This document summarizes the design of a two-way reinforced concrete slab according to ACI 318-05. It provides details of the slab geometry, materials, and loads. Moment calculations are shown for the x- and y-directions. Required flexural strengths are calculated for column strips and middle strips. Reinforcement sizing will be determined based on the calculated required strengths.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
542 views6 pages

RC Two Way Slab Design ACI318 05 PDF

This document summarizes the design of a two-way reinforced concrete slab according to ACI 318-05. It provides details of the slab geometry, materials, and loads. Moment calculations are shown for the x- and y-directions. Required flexural strengths are calculated for column strips and middle strips. Reinforcement sizing will be determined based on the calculated required strengths.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
1
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

RC TWO WAY SLAB DESIGN TO ACI 318 – 05

y
lx x

½ Column strip

ly Middle strip

½ Column strip

½ Column strip Middle strip ½ Column strip

TWO-WAY SLAB PANEL

200 mm
Section at middle strip along X axis

Slab definition
Slab thickness; h = 150 mm
Span along x – dir; lx = 6000 mm
Span along y – dir; ly = 4000 mm
Long span to short span ratio less than 2, hence two-way slab
Clear cover to positive reinforcement; cc = 20 mm
Clear cover to negative reinforcement; c’c = 20 mm
Effective flanged beam section
Flange width; bf = 1000 mm
Beam depth; hb = 550 mm
Beam width; bw = 300 mm
Materials
Specified compressive strength of concrete; f’c = 35 MPa
Specified yield strength of reinforcement; fy = 415 MPa
Modulus of elasticity; ESACI = 199948MPa
Loads
2
Total factored ultimate load on slab; wu = 18.00 kN/m
Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
2
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

Check for the depth of slab provided


Clear span x – dir; lnx = lx - bw / 2 - bw / 2 = 5700 mm
Clear span y – dir; lny = ly - bw / 2 - bw / 2 = 3700 mm
Ratio;  = max(lnx, lny) / min(lnx, lny) = 1.541
Moment of inertia of beam; Ib = 6922916667 mm4
Moment of inertia of slab along x – axis; Isx = 1125000000 mm4
Moment of inertia of slab along y – axis; Isy = 1687500000 mm4
Flexural stiffness ratio along x – axis; fx = Ib / Isx = 6.154
Flexural stiffness ratio along y – axis; fy = Ib / Isy = 4.102
Average flexural stiffness ratio; fm = (fx × 2 + fy × 2) / 4 = 5.128
Minimum depth required; hmin = 125 mm
PASS - slab thickness provided is sufficient for deflection
Moment computation (x – direction)
Width of column strip (half); lcol_stp = min(0.25 × lx, 0.25 × ly) = 1000 mm
Width of middle strip; lmid_stp_x = ly - 2 × lcol_stp = 2000 mm
Factored moment; Mox = wu × ly × lnx2 / 8 = 292.41 kNm
Moment distribution for interior panel; M’ux = 0.65 × Mox = 190.07 kNm
Mux = 0.35 × Mox = 102.34 kNm
Moment distribution in column and middle strips
ly / lx = 0.67
fx × ly / lx = 4.10
Moment distribution factors; fx_neg = 0.85
fx_pos = 0.85
Total column strip design moments; M’x_col_stp = fx_neg × M’ux = 161.56 kNm
Mx_col_stp = fx_pos × Mux = 86.99 kNm
Column strip beam moments; M’x_beam = 137.32 kNm
Mx_beam = 73.94 kNm
Column strip slab moments; M’x_slab = M’x_col_stp - M’x_beam = 24.23 kNm
Mx_slab = Mx_col_stp - Mx_beam = 13.05 kNm
Total middle strip design moments; M’x_mid_stp = (1 - fx_neg) × M’ux = 28.51 kNm
Mx_mid_stp = (1 - fx_pos) × Mux = 15.35 kNm
Required flexural nominal strength in column strip per 1 m width of slab
M’nx_col = M’x_slab / (0.9 × (2 × lcol_stp - bf)) = 26.93 kNm/m
Mnx_col = Mx_slab / (0.9 × (2 × lcol_stp - bf)) = 14.50 kNm/m
Required flexural nominal strength in middle strip per 1 m width of slab
M’nx_mid = M’x_mid_stp / (0.9 × lmid_stp_x) = 15.84 kNm/m
Mnx_mid = Mx_mid_stp / (0.9 × lmid_stp_x) = 8.53 kNm/m
Moment computation (y – direction)
Width of column strip (half); lcol_stp = min(0.25 × lx, 0.25 × ly) = 1000 mm
Width of middle strip; lmid_stp_y = lx - 2 × lcol_stp = 4000 mm
Factored moment; Moy = wu × lx × lny2 / 8 = 184.82 kNm
Moment distribution for interior panel; M’uy = 0.65 × Moy = 120.13 kNm
Muy = 0.35 × Moy = 64.69 kNm
Moment distribution in column and middle strips
lx / ly = 1.50
fy × lx / ly = 6.15
Moment distribution factors; fy_neg = 0.60
Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
3
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

fy_pos = 0.60
Total column strip design moments; M’y_col_stp = fy_neg × M’uy = 72.08 kNm
My_col_stp = fy_pos × Muy = 38.81 kNm
Column strip beam moments; M’y_beam = 61.27 kNm
My_beam = 32.99 kNm
Column strip slab moments; M’y_slab = M’y_col_stp - M’y_beam = 10.81 kNm
My_slab = My_col_stp - My_beam = 5.82 kNm
Total middle strip design moments; M’y_mid_stp = (1 - fy_neg) × M’uy = 48.05 kNm
My_mid_stp = (1 - fy_pos) × Muy = 25.87 kNm
Required flexural nominal strength in column strip per 1 m width of slab
M’ny_col = M’y_slab / (0.9 × (2 × lcol_stp - bf)) = 12.01 kNm/m
Mny_col = My_slab / (0.9 × (2 × lcol_stp - bf)) = 6.47 kNm/m
Required flexural nominal strength in middle strip per 1 m width of slab
M’ny_mid = M’y_mid_stp / (0.9 × lmid_stp_y) = 13.35 kNm/m
Mny_mid = My_mid_stp / (0.9 × lmid_stp_y) = 7.19 kNm/m
Reinforcement calculations
Stress block depth factor; 1 = max(0.65, 0.85 - 0.05  (f'c - 28 MPa) / 7 MPa = 0.85
Reinforcement percentage at strain of 0.004; b = 0.85  1  f’c / fy  (0.003 / (0.003 + 0.004)) = 0.026
Maximum reinforcement percentage; max = b = 0.026
Column strip (x – direction)
Negative Reinforcement
Depth to negative steel; d’x_col = h - c’c - D’col_x / 2 = 124 mm
Flexural resistance factor; R’ux_col = M’nx_col / d’x_col2 = 1.77 MPa
Reinforcement required; ’reqx_col =0.85f’c/fy×[1-(abs(1-2×R’ux_col /(0.85×f’c)))] = 0.00439
Outer compression steel not required
A’sx_req_col = ’reqx_col × d’x_col = 542 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; A’sx_min_col = max(1.4 MPa×d’x_col/fy,(f’c/1 MPa)×d’x_col1 MPa/(fy  4))
A’sx_min_col = 440 mm2/m
Maximum area of tension steel; A’sx_max_col = max × d’x_col = 3225 mm2/m
Maximum allowable spacing; smax = min(2 × h, 450 mm) = 300 mm
Reinforcement provided (negative), No. 4 @ 200 mm centers
Area of tension steel provided; A’sx_col = 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; s’x_col = 200 mm
PASS - spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dx_col = h - cc - Dcol_x / 2 = 124 mm
Flexural resistance factor; Rux_col = Mnx_col / dx_col2 = 0.95 MPa
Reinforcement required; reqx_col =0.85f’c/fy×[1-(abs(1-2×Rux_col/(0.85×f’c)))] = 0.00233
Outer compression steel not required
Asx_req_col = reqx_col × dx_col = 288 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; Asx_min_col = max(1.4 MPa×dx_col/fy,(f’c/1 MPa)×dx_col1 MPa/(fy  4))
Asx_min_col = 440 mm2/m
Maximum area of tension steel; Asx_max_col = max × dx_col = 3225 mm2/m
Reinforcement provided (positive), No. 4 @ 200 mm centers
Area of tension steel provided; Asx_col = 664 mm2/m
PASS - area of steel provided is OK
Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
4
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

Actual tensile bar spacing provided; sx_col = 200 mm


PASS - spacing of bars less than allowable
Middle strip (x – direction)
Negative Reinforcement:
Depth to negative steel; d’x_mid = h - c’c - D’mid_x / 2 = 124 mm
Flexural resistance factor; R’ux_mid = M’nx_mid / d’x_mid2 = 1.04 MPa
Reinforcement required; ’reqx_mid = 0.85f’c/fy×[1-(abs(1-2×R’ux_mid/(0.85×f’c)))] =0.00255
Outer compression steel not required
A’sx_req_mid = ’reqx_mid × d’x_mid = 315 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; A’sx_min_mid = max(1.4MPa× d’x_mid /fy,(f’c/1 MPa)× d’x_mid1MPa/(fy  4))
A’sx_min_mid = 440 mm2/m
Maximum area of tension steel; A’sx_max_mid = max × d’x_mid = 3225 mm2/m
Maximum allowable spacing; smax = min(2 × h, 450 mm) = 300 mm
Reinforcement provided (negative), No. 4 @ 200 mm centers
Area of tension steel provided; A’sx_mid = 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; s’x_mid = 200 mm
PASS - spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dx_mid = h - cc - Dmid_x / 2 = 124 mm
Flexural resistance factor; Rux_mid = Mnx_mid / (dx_mid2) = 0.56 MPa
Reinforcement required; reqx_mid = 0.85  f’c/fy×[1-(abs(1-2×Rux_mid/(0.85×f’c)))] = 0.00136
Outer compression steel not required
Area of tension steel required; Asx_req_mid = reqx_mid × dx_mid = 168.00 mm2/m
Minimum area of tension steel required; Asx_min_mid = max(1.4 MPa× dx_mid /fy,(f’c/1 MPa)× dx_mid1MPa/(fy  4))
Asx_min_mid = 440 mm2/m
Maximum area of tension steel; Asx_max_mid = max × dx_mid = 3225 mm2/m
Reinforcement provided (positive), No. 4 @ 200 mm centers
Area of tension steel provided; Asx_mid= 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; sx_mid = 200 mm
PASS - spacing of bars less than allowable
Column strip (y – direction)
Negative Reinforcement:
Depth to negative steel; d’y_col = h - c’c - D’col_x - D’col_y / 2 = 111 mm
Flexural resistance factor; R’uy_col = M’ny_col / d’y_col2 = 0.98 MPa
Reinforcement required; ’reqy_col =0.85f’c/fy× [1 -(abs(1-2×R’uy_col/(0.85×f’c)))] = 0.00241
Outer compression steel not required
A’sy_req_col = ’reqy_col × d’y_col = 266 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; A’sy_min_col = max(1.4 MPa×d’y_col/fy,(f’c/1 MPa)×d’y_col1 MPa/(4fy))
A’sy_min_col = 394 mm2/m
Maximum area of tension steel; A’sy_max_col = max × d’y_col = 2886 mm2/m
Maximum allowable spacing; smax = min(2 × h, 450 mm) = 300 mm
Reinforcement provided (negative), No. 4 @ 200 mm centers
Area of tension steel provided; A’sy_col = 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; s’y_col = 200 mm
Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
5
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

PASS - spacing of bars less than allowable


Positive reinforcement
Depth to positive steel; dy_col = h - cc - Dcol_x - Dcol_y / 2 = 111 mm
Flexural resistance factor; Ruy_col = Mnx_col / dy_col2 = 1.19 MPa
Reinforcement required; reqy_col =0.85f’c/fy×[1-(abs(1-2×Ruy_col/(0.85 × f’c)))] = 0.00292
Outer compression steel not required
Asy_req_col = reqy_col × dy_col = 322.74 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; Asy_min_col = max(1.4 MPa×dy_col/fy,(f’c/1 MPa)×dy_col1 MPa/(4fy))
Asy_min_col = 394 mm2/m
Maximum area of tension steel; Asy_max_col = max × dy_col = 2886 mm2/m
Reinforcement provided (positive), No. 4 @ 200 mm centers
Area of tension steel provided; Asy_col= 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; sy_col = 200 mm
PASS - spacing of bars less than allowable
Middle strip (y – direction)
Negative Reinforcement:
Depth to negative steel; d’y_mid = h - c’c - D’mid_x - D’mid_y / 2 = 111 mm
Flexural resistance factor; R’uy_mid = M’ny_mid / d’y_mid2 = 1.09 MPa
Reinforcement required; ’reqy_mid = 0.85f’c/fy×[1-(abs(1-2×R’uy_mid/(0.85×f’c)))] =0.00268
Outer compression steel not required
A’sy_req_mid = ’reqy_mid × d’y_mid = 297 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; A’sy_min_mid = max(1.4 MPa× d’y_mid/fy,(f’c/1 MPa)× d’y_mid1 MPa/(4fy))
A’sy_min_mid = 394 mm2/m
Maximum area of tension steel; A’sy_max_mid = max × d’y_mid = 2886 mm2/m
Maximum allowable spacing; smax = min(2 × h, 450 mm) = 300 mm
Reinforcement provided (negative), No. 4 @ 200 mm centers
Area of tension steel provided; A’sy_mid = 664 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; s’y_mid = 200 mm
PASS - spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dy_mid = h - cc - Dmid_x - Dmid_y / 2 = 111 mm
2
Flexural resistance factor; Ruy_mid = Mny_mid / dy_mid = 0.59 MPa
Reinforcement required; reqy_mid = 0.85  f’c/fy×[1-(abs(1-2×Ruy_mid/(0.85×f’c)))] =0.00143
Outer compression steel not required
Asy_req_mid = reqy_mid × dy_mid = 158 mm /m
2
Area of tension steel required;
Minimum area of tension steel required; Asy_min_mid = max(1.4 MPa× dy_mid/fy,(f’c/1 MPa)× dy_mid1 MPa/(4fy))
Asy_min_mid = 394 mm2/m
Maximum area of tension steel; Asy_max_mid = max × dy_mid = 2886 mm2/m
Reinforcement provided, No. (positive) 4 @ 200 mm centers
2
Area of tension steel provided; Asy_mid= 664 mm /m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; sy_mid = 200 mm
PASS - spacing of bars less than allowable
Distribution reinforcement (for shrinkage and temperature)
Minimum ratio of distribution reinforcement; t = 0.0018
Project Job Ref.

QF QF
Section Sheet no./rev.
DAR GROUP
6
Calc. by Date Chk'd by Date App'd by Date

MS 09-Nov-106 AE IC

Minimum area of distribution reinforcement required; At_req = t × h = 270 mm2/m


Maximum allowable spacing of bars; smax_t = min(5 × h, 450 mm) = 450 mm
Distribution steel provided , No. 4 @ 400 mm centers
2
Distribution reinforcement provided; At_prov = 332 mm /m
PASS - area of inner steel provided (Distribution) OK
Actual bar spacing provided; st = 400 mm
PASS - spacing of distribution bars is less than allowable
Check for shear
Shear force on the slab (along long beam); Vu = wu × (ly / 2 - bw / 2 - dx_mid) × 1 m = 31.08 kN
Design shear strength of slab; Vc = 0.75 × (f’c / 1 MPa) / 6  1 MPa × 1 m × dx_mid = 91.33 kN
PASS - one-way shear capacity
Check for clear cover (ACI 318 – 05 cl. 7.7.1)
Permissible min nominal cover to all reinforcement; cmin = 20 mm
Clear cover to tension reinforcement (negative); cc_neg = 20 mm
PASS - cover to steel resisting hogging exceeds allowable minimum cover
Clear cover to tension reinforcement (positive); cc_pos = 20 mm
PASS - cover to steel resisting sagging exceeds allowable minimum cover
Schematic reinforcement distribution.

lx x
½ Column strip

A’sy_col
Asx_col A’sx_col

Asx_mid
Asy_col
ly
Middle strip

Asy_mid A’sx_mid
½ Column strip

A’sy_mid

½ Column strip Middle strip ½ Column strip

TWO-WAY SLAB PANEL


(Reinforcement Layout)