0% found this document useful (0 votes)
303 views

ACCC Midal Data (Imperial Units) PDF

This document provides technical specifications for two energy efficient overhead conductors: Linnet and Hawk. It lists details such as conductor type and code, nominal aluminum area, cross sectional areas, diameters, masses, resistances, lay ratios, stranding configurations, thermal properties, ampacities and more. The conductors use concentric lay stranded trapezoidal aluminum wires around a composite core to provide high conductivity and current capacity while maintaining efficiency and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
303 views

ACCC Midal Data (Imperial Units) PDF

This document provides technical specifications for two energy efficient overhead conductors: Linnet and Hawk. It lists details such as conductor type and code, nominal aluminum area, cross sectional areas, diameters, masses, resistances, lay ratios, stranding configurations, thermal properties, ampacities and more. The conductors use concentric lay stranded trapezoidal aluminum wires around a composite core to provide high conductivity and current capacity while maintaining efficiency and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : LINNET

Conductor Type & Code ACCC - Linnet


2
(431 kcmil/219 mm )
Nominal equivalent Aluminum Area 449.2 kcmil
Cross Sectional Area - Aluminum 435.48 kcmil
Cross Sectional Area - CTC Core 0.043 sq.in
Total Area of Cross Section- conductor 0.385 sq.in
Overall Diameter of Conductor 0.72 in
Mass per Unit length - Aluminum 410 lb/kft
Mass per Unit length - Core 36 lb/kft
Mass per unit length - Conductor 446 lb/kft
Rated Strength of the Conductor * 16370 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.2073 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 7.921 in Max. single length /Drum 13480 ft ( 4110 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.235 in
o
No. of Aluminum Layers 2 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.142 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.151 in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.121 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0159 sq.in
Composite Core Layer-2 0.0179 sq.in
Conductivity Nil
Rated Breaking Load 13579 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 19.12 x10-6 /oC below thermal knee point 10.69 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
1200
Rated ampacity at max. temperature ^ 956 Amp. Imax (Amp)

AC Resistance at max. operating temp. 0.3372 Ω/mile 1000

Calculated max. ampacity at 120 Deg.C ^ 806 Amp. 800


Calculated AC Resistance at 120 Deg.C 0.29129 Ω/mile
Imax A

600
Geometric Mean Radius(GMR) 0.28 in
400
Inductive Reactance @1ft. radius at 60Hz 0.456 Ω/mile
Capacitive Reactance @1ft. radius at 60Hz 0.10395 MΩ.mile 200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =14700 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : HAWK

Conductor Type & Code ACCC - Hawk


2
(611 kcmil/310 mm )
Nominal equivalent Aluminum Area 630.2 kcmil
Cross Sectional Area - Aluminum 610.94 kcmil
Cross Sectional Area - CTC Core 0.062 sq.in
Total Area of Cross Section- conductor 0.541 sq.in
Overall Diameter of Conductor 0.857 in
Mass per Unit length - Aluminum 575 lb/kft
Mass per Unit length - Core 51 lb/kft
Mass per unit length - Conductor 626 lb/kft
Rated Strength of the Conductor * 23205 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.1477 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 9.432 in Max. single length /Drum 8010 ft ( 2440 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.2799 in
o
No. of Aluminum Layers 2 N
No. & equivalent Dia. of Trapezoidal wires in first layer 6 x 0.195 in
No. & equivalent Dia.of Trapezoidal wires in second layer 10 x 0.196 in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.144 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0298 sq.in
Composite Core Layer-2 0.0301 sq.in
Conductivity Nil
Rated Breaking Load 19290 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 19.09 x10-6 /oC below thermal knee point 10.7 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
1400
Rated ampacity at max. temperature ^ 1197 Amp. Imax (Amp)
1200
AC Resistance at max. operating temp. 0.2406 Ω/mile
1000
Calculated max. ampacity at 120 Deg.C ^ 1006 Amp.
800
Calculated AC Resistance at 120 Deg.C 0.20793 Ω/mile
Imax A

Geometric Mean Radius(GMR) 0.334 in 600

Inductive Reactance @1ft. radius at 60Hz 0.4348 Ω/mile 400


Capacitive Reactance @1ft. radius at 60Hz 0.09877 MΩ.mile 200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =20860 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : DOVE

Conductor Type & Code ACCC - Dove


2
(713 kcmil/361 mm )
Nominal equivalent Aluminum Area 743.26 kcmil
Cross Sectional Area - Aluminum 720.56 kcmil
Cross Sectional Area - CTC Core 0.073 sq.in
Total Area of Cross Section- conductor 0.639 sq.in
Overall Diameter of Conductor 0.927 in
Mass per Unit length - Aluminum 678 lb/kft
Mass per Unit length - Core 58 lb/kft
Mass per unit length - Conductor 736 lb/kft
Rated Strength of the Conductor * 27504 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.1253 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 10.199 in Max. single length /Drum 7480 ft ( 2280 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3051 in
o
No. of Aluminum Layers 2 N
No. & equivalent Dia. of Trapezoidal wires in first layer 7 x 0.196 in
No. & equivalent Dia.of Trapezoidal wires in second layer 11 x 0.203 in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.156 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0302 sq.in
Composite Core Layer-2 0.0322 sq.in
Conductivity Nil
Rated Breaking Load 22887 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 19.07 x10-6 /oC below thermal knee point 10.7 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
1600
Rated ampacity at max. temperature ^ 1333 Amp. Imax (Amp)
1400
AC Resistance at max. operating temp. 0.2042 Ω/mile
1200
Calculated max. ampacity at 120 Deg.C ^ 1119 Amp. 1000
Calculated AC Resistance at 120 Deg.C 0.17649 Ω/mile
Imax A

800
Geometric Mean Radius(GMR) 0.361 in 600
Inductive Reactance @1ft. radius at 60Hz 0.42532 Ω/mile 400
Capacitive Reactance @1ft. radius at 60Hz 0.09646 MΩ.mile 200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =24730 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : GROSBEAK

Conductor Type & Code ACCC - Grosbeak


2
(816 kcmil/414 mm )
Nominal equivalent Aluminum Area 850.54 kcmil
Cross Sectional Area - Aluminum 824.56 kcmil
Cross Sectional Area - CTC Core 0.08 sq.in
Total Area of Cross Section- conductor 0.728 sq.in
Overall Diameter of Conductor 0.99 in
Mass per Unit length - Aluminum 776 lb/kft
Mass per Unit length - Core 66 lb/kft
Mass per unit length - Conductor 842 lb/kft
Rated Strength of the Conductor * 30487 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.1095 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 10.887 in Max. single length /Drum 6990 ft ( 2130 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3201 in
o
No. of Aluminum Layers 2 N
No. & equivalent Dia. of Trapezoidal wires in first layer 7 x 0.209 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.208 in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.167 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0344 sq.in
Composite Core Layer-2 0.0339 sq.in
Conductivity Nil
Rated Breaking Load 25202 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 19.19 x10-6 /oC below thermal knee point 10.67 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
1600
Rated ampacity at max. temperature ^ 1457 Amp. Imax (Amp)
1400
AC Resistance at max. operating temp. 0.1786 Ω/mile
1200
Calculated max. ampacity at 120 Deg.C ^ 1220 Amp. 1000
Calculated AC Resistance at 120 Deg.C 0.15444 Ω/mile
Imax A

800
Geometric Mean Radius(GMR) 0.385 in 600
Inductive Reactance @1ft. radius at 60Hz 0.41738 Ω/mile 400
Capacitive Reactance @1ft. radius at 60Hz 0.09452 MΩ.mile 200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =27320 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : DRAKE

Conductor Type & Code ACCC - Drake


2
(1020 kcmil/517 mm )
Nominal equivalent Aluminum Area 1054.47 kcmil
Cross Sectional Area - Aluminum 1022.25 kcmil
Cross Sectional Area - CTC Core 0.111 sq.in
Total Area of Cross Section- conductor 0.913 sq.in
Overall Diameter of Conductor 1.108 in
Mass per Unit length - Aluminum 962 lb/kft
Mass per Unit length - Core 89 lb/kft
Mass per unit length - Conductor 1051 lb/kft
Rated Strength of the Conductor * 41128 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0883 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 12.191 in Max. single length /Drum 6360 ft ( 1940 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3752 in
o
No. of Aluminum Layers 2 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.219 in
No. & equivalent Dia.of Trapezoidal wires in second layer 14 x 0.213 in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.183 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0378 sq.in
Composite Core Layer-2 0.0358 sq.in
Conductivity Nil
Rated Breaking Load 34577 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 18.86 x10-6 /oC below thermal knee point 10.75 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
1800
Rated ampacity at max. temperature ^ 1682 Amp. 1600 Imax (Amp)

AC Resistance at max. operating temp. 0.1443 Ω/mile 1400


Calculated max. ampacity at 120 Deg.C ^ 1405 Amp. 1200
Calculated AC Resistance at 120 Deg.C 0.1249 Ω/mile
Imax A

1000
800
Geometric Mean Radius(GMR) 0.432 in
600
Inductive Reactance @1ft. radius at 60Hz 0.40366 Ω/mile
400
Capacitive Reactance @1ft. radius at 60Hz 0.09117 MΩ.mile
200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =37200 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : CARDINAL

Conductor Type & Code ACCC - Cardinal


2
(1222 kcmil/619 mm )
Nominal equivalent Aluminum Area 1266.53 kcmil
Cross Sectional Area - Aluminum 1222.46 kcmil
Cross Sectional Area - CTC Core 0.093 sq.in
Total Area of Cross Section- conductor 1.054 sq.in
Overall Diameter of Conductor 1.197 in
Mass per Unit length - Aluminum 1155 lb/kft
Mass per Unit length - Core 76 lb/kft
Mass per unit length - Conductor 1231 lb/kft
Rated Strength of the Conductor * 37083 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0742 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 13.17 in Max. single length /Drum 8790 ft ( 2680 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3449 in
o
No. of Aluminum Layers 3 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.179 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.184 in
No. & equivalent Dia. of Trapezoidal wires in third layer 16 x 0.1867in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.142 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0253 sq.in
Composite Core Layer-2 0.0267 sq.in
Conductivity Nil Layer-3 0.0274 sq.in
Rated Breaking Load 29249 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 19.90 x10-6 /oC below thermal knee point 10.51 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
2000
Rated ampacity at max. temperature ^ 1880 Amp. 1800 Imax (Amp)

AC Resistance at max. operating temp. 0.1217 Ω/mile 1600


1400
Calculated max. ampacity at 120 Deg.C ^ 1567 Amp.
1200
Calculated AC Resistance at 120 Deg.C 0.10543 Ω/mile
Imax A

1000
Geometric Mean Radius(GMR) 0.466 in 800
Inductive Reactance @1ft. radius at 60Hz 0.39428 Ω/mile 600
Capacitive Reactance @1ft. radius at 60Hz 0.08888 MΩ.mile 400
200
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =32380 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : BITTERN

Conductor Type & Code ACCC - Bittern


2
(1572 kcmil/797 mm )
Nominal equivalent Aluminum Area 1629.19 kcmil
Cross Sectional Area - Aluminum 1572.49 kcmil
Cross Sectional Area - CTC Core 0.093 sq.in
Total Area of Cross Section- conductor 1.328 sq.in
Overall Diameter of Conductor 1.345 in
Mass per Unit length - Aluminum 1486 lb/kft
Mass per Unit length - Core 76 lb/kft
Mass per unit length - Conductor 1562 lb/kft
Rated Strength of the Conductor * 39326 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0577 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 14.798 in Max. single length /Drum 7020 ft ( 2140 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3449 in
o
No. of Aluminum Layers 3 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.199 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.209 in
No. & equivalent Dia. of Trapezoidal wires in third layer 18 x 0.2015in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.167 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0312 sq.in
Composite Core Layer-2 0.0343 sq.in
Conductivity Nil Layer-3 0.0319 sq.in
Rated Breaking Load 29249 lbf
Coefficient of thermal expansion Modulus of elasticity
above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 20.51 x10-6 /oC below thermal knee point 10.38 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
2500
Rated ampacity at max. temperature ^ 2209 Amp. Imax (Amp)

AC Resistance at max. operating temp. 0.0953 Ω/mile 2000

Calculated max. ampacity at 120 Deg.C ^ 1835 Amp.


1500
Calculated AC Resistance at 120 Deg.C 0.08279 Ω/mile
Imax A

Geometric Mean Radius(GMR) 0.524 in 1000


Inductive Reactance @1ft. radius at 60Hz 0.38013 Ω/mile
Capacitive Reactance @1ft. radius at 60Hz 0.08542 MΩ.mile 500
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =33280 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : LAPWING

Conductor Type & Code ACCC - Lapwing


2
(1966 kcmil/996 mm )
Nominal equivalent Aluminum Area 2048.43 kcmil
Cross Sectional Area - Aluminum 1965.65 kcmil
Cross Sectional Area - CTC Core 0.116 sq.in
Total Area of Cross Section- conductor 1.66 sq.in
Overall Diameter of Conductor 1.504 in
Mass per Unit length - Aluminum 1869 lb/kft
Mass per Unit length - Core 95 lb/kft
Mass per unit length - Conductor 1964 lb/kft
Rated Strength of the Conductor * 49040 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0464 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 16.543 in Max. single length /Drum 8660 ft ( 2640 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.385 in
o
No. of Aluminum Layers 4 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.185 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.187 in
No. & equivalent Dia. of Trapezoidal wires in third layer 16 x 0.1878in
No. & equivalent Dia. of Trapezoidal wires in fourth layer 20 x 0.1884in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.14 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0268 sq.in
Composite Core Layer-2 0.0274 sq.in
Conductivity Nil Layer-3 0.0277 sq.in
Rated Breaking Load 36443 lbf Layer-4 0.0279 sq.in

Coefficient of thermal expansion Modulus of elasticity


above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 20.51 x10-6 /oC below thermal knee point 10.38 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
3000
Rated ampacity at max. temperature ^ 2546 Amp. Imax (Amp)

AC Resistance at max. operating temp. 0.0774 Ω/mile 2500

Calculated max. ampacity at 120 Deg.C ^ 2106 Amp. 2000


Calculated AC Resistance at 120 Deg.C 0.06744 Ω/mile
Imax A

1500
Geometric Mean Radius(GMR) 0.586 in
1000
Inductive Reactance @1ft. radius at 60Hz 0.3666 Ω/mile
Capacitive Reactance @1ft. radius at 60Hz 0.08212 MΩ.mile 500
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =41480 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : CHUKAR

Conductor Type & Code ACCC - Chukar


2
(2242 kcmil/1136 mm )
Nominal equivalent Aluminum Area 2336.1 kcmil
Cross Sectional Area - Aluminum 2241.68 kcmil
Cross Sectional Area - CTC Core 0.122 sq.in
Total Area of Cross Section- conductor 1.883 sq.in
Overall Diameter of Conductor 1.602 in
Mass per Unit length - Aluminum 2131 lb/kft
Mass per Unit length - Core 99 lb/kft
Mass per unit length - Conductor 2230 lb/kft
Rated Strength of the Conductor * 52720 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0407 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 17.622 in Max. single length /Drum 7550 ft ( 2300 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.3949 in
o
No. of Aluminum Layers 4 N
No. & equivalent Dia. of Trapezoidal wires in first layer 8 x 0.196 in
No. & equivalent Dia.of Trapezoidal wires in second layer 12 x 0.199 in
No. & equivalent Dia. of Trapezoidal wires in third layer 16 x 0.2008in
No. & equivalent Dia. of Trapezoidal wires in fourth layer 20 x 0.2018in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.151 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0301 sq.in
Composite Core Layer-2 0.0311 sq.in
Conductivity Nil Layer-3 0.0317 sq.in
Rated Breaking Load 38354 lbf Layer-4 0.032 sq.in

Coefficient of thermal expansion Modulus of elasticity


above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 20.69 x10-6 /oC below thermal knee point 10.34 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
3000
Rated ampacity at max. temperature ^ 2766 Amp. Imax (Amp)

AC Resistance at max. operating temp. 0.0685 Ω/mile 2500

Calculated max. ampacity at 120 Deg.C ^ 2283 Amp. 2000


Calculated AC Resistance at 120 Deg.C 0.05978 Ω/mile
Imax A

1500
Geometric Mean Radius(GMR) 0.624 in
1000
Inductive Reactance @1ft. radius at 60Hz 0.35893 Ω/mile
Capacitive Reactance @1ft. radius at 60Hz 0.08024 MΩ.mile 500
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =44100 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary
ENERGY EFFICIENT HIGH CURRENT OH CONDUCTORS

TECHNICAL DATA SHEET


Midal Cables Ltd

Concentric Lay Stranded Trapezoidal Conductor : BLUEBIRD

Conductor Type & Code ACCC - Bluebird


2
(2727 kcmil/1382 mm )
Nominal equivalent Aluminum Area 2841.44 kcmil
Cross Sectional Area - Aluminum 2726.6 kcmil
Cross Sectional Area - CTC Core 0.135 sq.in
Total Area of Cross Section- conductor 2.277 sq.in
Overall Diameter of Conductor 1.762 in
Mass per Unit length - Aluminum 2592 lb/kft
Mass per Unit length - Core 110 lb/kft
Mass per unit length - Conductor 2702 lb/kft
Rated Strength of the Conductor * 59807 lbf
o o
Maximum DC Resistance at 20 C (68 F) 0.0334 Ω/mile

Lay ratio - Outer layer of Aluminum wires : Min.10 Max.13 Lay Direction of outer layer Right Hand

- Inner layer of Aluminum wires : Min.10 Max.16 Surface finish Standard or Non Specular

Prefered Lay of outer layer 19.38 in Max. single length /Drum 7020 ft ( 2140 m)

Stranding configuration
No. & Diameter of CTC Core 1 x 0.415 in
o
No. of Aluminum Layers 4 N
No. & equivalent Dia. of Trapezoidal wires in first layer 9 x 0.201 in
No. & equivalent Dia.of Trapezoidal wires in second layer 14 x 0.203 in
No. & equivalent Dia. of Trapezoidal wires in third layer 18 x 0.2091in
No. & equivalent Dia. of Trapezoidal wires in fourth layer 23 x 0.2083in

Individual Aluminum wires Trapezoidal Wires


Minimum conductivity 63 %IACS height 0.168 in.
ASTM minimum Tensile Strength 8.5 ksi Area : Layer-1 0.0319 sq.in
Composite Core Layer-2 0.0323 sq.in
Conductivity Nil Layer-3 0.0343 sq.in
Rated Breaking Load 42334 lbf Layer-4 0.0341 sq.in

Coefficient of thermal expansion Modulus of elasticity


above thermal knee point 1.61 x10-6 /oC above thermal knee point 17.2 Msi
below thermal knee point 20.88 x10-6 /oC below thermal knee point 10.3 Msi
Max. allowable continuous operating temp. (surface) 175 oC ( 347oF )
3500
Rated ampacity at max. temperature ^ 3126 Amp. Imax (Amp)
3000
AC Resistance at max. operating temp. 0.0572 Ω/mile
2500
Calculated max. ampacity at 120 Deg.C ^ 2568 Amp.
2000
Calculated AC Resistance at 120 Deg.C 0.05022 Ω/mile
Imax A

Geometric Mean Radius(GMR) 0.686 in 1500

Inductive Reactance @1ft. radius at 60Hz 0.34739 Ω/mile 1000


Capacitive Reactance @1ft. radius at 60Hz 0.07743 MΩ.mile 500
^ Ampacity calculated at 25 Deg.C ambient, wind velocity 2ft/sec solar radiation: 93W/sq.ft
emissivity coefficient: 0.5 & absorptivity: 0.5 0
55 75 95 115 135 155 175
* Extreme Load Saftety Strength of Conductor =49320 lbf
( Applicable if sustained load over 80% RTS expected for prolonged periods. For further information please refer to ACCC o
Temperature C
Technical note TN-750-001.)

General Specification Standard : ASTM B 857


Manufactured under license from
Document version : Preliminary

You might also like