Calculation Sheet For Comb. Eff.
Calculation Sheet For Comb. Eff.
Input Data
Tca = temperature combustion air before burner (F) 70
Tex = temperature exhaust gasses (F) 367
EA = excess air (0=stoch, 0.1 = optimum) 1.02
Qng (mmBtu/h) = heat input to burner 7.300
Tw1 (F) 200
Tw2 (F) (for either "Steam" or "HotWater") 233
EAn = excess air (0=stoch, 0.1 = optimum) 0.10
"Steam" or "HotWater" Steam
If "Steam" then enter enthalpy of sat steam leaving boiler, hw2 (Btu/lb) 1158
Calculated Values
hr (Btu/lb) = heat of reaction = LHV if Tex > 140 else HHV 21,500
Tc (F) = temp combustion = Tca+hr/[(1+(1+EA)(Afs))cpp] 2,383
Effc = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex)/HHV 78.4%
Qu (Btu/h) = Useful heat transferred to water = Qng x 10^6 x Effc 5,723,887
dt1 (F) = Tc - Tw1 2,183
dt2 (F) = Tex - Tw2 134
dtlm (F) = (dt2-dt1) / ln(dt2/dt1) 734
UA (Btu/h-F) = Qu / (dtlm) 7,794
Tcn (F) = new temp combustion = Tca+hr/[(1+(1+EAn)(Afs))cpp] 4,221
Effcn (with EAn but Tex const) = [1 + (1+EAn)(AFs)]*cpp*(Tc-Tex)/HHV 83.5%
dt1n (F) = Tcn - Tw1 4,021
Guess current dt2n (F) (lower than dt2….) 17
This should equal zero if dt2 is correct 0
Texn (F) = dt2n + Tw2 250
Effcn = [1 + (1+EAn)(AFs)]*cpp*(Tcn-Texn)/HHV 86.1%
Qngn (mmBtu/h) = Qu / (Effcn x 10^6) 6.652
Input Data
EA = excess air (0=stoch, 0.1 = optimum) 0.10
Tca = temperature combustion air before burner (F) 70
Tex = temperature exhaust gasses (F) 350
Calculated Values
hr = heat of reaction = (if Tex<140 then hr=HHV else hr = LHV) 21,500
Tc = temp combustion (F) = Tca+hr/[(1+(1+EA)(Afs))cpp] 4,221
Efficiency = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex)/HHV 83.9%
Graphs
Tc = 72+21500/(.26(1+17.5EA))
Eff = (1 + 17.5EA)*.26*(Tc-Ts)/23900
90.0%
Efficiency
80.0%
70.0%
0 10 20 30 40 50 60 70 80 90 100
Excess Air (%)
Input Data
Tca = temperature combustion air before burner (F) 69
Tex = temperature exhaust gasses (F) 433
EA = excess air (0=stoch, 0.1 = optimum) 0.29
Qng (mmBtu/h) = heat input to burner 6.300
Tw1 (F) 150
Tw2 (F) (for either "Steam" or "HotWater") 210
EAn = excess air (0=stoch, 0.1 = optimum) 0.10
"Steam" or "HotWater" HotWater
If "Steam" then enter enthalpy of sat steam leaving boiler, hw2 (Btu/lb) 1000
Calculated Values
hr (Btu/lb) = heat of reaction = LHV if Tex > 140 else HHV 21,500
Tc (F) = temp combustion = Tca+hr/[(1+(1+EA)(Afs))cpp] 3,635
Effc = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex)/HHV 80.8%
Qu (Btu/h) = Useful heat transferred to water = Qng x 10^6 x Effc 5,088,894
dt1 (F) = Tc - Tw2 3,425
dt2 (F) = Tex - Tw1 283
dtlm (F) = (dt2-dt1) / ln(dt2/dt1) 1,260
R = (Tw1-Tw2)/(Tex-Tc) 0.018737
P = (Tex-Tc)/(Tw1-Tc) 0.918799
F (0 to 1) = F(R,P) correction factor for tube-in-shell hotwater boilers 1.00
UA (Btu/h-F) = Qu / (F x dtlm) 4,038
Tcn (F) = new temp combustion = Tca+hr/[(1+(1+EAn)(Afs))cpp] 4,220
dt1n (F) = Tcn - Tw2 4,010
Guess current dt2n (F) (lower than dt2….) 194
This should equal zero if dt2 is correct 0
Texn (F) = dt2n + Tw1 344
Effcn = [1 + (1+EAn)(AFs)]*cpp*(Tcn-Texn)/HHV 84.0%
Qngn (mmBtu/h) = Qu / (Effcn x 10^6) 6.058
Input Data
Rated Burner Input (MBtu/h) = Qb 5.00
Tsteam or Thotwater (F) = Ts 210
Excess Air = EA 0.3
Tca = temperature combustion air before burner (F) 69
Tex = temperature exhaust gasses (F) 433
Diameter Boiler (ft) = Db 10
Length Boiler (ft) = Lb 20
Temp Boiler Skin (F) = Tb 130
Conv Coeff (Btu/h-ft2-F) = h 7
Temp Indoor Air (F) = Tia 65
Temp Outdoor Air (F) = Toa 50
Stack Height (ft) = Hs 30
Stack Diameter (ft) = Ds 3
Frac Time at Full Fire = PLR 0.25
Num cycles per hour = N 6
Post-fire purge time (min) = PstP 1
Pre-fire purge time (min) = PreP 1
Annual Boiler Operating Hours (h/yr) = HPY 8,088
Cost of Natural Gas ($/MBtu) = CNG 5.50
Calculations
For On/Off Control
Area Boiler (ft2) = Ab = (3.14 x Db^2 / 4) + (3.14 x Db x Lb) 785
Area Stack (ft2) = As = 3.14 x Ds^2 / 4 7.07
mng (lb/hr) = Qb (MBtu/h) x 10^6 (Btu/MBtu) / 21500 (Btu/lbng) 233
ma (lb/hr) = mng (lb/hr) x 17.2 (lba/lbng) x (1+EA) 5,200
Off-Cycle Pres Diff = dP(lbm/s2-ft) = hs(ft) x 32.2 x 14.7 x (1/Toa-1/Ts) / 53.34 x 144 18
Off-Cycle Velocity (ft/min) = Vs = (2 x dP (lbm/s2-ft) / 0.07 lbm(ft3))^0.5 430
Off-Cycle Flow (ft3/min) = VFRs = Vs (ft/min) x 60 min/hr) x As (ft2) 3,036
Skin Heat Loss (Btu/h) = Qsk = Ab (ft2) x h (Btu/h-ft2-F) x (Tb - Tia) F 357,175
Purge Loss (Btu/h) = Qp = ma x (PstP+PreP)/60 x (1-PLR) x .26 x (Ts x .9 - Tia) 33,530
Off-Cycle Stack Loss (Btu/h) = Qstoff = VFRs x 60 x (1-PLR) x 0.018 x (Ts x .9 - Tia) 304,913
hr (Btu/lb) = heat of reaction = LHV if Tex > 140 else HHV 21,500
Tc (F) = temp combustion = Tca+hr/[(1+(1+EA)(Afs))cpp] 3,609
Effc = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex)/HHV 80.7%
On-Cycle Stack Loss (Btu/h) = Qston = Qb x 10^6 x PLR x (1-Effc) 241,150
Total Losses (Btu/h) = Ql = Qsk + Qp + Qstoff + Qston 936,767
Total Heat Input (Btu/h) = Qin = Qb x 10^6 x PLR 1,250,000
Total Heat to Steam/Water (Btu/h) = Qu = Qin - Ql 313,233
Total Efficiency (On/Off Control) = Qu / Qin 0.251
For ModulationControl
Qu (Btu/h) = Useful heat transferred to water at full fire = Qng x 10^6 x Effc 4,035,399
dt1 (F) = Tc - Tw2 3,399
dt2 (F) = Tex - Tw1 223
dtlm (F) = (dt2-dt1) / ln(dt2/dt1) 1,166
R = (Tw1-Tw2)/(Tex-Tc) 0
P = (Tex-Tc)/(Tw1-Tc) 0.9343907
F (0 to 1) = F(R,P) correction factor for tube-in-shell hotwater boilers 1.00
UA (Btu/h-F) = Qu / (F x dtlm) 3,461
mc (lb/h) = mng + mca 5,433
Guess PLR until Qu,n = Qu,target (fraction of Qng at which to calc new eff) 0.234
Tex,n (F) at PLR = Tw2-(Tw2-Tc)*exp(-UA/(mc*PLR*cpp)) (assumes const UA and Tw2) 210.10
Effc,n = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex,n)/HHV 86.4%
Qu,n (Btu/h) = Useful heat transferred to water = Qng x PRL x 10^6 x Effc,n 1,010,559
Qu,target 1,008,850
Skin Heat Loss (Btu/h) = Qsk 357,175
Total Heat Input (Btu/h) = Qinm = (Qu + Qsk) / Effc,n 776,181
On-Cycle Stack Loss (Btu/h) = Qstonm = Qinm x (1-Effc,n) 105,774
Total Losses (Btu/h) = Qlm = Qsk + Qstonm 462,949
Total Heat to Steam/Water (Btu/h) = Qum = Qinm - Qlm 313,233
Avg Efficiency (Modulation Control) = Qum / Qinm 0.404
Savings
Total Gas Savings (Btu/h) = Qsh = Qin - Qinm 473,819
Total Gas Savings (MBtu/yr) = Qsy = Qsh x HPY / 10^6 3,832
Total Gas Savings ($/yr) = Qsy x CNG 21,077
Directly calcs Effc,n
Boiler Efficiency At Part Loads
Input Data
Tca = temperature combustion air before burner (F) 69
Tex = temperature exhaust gasses (F) 433
EA = excess air (0=stoch, 0.1 = optimum) 0.30
Qng (mmBtu/h) = heat input to burner at full load 5.000
Tw2 (F) (for either "Steam" or "HotWater") 210
PLR = fraction of Qng at which to calc new eff 0.5
Calculated Values
Tw1 (F) = Tw2 for this calc since this calc assumes constant Tw 210
hr (Btu/lb) = heat of reaction = LHV if Tex > 140 else HHV 21,500
Tc (F) = temp combustion = Tca+hr/[(1+(1+EA)(Afs))cpp] 3,609
Effc = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex)/HHV 80.7%
Qu (Btu/h) = Useful heat transferred to water = Qng x 10^6 x Effc 4,035,399
dt1 (F) = Tc - Tw2 3,399
dt2 (F) = Tex - Tw1 223
dtlm (F) = (dt2-dt1) / ln(dt2/dt1) 1,166
R = (Tw1-Tw2)/(Tex-Tc) 0
P = (Tex-Tc)/(Tw1-Tc) 0.934391
F (0 to 1) = F(R,P) correction factor for tube-in-shell hotwater boilers 1.00
UA (Btu/h-F) = Qu / (F x dtlm) 3,461
mng (lb/h) = Qng x 10^6 / LHVng 233
mca (lb/h) = (1+ EA) x Afs x mng 5,200
mc (lb/h) = mng + mca 5,433
Tex,n (F) at PLR = Tw2-(Tw2-Tc)*exp(-UA/(mc*PLR*cpp)) (assumes const UA and Tw2) 235.29
Effc,n = [1 + (1+EA)(AFs)]*cpp*(Tc-Tex,n)/HHV 85.7%
Qu,n (Btu/h) = Useful heat transferred to water = Qng x PRL x 10^6 x Effc,n 2,143,311
Calculating Stack and Shell Losses For Idle Boiler
Input Data
Tsteam or Thotwater (F) = Ts 150
Diameter Boiler (ft) = Db 10
Length Boiler (ft) = Lb 20
Temp Boiler Skin (F) = Tb 80
Conv Coeff (Btu/h-ft2-F) = h 7
Temp Indoor Air (F) = Tia 65
Temp Outdoor Air (F) = Toa 50
Stack Height (ft) = Hs 30
Stack Diameter (ft) = Ds 3
Frac Time at Full Fire = PLR 0
Calculations
Area Boiler (ft2) = Ab = (3.14 x Db^2 / 4) + (3.14 x Db x Lb) 785
Skin Heat Loss (Btu/h) = Qsk = Ab (ft2) x h (Btu/h-ft2-F) x (Tb - Tia) F 82,425
1.5
0.5
0
0 0.2 0.
3.5
2.5
2 Eff
Eff Norm
1.5 exp(Y)
ln(Y)
1
0.5
0
0 0.2 0.4 0.6 0.8 1 1.2
Calcs Eff Gain For On/Off to Modulate Control
Input Data
Rated Burner Input (MBtu/h) = Qb 21.00
Tsteam or Thotwater (F) = Ts 170
Excess Air = EA 0.3
Combustion Efficiency at Full Fire = Effc 0.850
Diameter Boiler (ft) = Db 10
Length Boiler (ft) = Lb 20
Temp Boiler Skin (F) = Tb 130
Conv Coeff (Btu/h-ft2-F) = h 7
Temp Indoor Air (F) = Tia 65
Temp Outdoor Air (F) = Toa 50
Stack Height (ft) = Hs 30
Stack Diameter (ft) = Ds 3
Frac Time at Full Fire = PLR 0.25
Num cycles per hour = N 6
Post-fire purge time (min) = PstP 1
Pre-fire purge time (min) = PreP 1
Annual Boiler Operating Hours (h/yr) = HPY 8,088
Cost of Natural Gas ($/MBtu) = CNG 5.50
Calculations
For On/Off Control
Area Boiler (ft2) = Ab = (3.14 x Db^2 / 4) + (3.14 x Db x Lb) 785
Area Stack (ft2) = As = 3.14 x Ds^2 / 4 7.07
mng (lb/hr) = Qb (MBtu/h) x 10^6 (Btu/MBtu) / 21500 (Btu/lbng) 977
ma (lb/hr) = mng (lb/hr) x 17.2 (lba/lbng) x (1+EA) 21,840
Off-Cycle Pres Diff = dP(lbm/s2-ft) = hs(ft) x 32.2 x 14.7 x (1/Toa-1/Ts) / 53.34 x 144 14
Off-Cycle Velocity (ft/min) = Vs = (2 x dP (lbm/s2-ft) / 0.07 lbm(ft3))^0.5 384
Off-Cycle Flow (ft3/min) = VFRs = Vs (ft/min) x 60 min/hr) x As (ft2) 2,711
Skin Heat Loss (Btu/h) = Qsk = Ab (ft2) x h (Btu/h-ft2-F) x (Tb - Tia) F 357,175
Purge Loss (Btu/h) = Qp = ma x (PstP+PreP)/60 x (1-PLR) x .26 x (Ts x .9 - Tia) 99,940
Off-Cycle Stack Loss (Btu/h) = Qstoff = VFRs x 60 x (1-PLR) x 0.018 x (Ts x .9 - Tia) 193,257
On-Cycle Stack Loss (Btu/h) = Qston = Qb x 10^6 x PLR x (1-Effc) 787,500
Total Losses (Btu/h) = Ql = Qsk + Qp + Qstoff + Qston 1,437,871
Total Heat Input (Btu/h) = Qin = Qb x 10^6 x PLR 5,250,000
Total Heat to Steam/Water (Btu/h) = Qu = Qin - Ql 3,812,129
Avg Efficiency (On/Off Control) = Qu / Qin 0.726
For ModulationControl
Skin Heat Loss (Btu/h) = Qsk 357,175
Combustion Efficiency at PLR = Effcpl = Effc + .055/.75 x (1-PLR) 0.905
Total Heat Input (Btu/h) = Qinm = (Qu + Qsk) / Effcpl 4,606,965
On-Cycle Stack Loss (Btu/h) = Qstonm = Qinm x (1-Effcpl) 437,662
Total Losses (Btu/h) = Qlm = Qsk + Qstonm 794,837
Total Heat to Steam/Water (Btu/h) = Qum = Qinm - Qlm 3,812,129
Avg Efficiency (Modulation Control) = Qum / Qinm 0.827
Savings
Total Gas Savings (Btu/h) = Qsh = Qin - Qinm 643,035
Total Gas Savings (MBtu/yr) = Qsy = Qsh x HPY / 10^6 5,201
Total Gas Savings ($/yr) = Qsy x CNG 28,605
Off-Cycle Pres Diff = dP(lbm/s2-ft) = hs(ft) x 32.2(ft/s2) x 14.7psi x (1/Toa-1/Ts)(1/R) / 53.34(lbf-ft/lbm-R) x 144(in2/ft2)