MIB Settings of 20 MVA Power Transformer

This document contains settings calculations for a power transformer and current transformers. It provides details of a 20 MVA transformer with a 66kV/11kV configuration and Dyn11 vector group. Calculations determine the rated currents and multipliers needed for the high voltage and low voltage current transformer settings. The interposing current transformer selections are also outlined based on different power transformer vector groups.

Uploaded by

Ravi Shankar V
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
431 views3 pages

MIB Settings of 20 MVA Power Transformer

This document contains settings calculations for a power transformer and current transformers. It provides details of a 20 MVA transformer with a 66kV/11kV configuration and Dyn11 vector group. Calculations determine the rated currents and multipliers needed for the high voltage and low voltage current transformer settings. The interposing current transformer selections are also outlined based on different power transformer vector groups.

Uploaded by

Ravi Shankar V
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

MIB Settings [Date]

Power Transformer Details

Voltage HV 66
LV 11
Rating MVA 20
Tap Changer
Higher Side 5
Lower Side -20
Vector Group Dyn 11

Current Transformer Details


HV Side 200
LV Side 1200

Calculations

Rated Current on HV 174.96


Rated Current on LV 1049.76

Mean Tap Value -7.5

HV Current at Mean Tap 189.15

HV Multiplier 1.06
LV CT Secondary Current 0.87
LV Mulitplier 1.14312

Initial Settings 200 mA


Bias Setting 2 0%
Bias Slope Limit 4 times FL Current

HV ICT Multiplier 1.06


LV ICT Multiplier 1.14
CT SelectionLV
Power Transformer Vector Group HV
Interposing
Interposing
Dy11, Dyn11 Ydy0,0° CTYd1,30°
Selection
Dy1, Dyn1 Ydy0,0° Yd11,-30°

Station Name:
Transformer No.
Date of Relay Setting Calculations
MIB Settings [Date]

Inter posing CT selection Guide LV


HV
Interposing
Power Transformer Vector Group Interposing
CT Selection CT Selection
Yy0, YNy0, Yyn0, YNyn0, Ydy0,
Yd1,30° Yd1,30°
Yndy0, Ydyn0, YNdyn0
Yd1, YNd1 Yd1,30° Yy0,0°
Yd1, YNd1 + Earthing Transformer Yd1,30° Ydy0,0°
Yy2, YNy2, Yyn2, YNyn2, Ydy2,
Yd3,90° Yd1,30°
Yndy2, Ydyn2, YNdyn2
Yd3, YNd3 Yd3,90° Yy0,0°
Yd3, YNd3 + Earthing Transformer Yd3,90° Ydy0,0°
Yy4, YNy4, Yyn4, YNyn4, Ydy4,
Yd5,150° Yd1,30°
Yndy4, Ydyn4, YNdyn4
Yd5, YNd5 Yd5,150° Yy0,0°
Yd5, YNd5 + Earthing Transformer Yd5,150° Ydy0,0°
Yy6, YNy6, Yyn6, YNyn6, Ydy6,
Yd7,-150° Yd1,30°
Yndy6, Ydyn6, YNdyn6
Yd7, YNd7 Yd7,-150° Yy0,0°
Yd7, YNd7 + Earthing Transformer Yd7,-150° Ydy0,0°
Yy8, YNy8, Yyn8, YNyn8, Ydy8,
Yd9,-90° Yd1,30°
Yndy8, Ydyn8, YNdyn8
Yd9, YNd9 Yd9,-90° Yy0,0°
Yd9, YNd9 + Earthing Transformer Yd9,-90° Ydy0,0°
Yy10, YNy10, Yyn10, YNyn10, Ydy10,
Yd11,-30° Yd1,30°
Yndy10, Ydyn10, YNdyn10
Yd11, YNd11 Yd11,-30° Yy0,0°
Yd11, YNd11 + Earthing Transformer Yd11,-30° Ydy0,0°
Dy1, Dyn1 Ydy0,0° Yd11,-30°
Dy1, Dyn1 + Earthing Transformer Ydy0,0° Yd11,-30°
Dy3, Dyn3 Ydy0,0° Yd9,-90°
Dy3, Dyn3 + Earthing Transformer Ydy0,0° Yd9,-90°
Dy5, Dyn5 Ydy0,0° Yd7,-150°
Dy5, Dyn5 + Earthing Transformer Ydy0,0° Yd7,-150°
Dy7, Dyn7 Ydy0,0° Yd5,150°
Dy7, Dyn7 + Earthing Transformer Ydy0,0° Yd5,150°
Dy9, Dyn9 Ydy0,0° Yd3,90°
Dy9, Dyn9 + Earthing Transformer Ydy0,0° Yd3,90°
Dy11, Dyn11 Ydy0,0° Yd1,30°
MIB Settings [Date]

Dy11, Dyn11 + Earthing Transformer Ydy0,0° Yd1,30°