Danfoss String Inverters Vs Central Inverters
Danfoss String Inverters Vs Central Inverters
Concept paper
String inverters for PV power plants
February 2009
SOLAR INVERTERS
Table of Contents
It is well known that there is a coupling between inverter size and specific cost in €/kW. Therefore,
when creating state of the art PV plants in the multi MW range the norm has been to utilise as large
inverters as possible in the effort to drive down the investment cost. Today, central inverters are
available up to a power level between 1 and 2 MW. However, this development trend towards
larger and larger inverters is driving external costs higher.
The inherent modular nature of PV modules (largest module is still below 500W) means that a PV
plant of any size is modular. Hence, it makes sense to look at alternative ways to structure a PV
plant.
By using string inverters as a modular element in the plant, the built-in functionalities of the string
inverters make many of the additional functions that are needed when applying a central inverter
station superfluous.
String inverters of today offer the major advantages of central inverters such as high DC system
voltage range and three-phased output while still maintaining the high efficiencies. This leads to
reduced losses in both AC and DC cabling assuring higher yield. A large number of maximum
power point trackers ensure that more power from the panels is utilised. Additionally, string
combiners and external string monitoring are not required thus making simple cabling possible.
Using compact transformer stations to connect the string inverters to the Medium Voltage grid
means that both transformer stations and inverters can be placed amongst the PV module
substructures with little influence. Furthermore compact transformer stations and string inverters
are easy to install and have short lead times as they are commonly used.
Special training is not required to install, maintain or exchange string inverters, whereby service
contracts known from central inverters can be avoided. By omitting junction boxes, service on the
DC side is also avoided.
This paper will highlight why string inverters are an attractive alternative to central inverters in
power plants. This is done by means of an example of a 10 MWp plant in central Europe with 15
identical quadratic PV fields, 15 individual 630 kVA transformer stations and 15x42 TripleLynx
inverters.
By using inverters that can handle 1000 V input; junction boxes and a number of string combiners
can be omitted. The DC cables are laid directly from the string of modules to the inverter.
A 630 kVA transformer station can have 42 inverters connected directly and the necessary
switchgear including the low voltage distributor fit into the low voltage area of the transformer
station.
Additionally, 665 kWp PV fields of modular design are profitably erected in larger numbers.
Inverter
Substructures
1
MPPT
2 ~
3
The string voltage at NOCT is well above 600 VDC providing optimum efficiency. Additionally, yield
reductions due to DC cable losses are greatly reduced.
The individual MPP tracking for every string (or string group when using modules with lower MPP
current), which is a major advantage of string inverters, enables maximum energy yield per string.
If additionally the three rows of modules per PV substructure are connected to each their own MPP
tracker the risks of losses due to shading are greatly reduced. This is due to the fact that each string
group then has its own independent MPP tracker to control and optimise output. If a string
The use of a low loss transformer reduces the nightly power consumption of the transformer to
below 0.4% of the yearly production. Consequently, short circuit losses in the transformer have little
effect on overall yield. In the medium voltage area of transformers of this size, outgoing feeder
panels with HH-fuses can be inserted instead of the more expensive power-switches. All voltage in
long cabling is converted to the medium voltage level with consequently smaller losses.
To minimise losses due to shading (shed shading) it is advised to mount 3 rows of modules in
landscape orientation per substructure. Wire the modules so that each row forms its own string.
These three strings are then connected individually to the three inputs of the inverter.
Such a configuration will in addition provide a slight advantage on winter days where the lower
modules are often in shadow. A similar advantage can be found on summer days with no wind and
high irradiation where the top module row will experience a slightly higher temperature level and
thereby lower MPP voltage.
The 3 MMP trackers will then optimise the individual rows rather than use a combined average, as
would be the case if the strings were connected in parallel.
The layout with 5.28 kWp per string or 15.9 kWp in total will give a layout factor of Psolar/Pinverter =
1.06 which is within the recommendations given by Dr Bruno Burger1 for a plant placed in central
Europe. The high inverter efficiency and the lower module temperature experienced due to ground
based mounting have been taken into consideration.
The layout can be achieved in different ways but the 1000 V open circuit voltage must of course be
utilised.
For monocrystalline or polycrystalline modules based on 156 x 156 mm cells there are two options
depending on the number of cells per module:
• 1 string of 24 modules (220 W with 60 cells) on each of the 3 input
• 1 string of 30 modules (175 W with 48 cells) on each of the 3 input
1
Inverter sizing for grid connected PV plants, Dr.-Ing. Bruno Burger, Fraunhofer-Institut für Solare
Energiesysteme ISE, Heidenhofstraße 2, D-79110 Freiburg.
http://www.ise.fraunhofer.de/veroeffentlichungen/nach-jahrgaengen/2005/auslegung-und-dimensionierung-
von-wechselrichtern-fur-netzgekoppelte-pv-anlagen/at_download/file
For installations in southern Europe where a lower layout factor is recommended the power can
easily be lowered by:
- Connecting fewer modules on a single string when using polycrystalline modules
- Reducing the number of strings on a single input when using thin film modules.
With the inverters placed centrally in close proximity to the transformer station it is easy to carry
out the wiring for data transmission. Inverters can be connected in series using a standard Cat 5
cable. The cable can be connected directly to the inverter by either using screw terminals or pre-
fabricated cables with RJ45 connectors.
For all inverter inputs it is possible to monitor current and MPP voltage individually. This means
that even with 7 strings of CdTe modules detection of error in an individual string (720 Wp) is
possible down to the affected inverter input (5 kWp) without additional equipment. See figure 2.
Data is recorded in 10 minute intervals and is normally transmitted to a data warehouse service
daily.
Furthermore, in case of failure only a smaller part of the system will be affected. With the 10 MW
plant it means more than 6 inverters must completely fail before the loss reaches 1% of production.
With the proposed compact transformer stations yearly service on the medium voltage grid will
require slightly more effort, due to the number of transformer stations. However, no service is
required on the DC side as junction boxes are omitted. E.g. no problems due to broken DC fuses.
The 5-year warranty remains unchanged for inverters used in large plant applications and warranty
prolongation to 10 years is possible.
To aid the installer or plant supervisor during fault finding each inverter comes with a display.
GRÄPER
GRÄPER GRÄPER
GRÄPER GRÄPER
GRÄPER
GRÄPER GRÄPER
GRÄPER GRÄPER
GRÄPER
GRÄPER GRÄPER
Danfoss Solar Inverters A/S
Jyllandsgade 28
DK-6400 Sønderborg
Denmark
Tel: +45 7488 1300
Fax: +45 7488 1301
E-mail: [email protected]
www.solar-inverters.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Rev. date 2009-02-19