Slab Design

The document describes the design of a two-way reinforced concrete slab using ACI coefficients. It provides details of the slab dimensions, material properties, applied loads, design moments calculated, and reinforcement requirements and layout. Reinforcement amounts are calculated for various regions of the slab and checked against code minimum requirements. Shear demands are also verified to be below the slab's shear capacity. Diagrams show the slab panel layout and reinforcement bar locations.

Uploaded by

ImranSohail
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
117 views

Slab Design

The document describes the design of a two-way reinforced concrete slab using ACI coefficients. It provides details of the slab dimensions, material properties, applied loads, design moments calculated, and reinforcement requirements and layout. Reinforcement amounts are calculated for various regions of the slab and checked against code minimum requirements. Shear demands are also verified to be below the slab's shear capacity. Diagrams show the slab panel layout and reinforcement bar locations.

Uploaded by

ImranSohail
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 18

No Liability is accepted by the Developer of this software for any direct, indirect, consequential or accidental loss or damage

accidental loss or damage


SLAB DESCRIPTION: SERVICE FLOOR

SLAB DIMENSIONS

Short Span (la) 20 ft


Long Span (lb) 25 ft

SLAB THICKNESS

Thickness Required 6.00 in


Thikness Provided 5 in
Clear Cover (Top & Bottom) 0.75 in
Mu (-ve)=-1.09 k-ft/ft
IMPOSED LOADS Asmin = 0.12 sq.in/ft

Superimposed Dead Load (unfactd) 45 psf #3 @ 11 in c/c (T)

Superimposed Live Load (unfactd) 45 psf

MATERIAL STRENGTH

Concrete Strength f'c 3 ksi


Steel Yeild Strength 40 ksi

COEFFICIENTS TO BE USED ACI


PANEL No.: S1

Mu(-ve) =-1.69 k-ft/ft


As = 0.14 sq.in/ft
#3 @ 9 in c/c (T)

Mua+ =5.08k-ft/ft
As = 0.46 sq.in/ft
#4 @ 5 in c/c (B)
Two Way Slab Mu (-ve) =-1.09 k-ft/ft
Mub+ =3.26 k-ft/ft Asmin = 0.12 sq.in/ft
As = 0.32 sq.in/ft #3 @ 11 in c/c (T)
#3 @ 4 in c/c (B)

Mu(-ve) =-1.69 k-ft/ft


As = 0.14 sq.in/ft
#3 @ 9 in c/c (T)
DESIGN OF TWO-WAY SLAB BY ACI-COEFFICIENTS
SERVICE FLOOR
PANEL No : S1

Input Data:
Slab Dimensions
Short Span = 20 ft
Long Span = 25 ft
Span Ratio = 20 / 25 = 0.8
Slab Thickness (reqd) = 2 x (20+25) x 12 / 180 =
Slab Thickness (prvd) = 5 in

Edge Conditions
Short Span Edge Condition = Both Edges Discontinuous
Long Span Edge Condition = Both Edges Discontinuous

Applied Loads
Slab self wt = 62.50 psf
Service Dead Load = 45 psf
Service Live Load = 45 psf
Material Strengths
Concrete Strength = 3 ksi
Steel Yield Strength = 40 ksi

Design Moments
Loads
Total Ultimate DL = 1.4(62.5 + 45) = 150.5 psf
Total Ultimate LL = 1.7(45) = 76.5 psf
Total Ultimate Load = 150.5 + 76.5 = 227 psf

Short Span Moments


Positive Moment DL Mua(dl)+ = 0.056 x 150.5 x 20^2
Positive Moment LL Muall+ = 0.056 x 76.5 x 20^2
Total Postive Short Span Moment Mua+ = --------------------------------->

Negative Moment on Discontinuous Edge = 1/3 x 5.085


Negative Moment on Discontinuous Edge = 1/3 x 5.085

Long Span Moments


Positive Moment DL Mubdl+ = 0.023 x 150.5 x 25^2
Positive Moment LL Mubll+ = 0.023 x 76.5 x 25^2
Total Postive Long Span Moment Mub+ = --------------------------------->

Negative Moment on Discontinuous Edge = 1/3 x 3.263


Negative Moment on Discontinuous Edge = 1/3 x 3.263

DESIGN OF TWO-WAY SLAB BY ACI-COEFFICIENTS


SERVICE FLOOR
PANEL No : S1

Reinforcement Calculations
Along Short Span
Positive Steel
Mu=5.08 k-ft ; b=12 in ; d=4 in ; fc'=3ksi ; fy= 40 ksi
As+ = 0.85 x 3 / 40 x [1 - [1-2 x 12 x5.085/(0.9x0.85x3x12x4^2) ]^0.5 ] x 12 x 4
= 0.458 sq.in.
Asmin = 0.002 x 12 x 5 =
use As+ = 0.458 sq.in. (#4 @ 5 in )
Negative Steel
Mu=1.69 k-ft ; b=12 in ; d=4.063 in ; fc'=3ksi ; fy= 40 ksi
As- = 0.85 x 3 / 40 x [1 - [1-2 x 12 x1.695/(0.9x0.85x3x12x4.063^2) ]^0.5 ] x 12 x
= 0.142 sq.in.
Asmin = 0.002 x 12 x 5 =
use As- = 0.142 sq.in. (#3 @ 9 in )
Negative Steel
Mu=1.69 k-ft ; b=12 in ; d=4.063 in ; fc'=3ksi ; fy= 40 ksi
As- = 0.85 x 3 / 40 x [1 - [1-2 x 12 x1.695/(0.9x0.85x3x12x4.063^2) ]^0.5 ] x 12 x
= 0.142 sq.in.
Asmin = 0.002 x 12 x 5 =
use As- = 0.142 sq.in. (#3 @ 9 in )

Along Long Span


Positive Steel
Mu=3.26 k-ft ; b=12 in ; d=3.563 in ; fc'=3ksi ; fy= 40 ksi
As+ = 0.85 x 3 / 40 x [1 - [1-2 x 12 x3.263/(0.9x0.85x3x12x3.563^2) ]^0.5 ] x 12 x
= 0.325 sq.in
Asmin = 0.002 x 12 x 5 =
use As+ = 0.325 sq.in. (#3 @ 4 in )
Negative Steel
Mu=1.09 k-ft ; b=12 in ; d=4.063 in ; fc'=3ksi ; fy= 40 ksi
As- = 0.85 x 3 / 40 x [1 - [1-2 x 12 x1.088/(0.9x0.85x3x12x4.063^2) ]^0.5 ] x 12 x
= 0.091 sq.in
Asmin = 0.002 x 12 x 5 =
use As- = 0.120 sq.in. (#3 @ 11 in )
Negative Steel
Mu=1.09 k-ft ; b=12 in ; d=4.063 in ; fc'=3ksi ; fy= 40 ksi
As- = 0.85 x 3 / 40 x [1 - [1-2 x 12 x1.088/(0.9x0.85x3x12x4.063^2) ]^0.5 ] x 12 x
= 0.091 sq.in
Asmin = 0.002 x 12 x 5 =
use As- = 0.120 sq.in. (#3 @ 11 in )

Shear Check (aci-coefficient)


Total load on the panel = 20 x 25 x 227 = 113.5 kips

Shear Capacity of the section fVc = 0.85 x 2 x ( 3000 )^½ x 12 x 4 / 1000 = 4.46 k/ft

Shear along short side Vua = ( 0.29 x 113.5 ) / (2 x 20 ) = 0.82 k/ft


Shear along long side Vub = ( 0.71 x 113.5 ) / ( 2 x 25 ) = 1.61 k/ft
6 in

= 3.371 k-ft/ft
= 1.714 k-ft/ft
= 5.085 k-ft/ft

= 1.695 k-ft/ft
= 1.695 k-ft/ft

= 2.163 k-ft/ft
= 1.100 k-ft/ft
= 3.263 k-ft/ft

= 1.088 k-ft/ft
= 1.088 k-ft/ft

85x3x12x4^2) ]^0.5 ] x 12 x 4

0.120 sq in

85x3x12x4.063^2) ]^0.5 ] x 12 x 4.063

0.120 sq in

85x3x12x4.063^2) ]^0.5 ] x 12 x 4.063

0.120 sq in
85x3x12x3.563^2) ]^0.5 ] x 12 x 3.563

0.120 sq in

85x3x12x4.063^2) ]^0.5 ] x 12 x 4.063

0.120 sq in
use #3 @ 10 in

85x3x12x4.063^2) ]^0.5 ] x 12 x 4.063

0.120 sq in
use #3 @ 10 in

0 = 4.46 k/ft

<4.46 k/ft…. (O.K.)


<4.46 k/ft….(O.K).
39 5'-0''

45

20 Ft

6'-3''

10
3

39
5'-0''

25 Ft

SCHEMATIC DIAGRAM OF REINFORCED SLAB


SERVICE FLOOR
PANEL NO: S1
0
6'-3''

4 10
3 3

OF REINFORCED SLAB