The power behind competitiveness

Delta InfraSuite
Data Center Infrastructure Solutions

www.deltapowersolutions.com
Delta InfraSuite
Data Center Infrastructure Solutions

Enterprise growth and IT equipment have become so closely linked that planning and building a high performance data
room is one of the critical issues for IT managers today.
With 40 years of leadership in the core technologies of power electronics, the expert teams at Delta Electronics have
developed a new generation of data center infrastructure solutions: InfraSuite.
Delta InfraSuite includes power system, rack & accessories, precision cooling, and environment management system.

Power Rack &


Management Accessories
Integrated power Smart, modular design for
optimizing space utilization
distribution for optimal
power
management
InfraSuite
Fully integrated design
and scalable system
architecture

Precision Cooling Environment


Highly efficient,
Management System
energy-saving Have the entire data center at
temperature control your fingertips

2009 Frost & Sullivan Delta’s Manufacturing System is IECQ Certificate of


2007~ 2008 Hazardous Substance
Green Excellence Certified by ISO 9001 and
Forbes Asia’s Process Management
Award for Corporate ISO 14001 Standards
Fabulous 50
Leadership

Delta InfraSuite 1
Delta InfraSuite Products and Services
InfraSuite advantages include:

• Modular design for quick and easy assembly


• Scalability to match data center with enterprise growth
• Optimized installation and operation costs
• High efficiency, energy-saving power components for eco-friendly data rooms
• Easy integration with all data room structures
• A complete environment management system for worry-free operations

Power Management Rack & Accessories Management System Precision Cooling Service

➊ UPS ➏ Modular Rack ➑ InfraSuite Manager 11 RowCool


➒ System Design and Planning

➋ Power Distribution Cabinet ➐ Rack Accessories ➒ EnviroStation Rapid and Comprehensive


Services
➌ Rack-mounted Power 10 EnviroProbe

Distribution Cabinet

➍ Power Distribution Unit

➎ Static Transfer Switch

9
10

11 1
8 2 or 3
5

2
Delta InfraSuite
Data Center Infrastructure Solutions

InfraSuite Manager

Have the entire Power by Intel® Data Center Manager

datacenter
at your fingertips!

● InfraSuite Manager integrates all


facilities and IT equipment on
one platform.
● Power Capping Module
integrates with Intel® DCM,
delivers server-level power
capping for critical situations to
reduce server heat generation.

Rack and Accessories


● Modular server racks with high
perforation rate over 70% which
increases heat dissipation
● Avoids cold and hot air mixture to
significantly improve PUE < 1.5

Delta InfraSuite 3
CP+
Modular Green Container Cloud High High Power High TCO
Datacenter Datacenter Datacenter Datacenter C/P Value Density Reliability Optimization

Precision Cooling
● Highly-efficient variable fan speed control saves 27% of
power if fan speed reduced by 10%

Power Distribution System


● PDC : Modular and hot-swappable
output breakers
● PDU : Reliable branch circuit breaker
protection
● RPDC:an ideal power distribution
solution to small datacenters

UPS System

● Fully modular design. Hot-scalable and


hot-swappable.
● Ultra-integrated system with power supply,
power distribution and runtime.
● Output PF =1
● Leading power efficiency up to 96%

4
Delta UPS
Our clients are most concerned about power issues such as power failure, power sag, power surge, under voltage
or over voltage, frequency variation, harmonic distortion and line noise. Delta Electronics emphasizes the areas of
redundant power supply, voltage regulation, equipment protection and adjustment and has designed and developed
three UPS product families - Agilon, Amplon, Ultron and Modulon. Their power range, applications and the equipment
they protect are listed below:

Product Family Power Topology Applications


Agilon Under 1kVA Single-Phase UPS PC and Peripherals
Amplon 1kVA or higher Single-Phase UPS Server and Network Equipment
Ultron 10kVA or higher Three-Phase On-Line UPS Datacenter and Industrial Equipment
Modular unit expansion and redundant power supply
Modulon 20kVA or higher Three-Phase Modular On-Line UPS
can be achieved within a single rack.

Delta UPS systems feature the following:

• Leading AC-AC Efficiency


• Fully redundant design and configuration
• High input and output power factors
• Easy expansion without additional hardware
• Supports to seamless operations at low level of TCO (Total Cost of Ownership)

DPS
Delta provides full range of UPSs to fulfill
datacenters from small to big sizes NT
DPH

NH Plus

HPH 160~500kVA

20~500kVA
25~200kW
Large Data Center
EH
20~120kVA
Medium Data Center
20~120kVA

N, M, RT
10~20kVA
Small Data Center

1~10kVA
Rack/Computer Room

Delta InfraSuite 5
Power Management

Product Application Matrix

Amplon

M Series N Series N Series R Series RT Series RT Series


1-3 kVA 1-3 kVA 6-12 kVA 1-3 kVA 1-3 kVA 5-10 kVA
(line-interactive) (on-line) (on-line) (on-line) (on-line) (on-line)

Configuration 1:1 O O O O O O
Configuration 3:1
Configuration 3:3
Rack mountable O O O O
Stand-alone O O O O O O
Isolation transformer O
Battery ’ I,E I, E I, E E I, E E
Home and office * O O O 
Small enterprise, IT and
O O O O O O
medical **

Medium enterprice,
O O
telecom, IT, media ***

Heavy industry,
telecom, IT, Industrial
****
Ultron Modulon

EH Series HPH Series NT Series DPS Series NH Plus Series DPH Series
10-20 kVA 20-120 kW 20-500 kVA 160-500 kVA 20-120 kVA 25-200 kW
(on-line) (on-line) (on-line) (on-line) (on-line) (on-line)

Configuration 1:1
Configuration 3:1 O O
Configuration 3:3 O O O O O
Rack mountable
Stand-alone O O O O
Modular O O
Isolation transformer O O
Battery ’ E I, E E E E E
Home and office *
Small enterprise, IT and
O O
medical **

Medium enterprice,
O O O O O O
telecom, IT, media ***

Heavy industry,
telecom, IT, Industrial O O O O O
****

‘ I: internal battery, E: external battery

* PCs, laptops, modems, printers, WiFi and audio equipment


** Computers, servers, networking, medical control and diagnostics, education, banking, industrial automation
*** Telecom base stations, data centers, backbone networks, broadcasting, projection systems
**** Telecom centers, data centers, medical equipment at hospitals, government use, automatic control, oil, gas and power utilities, industrial
equipment, automation and control

6
Delta InfraSuite Power Management
Uninterruptible Power Supply, Modulon DPH Series

Achieve the ultimate availability and scalability


The Modulon DPH supports ultimate availability for datacenter operations and
provides the benefit of “pay as you go” without over-sizing the UPS. While
achieving ultimate availability, the Modulon DPH does not compromise on power
efficiency performance. When availability, efficiency and expanding according
to business needs are essential, the Modulon DPH is the ideal UPS system to
provide power protection and total cost of ownership (TCO) savings.

Ultimate Availability
• Advanced fault tolerance design achieved by self redundancy to guarantee
operation continuity
• Self-synchronization of power and control modules for continuous on-line
operation even in the event of control module failure to avoid downtime caused
by single point failure
• Hot-swappable key modules and components to ensure Mean Time To Repair
(MTTR) close to zero without downtime risk

High Scalability
• Vertical expansion from 25kW to 75/150/200kW supporting N+X redundancy in
a single rack enclosure to save footprint
• Parallel expansion up to four units without requiring additional hardware
• Optional Rack-Mount PDC (applicable for 75/150kW models) has flexibility to
arrange its UPS’s output power feeding according to its connected critical loads.
• Optional built-in battery modules (applicable for 75kW models) at maximum four
units (four battery trays each)

Excellent Power Performance and Efficiency


• Full rated power (kVA=kW) to maximize power availability
• High operating efficiency of 95% at 30% light load and 96% from 50% load
resulting in marked energy cost savings
• Low harmonic pollution (iTHD<3%) to reduce upstream investment costs and
meet demanding power requirements

Easy Maintenance
• Built-in manual bypass features to eliminate maintenance-related downtime
• Proactive detection of fan failure and switch fault for early diagnosis on UPS
malfunction
• Plug and play modularity to simplify the maintenance process

Delta InfraSuite 7
Power Management

Technical Specifications
Model DPH 75kW System DPH 150kW System DPH 200kW System
Power Rating (kVA) 25, 50, 75 25, 50, 75, 100, 125, 150 25, 50, 75, 100, 125, 150, 175, 200
Frame 75kW 150kW 200kW
Input Nominal Voltage 380/220V, 400/230V, 415/240V (3 phase, 4-wire +G)
Voltage Range 176~276 / 305~477 Vac *
Current Harmonic Distortion <3% **
Power Factor > 0.99
Frequency 50/60 Hz
Output Voltage 380/220V, 400/230V, 415/240V (3 phase, 4-wire +G)
Output Power Factor 1 (kVA = kW)
Voltage Harmonic Distortion ≤ 2% (linear load)
Voltage Regulation ±1% (static)
Frequency 50 or 60 Hz
Frequency Regulation ±0.05 Hz
Overload Capacity ≤ 125% : 10 minutes ; ≤ 150% : 1 minute
Interface Standard System communication port x 1, LCM port x 1, Parallel port x 2, Smart slot x 2,
Output dry contact x 6, Input dry contact x 2, Battery dry contact x 2, REPO
Optional SNMP IPv6 card, ModBus card, Relay I/O card,
Battery cabinet temperature sensor cable, Battery cabinet status detection kit
Conformance Safety & EMC BSMI, CE, EN62040-1
Other Features Parallel Redundancy and Expansion Module and system redundancy ; Maximum 4 units
Emergency Power Off Local and remote
Battery start Yes
Event Log 3000 records
Efficiency AC-AC 96% (Tested by TÜV)
ECO Mode 99%
Environment Operating Temperature 0 ~ 40 ºC
Relative Humidity 0 ~ 95% (non-condensing)
Audible Noise (at one meter) < 62 dBA
IP Protection IP20
Physical Dimensions (WxDxH) 600 x 1090 x 2000 mm
Weight UPS System 310 kg 320 kg 350 kg
Power Module 32 kg 32 kg 32 kg
Rack-mount PDC 32 kg 32 kg N/A
Battery Module 29.5 kg N/A N/A
System Frame 25kW Power Module 3 6 8
Maximum Capacity Rack-mount PDC 1 2 N/A
Breaker Module (for Rack-mount PDC) 6 12 N/A
Battery Module 4 N/A N/A

* When input voltage is 140/242~176/305 Vac, the sustainable loading is from 60% to 100% of the UPS capacity.
** When input harmonic distortion is less than 1%.
All specifications are subject to change without prior notice.

Scalable and Hot-swappable Optional Rack-Mount PDC Optional hot-swappable The Modulon DPH is designed
with hot-swappable breaker battery modules in modern IT aesthetics
modules and control modules aligned with Delta InfraSuite
datacenter solutions.

8
Delta InfraSuite Power Management
Power Distribution Cabinet

For power distribution requirements of medium to large


data centers, Delta’s Power Distribution Cabinet (PDC)
provides an optimal solution. The space-saving PDC is
easy to move and adapt to future reconfigurations of the
data center. The PDC offers superior power protection and
monitoring, and the flexibility & scalability to match your
actual power distribution requirements. Not only does
User-friendly LCD Interface
it improve availability, it reduces the cost of your initial
investment.

Convenience
• Configurable circuit breaker panel
• LCD display supporting multiple languages
• Recording more than 500 event logs
• Monitoring the current of each branch circuit breaker
• Built-in RS232 interface for remote monitoring
• Six built-in contact closure outputs
• Two built-in SNMP interfaces increasing availability

Safety
• Local and remote emergency power off functions
• Current unbalance and phase sequence error alarm
• Optional K-factor isolation transformer enhancing
safety and reduces harmonics
• Optional lightning surge protection module

Availability
• Easy to relocate, reducing investment costs
• Two built-in sets of panelboards with 42 poles each
• Optional transformers for different output voltages
• Hot-swappable output breaker

....
Rack 1 Rack 2 Rack #

▲ Scalable and configurable for present and future demands

Delta InfraSuite 9
Power Management

Technical Specifications
Model PDC 80 PDC 125

Capacity 80 kVA 125 kVA

Input Rated voltage 220/380 Vac, 3 phase 3 wire+ ground, or 3 phase 4 wire+ ground
Voltage tolerance range ±15%
Frequency 50 / 60 Hz ±5% (Automatic detection)

Output Rated voltage 220/380 Vac, 3 phase 4 wire+ ground

Total switching capacity Based on actual product specifications

Panelboard type Two sets of panelboards with 42 poles each

Shunt switch type Hot-swap switch capacity: 15 / 20 / 30A,


Optional: 1/2/3 pole

Transformer Input-Output Type Δ-Y

Efficiency 97.5% (Full-load)

LCD Display System Temperature, ground current, system overheat alarm, V-Loss alarm,
voltage imbalance alarm, ground fault alarm

Blue light 4.9” graphic interface Input Phase voltage, line voltage, phase current, line current, load(%), iTHD,
total kVA, total kW, total kWh, Over voltage/over current alarm, under-
voltage/under current alarm, Over line current alarm, iTHD abnormal
alarm

Total output Phase voltage, line voltage, phase current, line current, frequency,
neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over
voltage/over current alarm, under-voltage/under current alarm, Over
line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power
factor abnormal alarm

Output shunt plate Phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current,
over current alarm, under current alarm, Over line current alarm, iTHD
abnormal alarm, power factor abnormal alarm

Output shunt Current, load (%), over current alarm, under current alarm

Temperature Environment (instant and alarm), transformers (two stage-alarm)

Conformance Environment CE

Electromagnetic interference EN55022

Communication interface RS232 x 1, dry contact x 6, SNMP slot x 2

Optional accessories Lightning protector

Dimensions (WxDxH) 600 x 1090 x 2000mm (standard 19”cabinet)

Weight Excluding transformer: 225kg,


Including H transformer: 80kVA: 525 kg, 125 kVA: 630 kg

These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.

10
Delta InfraSuite Power System
Rack-Mount Power Distribution Cabinet

Delta’s rack-mount PDC (RPDC) is an ideal power


distribution solution to small datacenters up to 80kVA.
Composed of a 4U cabinet, the RPDC can be perfectly
integrated with standard server racks and results in
saving valuable datacenter space. For high requirement
of datacenter reliability, it also provides excellent branch
protection and branch monitoring functions. The RPDC is
a superior solution of power distribution management and
reduces the total cost of ownership (TCO) of your small
datacenters.

High Flexibility
• Provides three different rated power levels, 30kVA, 50kVA and 80kVA, for your selection
• The highly scalable design allows installation of at maximum six hot-swappable breaker modules (optional), which
means that it can connect at maximum 18 branches
• Various accessories are available for options like TVSS module, main input breaker and SNMP IPv6 card

High Reliability
• Detects any hot-swappable breaker module’s branch
current
• Provides abnormal voltage and phase-lack alarms
• Provides system and each branch’s current monitoring
and alarm functions
• Intelligently judges the specifications of each hot-
swappable breaker module installed
……
• Smartly monitors each latch is closed or open, each
branch’s status and the optional main input breaker’s
Rack-Mount PDC
status
• Provides REPO function

Convenience
• User-friendly 4.9-inch LCD interface
• Built-in RS-232 port and smart slot allow remote monitoring
• Records at maximum 2000 event logs
• Provides 6 sets of output dry contacts

Delta InfraSuite 11
Power Management

Technical Specifications
Model Rack-Mount PDC

Input Nominal Voltage 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)

Voltage Range 220/380V ±15%

Frequency Range 50/60Hz ±5%

Main Input Breaker 63 / 100 / 160 A

Output Full Load Rating 30 / 50 / 80 kVA

Nominal Voltage 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)

LCD Display Total output: Current, load (%), kVA, kW, kW.h and temperature
Each branch: Load (%), current and kW.h

Interface Standard RS-232 port x 1, CAN Bus port x 1, Smart slot x 1,


Output dry contact x 6, REPO x 1

Environment Operating Temperature 0 ~ 40ºC

Relative Humidity 90% (non-condensing)

Audible Noise <70 dBA in normal mode (at a distance of 1 meter in front of the Rack-
Mount PDC)

Protection (IP Degree) IP 20

Others Parallel Redundancy N/A

Emergency Power Off Yes (Remote)

Physical Dimensions (WxDxH) 430 x 665 x 173 mm

Weight 38kg (Max.)

Hot-Swappable Breaker Module 1~6 (at maximum 18-pole supported)

*All specifications are subject to change without prior notice.

Hot-swappable control module

Hot-swappable breaker module

12
Delta InfraSuite Power Management
Power Distribution Unit

Delta’s power distribution units (PDU) provide optimal power distribution for devices inside a rack. In addition to easily
distributing power to equipment, PDUs also provide complete power protection. Delta offers a range of basic and
metered PDUs that you can install vertically or horizontally inside a rack. It makes establishing a data center more
efficient.

LED Current Display


and Indicators

Technical Specifications
Model Input Plug Type Cable Nominal Input Input Voltage Rating Current Output Voltage
Phase Length Voltage (Vac) Range per Input (A) / Phase

PDU1113 1
X
G NEMA L5-30P 2.4m 110/120 ± 10 % 24 100-120 Vac / 1

PDU1213 1 NEMA L6-30P 2.4m 208/220 ± 10 % 24 200-240 Vac / 1


X
G
Y

PDU1311 1 IEC309-16A-3W 2.4m 230/240 ± 10 % 16 200-240 Vac / 1

PDU1315 1 IEC309-32A-3W 2.4m 230/240 ± 10 % 32 200-240 Vac / 1

PDU1425 3Y IEC309-32A-5W 1.8m 220/380 ± 10 % 32 200-240 Vac / 1


230/400

PDU2421 3Y IEC309-16A-5W 1.8m 220/380 ± 10 % 16 200-240 Vac / 1


230/400
Y

PDU2525 3∆ CS8365C 2.4m 208/220 ± 10 % 32 200-240 Vac / 1


X
G z

PDU5113 1 X
G NEMA L5-30P 2.4m 110/120 ± 10 % 24 100-120 Vac / 1

PDU5213 1 NEMA L6-30P 2.4m 208/220 ± 10 % 24 200-240 Vac / 1


X
G

PDU5315 1 IEC309-32A-3W 2.4m 220/230/240 ± 10 % 32 200-240 Vac / 1

PDU7111 1 X
G NEMA L5-20P 2.4m 110/120 ± 10 % 16 100-120 Vac / 1

PDU7211 1 X
G
NEMA L6-20P 2.4m 208/220 ± 10 % 16 200-240 Vac / 1

PDU7311 1 IEC309-16A-3W 2.4m 220/230/240 ± 10 % 16 200-240 Vac / 1

PDU7425 3Y IEC309-32A-5W 2.4m 220/380/230/400 ± 10 % 32 200-240 Vac / 1

Delta InfraSuite 13
Power Management

Metered PDU Basic PDU


Availability Availability
• Tool-less installation in Delta’s standard rack cabinets • Tool-less installation in Delta’s standard rack cabinets
• Brackets included for mounting in other brands’ rack • Brackets included for mounting in other brands’ rack
cabinets cabinets
• Zero-U installation saving valuable rack space • Vertical or horizontal mounting method, saving valuable
• Single or three phase input voltage available rack space
• Single phase or three phase input voltage available
Safety
• LED current (rms value) display and overload warning Safety
indicator • Branch circuit breaker protection
• Branch circuit breaker protection • International standards of cables and power plugs/
• International standards of cables and power plugs/ receptacle
receptacle

Management
• Upgradable firmware for maintaining optimal function
• Integrated with the InfraSuite management software
• Optional SNMP card for remote monitoring

Interface
Interface Function
RS232-1 Connect to a PC for remote operation or a firmware upgrade
RS232-2 Connect to an SNMP card or to another PDU

Number of Output Outputs Conformance LED Communication Dimensions Weight


Circuit Breakers (Number) Interface (WxHxD)

20A/2P Two (UL489) NEMA 5-15/20R (24) UL/cUL, FCC Yes RS232-1, RS232-2 48x1250x50/90 mm 5.34kg

20A/2P Two (UL489) IEC320 C13 (24) UL/cUL, FCC Yes RS232-1, RS232-2 48x1250x50/90 mm 5.24kg

20A/2P One (UL489) EC320 C19 (3) CE, CCC Yes RS232-1, RS232-2 48x1250x50/90 mm 4.56kg
IEC320 C13 (24)

20A/2P Two (UL489) EC320 C19 (3) CE, CCC Yes RS232-1, RS232-2 48x1250x50/90 mm 5.44kg
IEC320 C13 (24)

35A/2P Three (UL489) IEC320 C19 (9) CE, CCC Yes RS232-1, RS232-2 48x1250x50/100 mm 6.45kg
IEC320 C13 (3)

20A/2P Three (UL489) EC320 C19 (3) CE, CCC Yes RS232-1, RS232-2 48x1560x50/90 mm 6.06kg
IEC320 C13 (36)

20A/2P Three (UL489) IEC320 C13 (36) UL/cUL, FCC Yes RS232-1, RS232-2 48x1560x50/100 mm 8kg

20A/1P Two (UL489) NEMA 5-15/20R (24) UL/cUL X X 48x1250x50/90 mm 4.88kg

20A/2P Two (UL489) IEC320 C13 (24) UL/cUL X X 48x1250x50/90 mm 4.92kg

20A/1P Two IEC320 C19 (4) CE, CCC X X 48x1250x50/90 mm 4.90kg


IEC320 C13 (24)

20A/1P One NEMA 5-15/20R (8) UL/cUL X X 440x44x55 mm 1.56kg

20A/1P One IEC320 C13 (12) UL/cUL X X 440x44x55 mm 1.64kg

20A/1P One IEC320 C13 (12) CE, CCC X X 440x44x55 mm 1.48kg

20A/1P Six IEC320 C19 (6) CE, CCC X X 440x44x250 mm 4.80kg

14
Delta InfraSuite Power Management
Static Transfer Switch Series

The Static Transfer Switch (STS) is designed to guarantee the uninterrupted operation of sensitive
equipment. It is powered by two independent power sources and automatically makes a rapid
switch from one source to the other when the power supply used to power its connected load fails.
The STS offers an efficient and reliable switch that supports the high redundancy requirement of
power systems. In datacenter applications, power drop risks can be shared or distributed to each
rack to prevent power loss for the whole system.

Availability
• Adopts SCR design with a relay in parallel as a switching
device to increase reliability and handle high inrush current.
• Supports power redundant configurations for high reliability
• Monitors the health of the power source and performs the
transfer automatically
• Short transfer time (6ms)

Convenience
• Rack-mounted type with 1U size for easy installation and
relocation
• Built-in SNMP for remote management
• LED indicators show power flow
• Self-test function

Safety
• Break before make prevents short circuits between two
sources

Sourse 1 STS PDU Rack

Sourse 2

Delta InfraSuite 15
Power Management

Technical Specifications
Model STS30002SR

Capacity 30A

Regulatory CE / UL

Input 200/208/220/230/240 Vac

Output 200/208/220/230/240 Vac

Display LED

Input S1 : IEC309 / L6-30P

Connection Input S2 : IEC309 / L6-30P

Output : IEC309 / L6-30R

Communication SNMP

Operating temperature 0~40℃

Storage temperature 15~50℃

Humidity 5%~95% RH (non-condensing)

Audible Noise (at one meter) <45 dBA

Physical Dimensions (H x W x D) 43mm x 440mm x 355mm

Weight 7.6Kg

• All specifications are subject to change without prior notice.

Front

Rear

16
Delta InfraSuite Rack & Accessories
Modular Rack

The modular rack is essential gear for


data centers. Delta has developed a
modular rack that increases space
utilization and heat dissipation via
70% perforation to meet high density
IT room requirements.

Convenience Flexibility
• T
 ool-less installing and removing & reversing front and • S
 plit rear doors reducing space required for hot aisles
rear doors and simplifying maintenance
• R
 emovable power trough on the roof neatly managing • A
 djustable mounting rails with numbered guides helping
power, network and optic cables adjust depth for different installation needs
• T
 ool-less removable roof cable ports for easier cable • F
 our multipurpose mounting bays for installing 0U PDU
access and management or vertical cable trough
• R
 emovable bottom cover allowing cable access through • F
 ully meeting industry-standard EIA-310 rack
raised floor requirements
• Casters for convenient moving
• Front and rear U-position numbers for easy installation Safety
• E
 asy to join racks in a row for a clean and secure data • Supporting up to 1420kg static weight
room • IP20 environment protection rating
• F
 ront and rear doors open up to 130º for convenient • Adjustable leveling feet for stability and security
installation and repair
• Front and rear doors grounded to the rack
• F
 ull range of accessories supporting a well-managed
• Front and rear doors with locks
and organized data room

Roof Cable Trough Vertical Position 4 Universal Roof Cable Ports


Marks Mounting Brackets & Covers

Delta InfraSuite 17
Rack & Accessories

Conformance
Protection Rating IP20

Rack Standards EIA-310-D

Safe Grounding UL 60950 (max. 63A)

Environmental RoHS

Environment
Temperature Operating: 0 ~ 40˚C
Storage: -15 ~ 50˚C

Relative Humidity Operating: 0 ~ 95%

Elevation Operating: 0 ~ 3000m

Physical
Item Model W (mm) H (mm) D (mm) Packing Dimensions Net Weight (kg)
W x H x D (mm)

1 SR3110 800(19") 2000 1100 830*1160*2156 150

2 SR1110 600 2000 1100 630*1160*2156 137

These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.

Customer’s Site

Control
Network

Application
Controller

Fieldbus

MCB
Line Supply

Load
Motor (Pump)
MVD

18
Delta InfraSuite Rack & Accessories
Rack Accessories

1U Fixed Shelf 1U Sliding Shelf Bottom Cover

Model SR9004 Model SR9005 Model SR9003/SR8003


Load Capacity (kg) 60 Load Capacity (kg) 40
Dimensions (mm) W480.5xD664xH44 Dimensions (mm) W482xD718xH44 Dimensions (mm) W538xD834.6xH39
/W738xD834.6xH39

Power Cable Trough with


1U Blanking Panel 2U Blanking Panel Through Hole

Model SR9006 Model SR9007 Model SR9001/SR8001


(10pcs/per box) (10pcs/per box)
Dimensions (mm) W482.6xH43.7xT1.0 Dimensions (mm) W482.6xH88xT1.0 Dimensions (mm) W580xD316xH192
/W780xD316xH192

Cable Trough with Vertical Cable 1U Horizontal Cable


Through Hole Management Channel Management Channel

Model SR9002 / SR8002 Model SR7002 (2 pcs) Model SR7001


Dimensions (mm) W592xD75xH125 Dimensions (mm) W53xD63xH888 Dimensions (mm) W482xD50xH44
/W792xD75xH125

Delta InfraSuite 19
Rack & Accessories

Cable Ladder

Model SR7003
Dimensions (mm) W300xD50xH1560

Ring Type Wire Holder

Model SR7004 (10 pcs)


Dimensions (mm) W45xD85xH5

Accessory List
Model Description SR1110 SR3110
SR7001 1U HORIZONTAL CABLE MANAGEMENT ● ●
SR7002 VERTICAL CABLE MANAGEMENT CHANNEL ● ●
SR7003 CABLE LADDER,300 mm ● ●
SR7004 RING TYPE WIRE HOLDER (10 pcs/per box) ● ●
SR8001 POWER CABLE TROUGH WITH THROUGH-HOLE,800 mm ●
SR8002 CABLE TROUGH WITH TROUGH-HOLE,800 mm ●
SR8003 BOTTOM COVER FOR W800*D1100 RACK CABINET ●
SR9001 POWER CABLE TROUGH WITH THROUGH-HOLE,600 mm ●
SR9002 CABLE TROUGH WITH TROUGH-HOLE,600 mm ●
SR9003 BOTTOM COVER FOR W600*D1100 RACK CABINET ●
SR9004 1U FIXED SHELF ● ●
SR9005 1U SLIDING SHELF ● ●
SR9006 1U BLANKING PANEL (10 pcs/per box) ● ●
SR9007 2U BLANKING PANEL (10 pcs/per box) ● ●

These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.

20
Delta InfraSuite
Environment Management System
InfraSuite Manager - Data Center Infrastructure Management (DCIM)

Have the entire data center at your fingertips


InfraSuite Manager is a Data Center Infrastructure Management (DCIM) system, integrating all facility and IT
equipment on one platform simultaneously. The EnviroProbe and EnviroStation work together seamlessly to
immediately perform the complete management of energy, power system, cooling, environment, security, asset, server
monitoring and more, making it an eternally alert sentry to guard your data center.

Energy Management
InfraSuite
Energy consumption classifications are given using the Manager

actual device deployment of the data center in real time


with historical PUE records to assist the IT manager to
analyze and understand the power usage effectiveness
of the data center. Customized power consumption
management and electricity cost analysis are also
available to help you save energy.

Power Management Security Management


The status of all electrical equipment used for power By combining the camera function, datacenter managers
- including uninterruptible power supply (UPS), power can observe the environment status in the real world
distribution cabinets (PDC), power distribution units remotely. Multiple door access control readers, controllers
(PDU), and power meters – can be monitored by and user accounts can be integrated to provide the most
InfraSutie Manager. The system is also able to handle correct information of in and out times of users.
capacity management, power quality monitoring, power
paths, rack current, and server power consumption Asset Management
analysis. The asset management module displays the correct
installation position of servers and network equipment,
Cooling System Management and also provides capacity analysis, failure analysis,
The system displays the current status of cooling power paths, network topology, asset searching, and
equipment – including the precision cooling, the chiller, event management advice.
and the cooling tower – together with temperature data
and water-leakage alerts. The layout for the data center Server and Network Equipment Management
facility’s heat-exchange is displayed in an easy-to- To look into the server chassis environment, InfraSuite
understand fashion by the rack power consumption and Manager can communicate with the server BMC to
cooling capacity data. retrieve the power information, PCB thermal sensors, fan
speed. In addition, the OOB server power control is also
Environment Management available. InfraSuite Manager integrates with Intel DCM
Various environmental parameters, including to limit the maximum power consumption of servers.
temperature, humidity, water leakage, smoke detection,
door contact and more, are collected by the Delta Software KVM
EnviroProbe(EMS1000) and EnviroStation(EMS2000). This functional module needs not to install a KVM
hardware and reduces the cabling complexity. Integrating
with the Intel Virtual Gateway, it communicates with the
server BMC through IPMI. It cooperates with the asset
management module to identify the server position and
open the KVM interface at your fingertips.

Powered by Intel® Data Center Manager

Delta InfraSuite 21
Environment Management System

InfraSuite Manager Solution is created to extend the function to include all of the devices in the Facilities and IT
domains. It can easily integrate with the uninterruptible power supply (UPS), power distribution cabinets (PDC), power
distribution units (PDU), modular server racks, precision cooling, generators, and more.

Email InfraSuite Manager Slide Show


Web Monitor Client Monitor
(EMS3000)
SMS

Audio

Network

Facility IT
Power Cooling Environment Server Network Asset

Access Surveillance
+ Operating System Virtual Machine

Technical Specifications
Model EMS3525035
Hardware OS Support Windows XP SP2, 7, 8, 2003, 2008, 2012
CPU Speed 2GHz
Memory 8G
Hard Disk 500G Mirrored
Interface Web HTTP, HTTPS
Browser Support IE, Chrome, FireFox, Safari
Windows Applications Windows XP SP2 and above

• These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.

22
One Tool. Complexity Mastered.
Delta InfraSuite Manager. Integrated Efficiency.

InfraSuite Manager -
Data Center Infrastructure Management (DCIM)
Have the entire data center at your fingertips!
Energy Security

Power $ Asset

Cooling Server & Network

Environnment Software KVM

Delta InfraSuite 23
Environment Management System

Delta InfraSuite
Environment Management System
EnviroStation

Delta’s Environmental Management System (EMS) monitors the environment and conditions in the data center,
including temperature, humidity, water leakage, alarms for fire, smoke, and unauthorized entry.
The EMS offers IT managers an integrated platform for more convenient monitoring of today’s data center.

EnviroStation integrates the monitoring of the data center’s environment and other conditions, and sends the data to a
central manager via network. User-defined alarms ensure the data center’s security.

Easy to manage Technical Specifications


• A
 ssess and collect key data center information for Model EMS2000
enhanced management Input Power 100~240 Vac, 50/60 Hz
Digital Input Wet Contact Signal
• R
 eal-time notification providing faster management • Alarm Voltage 5~24 Vdc, 1-9 mA
response and more effective operations Dry Contact Signal
• Normal: Off (open circuit)
• Setting manager password for higher security • Alarm: On (short circuit)
Analog Input Voltage: 0~10Vdc
• S
 NMP allowing easy integration with any enterprise Current: 4~20 mA
RTD Range: 0~50°C
management system Accuracy: ± 1°C with 3-wire PT100
Resistance Temperature Support 2-wire or 3-wire resistance
Detection (x1)
Leakage Detect Voltage < 1V
Convenience (alarm signal with S-1FP leak sensor)

• Monitoring via internet browser Output Sensor HUB For connection with sensor devices (such
as smoke detectors, fire detectors, or door
• InfraSuite Manager remote monitoring software sensors, etc) and support:
+ 12V, 0.8A (max)
providing prompt handling of any data center situation + 24V, 1.0A (max)
One port limit 0.6A
• G
 raphical interface and historical data records for Delta Bus + 12V, 0.8A (max)
more effective management Relay Output 26 Vdc (max), 0.8A (max)

Alert Warning Light (X1) Included in the package and can connect
• R
 eal-time alarm notifications shortening management to EMS2000 via a Sensor Hub converter
response time (through Port 1 or Port 2) to alert for
abnormal conditions.

Network RJ45 (X1) 10/100 Base-T


Connection RS485 (X2) Standard ModBus
Flexibility Console (X1) Connect to PC via RJ-45 to DB9 cable
(cable is included in the package) A
• Supports SNMP communication protocol configuration port is available for the
console mode.
• S
 etting each alarm value based on actual
Environment Operating Temperature 0~45°C
requirements Storage Temperature -20°C ~ 60°C
Operating Humidity 0~ 90% RH (non-condensing)

Dimensions Product (W x D x H) 440 x 157 x 44 mm


Package (W x D x H) 510 x 410 x 150 mm

Weight Product 2.4 Kg


Package 5 Kg

• These specifications are subject to change without notice. Please contact us or our
distributors in your region for the latest specs.

24
EnviroProbe

EnviroProbe monitors temperature, humidity in a single cabinet or area and transmits signals from environment
sensor devices in the data center (e.g.: door sensors, smoke detectors, fire detectors, water-leakage detectors etc.)
to management via network. EnviroProbe also controls its connected devices when equipped with digital and analog
outputs, keeping the IT manager promptly informed of all environmental changes by giving alarms, controlling the
activation and deactivation of an external device (e.g. a magnetic lock), or by giving a sound alert using its own built-in
buzzer upon detection of water leakage.

Easy to manage
• Monitoring temperature, humidity of the environment
• Backlight LCD display
• Digital/analog inputs and outputs

Convenience
• W
 ork with EnviroStation(EMS2000) to monitor via Backlit LCD display
internet browser
• InfraSuite Manager software for remote monitoring and
recording

Flexibility
• W
 ork with EnviroStation(EMS2000) to support SNMP
communication protocol

Connecting EnviroProbes with EnviroStation can expand the scope of the monitored area.

Delta InfraSuite 25
Environment Management System

Delta InfraSuite
Environment Management System
EnviroProbe

Technical Specifications
Model EMS1000 EMS1100 EMS1200
Input Voltage EMS2000 Delta-BUS or SNMP Card: 12 Vdc (pin 1 & 4)
PDU SNMP card: 5 Vdc (Pin 2 & 4)
Purpose To collect data from connected devices To control connected devices To collect data from and control
(temperature & humidity) connected devices
Input/Output Contacts 4 dry/wet contact inputs 4 digital outputs 2 analog inputs, 1 analog output,
1 water-leakage detection (built-
in buzzer)
Connect to EnviroStation Connect to EnviroStation
(EMS2000) or SNMP IPv6 card (EMS2000)
Input Wet Contacts:5~24Vdc, 1~8mA; N/A Voltage: 0~10Vdc (12bit)
Dry Contacts: Open/Short Status Current: 0~20mA (12bit)
Output N/A Contact voltage/Contact Voltage: 0~10Vdc (12bit)
current/Contact tolerance Current: 4~20mA (12bit)
60Vdc/1A/60W;
30Vac/2.08A/62.5VA
Cascade number to EMS2000 Up to 16 units Up to 4 units Up to 5 units
Dimensions (WxDxH) Product: 66 x 33 x 103 mm
Package: 91 x 42 x 133 mm
Weight Net Weight: 120g 130g
Gross Weight: 140g 150g
Environment Temperature Operation: 0 ~ 60ºC
Storage: -30 ~ 80ºC Storage: 0ºC ~ 60ºC
Accuracy: ± 0.4ºC & 0 ~ 60ºC N/A
Humidity Operation: 0 ~ 90% RH (no condensation)
Storage: 0 ~ 100% RH (no condensation)
Accuracy: ± 3ºC & 0 ~ 80ºC N/A
Altitude 0 ~ 10,000 feet
Conformance CE
EN55022 (CISPR 22) Class B
EN55024 (Level 3 @Air 8 KV/contact 4 KV)

These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.

26
Using too much
energy to keep
your datacenter cool?

Delta InfraSuite Precision Cooling


The most reliable and efficient cooling solutions
Power consumption for air conditioning can account for 45% of a datacenter’s total electricity expenses. Delta’s InfraSuite
Precision Cooling is designed with smart cooling technology to effectively solve thermal issues and reduce the electricity
required for cooling. It provides the best cooling solution to meet 24 hours × 365 days of continuous operation requirements
for a constant temperature and humidity in a critical equipment environment, such as for:

• Communications rooms
• Datacenters
• Computing centers
• Medical equipment rooms
• Research laboratories
• Precision manufacturing
equipment rooms

Delta InfraSuite 27
Precision Cooling

Delta InfraSuite Precision Cooling


Modern datacenters have implemented a high-density model, mainly based on blade servers, to increase space
utilization and accommodate the rapid expansion of new IT equipment. This model requires a higher power supply
density and creates bigger heat dissipation problems, where increased power consumption for air conditioning can
account for 45% of total data center electricity expenses. With this in mind, heat dissipation and electricity expenses
are important indices against which operational expenditures of the data center can be measured.

As a leading global manufacturer of fans and a specialist in power management, Delta Electronics was perfectly
positioned to develop Delta InfraSuite precision cooling solutions to meet the needs of modern data centers. Delta’s
precision cooling enthalpy laboratory carefully verifies cooling performance and reliability during the engineering
development and design process to ensure high product performance. The specifications and testing ranges used by
the Delta Electronics precision cooling enthalpy laboratory are listed below:

Outdoor side Indoor side


Item Unit Range Tolerance Item Unit Range Tolerance
Air Volume CMM 0~100 ±3% Air Volume CMM 50~500 ±3%
Dry Bulb Temp °C -25~50 ± 0.3°C Dry Bulb Temp °C 0~40 ± 0.3°C
Wet Bulb Temp °C -25~50 ± 0.2°C Wet Bulb Temp °C 0~40 ± 0.2°C
Relative Humidity % 20~90 3% Relative Humidity % 30~90 3%
Fluid Volume LPM 0~500 ± 2% Fluid Volume LPM 0~500 ± 2%
Inlet Fluid Temp °C 4~34 ± 0.1°C Inlet Fluid Temp °C 4~4 ± 0.1°C
Cooling Capacity kW 0~70 ± 2% Cooling Capacity kW 17.5~106 ± 2%
Heating Capacity kW 0~70 ± 2% Heating Capacity kW 17.5~106 ± 2%
Humidity Capacity kW 0~60 Humidity Capacity kW 0~60
Dimension M 6H×10W×6D Dimension M 6H×10W×6D

Outdoor side Indoor side

Control Room

28
Delta InfraSuite Precision Cooling
RowCool 29kW, Chilled Water

As the power density increases in modern data centers, traditional precision air conditioning fails to provide
complete cooling for the following situations:
• Load variations for peak and off-peak period
• High power density
• Uneven heat distribution
The Delta InfraSuite Precision Cooling RowCool Chilled Water can effectively solve the above problems.

High Availability
• Built-in dual power supply input for better power reliability
• Hot-swappable rectifiers and fans greatly reduce maintenance time
• P
 anel made of cold-rolled steel plate and coated with surface electrostatic
spraying of epoxy is highly resistant to rust
• Built-in leakage detector capable of leak display and alert
• M
 odular rack design readily scalable by load to enable quick configuration of
new cooling units
• Built-in manual dehumidifying for quick and precise dehumidification
• Supporting group control and used as backup

High Flexibility
• C
 hilled water pipe suitable for both top and bottom insertion, with flexible
configuration as required
• Wheels on bottom for easy moving to locations that need cooling
• D
 isposable filter with high efficiency (MERV 8 ASHRAE 52.2, 45mm);
washable MERV 1 filter is optional for further cost savings
• R
 emote monitoring can be carried out through SNMP card, providing more
comprehensive system protection

High Efficiency
• Continuously variable speed fan design for energy saving
• Cooling system capable of variable flow control for energy saving
• Built-in vortex water flow meter capable of monitoring chilled water flow that
renders easy display of system status

Applications
• High power density rack area
• Environment that requires precise environmental control

Delta InfraSuite 29
Precision Cooling

Technical Specifications
Model HCH1850
Cooling method Chilled Water
Maximum cooling capacity 29 kW
Sensible cooling capacity 28.7 kW
Input power Single phase 220 Vac, 50/60 Hz
Maximum input current 5A
Power consumption 1 kW
Air flow 2900 (4930) CFM (CMH)
Tubing Dimensions 25A (1 inch), PT thread female
Connections of inlet/outlet water Top and bottom
Filter 30~35 %, MERV 8 (Disposable)
Communication interface SNMP slot x1 (SNMP card is optional), RS232x1, RS485x1 (Modbus protocol), Input dry
contact x2, Output dry contact x2, Temperature sensor x3 , Remote temperature/humidity
sensor x1
Accessories Washable filter
Remote temperature/humidity sensor, SNMP card, Drain Pump
Environment Operation temperature 4 ~ 40°C
Relative humidity 30 ~ 85%, non-condensing
External dimensions Dimensions (WxDxH) mm 300 x 1090 x 2000
Weight (kg) 185

Test conditions of total cooling capacity: Return air temperature: 40.6°C DB / 21.6°C WB / chilled water inlet temperature: 7.2°C/ chilled water outlet temperature: 13.8°C
Please contact Delta or a local distributor for new specifications regarding the constant improvements Delta makes for various lines of products

Power Supply Redundancy

Disposable Filter

Hot-swappable fans

Front View Rear View

30
Delta InfraSuite Precision Cooling
RowCool 70kW, Chilled Water

As the power density increases in modern data centers, traditional precision cooling fails to provide
complete cooling for the following situations:
• Load variations for peak and off-peak period
• High power density
• Uneven heat distribution
The Delta InfraSuite Precision Cooling RowCool Chilled Water can effectively solve the above problems.

High Availability
• Built-in dual input for better power reliability
• P
 anel made of cold-rolled steel plate and coated with surface electrostatic
spraying of epoxy is highly resistant to rust
• Built-in leakage detector capable of leak display and alert
• M
 odular rack design readily scalable by load to enable quick configuration of
new cooling units
• Built-in manual dehumidifying for quick and precise dehumidification
• Supporting group control and used as backup

High Flexibility
• C
 hilled water pipe suitable for both top and bottom insertion, with top and
bottom input power wiring, providing flexible configuration as required
• Wheels on bottom for easy moving to locations that need cooling
• D
 isposable filter with high efficiency (MERV 8 ASHRAE 52.2); optional
washable MERV 1 filter for further OPEX savings
• R
 emote monitoring can be carried out through SNMP card, providing more
comprehensive system protection
• O
 ptional reheater and humidifier accessories for more precise temperature
and humidity control

High Efficiency
• Continuously variable speed fan design for energy saving
• Cooling system capable of variable flow control for energy saving
• B
 uilt-in vortex wafer flow meter capable of monitoring chilled water flow that
renders easy display of system status

Applications
• High power density rack area
• Environment that requires precise environmental control

Delta InfraSuite 31
Precision Cooling

Technical Specifications
Model No. HCH1CB0 HCH1CB0 with
Humidity Control
Capacity Maximum cooling capacity *1 kW 70 70
Sensible cooling capacity kW 69.3 69.3
Power Input power Φ/Hz/V 3Φ4W+G/50,60Hz/ 380V 3Φ4W+G/50,60Hz/ 380V
Maximum input power kW 3 14
Maximum current AMP 5 22
Fan Air flow CMH (CFM) 11400 (6700) 11400 (6700)
Type EC Fan EC Fan
Number of fans n 3 3
Coil Water flow LPM 111.2 111.2
Reheater Capacity kW(Btu/HR) N/A 8.1(27600)
Current Amp N/A 12.3
Stages n N/A 3
Humidifier Capacity kg/h N/A 3
Power consumption kW N/A 2.25
Current Amp N/A 3.5
Filter (disposable) Filter class 30~35% MERV8 30~35% MERV8
Tubing Dimensions Inlet water mm(in) 32A(1 1/4") 32A(1 1/4")
PT thread female PT thread female
Outlet water mm(in) 32A(1 1/4") 32A(1 1/4")
PT thread female PT thread female
Drain pipe mm(in) 20A (3/4”) 20A (3/4”)
PT thread male PT thread male
Humidifier supply water mm(in) N/A 10A (3/8")
PT thread male
Connections of inlet/outlet water Bottom/ Top (selectable) Bottom/ Top (selectable)
Power Wiring Both at top and bottom Both at top and bottom
Communication Interface SNMP slot x1 (SNMP card is optional),
RS232x1, RS485x1 (Modbus protocol),
Input dry contact x2,Output dry contact x2, Temperature sensor x3,
Remote temperature/humidity sensor x1
Accessories SNMP card, Remote temperature/humidity sensor, Drain Pump,
Washable filter
Physical Height (wo/w packaging) mm 2000 / 2220
Width (wo/w packaging) mm 600 / 764
Depth (wo/w packaging) mm 1090 / 1342
Weight (Gross / Operating) kg 368 / 414

Please contact Delta or a local distributor for new specifications regarding the constant improvements Delta makes for various lines of products

1. Testing standard of cooling capacity at 60Hz


Returned air 40.6°C (DB) / 21.6°C(WB)
Incoming chilled water temperature 7.2°C
Temperature difference of inlet and outlet chilled water 8.8°C

2. Reference for cooling capacity testing: ASHARE 127 and GB/T 19413-2003
3. Operation conditions: inlet water temperature 5~15°C, return air temperature 4~40°C DB, 30~85% non-condensing
4. Specifications are subject to change due to constant product updates

32
Delta InfraSuite Precision Cooling
RowCool 35kW, Air-Cooled

As power density increases in modern data centers, traditional precision cooling


fails to provide complete cooling for the following situations:
• Load variations for peak and off-peak periods
• High power density
• Uneven heat distribution
The Delta InfraSuite Precision Cooling RowCool Series can effectively
solve the above.

High Efficiency
• H
 igh Energy Efficiency Ratio (EER) design with best indoor and
outdoor unit combinations provide low annual operating costs
• B
 uilt-in compressor with inverter capable of variable speeds at
different loadings for cost saving operations
• C
 ontinuously variable speed EC indoor and outdoor fan design for
energy savings
• H
 igh cooling capacity within compact footprint helps users save on
data center space and procurement investment

High Availability
• Modular rack design readily expandable as required to enable quick configuration and eliminate hot spots
• Supporting group control and use as backup for load variations in peak and off-peak periods
• Optional reheater and humidifier accessories for more precise temperature and humidity control
• B
 uilt-in high / low pressure switch, compressor temperature sensor, air flow sensor, and more that notify users
early and reduce maintain time
• Repair from front/rear and a modular components design reduces checking and maintenance time.
• Low speed to keep compressor running at low loading and avoid frequent stop/start to ensure compressor life.

High Flexibility
• Horizontal air flow suitable for data centers without raised floor saves on construction costs
• Pipe and power connections suitable for both top and bottom insertion, with flexible configuration as required
• D
 isposable filters with high efficiency (MERV 8), and washable MERV 1 filters are available for purchase to
save cost
• Remote monitoring through SNMP card providing more comprehensive system protection

Delta InfraSuite 33
Precision Cooling

Technical Specifications
Model HCH6C60 HCH6C60 Humidity Control
Type Air-Cooled Air-Cooled
Max cooling capacity 37.2kW 37.2kW
Max sensible cooling capacity 36.1kW 36.1kW
Input power 3N~, 380V, 50/60Hz 3N~, 380V, 50/60Hz
Max input current 28.4A 36.6A
Air flow 8340 CMH 8340 CMH
Compressor Inverter-driven scroll compressor Inverter-driven scroll compressor
Refrigerant R410A R410A
Filter MERV 8 MERV 8
Reheater N/A 5.4kW
Humidifier N/A 3kg/h
Communication RS232×1, RS485×1, CAN IN/OUT×1, Input dry contact×1,Output dry contact× 1, SNMP Slot×1
Piping Gas pipe 7/8” ODF solder Gas pipe 7/8” ODF solder
Liquid pipe 5/8” ODF solder Liquid pipe 5/8” ODF solder
Drain pipe PVC 3/4” ID Drain pipe PVC 3/4” ID
Humidifier supply water PVC 3/8” ID
Optional parts Remote temp/RH sensor, remote temp sensor, SNMP card, drain pump, leakage detector, reheater, humidifier,
low pressure transducer, liquid pipe temperature sensor, suction pipe temperature sensor
Dimensions (W×D×H) 600×1090×2000mm 600×1090×2000mm
Weight 340kg 352kg

* Cooling capacity is measured at 40.6°C dry bulb, 21.6°C wet bulb return temperature and 35°C outdoor temperature condition.
* The pressure of humidifier supply water should be between 0.1~0.35MPa.
* Please contact Delta or a local distributor for new specifications and details on continuous improvements Delta makes for various lines of products.

Outdoor Condenser
Model HCC6C50-28 HCC6C70-43
Power 3~, 380V±10%, 50/60Hz
Max input current 2A / each fan
Air flow 11220 CMH 18600 CMH
Operating temperature -15~35°C -15~40°C
Dimensions (W×D×H) 1732×1100×1160mm 1932×1100×1160mm
Weight 160kg 200kg

Scroll Type Compressor


• Small size, low noise, high reliability
• Driven by an inverter, the cooling capacity is variable from 30% to 100%
• Automatic over-temperature protection
• Longer compressor life through reduced frequency of system start and stop

34
Delta InfraSuite Precision Cooling
RowCool 43/95kW, Chilled Water

As the power density increases in modern data centers, traditional precision air conditioning fails to provide complete
cooling for the following situations:
• Load variations for peak and off-peak period
• High power density
• Uneven heat distribution
The Delta InfraSuite Precision Cooling RowCool Chilled Water can effectively solve the above problems.

High Efficiency
• T
 o comply with the high power density of racks, the RowCool
series cooling capacity can increase up to 60kW (HCH1870)
and 120kW (HCH1CD0) without changing footprint
• W
 hen Applied to the high temperature settings of inlet water,
outdoor units save on power consumption by up to 15~20%
when the chiller water temperature increases from 5°C to
12°C
• D
 C or EC fans provide continuously variable fan speed
control and energy savings
• V
 ariable flow control capability saves on pump power
consumption

High Flexibility
• Built-in dual power supply input for better power reliability
• C
 hiller water pipe suitable for both top and bottom insertion
providing flexible configuration as required

High Manageability
• R
 emote monitoring can be carried out through RS232,
RS485 or Modus protocol via SNMP card, providing more
comprehensive system protection
• B
 uilt-in vortex water flow meter capable of monitoring chiller
water flow that renders easy display of system status
• Hot-swappable
 power supply and fans greatly reduce
maintenance time (applicable for HCH1870)

Applications
• High power density rack area
• Environment that requires precise environmental control

Delta InfraSuite 35
Precision Cooling

Technical Specifications
HCH1CD0 with
Model HCH1870 HCH1CD0
Humidity Control
Power Input power 1~, 220V, 50/60Hz 3N~, 380V, 50/60Hz 3N~, 380V, 50/60Hz
Power consumption kW 2 4.8 4.8
Rating capacity* Capacity kW 43.4 95.9 95.9
Sensible Capacity kW 43 95.9 95.9
Max capacity** Capacity kW 59.1 122.7 122.7
Sensible Capacity kW 59.1 122.7 122.7
Capacity at high Capacity kW 37 81.2 81.2
inlet water*** Sensible Capacity kW 37 81.2 81.2
Fan Type DC fan EC fan EC fan
Qty n. 8 3 3
Valve Air flow m3/h 7475 14050 14050
Type - 2way / 3way 2 way 2 way
Max flow LPM 100 150 150
Inlet water temp. range °C 5~22 5~22 5~22
Reheater Type N/A N/A Electric heater
Capacity kW N/A N/A 8.1
Humidifier Type N/A N/A Electrode
Capacity kg/h N/A N/A 3
Filter Type MERV 1 MERV 1 MERV 1
Connection Inlet pipe in 1 PT Female 1 1/4 PT Female 1 1/4 PT Female
Outlet pipe in 1 PT Female 1 1/4 PT Female 1 1/4 PT Female
Drain pipe in 5/8” ID 3/4” ID 3/4” ID
Dimension Width mm 300 600 600
Depth mm 1090 1090 1090
Height mm 2000 2000 2000
Weight kg 187 415 422

* Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 7°C, rated water flow
** Operation conditions: 48.9°C (DB), 23.9°C (WB), inlet water temperature 7°C, maximum water flow
*** Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 12°C, temperature difference 8°C(HCH1870)/9°C(HCH1CD0)

36
Protect Your
The DPS Series UPS The DPH Series UPS The G
safeguards one of the provides continuous ensure
largest fixed line protection to a major a lead
operators in Poland. airport in Poland.

The DPH Series UPS


secures one of the major
railway upgrade projects in
Germany.

The DPH & NH Plus Series


UPSs provide continuous
power to one of the largest
telecom operators in Spain.

The NT Series UPS powers a


world-leading consumer goods
company in Brazil.

The DPH Series UPS ensures


operations for one of Angola's
largest datacenters.

The GAIA Series UPS


secures the operations for one
of the major governmental
datacenters in South Africa.

Delta InfraSuite 37
Critical Operations 24/7
GAIA Series UPS The DPS Series UPS The NT Series UPS secures
es the operations of protects one of Russia’s power to the most advanced
ding bank in Poland. most advanced medical datacenter in Russia.
healthcare centers

The InfraSuite Datacenter


Solution ensures the continuous
operations of China’s most
modern TV tower.

Delta’s UPS and Precision


Cooling products protect the
leading semiconductor foundry
in Taiwan.

The InfraSuite Datacenter


Solution safeguards the
datacenter of a major university
in Taiwan.

The NH Plus Series UPS


provides continuous power to
one of the largest manufacturers
in Thailand.

The NT Series UPS The N Series UPS safeguards


powers a major water one of the largest city monitor-
utility in Australia. ing operators in Thailand.

38
Europe Asia Pacific
The Netherlands Switzerland China
Delta Electronics (Netherlands) BV Delta Energy Systems (Switzerland) AG Delta GreenTech (China) Co., Ltd.
Zandsteen 15, 2132MZ Hoofddorp, Freiburgstrasse 251, 3018 Bern-Bümpliz, 238 Minxia Road, Pudong, Shanghai,
The Netherlands Switzerland 201209 P.R.C
T +31 (0)20 655 09 00 T +41 31 998 53 11 T +86 21 5863 5678
E [email protected] E [email protected] T +86 21 5863 9595
E [email protected]
Finland Turkey
Delta Energy Systems (Finland) Oy Delta Greentech Electronic San. Ltd. India
P.O. Box 63, Juvan teollisuuskatu 15, FIN- Serifali Mevkii Barboros Bulvari Soylesi Sok No Delta Power Solutions (India) Pvt. Ltd.
02921 Espoo, Finland 19 Y.Dudullu-Umraniye/Istanbul, Turkey Plot No. 43, Sector-35, HSIIDC,
T +358 9 84966 0 T +90 216 499 9910 Gurgaon-122001, Haryana, India
E [email protected] E [email protected] T +91 124 4874 900
E [email protected]
France United Kingdom
Delta Energy Systems (France) S.A. Delta Electronics Europe Ltd. Taiwan
ZA Bois Chaland2 - 15 rue des Pyrénées - 1 Redwood Court, Peel Park Campus, East Delta Electronics Inc.
Lisses 91090, France Kilbride, G74 5PF, United Kingdom 39 Section 2, Huandong Road,
T +33 1 69 77 82 60 T +44 1355 588 888 Shanhua Township
E [email protected] E [email protected] Tainan County 74144, Taiwan
T +886 6 505 6565
Germany Spain E [email protected]
Delta Energy Systems AG Delta Energy Systems Spain, S.L.
Coester Weg 45, 59494 Soest, Germany Carretera de Villaverde a Vallecas 265 1ºD Australia
T +49 2921 987 337 Edificio Hormigueras. 28031 - Madrid, Spain Delta Energy Systems Australia Pty Ltd.
E [email protected] T +34 91223 7420 Unit 20-21, 45 Normanby Road, Notting
E [email protected] Hill VIC 3168, Australia
Czech Republic T +61 3 9543 3720
Delta Energy Systems Middle-East & Africa E [email protected]
(Czech Republic), spol.s r.o. South Africa
Perucka 2482/7 Sydney office:
Delta Energy Systems MEA (Switzerland) AG
120 00 Praha 2 Level 3 / 67-69 Epping Rd, North Ryde,
South Africa Representative Office
Czech Republic NSW 2113
Unit 305B, Lougardia Building, Cnr
T +420 272 019 330
Embankment and Hendrik Verwoerd Drive,
E [email protected] Thailand
Centurion, 0157, South Africa
T +27 12 663 2714 Delta Electronics (Thailand) Public Co.,
Poland E [email protected] Ltd.
Delta Energy Systems (Poland) Sp. z.o.o. 909 Soi 9, Moo 4, E.P.Z., Bangpoo
23 Poleczki Str., 02-822 Warszawa, Industrial Estate, Tambon Prakasa,
Americas
Poland Amphur Muang-samutprakarn,
T +48 22 335 26 00 Brazil Samutprakarn Province 10280, Thailand
E [email protected] Delta Greentech (Brasil) S/A T +662 709-2800
Rua Itapeva, Nº 26 - 3º andar E [email protected]
Russia 01332 000 - São Paulo - SP
Delta Energy Systems LLC T +55 11 3568 3850 Singapore
Vereyskaya Plaza II, office 401, Vereyskaya E [email protected] Delta Electronics Int’l (Singapore) Pte Ltd.
str.17, 121357 Moscow, Russia 4 Kaki Bukit Ave 1, #05-04, Singapore
T +48 22 335 26 00 417939
E [email protected] T +65 6747 5155
E [email protected]
Slovak Republic
DELTA ELECTRONICS (SLOVAKIA), s.r.o.
Botanicka 25/A, SK - 841 04 Bratislava,
Slovakia
T +421 (0)2 6541 1258
E [email protected]

Delta InfraSuite 39
Brochure_InfraSuite_en-us_v5