 kW
Moisture Added 0.0653 l/s
<<< Back
-
DATE:-
DATE:-
DATE:-
SUMMER HEAT
TEMP DIFF OC GAIN, W.
- -
14 180.32
15 789.45
14 140
14 0
14 224
14 560
0
1893.77
HEAT GAIN,
TEMP DIFF OC
W.
22.6 542
6.5 0
22.6 291
0 0
22.2 888
22.2 0
0 0
1721
EAT GAIN SUMMARY
ITEM GAIN, W.
MITTANCE. 1894
1721
140
1040
9411
14206
160
14366
ITEM 32/ITEM 34) % 98.89%
LY AIR TEMP. C
O
11
PLY AIR TEMP.OC 10
PLY AIR TEMP. RISE OC 10
INARY S.A.V. (m3/s) 1.19
AIN = SAVx1.21x 2OC, W 2886
6098
NG LOAD, W
14366
2886
COOLING LOAD, W. 17252
COOLING LOAD, T.R. 4.91
Air Changes per hour = 1.28
alues and other Design Data
levant C.I.B.S.E. Guide.
<<<Back
ENTER
Imperial to Metric
N/m2
"wg
mm wg
"hg
mm hg
psi
torr
m.bar
bar
Start Date: 22-Oct-01 Days freq. 1
22-Oct-01
27-Oct-01
28-Oct-01
23-Oct-01
24-Oct-01
25-Oct-01
26-Oct-01
29-Oct-01
30-Oct-01
31-Oct-01
1-Nov-01
2-Nov-01
ACTIVITIES
Date
Ref
31 1 2 3 4 5 6 7 8 9 10 11
Sa
6
12
13
3-Nov-01
12
<<<Back
CALCULATION OF THERMAL TRANSMITTANCE (U-VALUE) W
GO TO 'k' Factors>>>
HEAT FLOW
HORIZ. UP DOWN
Rsi 0.13 0.1 0.17
Rso 0.04 0.04 0.04
Rsi+Rso 0.17 0.14 0.21
R air gap 0.18 0.12 0.12
R total 0.52 0.4 0.54
L1 (m) 0.005 0.005 0.005
K1 50 50 50
L2 (m) 0.1 0.1 0.1
K2 0.057 0.057 0.057
L3 (m) 0.05 0.05 0.05
K3 0.026 0.026 0.026
L4 (m) 0.015 0.015 0.015
K4 0.16 0.16 0.16
N.B:- Enter 'k' from table below.
Where no material is used enter L=0 & K=1.
U-value =
0.243 0.248 0.244
(W/m2oC)
Walls Roofs
Brick 0.84 Asphalt
Dense Plaster 0.5 Concrete
Lightweight Plaster 0.16 Lightw't Concrete
Plasterboard 0.16 Dense Plaster
Exp. Polystyrene 0.033 Lightweight Plaster
Lightw't Concrete 0.38 Concrete
Concrete 1.4 Phenolic Foam
Concrete Block 0.19 Fibreboard
Asbestos Sheet 0.36 Exp. Polystyrene
Woodwool Slab 0.09 Tiles
Glass Fibre 0.035 Roofing Felt
Timber 0.14 Glass Fibre
Weatherboarding 0.14 Asbestos Sheet
Air 0.026 Slate
Miscellaneous Materials
Bitumen 0.85 Granite
Carpet - woollen 0.055 Wood Chipboard
Carpet Underlay 0.045 Woodwool Slab
Corkboard 0.042 Water
Glass Sheet 1.05 Seawater
Gravel 0.3 Carbon Steel
Hardboard 0.08 High Alloy Steel
PVC Flooring 0.35 Fresh Snow
Phenolic Foam 0.037 Compacted Snow
TANCE (U-VALUE) W/m2oC)
Wall
(Enter description)
Thickness K value
(Enter description) (mm) (W/moC)
Steel Cladding L1 5 50
Fibre Board Slabs L2 100 0.057
L3 0 1
Plasterboard L4 15 0.16
U Value Heat Flow (W/m2oC)
Horiz. 0.495
Up 0.503
Down 0.486
HEAT FLOW
HORIZ. UP DOWN
Rsi 0.13 0.1 0.17
Rso 0.04 0.04 0.04
Rsi+Rso 0.17 0.14 0.21
R air gap 0 0 0
R total 0.34 0.28 0.42
L1 (m) 0.005 0.005 0.005
K1 50 50 50
L2 (m) 0.1 0.1 0.1
K2 0.057 0.057 0.057
L3 (m) 0 0 0
K3 1 1 1
L4 (m) 0.015 0.015 0.015
K4 0.16 0.16 0.16
N.B:- Enter 'k' from table below.
Where no material is used enter L=0 & K=1.
U-value =
0.495 0.503 0.486
(W/m2oC)
0.9
1.4
Lightw't Concrete 0.38
Dense Plaster 0.5
Lightweight Plaster 0.1
0.16
Phenolic Foam 0.038
0.057
Exp. Polystyrene 0.033
0.84
Roofing Felt 0.19
0.035
Asbestos Sheet 0.36
2
2.5
Wood Chipboard 0.15
Woodwool Slab 0.11
0.6
0.58
Carbon Steel 50
High Alloy Steel 15
0.17
Compacted Snow 0.43
1
HYGROMETRIC TABLES
FOR ANY GIVEN TEMPERATURE, ENTER A HUMIDITY VALUE TO DETERMINE RELEVANT PSYCHROMETRIC DATA
Back
HVAC Process
Energy Change 85 kW
m3/s -85
5.25 kW Total
Inlet Condition Fan Cooling
20 C (db)
84 % rh
kW
-38.3 Sensible Cooling
0.01239 kg/kg Moisture Content -46.71 Latent Cooling
0.84664 m3/kg Specific Volume
51.70450 kJ/kg Specific Enthalpy
0.01475 kg Specific Moisture Conteny -58.88
20.11000 kJ/kg Enthalpy Dry air ### Water Removed
23.37000 Pa Saturated Vapour Pressure
###
Outlet Condition
14 C (db)
95 % rh
Sensible Cooling
Latent Cooling 0.00951 kg/kg
0.82554 m3/kg
38.32923 kJ/kg
kg/h 0.01001 kg
Water Removed 14.08000 kJ/kg
15.98000 Pa
HYGROMETRIC TABLES
15
15
20
20
25
32
32
40
50
1.5 ea
7.5 each
10 each
4 ea
only
JOB NO.
MODULE INTEGRITY LOCATION
TEST RESULTS DATE
TEST BY
WITNESS
The following data is used to calculate the actual leakage rate for the module
Volume of Module =
MEASURED RESULTS
Comments:
r hour (ac/h)
548.00 m3
109.60 m3/h
0.030 m3/s)
109.60 m3/h
110.40 m3/h
108.20 m3/h
109.30 m3/h
<<Back
Accommodation Module
20.00
10.00
5.00
0.00
40
To 10 degC
Gains 58.35 kW (kj/s)
35
30
25
20
15
10
1
8 6
55 5
2
9 5
5 3 4Minutes
6 4 To
0 4
Module heat Surplus Module heat 7 4 Surplus 5
34 3
Loss Energy 1
Loss
3 Energy
28
kj kj 2 25 kj kj
2
19
0 3 16
0 1
7 1
30
1
(To) Temp Outside991.07 2509.93 788.24 2712.76
1003.60 2497.40 801.78 2699.22
1016.07 2484.93 815.25 2685.75
1028.47 2472.53 828.66 2672.34
1040.81 2460.19 842.00 2659.00
1053.09 2447.91 855.27 2645.73
1065.31 2435.69 868.48 2632.52
1077.47 2423.53 881.62 2619.38
1089.57 2411.43 894.70 2606.30
1101.61 2399.39 907.71 2593.29
1113.58 2387.42 920.65 2580.35
1125.50 2375.50 933.53 2567.47
1137.36 2363.64 946.35 2554.65
1149.16 2351.84 959.10 2541.90
1160.90 2340.10 971.79 2529.21
1172.58 2328.42 984.41 2516.59
1184.20 2316.80 996.98 2504.02
1195.77 2305.23 1009.48 2491.52
1207.27 2293.73 1021.91 2479.09
1218.72 2282.28 1034.29 2466.71
1230.12 2270.88 1046.60 2454.40
1241.45 2259.55 1058.85 2442.15
1252.73 2248.27 1071.04 2429.96
1263.95 2237.05 1083.17 2417.83
1275.12 2225.88 1095.24 2405.76
1286.23 2214.77 1107.25 2393.75
1297.29 2203.71 1119.20 2381.80
1308.29 2192.71 1131.09 2369.91
1319.23 2181.77 1142.92 2358.08
1330.12 2170.88 1154.69 2346.31
1340.96 2160.04 1166.40 2334.60
1351.74 2149.26 1178.06 2322.94
1362.47 2138.53 1189.65 2311.35
1373.15 2127.85 1201.19 2299.81
1383.77 2117.23 1212.67 2288.33
1394.34 2106.66 1224.09 2276.91
1404.85 2096.15 1235.46 2265.54
1415.31 2085.69 1246.77 2254.23
1425.73 2075.27 1258.02 2242.98
1436.09 2064.91 1269.22 2231.78
1446.39 2054.61 1280.36 2220.64
1456.65 2044.35 1291.44 2209.56
1466.85 2034.15 1302.47 2198.53
1477.01 2023.99 1313.44 2187.56
1487.11 2013.89 1324.36 2176.64
1497.16 2003.84 1335.23 2165.77
1507.17 1993.83 1346.04 2154.96
1517.12 1983.88 1356.80 2144.20
1527.02 1973.98 1367.50 2133.50
1536.88 1964.12 1378.15 2122.85
1546.68 1954.32 1388.75 2112.25
1556.44 1944.56 1399.29 2101.71
1566.14 1934.86 1409.78 2091.22
1575.80 1925.20 1420.22 2080.78
1585.41 1915.59 1430.61 2070.39
1594.97 1906.03 1440.94 2060.06
1604.49 1896.51 1451.23 2049.77
1613.95 1887.05 1461.46 2039.54
1623.37 1877.63 1471.64 2029.36
61
58
3949.47
3929.76
3910.14
3890.62
3871.20
3851.88
3832.65
3813.52
3794.48
3775.54
3756.69
3737.94
3719.28
3700.72
3682.24
3663.86
3645.57
3627.38
3609.27
3591.25
3573.33
3555.49
3537.74
3520.08
3502.51
3485.03
3467.63
3450.32
3433.10
3415.96
3398.91
3381.94
3365.06
3348.26
3331.55
3314.92
3298.37
3281.91
3265.52
3249.22
3233.00
3216.87
3200.81
3184.83
3168.93
3153.11
3137.38
3121.71
3106.13
3090.63
3075.20
3059.85
3044.57
3029.38
3014.25
2999.21
2984.24
2969.34
2954.52
2939.77
Minutes 0 5 10 15 20 25 30
0 24 24 24 24 24 24 24
1 24.31 24.33 24.36 24.38 24.41 24.43 24.46
2 24.62 24.67 24.72 24.77 24.82 24.87 24.91
3 24.92 25.00 25.07 25.15 25.22 25.29 25.37
4 25.23 25.33 25.42 25.52 25.62 25.72 25.82
5 25.53 25.65 25.78 25.90 26.02 26.15 26.27
6 25.83 25.98 26.13 26.27 26.42 26.57 26.72
7 26.13 26.30 26.47 26.65 26.82 26.99 27.16
8 26.43 26.62 26.82 27.02 27.21 27.41 27.61
9 26.72 26.94 27.17 27.39 27.61 27.83 28.05
10 27.02 27.26 27.51 27.75 28.00 28.24 28.48
11 27.31 27.58 27.85 28.12 28.38 28.65 28.92
12 27.61 27.90 28.19 28.48 28.77 29.06 29.35
13 27.90 28.21 28.53 28.84 29.16 29.47 29.79
14 28.19 28.52 28.86 29.20 29.54 29.88 30.22
15 28.47 28.84 29.20 29.56 29.92 30.28 30.64
16 28.76 29.15 29.53 29.92 30.30 30.68 31.07
17 29.05 29.45 29.86 30.27 30.68 31.08 31.49
18 29.33 29.76 30.19 30.62 31.05 31.48 31.91
19 29.61 30.07 30.52 30.97 31.43 31.88 32.33
20 29.89 30.37 30.85 31.32 31.80 32.27 32.75
21 30.17 30.67 31.17 31.67 32.17 32.67 33.16
22 30.45 30.97 31.49 32.01 32.54 33.06 33.58
23 30.73 31.27 31.81 32.36 32.90 33.44 33.99
24 31.00 31.57 32.13 32.70 33.27 33.83 34.40
25 31.28 31.86 32.45 33.04 33.63 34.22 34.80
26 31.55 32.16 32.77 33.38 33.99 34.60 35.21
27 31.82 32.45 33.08 33.72 34.35 34.98 35.61
28 32.09 32.74 33.40 34.05 34.70 35.36 36.01
29 32.36 33.03 33.71 34.38 35.06 35.74 36.41
30 32.63 33.32 34.02 34.72 35.41 36.11 36.81
31 32.89 33.61 34.33 35.05 35.76 36.48 37.20
32 33.16 33.90 34.64 35.37 36.11 36.85 37.59
33 33.42 34.18 34.94 35.70 36.46 37.22 37.99
34 33.68 34.46 35.24 36.03 36.81 37.59 38.37
35 33.94 34.74 35.55 36.35 37.15 37.96 38.76
36 34.20 35.02 35.85 36.67 37.50 38.32 39.15
37 34.46 35.30 36.15 36.99 37.84 38.68 39.53
38 34.71 35.58 36.45 37.31 38.18 39.04 39.91
39 34.97 35.86 36.74 37.63 38.52 39.40 40.29
40 35.22 36.13 37.04 37.95 38.85 39.76 40.67
41 35.48 36.40 37.33 38.26 39.19 40.11 41.04
42 35.73 36.68 37.62 38.57 39.52 40.47 41.42
43 35.98 36.95 37.91 38.88 39.85 40.82 41.79
44 36.23 37.22 38.20 39.19 40.18 41.17 42.16
45 36.48 37.48 38.49 39.50 40.51 41.52 42.52
46 36.72 37.75 38.78 39.81 40.83 41.86 42.89
47 36.97 38.02 39.06 40.11 41.16 42.21 43.26
48 37.21 38.28 39.35 40.41 41.48 42.55 43.62
49 37.45 38.54 39.63 40.72 41.80 42.89 43.98
50 37.70 38.80 39.91 41.02 42.12 43.23 44.34
51 37.94 39.06 40.19 41.32 42.44 43.57 44.69
52 38.18 39.32 40.47 41.61 42.76 43.90 45.05
53 38.41 39.58 40.74 41.91 43.07 44.24 45.40
54 38.65 39.83 41.02 42.20 43.39 44.57 45.75
55 38.89 40.09 41.29 42.50 43.70 44.90 46.10
56 39.12 40.34 41.57 42.79 44.01 45.23 46.45
57 39.35 40.60 41.84 43.08 44.32 45.56 46.80
58 39.59 40.85 42.11 43.37 44.63 45.88 47.14
59 39.82 41.10 42.37 43.65 44.93 46.21 47.49
60 40.05 41.34 42.64 43.94 45.24 46.53 47.83
35
24
24.48
24.96
25.44
25.92
26.39
26.87
27.33
27.80
28.27
28.73
29.19
29.65
30.10
30.55
31.01
31.45
31.90
32.34
32.79
33.23
33.66
34.10
34.53
34.96
35.39
35.82
36.24
36.67
37.09
37.50
37.92
38.33
38.75
39.16
39.56
39.97
40.37
40.78
41.18
41.57
41.97
42.36
42.75
43.14
43.53
43.92
44.30
44.69
45.07
45.44
45.82
46.20
46.57
46.94
47.31
47.68
48.04
48.40
48.77
49.13
<<<back Airflow due to temperature difference (CIBSE A4-6)
Enter
40 A1 0.036 m2
A1 A3 A3 0.080 m2
ti to A2 0.036 m2
31 18 A4 0.070 m2
A2 A4 ha 1.50 m
22 Cd 0.61 f
m3/s Th 40 deg C
Qb displaced air is 0.054 Tl 22 deg C
to 18 deg C
at outlet m3/s kW
A1 0.017 0.448 13
A3 0.037 0.995 24.5
1.443 0.07825025
Area of top opening
Area of top opening
ti - to
(ti + to) / 2
Ab
<<< Back
75 65 59 53 50 47 45 43
Antilog Lp/10 79432.82347243 79432.82347243 100000 100000 100000 63095.73444802 39810.71705535 15848.93192461