Level Sensor

The document provides a detailed report on the configuration and status of a Cerabar M 5x pressure transmitter with the tag LT101. Key details include: 1) The transmitter is configured to measure level using pressure with an output range of 1.4 to 6 meters. 2) Diagnostics indicate the transmitter is in good condition with no errors reported. 3) Current output is configured to produce a signal between 3.8 to 22 mA corresponding to the set level range with the current output at 6.309 mA.

Uploaded by

ykanchanam
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
235 views

Level Sensor

The document provides a detailed report on the configuration and status of a Cerabar M 5x pressure transmitter with the tag LT101. Key details include: 1) The transmitter is configured to measure level using pressure with an output range of 1.4 to 6 meters. 2) Diagnostics indicate the transmitter is in good condition with no errors reported. 3) Current output is configured to produce a signal between 3.8 to 22 mA corresponding to the set level range with the current output at 6.309 mA.

Uploaded by

ykanchanam
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Page 1 of 8

Device Report
Tag: LT101

Host PC, COM4 [HART Communication], HARTCH,


Communications Path:
[Cerabar M 5x / PMx 5x / V1.00.xx]:0
DTM Status: Online
Device address: 0
Serial number: KB07C401129
Device Type: Cerabar M 5x / PMx 5x / V1.00.xx
Vendor: Endress+Hauser
Class: Pressure
Version: 1.4.184.499

about:blank 7/3/2016
Page 2 of 8

DTM Version: 1.4.184

about:blank 7/3/2016
Page 3 of 8

OnlineParameterize
Language
Language English

Display/Operat.
Display mode Main value only
Add. disp. value None
Format 1st value Auto

Setup
Measuring mode Level
Press. eng. unit mH2O
Corrected press. 0.958mH2O
Pos. zero adjust Abort
Damping switch On
Damping value 2.0s
Level before Lin 2.133m
Pressure af.damp 0.956mH2O

Extended setup
Code definition 0
Device tag LT101
Operator code 0

Level
Level selection In pressure
Output unit m
Calibration mode Dry
Empty calib. 1.4000m
Empty pressure 0.0000mH2O
Full calib. 6.0000m
Full pressure 6.0000mH2O
Adjust density 1.000g/cm³
Process density 1.000g/cm³
Level before Lin 2.133m

Linearization
Lin. mode Linear
Unit after lin. %
Line-numb: 1
X-val: 0.000m
Y-val: 0.000%
Edit table Current Point
Tank description ________________________________

Current output
Alarm behav. P Warning
Alarm cur.switch SW setting
Output fail mode Max
High alarm curr. 22.000mA
Set min. current 3.8 mA
Output current 6.503mA
Set LRV 1.4000m
Set URV 6.0000m

about:blank 7/3/2016
Page 4 of 8

Diagnosis
Status Good
Diagnostic code No error
Instructions No action needed
Last diag. code S971 Adjustment
Min. meas.press. -0.4381966mH2O
Max. meas.press. 14.2257271mH2O

Diagnostic list
Diagnostic 1 No error
Instructions 1 No action needed
Diagnostic 2 No error
Instructions 2 No action needed
Diagnostic 3 No error
Instructions 3 No action needed
Diagnostic 4 No error
Instructions 4 No action needed
Diagnostic 5 No error
Instructions 5 No action needed
Diagnostic 6 No error
Instructions 6 No action needed
Diagnostic 7 No error
Instructions 7 No action needed
Diagnostic 8 No error
Instructions 8 No action needed
Diagnostic 9 No error
Instructions 9 No action needed
Diagnostic 10 No error
Instructions 10 No action needed

Event logbook
Last diag. 1 S971 Adjustment
Last diag. 2 S841 Sensor range
Last diag. 3 S971 Adjustment
Last diag. 4 S140 Working range P
Last diag. 5 S971 Adjustment
Last diag. 6 S841 Sensor range
Last diag. 7 S140 Working range P
Last diag. 8 S971 Adjustment
Last diag. 9 S140 Working range P
Last diag. 10 No error

Instrument info
Firmware version 01.00.03
Serial number KB07C401129
Ext. order code PMP51-AA21JA1HGDU4JA1+AAMBPA
Order identifier PMP51-4KL25/0
Cust. tag number ________
Device tag LT101
ENP version 02.01.01
Config. counter 103
LRL sensor -10.20mH2O
URL sensor 10.20mH2O
Manufacturer ID 17
Device type code 25
Device revision 1

about:blank 7/3/2016
Page 5 of 8

Measured values
Level before Lin 2.082m
Meas. pressure 0.889mH2O
Sensor pressure 0.907mH2O
Corrected press. 0.883mH2O
Pressure af.damp 0.886mH2O
Sensor temp. 37.6°C

Simulation
Simulation mode None

Reset
Enter reset code 0

System
Code definition 0
Lock switch Off
Operator code 0

Instrument info
Cust. tag number ________
Device tag LT101
Serial number KB07C401129
Firmware version 01.00.03
Ext. order code PMP51-AA21JA1HGDU4JA1+AAMBPA
Order identifier PMP51-4KL25/0
ENP version 02.01.01
Electr.serial no KB4D7801BCC
Sensor serial no KB003801BCF

Display
Language English
Display mode Main value only
Add. disp. value None
Format 1st value Auto

Management
Download select. Configuration copy
Enter reset code 0

Measurement
Measuring mode Level

Basic setup
Pos. zero adjust Abort
Calib. offset 0.0000mH2O
Damping switch On
Damping value 2.0s
Press. eng. unit mH2O
Temp. eng. unit °C
Sensor temp. 37.6°C

Pressure
Meas. pressure 0.889mH2O

about:blank 7/3/2016
Page 6 of 8

Sensor pressure 0.907mH2O


Corrected press. 0.883mH2O
Pressure af.damp 0.886mH2O

Level
Level selection In pressure
Output unit m
Calibration mode Dry
Empty calib. 1.4000m
Empty pressure 0.0000mH2O
Full calib. 6.0000m
Full pressure 6.0000mH2O
Density unit g/cm³
Adjust density 1.000g/cm³
Process density 1.000g/cm³
Level before Lin 2.082m

Linearization
Lin. mode Linear
Unit after lin. %
Line-numb: 1
X-val: 0.000m
Y-val: 0.000%
Edit table Current Point
Tank description ________________________________

Sensor limits
LRL sensor -10.20mH2O
URL sensor 10.20mH2O

Sensor trim
Lo trim measured 0.0227734mH2O
Hi trim measured 10.0335197mH2O
Lo trim sensor 0.0003mH2O
Hi trim sensor 10.0096mH2O

Current output
Output current 6.309mA
Alarm behav. P Warning
Alarm cur.switch SW setting
Output fail mode Max
High alarm curr. 22.000mA
Set min. current 3.8 mA
Set LRV 1.4000m
Set URV 6.0000m
Startcurrent 12mA
Curr. trim 4mA 4.000mA
Curr. trim 20mA 19.998mA
Offset trim 4mA 0.000mA
Offset trim 20mA 0.002mA

HART config
Burst mode Off
Burst option Command 1
Current mode Signaling

about:blank 7/3/2016
Page 7 of 8

Bus address 0
Preamble number 5

HART info
Device type code 25
Device revision 1
Manufacturer ID 17
Hart version 6
Descriptor ________________
HART message ________________________________
HART date 19.11.15

HART output
Primary value is Level before lin
Primary value 2.0475657m
Secondary val.is Meas. pressure
Secondary value 0.8417556mH2O
Third value is Corrected press.
Third value 0.8350395mH2O
4th value is Temp. sensor
4th value 37.5221252°C

HART input
HART input value 0.0Unknown
HART input stat. Uncertain
HART input unit Unknown
HART input form. x.x

Application
Electr. delta P Off

Diagnosis
Status Good
Diagnostic code No error
Instructions No action needed
Last diag. code S971 Adjustment
Reset logbook Abort
Min. meas.press. -0.4381966mH2O
Max. meas.press. 14.2257271mH2O
Reset peakhold Abort
Operating hours 3900
Config. counter 103

Diagnostic list
Diagnostic 1 No error
Instructions 1 No action needed
Diagnostic 2 No error
Instructions 2 No action needed
Diagnostic 3 No error
Instructions 3 No action needed
Diagnostic 4 No error
Instructions 4 No action needed
Diagnostic 5 No error
Instructions 5 No action needed
Diagnostic 6 No error

about:blank 7/3/2016
Page 8 of 8

Instructions 6 No action needed


Diagnostic 7 No error
Instructions 7 No action needed
Diagnostic 8 No error
Instructions 8 No action needed
Diagnostic 9 No error
Instructions 9 No action needed
Diagnostic 10 No error
Instructions 10 No action needed

Event logbook
Last diag. 1 S971 Adjustment
Last diag. 2 S841 Sensor range
Last diag. 3 S971 Adjustment
Last diag. 4 S140 Working range P
Last diag. 5 S971 Adjustment
Last diag. 6 S841 Sensor range
Last diag. 7 S140 Working range P
Last diag. 8 S971 Adjustment
Last diag. 9 S140 Working range P
Last diag. 10 No error

Simulation
Simulation mode None

about:blank 7/3/2016