Grounding System For PDS
Grounding System For PDS
Wye
Connected
Summing
Point
.
E
.
P
,
S
P
I
Residually Connected Ground Fault Scheme Current In Amperes L
L
I
H
P
M
I
J
.
E
.
P
,
S
P
I
L
L
I
H
P
M
I
J
The simulation illustrates the dramatic reduction in Since the resistor is connected between the neutral
ground fault current from 11,202 amps to a very man- and ground, the voltage on the ground side of the resis-
ageable 596 amps, which would greatly limit damage tor should normally be zero. However when there is a
but be large enough to trip a correctly set ground fault ground fault, the return current will develop a large
protective device. voltage across the resistor that raises the voltage on the
Grounding resistors used for low-resistance grounding neutral side of the resistor. According to NEC Article
are not usually designed to carry the rated current 250.186 (B), the conductor insulation rating for the
continuously, 600 amps for this example, but rather neutral conductor of a grounding resistor used in
for a limited time such as 10 seconds. The time rating systems greater than 1000 volts must have the same
is the duration that the resistor can carry rated current insulation rating as the phase conductors. This is a
without exceeding its temperature rating. Both time and different requirement than if an insulated neutral was
temperature ratings for grounding resistors are defined part of a solidly grounded system. In the case of a
by IEEE Standard 32-1972 and have time ratings from solidly grounded system, Article 250.184 (A) (1) allows
10 seconds to continuous, and temperature ratings from a minimum insulation level of the neutral conductor to
385 ºC to 760 ºC for their allowable temperature rise be 600 volts for solidly grounded systems.
as shown in the table below. Since the current rating of
low-resistance grounding resistors is not for continuous The Design will use a ___________Grounded System
operation, it is important that ground fault protection Just fill in the blank. Solidly grounded, ungrounded, high-
be set to trip off-line before the combination of time resistance grounded, low-resistance grounded; there are
and current allows the resistor to exceed its temperature so many options available for grounding power distribu-
rating. tion systems. Most of the time, solidly grounded systems
are used and work quite well. However, when service
Allowable Temperature Rise for Various Time Ratings
continuity or minimizing damage due to ground faults are
IEEE Standard 32-1972
of paramount importance, options other than solidly
Time Rating Duration Allowable Temperature grounded systems should be explored.
Rise above 30°C Ambient Selecting the correct grounding scheme for a power dis-
Short Time Typically used where tribution system is a function of economics, reliability,
protective devices will 760 ºC and Code requirements. When allowed by the NEC,
clear the fault quickly resistance grounding schemes can reduce ground fault
Extended Used where fault currents current, voltage transients and damage. High-resistance
Time can last an extended 610 ºC grounded systems are becoming more widely used as an
period of time but not more alternative to traditional ungrounded systems offering the
. than 90 days per year
E
.
P
same continued operation during a ground fault. Unlike
,
S
P
I
L Continuous Can carry the rated current the ungrounded system, the high-resistance system also
L
I
H
P for an indefinite period of time 385 ºC minimizes transient overvoltages and provides easier fault
M
I
J location capability.