DC1000 Controller Spec
DC1000 Controller Spec
Technical data
Thermocouples : K, J, R, S, B, E, N, T, W, PL II, U, L
Type of Input RTD : Pt100, JPt100, JPt50
PV Input Linear : 4~20mA
Input Sampling Time 250 ms
Input Resolution 14 bit (each)
PV/SP Indication 4-digit, 7 segment display
Indication Constant Value Storage System Non-volatile memory (EEPROM)
Indication Accuracy +/-0.2%FS
Proportional Band ( P ) 0~200% (On/Off action at P=0)
Integral Time ( I ) 0~3600 sec (PD action at I=0)
Control Mode Derivative Time ( D ) 0~900 sec (PI action at D=0)
Cycle Time 0~150 sec (4~20mA=0, SSR=1, Relay=10)
Dead Band Time 0~1000 sec (dead time compensation)
Relay Output Electromechanical relay
• SPDT contacts (DC101 :SPST)
• 3A/240Vac
Static relay driver output Voltage Pulse, 20VDC/20mA
Output Current & Voltage outputs 0~20mA, 4~20mA,
0~5V, 0~10V, 1~5V, 2~10V
Motor Control Output Servo motor valve control (open loop circuit)
Others Phase angle control :
1ϕ SSR, 3ϕ SSR, 1ϕ SCR, 3ϕ SCR
Number Up to 3 (optional, DC101 :2sets)
Modes 17 alarm modes available, hability to ignore the alarm
the first time it occurs :
Deviation high or low alarms.
Deviation alarms.
51-52-03-33 08/03 2
2nd Input Type of Input 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
(Remote SP) Sampling Time 500 ms.
Programs Number 2 programs of 8 segments each.
Type of Communication RS-232 or RS-485. Modus rtu(HEX), Modbus ASCII
Communication
Specification Partity= Odd/Even, Data bit= 8bits,
Stop bit=1 or 2 bit
Communication Speed 2400,4800,9600,19200,38400 bps
Rated Power Supply Voltage & AC 85 ~ 265V, 50/60Hz
Frequency DC24V(optional)
Operating Power Consumption 8VA (110V), 12VA (220V)
conditions
Ambient Temperature -20°C ~ 65°C (-4°F ~ 149°F)
Ambient Humidity 50 ~ 85% RH (non condensing)
UL (QUXY2-E201698)
Approvals
CE Mark.
°C °F
B 0~1820 °C 0~3308 °F
51-52-03-33 08/03 3
Control Algorithms
K1 K1
K2 G2
OFF
G2
K2 ON
G3
K3
Thyristor P
Module R
PROT
O
T L
L
3φ LOAD
1φ LOAD
In phase angle control, power is regulated by changing the point at which the SCR is turned on within each 1/2 period.
Single Phase : Output is changed every half-cycle in response to output signals from the Temperature Controller.
Three Phase : The outputs are changed every 120° in response to signals from the Temperature Controller.
Using this form of control, high-precision temperature control is possible.
• Zero-crossover control
Single Phase Three Phase
L N R S T
Controller Controller
Thyristor
G1 Module
RG1
RG2
G2
TG1
TG2
Thyristor
P P
Module
R R
O O
T L T L
1φ LOAD 3φ LOAD
The term Zero-Crossover means that the SCR's are turned on only when
the instantaneous value of the sinusoidal wave is zero. Power is then
applied for a several continuous half-cycles and then removed for
several half-cycles to achieve the desired load power.
ON OFF
OPEN
Slidewires wear over a period of time, which can result in
OPEN
COM OUT1 poor or intermittent control. This type of control reduces
Relay
51-52-03-33 08/03 4
EXTERNAL DIMENSIONS, PANEL CUTOUT
DC1010
68 mm - 2.68 in
50 mm - 1.97 in 6 mm 13.5 mm
45.5 mm - 1.79 in
0.24 in 74.5 mm - 2.97 in 0.53 in
50 mm - 1.97 in
60 mm - 2.36 in
44 mm - 1.73 in
45.5 mm - 1.79 in
DC1020
6 mm 13.5 mm
48 mm - 1.89 in 0.24 in 74.5 mm - 2.97 in 0.53 in
60 mm - 2.36 in
96 mm - 3.78 in 91mm
3.58 in
86 mm
116 mm
3.39 in
4.57 in
45.5mm
1.79 in
DC1030
6 mm 13.5 mm
72 mm - 2.83 in 74.5 mm - 2.97 in 91 mm - 3.58 in
0.24 in 0.53 in
69.55 mm
91 mm - 3.58 in
66 mm - 2.60 in
72 mm - 2.83 in
2.74 in
69.55 mm
2.74 in
51-52-03-33 08/03 5
EXTERNAL DIMENSIONS, PANEL CUTOUT
DC1040
96 mm - 3.78 in 6 mm 13.5 mm
74.5 mm - 2.97 in 116 mm - 4.57 in
0.24 in 0.53 in
90 mm
116 mm - 4.57 in
96 mm - 3.78 in
3.54 in
90 mm
3.54 in
LEDs :
OUT1 : Status of output 1.
OUT2 : Status of output 2.
AT : When the LED is ON an automatic tuning of the parameters is on going.
AL1 : Status of alarm 1.
AL2 : Status of alarm 2.
AL3 : Status of alarm 3.
MAN : ON if we are in Auto mode. OFF if manuel mode.
PRO : Flickers when a program is running.
Continuously ON when a program is suspended.
OFF when no program is running.
SET allows to change from one parameter to another. Pressing it for 5 seconds grants access to the
configuration level 1 (PID parameters+locking the instrument).
Pressing simultaneously for 5 seconds on the left arrow and SET grants access to the configuration
level 2 (input type, alarmes, SP limits, field calibration, communication parameters, …).
A/M allows to switch from Auto to When modifying a parameter, pressing this key
Manual. allows to change the digit to modify.
Pressing this key decreases the Pressing this key increases the parameter or
parameter or digit being modified. digit being modified.
51-52-03-33 08/03 6
MODEL SELECTION GUIDE
• Select the desired Key Number.
• Make One selection each from Tables I through III.
Dimension
1 48*48mm
2 48*96mm
3 72*72mm
4 96*96mm
Table III
Program Input
Manual
C None R RTD
E English
P Program T TC
F French
L Linear
I Italian
G German
S Spanish
Table I Table II
Output 1 Output 2 Alarm Aux. Output 2nd Input Comm.
0 None 0 None 0 None 0 None 0 None 0 None
1 Relay 1 Relay 1 1 alarm 1 4~20mA 1 4~20mA 1 RS232
2 Voltage 2 Voltage 2 2 alarms 2 0~20mA 2 0~20mA 2 RS485
3 4~20mA 3 4~20mA 3 3 alarms A 0~5V A 0~5V
5 1 ϕ SSR A 0~5V B 0~10V B 0~10V
6 3 ϕ SSR B 0~10V C 1~5V C 1~5V
7 Motor V C 1~5V D 2~10V D 2~10V
8 1 ϕ SCR D 2~10V
9 3 ϕ SCR
A 0~5V
B 0~10V
C 1~5V
D 2~10V