TOTAL Fire Fighting Guidelines For Liquid HC Depots
TOTAL Fire Fighting Guidelines For Liquid HC Depots
Outre-Mer
Logistic Division
FIRE-FIGHTING
GUIDELINES
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 2 / 95
CONTENTS
1. OBJECT _________________________________________________________________ 6
2. DEFINITIONS ____________________________________________________________ 7
3. REFERENCE DOCUMENTS _______________________________________________ 9
3.1. Regulatory texts ________________________________________________________ 9
3.2. Norms ________________________________________________________________ 9
3.3. Total Outre-Mer technical documents ______________________________________ 10
3.3.1. Specifications _____________________________________________________ 10
3.3.2. Procedures _______________________________________________________ 10
3.3.3. Construction standards ______________________________________________ 11
3.4. Other documents_______________________________________________________ 11
3.5. Total Outre-Mer rule ___________________________________________________ 12
4. FF SIZING ______________________________________________________________ 13
4.1. Hazard study__________________________________________________________ 13
4.2. Internal Emergency Plan (IEP) / Scenarios __________________________________ 13
4.3. Networks ____________________________________________________________ 14
4.4. Water flow rate________________________________________________________ 14
4.4.1. Protection/cooling zone _____________________________________________ 14
4.4.2. Application rate of cooling water / thermal screens ________________________ 16
4.4.3. Premix application rate______________________________________________ 17
4.5. Fire-fighting water resources _____________________________________________ 18
4.5.1. Liquid hydrocarbon depots in Category B, C or D1________________________ 18
4.5.2. Liquid hydrocarbon depot in category C2 only or C2 and D2 _______________ 18
4.6. Foam agent resources ___________________________________________________ 19
4.7. Foam agent flow rate ___________________________________________________ 19
5. DESIGN RULES _________________________________________________________ 19
5.1. Fire-fighting water pumping _____________________________________________ 19
5.1.1. Fire-fighting water pumps ___________________________________________ 19
5.1.1.1. Number of fire-fighting water pumps ________________________________ 20
5.1.1.2. Discharge pressure of fire-fighting water pumps________________________ 20
5.1.2. Motorization of fire-fighting water pumps_______________________________ 22
5.1.2.1. Diesel engines __________________________________________________ 22
5.1.2.2. Electrical motors ________________________________________________ 22
5.1.3. Pump starting _____________________________________________________ 22
5.1.4. Pump station ______________________________________________________ 22
5.1.4.1. Generality______________________________________________________ 22
5.1.4.2. Design ________________________________________________________ 23
5.1.4.3. Pump building __________________________________________________ 25
5.1.4.4. Jockey pump for keeping pressure into fire-fighting network ______________ 25
5.2. Production of premix ___________________________________________________ 26
5.2.1. Proportioner ______________________________________________________ 26
5.2.2. Foam pump_______________________________________________________ 27
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 3 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 4 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 5 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 6 / 95
1. OBJECT
This document has been prepared by the TOM Logistic department and is intended for Total
Outre-Mer subsidiaries (excluding DOM-TOM subject to strict French regulations). The
document will guide subsidiaries in the design, choice of equipment and operation of fire-
fighting (FF) systems in liquid hydrocarbon depots.
In the subsidiaries involved, the fire-fighting systems in depots are at a performance level
varying according to their age, design and local regulations, where such existent.
To ensure that a satisfactory safety level exists in compliance with the safety policy of the
TOTAL group, guidelines that constitute an acceptable base for FF in all liquid hydrocarbon
depots must be available.
The purpose of this document is to define technical choices that may be used by all
subsidiaries to:
o design new FF systems
o diagnose the level of their existing FF systems
o upgrade existing FF systems
o purchase FF equipment
Also, this document sets down the internal facilities that must be available in a depot in case
of an accident, especially the foam and fire-fighting water resources.
Any project for a new system or modification to an existing FF system must be forwarded to
the TOM Logistic department for opinion and validation prior to starting works or equipments
purchase.
Safety of personnel, property and the environment is a major priority of the group and
consequently the fire-fighting systems must be permanently operational and efficient.
To achieve this goal, training, routine performance of the exercises defined in the IEP
(Internal Emergency Plan) and thorough serious maintenance of equipment are mandatory.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 7 / 95
2. DEFINITIONS
9 Classification of hydrocarbons
Liquid or liquefied hydrocarbons are classified in four categories: A, B, C and D (see
appendix 1) according to their physical state.
9 Concentration
This is the desired proportion of foam agent in water. For example, a 3% foam agent means
that it is necessary to add 3 parts of foam agent to 97 parts of water to produce the foaming
solution at the correct concentration.
9 Expansion factor
This is the ration between the volume of foam produced and the volume of premix.
• Low expansion factor: 5 to 15
• Medium expansion factor: 50 to 200
• High expansion factor: 300 to 1000
For example: if 100 liters of premix produce 1 m3 of foam, the expansion factor is 10.
9 Extinguishing foam
Foam is an emulsion made by assembling air bubbles in an aqueous envelope. Foam is
made with water, air and foam agent.
9 Foam agent
A foam agent is a chemical preparation which, when added in suitable proportions to water,
makes an extinguishing foam through the incorporation of air.
9 Nozzle monitor
Nozzle monitors consist of a monitor and water stream delivery equipment (branch pipe,
turbo head, etc…). They are either fixed (flanged inlet), portables or maneuverable (in the
depot), or towable (on the road) and can incorporate a hydraulic powered swiveling head or
be manually positioned.
9 Polar products
The following are considered as polar products: petrol and fuels containing more than 5%
oxygenated products (example: methanol, ETBE…)
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 8 / 95
9 Portable monitor
There are three types of portable monitors:
• The portable water monitor comprising a branch pipe and a valve. The
monitor operates in three different positions (shut off, solid water jet, sprayed
water jet)
• The mixed water or foam portable monitor (low expansion factor) called
VFRM (variable flow rate monitor) enabling adjustment of the water jet (solid
water jet to sprayed water jet). The flow rate from this monitor is either fixed
or variable.
• The portable fixed flow rate foam monitor (low and medium expansion factor).
9 RAEDHL
Fitting out and operating French rules for liquid hydrocarbon depots.
9 Retention bund
A retention bund is designed to collect accidental hydrocarbons spillage from tanks
9 Worst scenario
The worst scenario is the scenario from the hazard study the most penalizing in terms of
equipment and personnel resources to implement to fight a fire.
9 Zone 0 (*)
Zone where an explosive mixture of gas or vapor is located permanently (the gaseous phase
inside a closed tank or recipient constitutes a zone “0”).
9 Zone 1 (*)
Zone where an explosive mixture of gas or vapor is likely to form during normal operation of
the system.
9 Zone 2 (*)
Zone where an explosive mixture of gas or vapors can only occur when the system operates
abnormally (leak or operating error).
(*) as per new international regulations CEI 79.10 (1995), decree dated the 19/12/1988 and
decree dated the 29/11/1991.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 9 / 95
3. REFERENCE DOCUMENTS
Reference Description
Decrees dated 09/11/72 • Fitting out and operating rules for liquid hydrocarbon depots,
and 19/11/75 o with global fictive capacity at least equal to 1000 m3
(RAEDHL) o with global fictive capacity more than 1000 m3
Circular dated 09/11/89 Technical instruction dated November 9, 1989
(IT 89)
Circular dated 06/05/99 Circular dated May 6, 1999
3.2. Norms
Existing fire norms are given to readers; all of them are not applicable over Total Outre-Mer
perimeter.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 10 / 95
3.3.1. Specifications
Reference Title
OMLOG-SPEC-001-an Fire-fighting water motor driven pump unit
OMLOG-SPEC-002-an Foam agent motor driven pump unit
OMLOG-SPEC-003-an Foam agent storage tank
OMLOG-SPEC-004-an Fire-fighting equipment
OMLOG-SPEC-005-an Anti-pollution kit
OMLOG-SPEC-006-an Fixed proportioner
OMLOG-SPEC-007-an Piping and fitting for depots fire fighting lines (LU1-CS-AN)
3.3.2. Procedures
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 11 / 95
Reference Title
SEC/DEP/50 Internal emergency plan
SEC/DEP/52 Fire safety
SEC/DEP/65 Emergency stop
SEC/DEP/70 Depot extinguisher replacement and maintenance
SEC/DEP/90 Mandatory fire-fighting drills
SEC/PRV/90 Mandatory provisions for services and works carried out in depots
by contractors
(SEC/PRV/90 DT1 to 9) And associated documents
IMPORTANT NOTA: all standards are up to date at the date of creation of guideline. Don’t
forget to check if they are always in force before using them.
Reference Title
OMLOG-STD-165-an Fire arrester manhole on oily water network
OMLOG-STD-167-an Stone trap
OMLOG-STD-194-an Fire hydrant DN 100 2 x 65 and 1 x 100
OMLOG-STD-196-an Fire hydrant DN 150 1 x 65 and 2 x 100
OMLOG-STD-240-an Tank bund water discharge manhole
OMLOG-STD-275-an Bund wall – cold pipe fire arrester passage
OMLOG-STD-283-an Fire hydrant 2 x DN 65
OMLOG-STD-293-an Pipe openings in a wall
OMLOG-STD-308 (1&2) -an Tank foam agent generator
OMLOG-STD-315-an Symbols representing fire-fighting protection equipment
OMLOG-STD-316-an Installation of tank fire ring
OMLOG-STD-317-an Diagram of fire-fighting system
Reference Title
GESIP Report Calculation method for the extinguishing rate of flammable liquid
No.99.02 fires – Circular dated May 6, 1998 – Revised 2002
GESIP Report Absorption of thermal radiation emitted by a fire using a water
No.03.01 spray curtain
GESIP Report Range of foam generators used for fire protection of flammable
No.03.02 liquid tank retention bunds
GESIP Report GESIP method guidelines for writing of the Internal Emergency
No.96.02 Plan of a Flammable Product Storage Center (Depot) or Small
Industrial Company, Reissued Guide 2001
GESIP Report Recommendations for the protection of industrial centers against
No.94.02 the effects of lightning – updated October 2000
GESIP Report Recommendations for the use of the UFIP method guide on how
No.00.04 to carry out danger studies in refineries, storage of liquefied and
liquid products
Guide TOM-HSEQ of Method guidelines for calculating of the major accident danger
December 2005 zones on hydrocarbon depot and LPG depot of Total Outre-Mer.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 12 / 95
Method guidelines of Method guide for hazard analysis of Industrial Safety Group
DSER – 12/2005 department
Reference Title
NFPA Rule National Fire Protection Association
NFC Rule National Fire Code
APSAD General Assembly of Property and Casualty Insurance Companies
RAEDHL IT 89 Circular
(**) May 6, 1999
Existing depots
less than 1500 m3
Applicable (*) Non applicable
and more than
100 m3
Existing depots (*)
greater than or Joint study with the
Applicable Non applicable
equal to 1500 m3 TOM Logistic
department
New depots To study conjointly with
Applicable Applicable the TOM Logistic
department
Small depots less
than 100 m3 of Rules above not applicable
equivalent Standard decree 253 (section 1430) to respect
capacity
(*) Some points in the RAEDHL (Liquid hydrocarbons) are out of date and systematically
replaced by IT 89; see details below and in appendices 8 and 9.
(**) RAEDHL (Liquid hydrocarbons) specifications are the basic minimum requirements.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 13 / 95
4. FF SIZING
Without any obligation to follow European regulations, a brief hazard study must be carried
out for each depot, according to the principles defined below.
The hazard study must describe the type and scope of consequences, for the environment
and the population involved, which may occur following a hypothetical accident. The
assumptions, the accident scenarios and the methods used to estimate the consequences
must be clearly explained. The study must take into account the characteristics of the
location.
Also, it is necessary to include in the scope of the study the causes of accidents such as
earthquakes, lightning, flooding, malicious intent, attacks and hazards related to the
proximity of dangerous systems or liquid hydrocarbons or dangerous goods transport
facilities (pipelines).
With regard to complex systems or for more details, it is better to refer in the preferential
order either to the method guide for hazard analysis (guide revision 0, 2005-02-12) or to the
UFIP method guide on the "Carrying out of danger studies in refineries, storage of liquefied
and liquid products".
The Internal Emergency Plan, also called IEP, is prepared by the Depot Manager of the
concerned site under his responsibility. The purpose of the plan is to organize fire-fighting
in the depot enclosure and shall detail organizational steps, fire-fighting methods and the
facilities necessary that the Depot Manager must implement at the location to protect the
personnel, the facilities, the population and the environment. Also, the plan details the
emergency steps under the responsibility of the Depot Manager, with regard to
communicating and informing the public, the departments and administrative services
involved.
The IEP is written based on scenarios identified and quantified in the hazard study.
In case of an accident, the Depot Manager triggers and applies his IEP.
All Total depots of the Outre-Mer perimeter must have an IEP up to date.
Total Outre-Mer has distributed a writing guide for the IEP - see procedure SEC/DEP/50.
With complex systems or to obtain more details, it is better to refer to the guide edited by the
GESIP "Method guide for the writing of an internal operations plan for a flammable product
storage depot or a small industrial depot, - reedited in 2001” (Ref. 96.02) and, eventually
refer to the expertise’s head office of Total Outre-Mer.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 14 / 95
The scenarios to take into account when calculating the size of a FF of a liquid hydrocarbon
depot are:
a) Tank fire
b) Bund fire
c) Loading/offloading station fire (tank ship, rail tanker, road tanker)
d) Pump station fire
NOTE: The IEP must cover scenarios other than those related to fire such as tank overflow,
accidental pollution, natural disasters, etc.
4.3. Networks
Several cases exist on liquid hydrocarbon depots. The depot may be equipped with:
• Either with a water network (to cool systems located close to the zone on fire) and a
premix network (for hydrocarbon fire-fighting with foam),
• Or with a mixed water/premix network (if approval received from the TOM Logistic
department
• for small capacity depots a water network with mobile foam production facilities (e.g.:
storage at customer premises)
The global water flow rate that the depot must produce is equal to the sum of the water flow
rate required for cooling and the water flow rate required to produce the premix in the case
of the worst scenario in the hazard study.
Global water flow Water flow rate required Water flow rate required
rate = for cooling + for production of premix
The fire-fighting water flow rate should enable cooling of equipment located in zones defined
below.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 15 / 95
Example: tank R1, radius R, is assumed to be on fire and tanks R2 and R3 are located
totally or partially in the fictive cylinder.
Tanks R1, R2 and R3 are to be taken into account in the water flow rate calculation.
R is given in meters.
2.5 R
(with minimum R2
of R+15m)
Tank
assumed to R
be on fire
R1
R3 R4
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 16 / 95
Example: The bund below in red is assumed to be on fire and the pump station and tank R5
are fully or partially located in the imaginary perimeter.
The pump station and tank R5 are therefore to be included in the cooling water flow rate
calculation.
Administration
building Bund assumed on fire
Pump
station
50 m
R5
Water flow rate calculation examples in case of a tank fire or a bund fire are included in the
appendices.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 17 / 95
The Total Outre-Mer rule concerning the premix application rate when injecting in a bund on
fire or a tank on fire is:
For a tank on fire, the premix application rate on the tank on fire is 15 l/min/Lm of the
circumference (For a cylindrical tank installed horizontally, the perimeter of its vertical
projection on a horizontal plan must be taken into account)
The surface areas to take into account for the application surface area for the premix are as
follows:
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 18 / 95
However, depending on locations and with the approval of the TOM logistic department, a
greater or smaller volume may be prescribed.
All hydrocarbon depots in category C2 or C2 and D2 must have the water resources
capable of providing the water flow rate defined in point 4.4 for at least 90 minutes.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 19 / 95
The facilities maintained on the location, especially with regard to the foam agent reserve
and its implementation facilities, must make it possible to provide an extinguishing flow rate
of the worst scenario for:
• at least 40 minutes
The timing strategy is not selected for the Outre-Mer perimeter, i.e. the application rates for
extinguishing are immediately implemented.
5. DESIGN RULES
The design of the fire-fighting system must take into account the number of fire-fighters
available instantaneously and competent (depot operators having followed an appropriate
training course). Those persons would be able to operate the system.
Fixed equipments must be installed for fires in retention bunds and tanks. They make it
possible to reduce the setting up time, to operate at a safe distance and to reduce
hazardous operations for the staff.
Mobile equipment is acceptable:
As only fire fighting means, just for fires at the loading / offloading station and pump
house,
As spare means of a fixed system.
As far as possible, control devices must be grouped together and distant from hazardous
zones.
See fire-fighting water motor driven pump unit specifications (OMLOG-SPEC-001-an) being
written.
The pump or pumps must be sized to provide QE which is 110% of the water flow rate
calculated in paragraph 4.4.
The diesel pumps can’t be into Type 1 or 2 zones.
The diesel pumps will be under liquid head in relation to water storage.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 20 / 95
In all cases, the depot will be provided by a minimum of two fire fighting pumps which each
of them can deliver 110% of the flow rate calculated in paragraph 4.4. When the flow rate
required by the worst scenario exceeds 120 m³/h, and with a design implicating more than 2
pumps, an emergency extra pump must be added with similar flow rate (if there are n pumps
used to obtain the global water flow rate, n+1 pumps must be installed)
For instance:
If global water flow rate = 140 m³/h, the depot will be equipped with 2 x 160 m³/h
pumps (160 m3/h which is 114% of 140 m3/h) or 3 x 80 m3/h pumps (2 simultaneous
pumps are enough for the global water flow rate and the third is for assistance).
If global water flow rate = 200 m³/h, the depot will be equipped with 2 x 220 m³/h
pumps (220 m3/h which is 110% of 200 m3/h) or 3 x 110 m3/h pumps (2 simultaneous
pumps are enough for the global water flow rate and the third is for assistance).
If the required flow rate calls for several pumps working in parallel, the number of pumps
must be worked out so that the power of the motors remains reasonable.
For example, a 500 m3/h pump is the top acceptable limit (above this size, a pump may have
starting problems and require specific maintenance).
The total dynamic discharge head must be calculated to keep, under all circumstances, the
maximum flow rate as defined in paragraph 4.4, a minimum pressure of 8 bar, at the highest
use point or at the point of the hydrant network with the maximum loss of charge.
On flat ground (‘’level difference between highest point and lowest point’’ 10m), the
discharge pressure read on the pressure gauge at zero throughput (discharge valve
closed) must be between 10 bar and 14 bar and at least inferior to the maximum allowable
working pressure for the flanges (PN16 or PN20). This pressure will be fixed by the area of
the depot and the loss of charges of the whole fire fighting piping (elbows, tees, pipeline).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 21 / 95
The correct operating ranges of FF equipment are given below for information purposes
(refer to the technical data sheets of suppliers for more details):
Equipment input
Equipment acceptable pressure
range
Retention bund foam generator between 5 and 7 bar
Tank foam generator between 4 and 6 bar (*)
Nozzle between 6 and 10 bar
Cooling ring sprayers between 1 and 4 bar
Water curtains between 5 and 10 bar
The adjustment of the equipments supply pressure is secured with calibrated restriction
orifices installed as close as possible of the equipments.
The sources and quantities of loss of head in the fire-fighting network are given below for
information purposes:
(*) This data is given for information purposes. It is to demonstrate that flow speeds greater than or
equal to 4 m/s in pipes leading to high loss of charge should be avoided.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 22 / 95
Preference will be given to diesel engines for the whole power pumping (refer to
specification OMLOG-SPEC-001).
Diesel engines must be supplied with fuel from a fuel reserve sized to ensure a minimum
range of P + 1 hour (P is defined in paragraph 4.5.1). There can be only one fuel reserve
for all units. This fuel reserve must be independent and its filling or draining must be easy.
Foundations of water pumps must been designed with a 5 to 6 the weight of the engine
(engine 1 Ton Ö foundation 6 Tons of concrete).
Rubber bellows (eg. Elaflex red ring) can be installed to absorb the fire
fighting diesel group vibration (for the outlet, they will be tied with bolts
and threaded shafts). Those rubbers must be checked regularly and
replaced systematically in case of wear (cracks, deformations, etc)
and maximum after 10 years.
Electrical motors must be supplied by two separate and independent electricity sources (for
example: public network and emergency generator set of the depot).
In the case of simultaneous internal and external production, the pump supply must be
distributed between these two sources.
When there are several electric powered pumps, they must be connected to separate outlets
of the low voltage switchboard.
5.1.4.1. Generality
Pumps must be of the centrifugal type, self-priming and fitted with easy to clean filters as per
standard OMLOG-STD-323-AN. Air/water cooled pumps are preferred than water cooled
pumps (with heat exchanger). Maintenance of the air/water cooling system of the pumps is
the same than a car: to check the water level into the surge tank, to clean the cooler if
needed (be careful with the sand winds) and to check possible leaks from hoses. Water
cooling is more liable for the grade of used water (hard water, water with sediments). In
those cases, clogging could appear.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 23 / 95
When the water source is inexhaustible, (river, lake, sea), the pump station must be installed
closed to the source (safety of the site is important, including protection of the pump from
stealing electricity and from malevolence and vandalism).
Foot filter valves must be implemented to prevent pipes from being clogged (for example,
sea weed, clams, etc.) when seawater or brine is pumped. In addition, the installation of a
concrete collection chamber or manhole must be envisaged.
When seawater or brine is used for fire-fighting, an corrosion inhibitor must be added for the
tank storage.
If sea water or brine is used for fire-fighting, the depot must have a clear water buffer tank of
at least 3 times the volume of fire-fighting pipes networks in order to make it possible to rinse
those networks after carrying out the drills of the Internal Emergency Plan (IEP).
5.1.4.2. Design
To ensure correct operation of the pump, a straight section of pipe at least 6 times the
diameter of the pipe will be installed at the pump suction (see scheme below)
In case of diameter reduction, it must be an eccentric reduction as per scheme below (this to
avoid dissolved gas storage).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 24 / 95
• a filter at the inlet of each pump (between 800 and 1000 microns)
• isolating valves at the inlet and outlet of each pump
• check valve at outlet from each pump (when there are several pumps)
• systematically, a pressure gauge at the inlet and outlet of each fire-fighting pump
(according OMLOG-STD-219)
• A re-circulation circuit, with a return line to the water tank, to test correct operation of fire
units. A gate valve or restriction orifice simulates loss of head on this re-circulation circuit.
The network must be supplied by 2 isolatable outputs. Each output shall be capable of
providing the maximum flow rate required (gridded network).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 25 / 95
For prospective extension, it is very useful to schedule branch connections for the
installation of an emergency pump or a pump providing the additional pumping power.
Pumps shall be enclosed in a closed room, ventilated or semi closed, or open room that is at
least covered by a roof to protect equipment from inclement weather conditions (rain, wind,
sand, etc).
The ideal pump station is located 50 m from the fire zones. By default, the protection steps
will be implemented (water curtain, thermal effect arrester wall).
If there is a pump room close to the loading/offloading station for ships or tankers, a water
curtain protection system must be set up.
The water curtain can be made with line spades, sprayers or monitors.
Optionally, the pressure into water network can be kept between 6 and 8 bar with a
pressurization pump (Jockey pump) with a flow rate around 5 to 10 m3/h.
The pump is electrical powered and its supply is compulsory onto the prior electrical circuit.
When the jockey pump may be out of work, the pressure into the water fire-fighting network
can be kept with a connection to another water cooling network. A manual block valve and a
check-valve will equip this connection.
Some meters must be installed near the electrical equipment box: meter of hours and meter
of starting engine just to know the use of the pump and to detect a possible leak on the fire-
fighting network.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 26 / 95
According to the characteristics of the depot, the premix production is either by:
• An on line fixed flow rate proportioner
• An automatic variable flow rate proportioner and a pump operated foam agent supply
device (see scheme below)
5.2.1. Proportioner
5xD 3xD
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 27 / 95
Foam pumps shall be equipped with a recycling device connected to the foam agent tank
which will also make it possible to fill the foam tank. This circuit is fitted either with 1m3/h or
an isolatable excess flow rate valve (refer to the standard plan in appendix 5).
The foam agent pumps shall be sized to provide 110% of the foam agent flow rate for the
worst scenario.
At least 2 foam agent pumps will be installed. Each pump shall be capable of providing
110% of the flow rate required.
The discharge pressure required for the foam agent pump is equal to the discharge pressure
of the fire pump plus at least two bar.
(*) If sea water is used for fire-fighting, the depot must have a clear water buffer tank of a
capacity at least equal to 3 times the volume of fire-fighting pipes in order to make it possible
to rinse them after carrying out the drills of the Internal Emergency Plan (IEP).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 28 / 95
With an above ground tank, the tank must be equipped with the following branch
connections
The capacity of the above ground tank corresponds to the quantity of fire-fighting water
calculated in paragraph 4.5 plus 10 %.
The foam agent is stored in a fixed above-ground tank. Depending on the locations and with
the approval of the TOM Logisitic department, the foam may be stored in 1000-liter portable
containers. In that case, the suction could be done with plunger tube.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 29 / 95
If the foam tank is horizontal, it may be compartmented to facilitate management of the foam
agent stock.
The tank is painted on the outside according to foam agent code (red).
The capacity of the tank corresponds to the quantity of foam agent calculated in paragraph
4.6 plus 10 %.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 30 / 95
The location of the foam agent reserve varies according to the site:
• either inside the fire-fighting premises if this room is big enough
• or outside, but close to the premises.
In the latter case and depending on the climate, the tank may be covered to reduce
radiation.
The reserve must be protected by a fixed equipment (water curtain or line spades) if
hydrocarbon installation is near less than 50 meters.
Parking areas next to the foam agent reserve will enable mobile fire-fighting machinery to
park without hindering traffic on access ways.
A connection fitted with a bronze symmetrical locked DSP coupling, DN65, with rubber seal,
closed by a plug with locking chain will allow for the foam agent reserve to be filled from
mobile containers or mobile tanks.
This is a gridded network, equipped with conveniently positioned isolating valves so that
isolation of a leg of this network, should a problem arise, cannot entail the putting out of
service of the other legs.
The fire-fighting pipelines would respect 200 mm between the bottom of the bunds and the
lower generatrix of fire pipe.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 31 / 95
Separator
BUNDWALL 1 BUNDWALL 2
A fire hydrant network is looped around the bunds. Posts shall be installed every 40 to 50
meters.
The diameter of pipes is determined by calculating loss of head for the maximum flow rate
defined in paragraph 4.7 and the minimum pressure required at all points of use, as defined
in paragraph 5.1.1.2.
Losses of head caused by foam production units must be taken into account in pipe sizing
calculations. The purpose is to ensure a sufficient range for mobile monitor (minimum 40
meters).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 32 / 95
The suction speed must be limited to 1.5 m/s. The discharge speed must be between
2 and 4 m/s (refer to the appended table for pipe diameters, depending on the flow rates)
Valves fitted to the network (main lines, bypasses and branch connections of fire hydrants)
are direct throughput valves, either overhead (preferred choice) or in manholes.
Operating handles are located 1 meter above the finished ground level.
Fire hydrants are isolated by a butterfly valve, fitted with a reducer.
Mounts shall be installed to fit pressure gauges as close as possible to the fire-fighting
equipment to verify the operating conditions.
Caution: The connections between ordinary symmetrical couplings (“Guillemin”) and self
water-tight symmetrical couplings (“DSP” or “AR”) are not water-tight.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 33 / 95
The installation of premix production units and distribution networks shall be considered for
protection of storage facilities.
5.6. Manifold
A block diagram of the network showing the cross-references between the valve and the
equipment to protect shall be posted at each manifold (whether centralized or remote).
5.7. Identification
Pipes shall be painted according to a color code to identify products (see table below):
Product Color
Fire-fighting water red
Premix yellow
water or premix (mixed piping) yellow with mixed red rings
Foam agent orange
Example:
BV-14 FC-T3
Butterfly Valve No.14 / Foam Chamber of Tank 3
"A retention bund must be connected to any aboveground hydrocarbon tank or several
tanks. This bund can not be allocated both to category A hydrocarbon tanks and to category
B, C or D liquid hydrocarbons tanks" (RAEDHL).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 34 / 95
Preferably, the tank is bordered by reinforced concrete or earth bund walls (cement breeze
blocks are prohibited). Bund walls or breast walls are impervious and offer 6 hours fire
resistance. (IT 89)
The capacity and the size of retention bunds are defined in RAEDHL.
Bunds containing several tanks must be divided into compartments. The number of
compartments is calculated according to the capacity of tanks (cf. RAEDHL).
Caution: When calculating the size of the FF (retention bund fire extinguishing) the
total surface area of the bund is taken into account and not that of the compartments.
When pipelines cross walls or earth bund walls, the crossings shall be:
• Either jointed with 4 hours fire resistor products ( IT 89)
• Or made in compliance with standard OMLOG-STD-293-an or OMLOG-STD-275-an
• Or made using the link-seal system (FD or FS design) (see pictures below)
The length of pipes in retention bunds must be as short as possible. Preferably, group the
FF pipes with product pipes to limit crossings in retention bund walls or earth bund walls.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 35 / 95
The water curtain may be made with “line spades”, sprayers or monitors.
For water curtains of the “line spade” type, acting as thermal and mechanical screens, the
recommended flow rate ( IT 89) is:
o 500 l/min for a 30 meter length
o 1 000 l/min for a 40 meter length
For water curtains made with monitors, the recommended flow rate is:
o 500 l/min for a 30 meter range
o 1000 l/min for a 40 meter range
The efficiency of line spades must be checked with manufacturers before using them in a
fire-fighting study.
6.2. Storage
When a bund contains tanks with different types of products and/or a tank may be used to
store different types of products, the sizing and design of fire-fighting equipment to be
provided shall correspond to the most dangerous category of products.
NOTE: Supply of cooling rings or pipes from the hydrant network is prohibited.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 36 / 95
6.2.1. Protection
The installation of cooling rings is systematic for vertical tanks containing products in
categories B, C1 and D1.
The installation of cooling rings is examined on a case by case basis for vertical tanks
containing products in categories C2 or D2 and in horizontal tanks.
Refer to Standard OMLOG-STD-316-an.
The riser pipes of cooling rings are systematically fitted with stone traps.
(*) For a cylindrical tank installed horizontally, the perimeter of its vertical projection on a
horizontal plan must be taken into account.
The stone traps of cooling rings must be made in compliance with construction standard
OMLOG-STD-167-an.
The stone trap, riser pipe, cooling pipe and sprayers are made of 316L stainless steel and
supply pipes upline from the stone trap are made of steel, according to specification
OMLOG-SPEC-007-an.
The use pressure of sprayers shall be between 1 and 4 bars (it may be adjusted if necessary
using a restriction orifice located above the stone trap).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 37 / 95
The tank input line must be fitted with a check valve as represented in
the opposite diagram. For new tanks, the check valve will be installed
between the tank and the valve.
6.2.2. Extinction
It is recommended to equip riser supply pipes of foam generators with stone traps or to plan
at least one draining system for riser pipe (valves, symmetrical coupling).
The stone trap, riser pipe, ring (if several foam generators), and foam generator are made of
316L stainless steel and upline supply pipes of the stone trap are made of steel according to
specification OMLOG-SPEC-007-an.
One or more tank foam generators are installed according to the standard plan OMLOG-
STD-308-an 1/2 and 2/2.
The number of foam generators to install on a tank depends on the diameter of the tank (see
table below):
Foam generators must provide a premix flow rate according to the product stored in the
tank, as defined in paragraph 4.7 in these guidelines.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 38 / 95
The foam generator shall be of the inspection door type, quick opening and accessible from
the tank roof for routine tests.
Riser pipes must be fitted with stone traps according to the standard OMLOG-
STD-167-an. A riser pipe can only supply 1 or 2 foam chambers with 2 half rings
in top position with a return slope of 2 percent to the riser pipe (example: for
4 foam chambers, 2 riser pipes need to be installed).
Riser pipes on tank for the foam chamber(s) shall preferably be made of
stainless steel (see specification OMLOG-STD 009-an) or by default made from
hot dip zinc with flanges. This is to avoid the corrosion, which would require
periodic maintenance (painting, work at heights).
4 spare sheets of glass for each type of foam generator shall be available in the
depot (depending on diameters of sheets of glass).
The fixed foam injection systems at the foot of the tank are not recommended for new
systems.
Foam generators must be made of 316L stainless steel and provide for good distribution of
foam along the inner side of the tank to cover the roof joint as quickly as possible. The joint
must be fully covered in less than 2 minutes.
The number of foam generators to install on a tank depends on the diameter of the tank (see
table for fixed tanks).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 39 / 95
The drain used to recover rainwater from the floating roof must be closed (NC Normally
Closed during normal operation).
These tanks shall be protected in the same manner as the fixed roof
tanks. The floating screen or the fixed roof is equipped with a foam
barrier to keep the foam on the peripheral seal.
Foam box
Material INOX 316L
Foam spillway or
deflector
Galvanized foam
barrier 1.5 mm
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 40 / 95
Foam is applied in the bund through the cooling rings, when they exist to protect tanks from
fire at the first step. Supplementary foam in the bund is provided by fixed fire-fighting
facilities (retention bund foam generators, fixed monitors) or by mobile facilities (mobile
monitor).
Distance
tank /
bund wall Tank / bund wall distance less Tank / bund wall distance
than 6 m more than 6 m
Bund construction
Concrete bund wall Jet foam generator Foam generator with spillway
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 41 / 95
• the proximity (less than 50 meters) from buildings outside the depot
• close to tank inlet and outlet pipes (which may be the source of leaks)
• prevailing winds
NOTE: evacuation peep holes for water of the bund shall be designed as mentioned into the
standard OMLOG-STD-240 (flame arrester elbow).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 42 / 95
6.3.1. Protection
Pump stations located in the protection zone defined in paragraph 4.4.1, must be provided
with the following protection systems:
dedicated water curtain (made with line spades, sprayers or monitors or fire arrestor wall)
or fire protective wall to protect from thermal flow.
or
fire hydrants (water) located between 25 and 40 meters and 1500 l/min monitors
When the fire-fighting pump station is located in the protection zone, the access ways and
openings must be facing away from the zones exposed to the thermal flows.
Pump rooms and retention bunds can be equipped with gas/flame protection systems.
Visual and audible alarms shall be transmitted to the operations room.
6.3.2. Extinction
6.4.1.1. Protection
either by a fixed sprayer system making up a screen around the Road Tanker Loading
Station (TLS), and possibly between each island. Sprayers must be capable of
indifferently spraying water or foam.
or by 2000 l/min monitors, appropriately located (2 monitors at least for each one for
cooling structures and the other to make up a thermal screen) and at least 4 fire
hydrants (water/premix) located between 25 and 40 meters from the Road TLS. These
posts must be very carefully positioned (scenarios, prevailing winds, etc.).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 43 / 95
6.4.1.2. Extinguishing
by means of a fixed
water/foam device indicated
above.
An attempt shall be made to create a blanket of foam under vehicles in case of fire at the
loading/offloading station. Foam and water needs shall be calculated (storage and flow rate)
to check if the worst scenario (TLS completely in fire) could be handled (can be occurred if
product is stored into the depot).
6.4.2.1. Protection
either by a fixed water device making up a thermal screen (the length of the water
screen is the entire length of the train plus distance equal to a tanker track at each end
of the train). The water curtain may be made with line spades, sprayers or monitors.
RT RT RT
Water curtain
or by 2000 l/min monitors and a fire hydrant network (water/premix) with posts installed
every 40 to 50 meters.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 44 / 95
6.4.2.2. Extinguishing
Extinguishing is by 2000 l/min monitors and a fire hydrant network (water/premix) with
hydrants installed every 40 to 50 meters.
An attempt shall be made to create a blanket of foam under vehicles in case of fire at the
loading/offloading station.
When possible, a road accessible by vehicles shall be located alongside quays. A fire
hydrant network (water/premix) shall be installed along this road. This network shall be
equipped with posts installed every 40 to 50 meters.
Each loading/offloading station shall be reachable by at least two 2000 l/min Monitor nozzles
for boat, barge stations and ship stations.
If there is a fire at the loading/offloading station for boats and barges, all efforts shall be
made to create a foam mat on the platform and the access foot bridges.
Considering the great variety of possible cases, each project shall be the subject of a special
study. The envisaged solution shall be forwarded to the TOM Logistic department for
approval.
Each oil separator shall be within the reach of at least one 1500 l/min monitor.
If a fire is declared in the oil separator, the range of application of the foam is that of
category “B” hydrocarbons (refer to paragraph 4.4.3).
If a “slop tank” is installed close to the oil separator, it must be provided with water and foam
protection systems for products in category “B”, as described in paragraph 6.2.
Protection based on the provisions implemented for pump stations (paragraph 6.3 of these
rules) must be forwarded to the TOM Logisitic department for approval.
6.7. Buildings
The fire-fighting water network shall provide efficient protection of the following rooms, from
posts:
Administration rooms
Workshops, stores
Infirmary
Control station
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 45 / 95
Electrical rooms and the computer room could be protected by a fixed detection and
extinguishing system. The protection here shall be envisaged on a case-by-case basis.
Rooms such as laboratories, archives, shall be the subject of a special study forwarded for
approval to the Operations department. In particular, this study shall bear on:
The detection systems used,
The fixed extinguishing systems.
Note: for example, in laboratories, electrical devices are neither explosion proof, nor water-
tight; be careful when using water for extinguishing).
7.1. Consumables
Each location must only use one type of foam agent (if no polar products stored). If the
mutual assistance or fire brigade bring foam agents different from the one used in the depot,
they must not be mixed. On the other hand, foams are inter-compatible; for example, a fire-
fighting truck may spray foam on an area already sprayed with foam by the fire-fighting
facilities of the depot even if the foam agents are of different types.
The depot must ensure that the foam agent is compatible with the type of water used (clear
water, sea water, brine) according to the supplier recommendations.
Caution: for polar type or polar solvent fires (e.g.: ethanol, acetone…), polyvalent type foam
agents must be used (see specification OMLOG-SPEC-011-an).
7.1.1.2. Conditioning
The foam agent stock shall be made available in a container of at least 1000 liters. The 200
liters barrels must be replaced as soon as possible (IT 89).
If the depot wished to keep the foam agent in 200 liters drums, these quantities shall not be
counted in the foam agent resources of the depot.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 46 / 95
After the guarantee period, depots must analyze the foam agent stocks five years after
purchasing. The analysis of the foam agent may be carried out by the supplier (checking of
the physical-chemical characteristics of the product) or by another supplier, according to
standard EN 1568-1 (test on real fire). Refer to technical information OMLOG-IT-023.
Note: Foam agent stocks must therefore be managed over the long term. Real foam
agent tests will make it possible to gradually renew stocks of foam agents.
• town supply
• a river or the sea (*)
• an artesian well
(*)If sea water is used for fire-fighting, the depot must have a clear water buffer tank of a
capacity equal to at least 3 times the volume of fire-fighting pipes in order to make it possible
to rinse them after carrying out the drills of the Internal Emergency Plan (IEP).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 47 / 95
The depot must be equipped with couplings for network water supply by third parties at the
pumping station and water tank (coupling Ø100 + valve + connection).
7.2.3. Nozzles
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 48 / 95
Special case: in a suction scenario, choose a solid pipe and fit a filter and a check valve to it.
Hoses must be rinsed in clear water and rolled after each use if
necessary (sea water). They will be stored into a safe cupboard near
the hydrants to prevent from the sun.
In small depots, the hoses can block the traffic of fire department
vehicles. Some beams shall be stored for crossing hoses.
Each depot shall have at least two complete sets of fire intervention suits (see specification
Fire intervention clothing - OMLOG-SPEC-009-an).
The fire intervention suit, usually called “fire suit” is all suits that operators wear when they
fight the fire. They are: a helmet, a jacket, some boots, some gloves, a cowl which covers all
parts of the face not protected by the helmet, an operating wrench, belt and eventually an
on-trouser.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 49 / 95
7.2.7. Extinguishers
Hydrocarbon fires
The depot shall equip top loading stations with actuating rods (at least one) to enable
manholes to be closed. This rod shall be identified and stored vertically.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 50 / 95
The depot must be equipped with the wrenches corresponding to its systems.
Each depot must be equipped with an anti-pollution kit or otherwise sand to channel or stop
products from flowing.
See specification OMLOG-SPEC-005-an. This specification gives the list and minimal
quantity (sheet, roll) and an individual protection list to have.
7.2.10.2. Sand
Sufficient sand bins shall be appropriately distributed to channel or stop product flowing:
Sand must be maintained loose and handling tools must be available at each sand bin
(shovel or bucket).
8. FIRE-FIGHTING ROOM
The fire-fighting room must be designed according to the size of the depot. In particular it
comprises:
The room intended for storage of foam agent and powder reserves
A fire-fighting equipment store (hoses, monitors, etc.)
The changing room with the initial intervention equipment
The depot must be equipped with a high performance alerting system and internal and
external communication means.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 51 / 95
The commissioning of the diesel groups must imperatively be done by a specialist (for
instance the purchaser)
(*) Have available a fine filter to be used when the system is initially started up, to prevent
deterioration to the pump by any particles created when installing the pipeline.
Start up the pump and check the foam pump in a closed circuit on the tank for correct
operation (by means of a re-circulation circuit) for one hour.
Check pump discharge pressure.
Check pump suction pressure (to detect filter clogging, where applicable).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 52 / 95
Pressure gauges upstream and downstream from proportioners will make it possible to
control the normal loss of head during operation.
If the loss of head is greater than normal, check the venturi or upstream foam agent supply
circuits.
Other than for acceptance operations of a new system, existing depots can carry out
this test procedure to verify the efficiency of their FF system.
The Depot Manager must keep an inventory of stocks and the allocation of tanks in the
reception office or guard house. This inventory shall be updated each working day, at the
end of the day, after transfer of products.
When safety can no longer be ensured (dismantling of fire-fighting facilities, works, abnormal
occupation of traffic areas, etc.) the operating activity must be stopped in the part of the
depot involved.
The Depot Manager must keep an up-to-date copy of the IEP in the reception office or guard
house.
The block diagram of fire-fighting facilities and FF facilities use procedures shall be visibly
displayed in the fire-fighting pump station.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 53 / 95
11.2. Training
Foam agent expansion checks must be carried out at least once a year.
Each depot must carry out a drill based on an IEP scenario at least once a year, effectively
implementing equipment – see procedure OM SEC/DEP/90.
Pipes must be rinsed with clear water after each drill of the Internal Emergency Plan (IEP) if
foam agent and/or sea water has been used.
All valves shall be labeled and identified. The normal position of each valve when not in use
shall be indicated:
• NC: normally closed
• NO: normally open
These default positions shall be indicated on the FF block diagram of the pump station.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 54 / 95
11.7. Guards-Security
Outside the periods with product transfer operations, depots must be guarded.
The above-mentioned guard or personnel must be trained by the Depot Manager and know
all instructions to follow in case of a fire.
11.8. Works
Experience feedback shows that many outbreaks of fire in hydrocarbon depots are linked to
the performance of works. Therefore, it is important to prepare prevention plans with
contractors (see SEC/DEP/20 and SEC/DEP/201 to 208).
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 55 / 95
APPENDICES
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 56 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
Non exhaustive list of Classified center decree Depot fitting out rules – order Dangerous material transport rules
products Flash point dated 20/05/1953 dated 9/11/1972 Order dated15/04/1945 La Haye regulation
(International)
Category A
Vapor pressure > 1 bar at KO vapor pressure
Liquid hydrocarbons < 0°C Liquid combustible gas 15°C Class 1d 4th category REID > 600 mm HG at
A1>0°C 37,8°C
A2 other conditions
Ethylene oxide or Ether Especially inflammable if
Carbon sulphide < 0°C boiling point < 35°C Category B 2nd category K0 ditto
Petroleum ether under760 mm HG
Mercaptan - pentane
Crude oil
Premium petrol
Automobile petrol
Aviation gasoline < 21°C 1st category Category B 3rd category K1
Special fuels A to II
Acetone
Certain alcohols
Benzene <21°C 1st category Category B Class IIIa 3rd category K1 Z
Certain white-spirits
White-spirit > 21°C
Petroleum oil
Jet fuel 1st category Category B 3rd category K2
Cyclohexane
Certain alcohols <55°C
Gas oil > 55°C
Paraffin based distillates Category C
Domestic fuel– light fuel 2nd category C1> flash point 4th category K3
Certain oils C2 < flash point
<100°C
Heavy F.O. <100°C 2nd category Category C2 4th category K3
Heavy F.O. > = 100°C Non classifiable Category C2 4th category K3
Lubricating oils >100°C Non classifiable Category D No Non classifiable Non classifiable
classifiable
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 58 / 95
The premix flow rate required is obtained by multiplying the useful surface area of the tank by
the rate of application indicated by paragraph 4.4.3 in these guidelines, depending on the
hydrocarbon category.
The minimum flow rate to take into account corresponds to the worst tank case.
The cooling flow rate of the tank on fire is calculated at a rate of 15 l/min per meter of
circumference; i.e.:
CWtf (l/min) = 15 x π x D(m)
The tanks to protect are those located in an imaginary cylinder centered on the tank of radius
R, assumed to be on fire, and a radius equal to 2.5 R, with a minimum of R + 15 meters.
Protection is provided:
either by water curtains,
or by the cooling system of tanks with a 15 l/min flow rate per meter of circumference.
The water curtains may be provided:
either by monitors, with a 500 l/min flow rate for a 30 m range, or a 1 000 l/min flow
rate for a 40 m range,
or by "line spades" devices with a 500 l/min flow rate for a 30 m length and a
1 000 l/min flow rate for a 40 m length.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 59 / 95
The premix flow rate to schedule to control the fire is obtained by multiplying the useful
surface area at the top edge of the bund (tanks deducted) by the rate of application for the
most constraining category of hydrocarbon contained in the bund. The minimum flow rate to
take into account corresponds to the most constraining bund. When a bund contains tanks
with different types of products and/or a tank may be used to store different types of products,
the sizing and design of fire-fighting equipment to be provided shall correspond to the most
dangerous category of products.
The systems to protect are those located outside and less than 50 m from the edge of the
bund on fire.
Protection is provided:
either by water curtains,
or by the cooling system of tanks, at the rate of 15 l/min per meter of circumference.
Water flow rate for the protection of neighboring tanks (outside bund)
PWnt = [15 x π x D1] + [15 x π x D2] + ………………[15 x π x Dn]
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 60 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 62 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 64 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
RM/OM/LA/LOG Created : 01/03/2000
HYDROCARBON LIQUID VERTICAL TANK STORAGE
Revised : 11/12/2006
CHART OF CALCULATION FOR NPS OF COLUMN RISER AND COOLING RING QUANTITY AND LOCATION OF SPRAYERS
Working hypothésis :
Cooling flow rate : 15 l / min / meter of circumference A Center line of rings axis / to tank shell
Type of sprayers : TKN ø 8,5 mm (EAU et FEU) B Height of covering aéra by sprayer jet
D Distance between two sprayers
Notes:. H Distance from top of stifener to ring bottom at the hight ring point
(*) For other diameter see OMEX-NDC-012-an ∆h Vertical interval between high and low point of the ring
'(1) α Maximum pitch angle of sprayers from top to bottom level ring
may be designed with two NPS 4'' columns riser
- Reference to Std OM-316 E Distance between two ring supports
P Ring slope
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 77 / 95
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 78 / 95
NB: Those regulations are given below for information purposes. Some parts are
lapsed (in red in the text)
TITLE VI – FIRE-FIGHTING
Retention bunds only containing heavy fuel tanks are subject to the provisions in articles 602,
604-1, 604-3, 606-2, 607, 608 and 609.
Buried depots are subject to the provisions in articles 607, 608 and 609.
As an exception to rule in article 602.11, any depot only containing hydrocarbons in categories
C2, or C2 and D2 must have available water resources capable of providing the regulatory
water flow rate as defined in article 606 for at least 1.5 hours.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 79 / 95
602.23 – This equipment must be judiciously located throughout the depot and installed under
access and distance conditions compatible with the hazards and possibly providing the
protection necessary to ensure maximum use safety.
602.24 – It must be possible to protect all hydrocarbon locations from this network.
602.31 – Pipelines
The pipelines making up the fire-fighting network must only be used for this purpose.
However, supply of other circuits from the fire-fighting network shall be accepted on condition
that the requirements set down for fire-fighting water (flow rate, pressure, reserve) remain
satisfactory.
Pipelines and accessories making up the fire-fighting network shall be made of materials
offering suitable resistance to mechanical and physical constraints to which they are subject in
service. Moreover, they must be made of fire resistant materials, protected against corrosion.
The cross sections of pipeline shall be calculated to provide the required flow rate at any
location, at the required pressures to ensure correct operation of fire-fighting facilities.
As far as possible, pipelines shall be laid alongside roadways, paths or working areas.
The network must be gridded as far as possible and include isolating valves in order to be
able to quickly isolate any section where there is a breakage and thus enable continuation of
fire-fighting. These barrier valves must be left open under normal operating conditions.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 80 / 95
If necessary, easy to remove filters shall be installed at judiciously selected locations on the
network to ensure correct operation of fire-fighting facilities (foam generators, sprayers, etc.).
The fire-fighting network pressure and flow rate shall be provided by pumping facilities
belonging to the depot or by a connection to an external pressurized water network offering all
guarantees required to ensure safe operation.
All fire-fighting water pumping facilities must be capable of providing the regulatory flow rate
as defined in article 606, at the pressure required to ensure correct operation of emergency
facilities.
There must be at least two pumps when the flow rate exceeds 120 m3/hour.
When more than half of the regulatory flow rate is provided only by electric motor-driven
pumping facilities, these motors must be powered by two separate and independent electricity
sources.
This rule is interpreted as follows: for example, separate energy sources are considered as
being the public power supply network and the electricity produced by the depot involved.
All diesel engines of a pumping unit must be provided with a starting system guarantying
immediate starting. This engine must be appropriately run-in.
602.322 – Special case concerning adjacent depots or depots close one to the other
When there are several adjacent depots or depots very close one to the other with a fire-
fighting network supplied by common pumping facilities, these facilities must be capable of
providing a flow rate equal to the sum of:
• the greatest flow rate prescribed for each of the depots separately;
• half of the total flow rate which would be prescribed for each depot involved.
[…]
604.1 – Water
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 81 / 95
604.2 – Foam
Without a preconceived opinion on the provisions below, the choice between fixed and mobile
facilities is left to depot managers who remain responsible for their choice. This choice must
be justified.
Floating roof tanks must comprise, when protected by fixed systems, a device making it
possible to retain the foam around the roof so as to be able to quickly cover the seal between
the roof and the tank shell. All provisions must, in addition, be taken to prevent that the scales
covering the seal impede the penetration of the foam in this seal.
Floating roof tanks of a unit capacity at least equal to 60 000 m3 must be protected by fixed
equipment making it possible to lay a minimum 0.20 meter layer of foam in 10 minutes over
the annular space of the roof, included between the tank shell and the previously mentioned
foam retaining device.
605.1 – Supply
Fixed cooling systems on the one hand, and fixed foam systems on the other hand, providing
protection of storage facilities must have separate connections to the internal fire-fighting
water distribution network.
605.2 – Control
Several fixed systems may be supplied by the same control valve. In this case, it is necessary
to be able to isolate each system in case of fire, in order to prevent useless water flow and
enable the efficient fire-fighting work. The valves used for isolation shall remain open during
normal operation.
605.3 – Accessibility
Control valves or connections must be accessible under all circumstances and be located
outside the retention bunds. If the distance is less than 25 meters from the closest wall of the
supplied tank(s), the valves must be located behind an incombustible screen with a four hour
fire resistance. This provision applies to collective premix or foam producing units.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 82 / 95
605.4 – Signage
Controls of all fixed fire-fighting systems including drain valves for water from retention bunds
must be identified by means of easy to read labels.
Article 606 – Calculation principles for the regulatory water flow rate
The regulatory water flow rate to schedule in a depot is the rate corresponding to the greatest
flow rate ensuing from the application of the provisions stipulated in articles 606-1 and 606-2.
The global flow rate available in the network must be calculated under the most unfavorable
assumptions of a fire occurring in a hydrocarbon tank in category B, C or D1.
The most unfavorable assumption is the case corresponding to the tank for which the sum of
Q1 and Q2 results in the greatest global flow rate Q:
• Q1 is the flow rate corresponding to cooling of all hydrocarbon tanks in categories B, C
or D1 located entirely or partly in the fictive cylinder plotted around the tank assumed
to be on fire and defined in the table below (including the tank assumed to be on fire),
• Q2 is the flow rate corresponding to the production of the foam on the tank assumed to
be onfire.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 83 / 95
R is given in meters
S is given in square meters
Q is given in cubic meters per hour
l/m2/min = liters per square meter per minute.
(1) For a cylindrical tank installed horizontally, the perimeter of its vertical projection on a
horizontal plan must be taken into account.
(2) The surface area involved is:
the total surface area for cylindrical tanks installed horizontally and for spherical tanks,
the side surface area (shell) for cylindrical tanks installed vertically.
606.2 – Special rules applicable to retention bunds only containing heavy fuel tanks
In retention bunds only containing heavy fuel tanks, the regulatory water flow rate corresponds
to the rate required to cool the largest tank at a rate of 15 liters per minute per meter of
circumference of this tank.
All hydrocarbon locations, other than pipelines, tanks and retention bunds, must be protected
by portable extinguishers or wheeled extinguishers, in compliance with certified standards and
efficient for the extinguishing of fires likely to occur.
The depot manager is responsible for defining the position and quantity of extinguishers
according to the locations and good works practice, on condition that the following minimum
requirements are satisfied:
• close to bulk offloading or loading stations: one wheeled 100 kg powder extinguisher or
two 50 kg extinguishers (extinguishers using other extinguishing products with
equivalent extinguishing capability and capacity are accepted),
• in container filling or packaging workshops: one certified 55B per 10 m2 or fraction of a
100 m2 surface area, with at least two extinguishers per location.
All transformer sub-stations, cutting stations or any location where one or several electric
motors are used must be equipped with at least two portable extinguishers, suitable for fires
involving electrical power.
Locations where numerous electrical equipment is used must be protected by an extinguisher
of the same type.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 84 / 95
607.3 – Extinguishers
Appropriate sand piles, with shovels and wheel-barrows, must be suitably located to channel
or stop product flow.
Sand must be maintained in a loose condition.
Precautions must be taken so that fire-fighting equipment is useable during freezing weather
conditions as well as normal conditions.
Fire-fighting and emergency facilities must be maintained in good working condition and be
routinely verified.
Moreover, diesel engines mounted in fire-fighting pumping units must be tested once every
fortnight and fuel feeders topped up after engines are used.
The foam agent expansion factor must be checked at least once per year.
Foam agent storage tanks must be cleaned as often as necessary.
All personnel working in the depot must undergo routine training, during drills organized once
a month, in the implementation of fire-fighting and emergency equipment and in the
performance of the various tasks scheduled in the Internal Emergency Plan.
A yearly drill is carried out with the participation of the fire brigade and the specialized
departments of depots which may have concluded a mutual assistance agreement, according
to the arrangements made between the depot manager and the authorities to whom the
specialized departments or fire brigade report.
All depot personnel must participate in a drill on a real fire at least once every two years.
Moreover, any user of a diesel or fuel oil self-service station must be trained in the steps to
take in case of a fire.
Transmission and alerting facilities are indispensable both for calling the emergency services
and for mustering of fire-fighting personnel, routing of reinforcements and communications in
case of a major operation.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 85 / 95
The date of drills and routing testing of fire-fighting equipment, as well as any remarks that
may be made, are recorded in a fire register of the type prescribed in article 28 of the decree
modified on July 10, 1913, related to public administration rules on the execution of provisions
in book II of the work code and the social provident scheme with regard to all general
protection and sanitation provisions, applicable to all related events.
In any depot housing more than 600 m3 of hydrocarbons in category B, C1 or D1, or more
than 10 000 m3 of hydrocarbons in category C2, except for self-service systems, the personnel
present at the depot must be appropriately trained for product transfer.
These types of depots may be guarded when no product transfer operations are being
performed, unless the intervention and surveillance task in case of an accident is performed
by operating personnel on the site or living less than 500 meters from these depots.
The guard or the personnel mentioned above must be trained by the depot manager and be
aware of the instructions to follow in case of a fire.
It is accepted that, in a depot automatically monitored by means of a remote signaling device,
the surveillance role is performed, when no product transfer operations are being performed,
by the operating personnel performing permanent safety duty at the monitoring center
transmitting alerts (alerts in case of fire or explosion, etc.) from the previously mentioned
remote signaling system. The surveillance center may be common to several depots and
must be provided with a telephone system.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 86 / 95
Diesel or fluid fuel self-service systems associated with depots containing more than
10 000 m3 of hydrocarbons in category C2 must be guarded unless the surveillance and
intervention role in case of an accident is performed by operating personnel of the depot, or
living less than 500 meters from these depots.
The dealer must ensure that the guard or the personnel indicated above have all instructions
to follow in case of an accident.
It is accepted that a common guard system can be organized in the case of a hydrocarbon
depot complex.
Depots located beside public roads must comply with ministerial instructions concerning
special signage in order to prohibit traffic on these roads, where applicable.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 87 / 95
The fire-fighting water network for protection water as well as the foaming system shall be
gridded and isolatable.
Dead end branches may be authorized following approval of a plan from the classified system
inspection department sent to the Prefect, under the condition that none of these non-gridded
sections are longer than 50 meters and are intended for works accessible or protectable by
other sections.
Comments:
Networks must be gridded at the output of the fire-fighting pumping room and branch lines
must start in the different directions immediately.
For example, the grid must not start at the corner of the first bund as this would make this
connection primordial to depot safety and endanger it in case of an explosion.
Dead end branch lines are an exception. In particular, branch lines are prohibited on bunds
with more than three rows of tanks or on bunds with no access from two other sides.
Fixed cooling rings on inaccessible tanks (several rows, retaining breast walls too high) shall
be designed both for water spraying and spreading of the foaming solution. Rings shall be
independently isolatable from the water network and the emulsion network. Furthermore, they
shall be isolatable tank by tank from outside the bunds.
Comments:
Fixed cooling rings must now be mixed (water and foam) so as to enable water spraying in
case of a neighboring fire, and foam spraying in case of a fire in the bund.
To limit spraying, especially in the case of a neighboring fire or destruction in case of an
explosion, each tank must be supplied separately from outside the bunds, where the isolating
valves shall be installed.
The water network shall be equipped with unfreezable standardized hydrants or outlets,
diameter 100 mm or 2 x 100 mm.
This network shall be equipped with standardized couplings for supply by mobile facilities such
as engine-driven pumps. These couplings shall be installed in compliance with the
instructions of the fire-fighting and emergency services and, if possible, located far from the
fixed fire-fighting pumping unit.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 88 / 95
Comments:
Network supply couplings must be provided in case the pumping unit does not operate or if
the flow rate or pressure is insufficient.
Fire hydrants recently installed during the extension to or repair of the network shall comply
with new standards (100 mm and 2 x 100 mm). However, former 150 diameter hydrants may
be used as long as appropriate adapting couplings are available.
The fire-fighting flow rate set down in the Prefectoral Order shall make it possible to protect all
buildings or units located within the fire zone, or less than 50 meters from it, and to fight or
confine the fire as defined in article 12.
For tanks fitted with non-isolatable cooling rings, or tanks located in fire zones (e.g. retention
bund fire) the reference flow rate shall be the same as the ring flow rate.
For tanks located outside the fire zone and fitted with cooling rings isolatable sector by sector,
only the flow rate of sectors exposed to the fire shall be taken into account.
For tanks not fitted with cooling rings, the reference flow rate will be that given for nozzles
recommended for protection.
The water flow rates shall be those selected in pursuance of article 12 for the production of
foaming solution intended for confinement or fighting of liquid fires.
Comments:
The regulatory water flow rate must be calculated on concrete cases using hazard studies
complying with the legislation related to classified systems and indicated on Internal
Emergency Plans of depots. This flow rate will be used for the protection of equipment in the
fire zone and for fighting fires with foam, as well as for the protection of neighboring systems
with water.
As an example, the National Fire Protection Agency (N.F.P.A.) and British Standards
recommend a 10 l/m²/min water flow rate on surfaces exposed to the fire. This value may be
used to size mobile spraying facilities according to surface areas directly exposed to the fire.
For fixed rings, the flow rate of 15l/mm/m of circumference retained in the ministerial order
dated 1972 can be used for both fixed and floating roofs. This value is used in Germany.
For water curtains, the Civil Security Department retains a set flow rate of 500 l/mm for a 30 m
length and 1000 l/mm for a 40 m length.
The depot manager shall take the necessary steps to have available the equipment required
to extinguish all types of fires likely to occur in the depot, either by means of the facilities of the
depot, or by mutual assistance agreements or protocols specified in the Internal Emergency
Plans prepared with the fire-fighting services. The facilities maintained on the site, especially
the foam agent reserve and its means of implementation, shall make it possible to:
• extinguish, in 20 minutes, and cool the largest diameter tank as well as protect
threatened neighboring tanks
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 89 / 95
• fight the fire in the largest retention bund (less tanks) with foam at a reduced rate of
application to contain the fire and simultaneously protect systems threatened by the
fire, as defined in articles 11 and 19. These facilities shall be operational for at least
one hour up to the arrival of external assistance.
To determine the foaming solution facilities required to extinguish liquid fires (tank fire or
retention bund fire) the theoretical rate of application shall be as follows, unless explicit
substantiation is provided:
o 5 l/m²/min for hydrocarbons without additives,
o 7 l/m²/min for hydrocarbons with less than 5% additives,
o 10 l/m²/min for hardly soluble polar products,
o 15 l/m²/min for polar products, more than 50% soluble in water. (To calculate
the foam agent reserve, the concentration in the foaming solution shall be
considered as a fixed amount, being 5%).
The reduced rate of application intended to contain the fire shall be considered as being half
the theoretical rate of application.
The depot manager shall verify the quality of the foam agents selected to check that it is
compatible with stored products, and the facilities of the depot as well as common facilities.
The Internal Emergency Plan shall be revised taking into account these new provisions and
shall make it possible to envisage the extinguishing of a retention bund fire within three hours.
Comments:
The latest fires in depots have led the Civil Safety Department to revise its technical
instruction dated 1979 concerning hydrocarbon fires.
As of now, the following technical provisions may be implemented:
• the foam agent reserves and the facilities required to extinguish a major tank fire shall
be 20 minutes, based on the rate of application prescribed according to the type of
liquid on fire;
• the equipment and water facilities (monitors, spillways, etc.) must correspond to the
targeted goals (currently it is recommended to only count foam monitors with a
capacity greater than 1 000 l/min, with preference for 2 000 l/min, since the range of
the least powerful monitors is often insufficient).
As of the beginning of a retention bund fire up to grouping of all facilities required to fully
extinguish the fire, it is recommended, to contain the fire, to apply a reduced rate of product on
the surface on fire equal to half the application rate required to extinguish the fire.
For some recent exceptionally high performance foam agents, the general rules may therefore
be revised following presentation of technical justification by depot managers and foam agent
suppliers, following approval by the fire-fighting and emergency services and the classified
system inspection department.
It will be accepted that chemical or petroleum companies belonging to organizations such as
the GESIP, replace depot managers to qualify or test the foam agents.
The foam agent reserve shall be available in 1 000 liters minimum containers. The location of
containers shall be studied to enable easy use when increasing the number of facilities used
for fire-fighting. The 200-liter barrels shall be replaced as soon as possible. Containers of a
lower capacity shall not be counted in the foam agent reserves.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 90 / 95
Mixed hydrocarbon and polar product depots shall only have polyvalent foam agent reserves.
Gasoline and fuels containing more than 5% oxygenated products are assimilated to polar
products.
Comments:
As hydrocarbon foam agents are not compatible with polar product fires, it is not advisable to
have the two different types of quality available in a single depot. The use of polyvalent foam
agents shall be preferred to prevent any confusion during an accident.
Implementation drills of fire-fighting equipment, especially foam agent tests on a real fire,
musty be organized once per year, conjointly between the depot manager, the fire brigade and
the authorities.
Comments:
The reaction of certain chemical products with regard to foam agents is not well known.
Furthermore, the gradual introduction of oxygenated compounds (TAME, MTBE, TBA) in
gasoline gives the compounds a more and more significant polar characteristic.
Tests must be undertaken for each significant modification to stored products.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 91 / 95
Technical instruction dated November 9, 1989 stipulates in article 12 the objectives making it
possible to assess the technical facilities required to extinguish a flammable liquid fire. These
objectives are as follows:
extinguish, within twenty minutes, a fire on the largest tank while cooling it and protecting
threatened neighboring tanks,
contain, for sixty minutes minimum, a fire on the largest retention bund by spraying foam with
a reduced foaming solution rate of application (timing strategy) whilst protecting threatened
neighboring tanks.
The flow rates and quantities of foaming solution required to attain these objectives are
calculated on the basis of the timing strategy (also called reduced rate) or extinguishing rate of
application. Flow rates and quantities depend on the quality of the foam agent used, the type
of product on fire and the operational implementation conditions of fire-fighting facilities.
The rate of application values prescribed in technical instruction dated November 9, 1989 is
fixed values overriding the different criteria given above. In order to take into account changes
to the quality of foam agents and to better integrate the importance of the fire-fighting capacity
in the definition of extinguishing facilities, a work group comprising the various administrations
involved and representatives from the petroleum industry has defined a method to determine
the rates of application based on experience feedback.
This method is based on an extinguishing test campaign carried out on fuel fires with 15%
added oxygenated organic products and on the difficulties encountered in a true life situation.
The recommended rate of application thus takes into account stressing factors proper to the
configuration of the site involved, time delays and intervention facilities. This method is
summarized in appendix 1.
Intervention facilities must be designed to meet the objectives of technical instruction dated
November 9, 1989, presented above. The assumption in which the reduced rate of
application (timing strategy) is equal to half the extinguishing rate of application is kept.
The provisions in this circular will be taken into account for new authorization requests
concerning storage of flammable liquids. Also, requests may be received from dealers
managing existing systems and wanting to assess the intervention facilities required on the
site, based on this new method. In this case, it will be necessary to ask the depot manager to
provide all necessary justification in compliance with the methods provided in this circular, in a
rider to the hazard study.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 92 / 95
In all cases, make sure that the Authorities receive the opinion and proposal from the fire
brigade with regard to the operational coefficient, the water flow rates and the quantity of foam
agents, as calculated. This dossier shall be accompanied by a report from the Authorities.
Also, make sure that the Internal Emergency Plan is updated to integrate any new steps
related to the intervention.
To extinguish a fuel fire with 15% oxygenated products added, the experimental extinguishing
rate of application values calculated using test campaign results are:
• 2 l/m²/min for film forming foam agents, class I,
• 2.5 l/m²/min for non-film forming foam agents, class I,
• 3 l/m²/min for class II foam agents.
Following application of the set increase of 0.5 l/m²/min, the minimum rate of application
values are therefore:
• 2.5 l/m²/min for film forming foam agents, class I,
• 3 l/m²/min for non-film forming foam agents, class I,
• 3.5 l/m²/min for class II foam agents.
The operational coefficient, K, is calculated by working out the sum of increases allocated to
the various parameters in the tables below, in compliance with the formula:
K1= 1 + (f1xf2)
where f1 represents the sum of increases related to factors directly affecting the rate of
application, i.e. accessibility to the sides of the retention bund, encumbrances in the bund,
range of nozzle jets and climatic considerations. Its value is between:
• f1 min = 0
and
• f1 max = 1.25 for a class I foam agent
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 93 / 95
or
• f1 max = 1.5 for a class II foam agent.
• f2 represents the increase related to the implementation time delay factor of facilities.
Its value is equal to: f2 = 0 or f2 = 0.25 or f2 = 0.5
The different parameters must be assessed on a case by case basis integrating the presence
of fixed facilities making it possible to compensate for increases due to penalizing conditions.
The definition and the explanatory notice of these parameters are given in report no. 97/06 of
the GESIP. This report also includes examples for the calculation of operational coefficient K.
Operational coefficient K may be assessed no matter what the flammable liquid is contained in
the tank involved as it characterizes the intervention capability proper to the depot. A set
increase of 0.5 l/m²/min should also be added to the rate calculated by testing for any other
flammable liquid.
The experimental rate of application presented above for fuel with 15% oxygenated products
added may also be used as a reference for all standard hydrocarbons with at the most 15%
oxygenated products added, as their characteristics prove that they are not more difficult to
extinguish. On the other hand, these rates cannot be used as a reference for flammable
liquids containing more than 15% oxygenated products.
In cases where the dealer does not have significant information (meaningful test results,
information from experience feedback, etc.), the experimental rate of application for another
flammable liquid shall be calculated using a test campaign carried out, taking into account the
specific nature of the product, using a protocol comparable to the one in the report no. 97/06
of the GESIP. The rates currently indicated in the texts in force shall be used if there are no
such tests analyzed conjointly with the ministerial departments involved.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 94 / 95
(*) The zones correspond to regions I, II, III or IV in the "Snow and Wind Rules".
When a retention bund fire surface area becomes too high, the intervention is faced with
logistic problems which do not make it possible to guarantee the extinguishing of the entire
surface area of the retention bund, even with a large rate of application allowance. The
method proposed below for surface areas greater than 6 000 m2 is based on the limiting of the
propagation of the fire to a more restricted surface area on fire.
To attain this goal, one of the most appropriate techniques consists of dividing the bund into
sub-bunds, where the surface areas are calculated according to:
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.
GUIDELINES OMLOG-LD-001-an
Revision: 03
Liquid hydrocarbon depots – Date: 19/12/2006
Fire-Fighting Guidelines
RM/OM/LA/LOG Page 95 / 95
The maximum leakage flow rate shall be calculated based on scenarios selected in the hazard
study.
This document belongs to TOTAL. Disclosure and reproduction subject to its permission.