Instrumentation and Controls For HVAC
Instrumentation and Controls For HVAC
PART 1: GENERAL
1.01 Purpose:
1.02 References:
E. FCI 70-2 - Fluid Controls Institute, Control Valve Seat Leakage (Supersedes ANSI
B16.104).
J. ISA 75.13 – Method of Evaluating the Performance of Positioners with Analog Input
Signals and Pneumatic Output.
L. ISA 75.25.01 – Test Procedure for Control Valve Response Measurement from Step
Inputs.
1.03 Requirements:
A. Provide identical field devices for existing facility modifications where possible.
B. Provide verification that instruments and control valves supplied are properly sized per
industry and manufacturer’s standards to meet specified performance criteria for the intended
application.
C. Provide instruments including pipe, tubing, manual valves, supports, pipe and tube
fittings, wire/cable, conduit, tray, terminations, racks, mounting stands, mounting plates, and
other accessories as needed to complete a working and operable instrumentation and control
system.
D. Provide intrinsic safety barriers for instruments and valve controllers that are installed in
hazardous areas as defined by NFPA 70.
E. Protect equipment from entry of foreign materials by using temporary covers, caps,
closures and store equipment in environmentally controlled space until installation of
equipment are complete.
1. Temperature:
a. Space – +/- 0.8 F, over 0 to 130F range
b. Duct Air – +/- 0.8F, over 0 to 130F range
c. Outside Air - +/- 1F, over -30 to 130 range
d. Water – +/- 0.5F, over 0 to 230F range
e. Delta-T – 0.1F
3. Carbon Dioxide – 5%
4. Flow:
a. Fluid – +/- 1% of range
b. Air – +/- 2% of range
5. Pressure:
6. Level:
7. Electrical:
a. KWH - +/- 1% of range
b. KW - +/- 1 % of range
PART 2: PRODUCTS
B. Preference for mounting of temperature control valves is for serviceability from floor
without the use of ladder—maximum height 5’0” AFF. Where control valves are above
serviceability height, locate over equipment in an accessible location such that top of
equipment can be used for service platform. Other types of service valves shall be similarly
located. Where service valves are mounted 8 feet above the floor (or other walkway) and not
over service platform provide with Rotohammer chain wheels and safety-trimmed chains.
D. Provide valves with the manufacturer’s name, pressure rating and flow direction clearly
marked on the outside of the valve body.
E. Control valves of the same type shall be of the same manufacturer when possible.
F. Size valves in accordance with ISA 75.01 flow equations with valve sized to pass 110
percent of maximum flow.
H. Valve failure mode shall be designed to ensure safe operation and shut down of the
appropriate process equipment.
K. Provide valves with equal percentage or modified equal percentage flow characteristics
for modulating applications.
L. Valves shall be hydrostatically tested at the factory simulating dead end service at the
design pressure in psig.
N. Steam system control valves shall be globe style where renovations for pneumatic
actuation characterize v-ball.
B. Valve and damper actuators shall be provided with stall protection to prevent actuator
damage throughout the actuator’s rotation.
D. Actuators used for power-failure or safety applications shall be equipped with an internal
spring return mechanism or an uninterruptible power supply (UPS).
E. Proportional actuators shall accept a 0-10 Vdc or a 0-20 mA control signal and have a 2-10
Vdc or 4-20 mA operating range.
F. Valve actuators shall provide the following minimum close off pressure ratings 150% of
total system (pump) head. Belimo VS series or approved equal.
G. Actuators shall feature the ability for Operators to manually position each actuator when
actuator is not powered. Non-spring return actuators shall feature an external manual gear
release. Spring return actuators with more than 60 in.-lb torque capacity shall feature a
manual crank.
H. Provide a minimum of one actuator for each damper and one actuator for each 16 square
feet of damper area. Belimo F series, Siemens Open Air G, or approved equal.
I. Dampers 16 square feet and smaller shall be driven by an externally mounted damper
actuator. Dampers larger than 16 square feet shall have each section independently driven
by a separate externally mounted damper actuator. Actuators on multi-section dampers
shall operate smoothly and in unison.
2. Flow tube should be sized to operate within a velocity range of 2-15 ft./sec.
3. Differential temperature to use Rosemount transmitter (model 3144) with matched pair of
RTD temperature sensors on supply and return lines.
2. SRH Compound turbine water meters are to be used for 4-6” applications.
3. Local display:
a. Volumetric rate
b. Totalizer
2. Local Display:
a. Amperage
b. Voltage (per phase and phase-to-phase)
c. KW
d. Power Factor
D. Condensate Meters:
2. Local display:
a. Volumetric rate
b. Totalizer
E. Steam Meter
B. Provide local process gauges with dial sizes between 3 to 5-inches in diameter unless
location is further away than 3-feet when 6 to 8-inch or larger gauges will be required.
Gauges shall use 1/2 NPT connections.
C. Provide analog process gauge scales so that the expected normal operating value is
approximately 1/2 of full-scale range. Working pressure in all cases shall be limited to 75
percent of full-scale range.
E. Provide remote sensing electronics for transmitters with local indication if needed to
mount at a location accessible by plant operators as close as possible to sensing point. Output
signal to be 4-20mA unless otherwise specified.
F. Provide transmitters with required environmental ratings for service duty, for process and
location (indoor or outdoor) temperature and pressure ratings.
H. Provide process instruments with wetted parts that are compatible with the intended
service.
I. Field sensors measurement methodology (type of sensor) dependent upon system service
conditions and application. Typical applications are included below.
J. Provide 1/2” brass body, stainless steel ball isolation valves at locations where sensor lines
tap into fluid
3. Test equipment shall have accuracy two times or better than equipment being
tested, traceable to NIST.
4. Calibration and installation records shall be prepared and maintained with the
following information:
d. Serial number.
f. Date of calibration.
i. Date calibrated.
k. Provide field calibration kits for carbon monoxide and dioxide sensors.
M. Temperature:
1. Provide 3-wire thermistor Type II or Type III (bead coated with glass, covered in
metal sheath, encapsulated with moisture proof epoxy) probe temperature sensors
as required to meet accuracy and service conditions. RTD type sensors to be used
in special conditions with owner’s approval.
3. Provide sensor type and mounting material compatible with environment and
service conditions.
5. Duct Sensor: Encapsulated moisture proof coated thermister Type II or Type III
Material. All sensors in ducts shall be of the single point type. Precon model ST-
R3R, ST-D3, or approved equal.
6. Averaging Sensor: Employed in ducts which are larger than 24-inches. The
averaging sensor tube must contain at least one sensor for every 3 feet of length,
with a minimum tube length of 12 feet. Precon model ST-FZ or approved equal.
7. Outside Air Sensor: Approved thermistor, sheathed in stainless steel tubing and
mounted inside a ventilated, treated, shield to minimize radiant energy and wind
effects. Precon model ST-03 or approved equal.
10. Temperature Gauges: Bimetallic helix actuated type, and shall have a white dial
with black figures, and pointer zero adjustment. Accuracy shall be plus or minus 1
percent of the range. Gauges shall conform to ANSI/ASME B40.1.
11. Thermowells: Provide 304 Stainless Steel well, sized for 1/2 the pipe diameter or
6 inches whichever is less. Well shall be installed with Thread-o-let. Kele WEL-S
with threadolet or approved equal.
N. Analytical Instruments:
1. Humidity Sensors:
a) Duct mounted sensor shall have a minimum 6-inch rigid probe. Duct
sensors shall be provided with a sampling chamber and calibration
adjustments. RE Technology model HD20K or approved equal.
d) Room sensor:
2. Conductivity:
a. Platinum electrode.
3. pH/ORP:
a. Glass electrode
O. Freezestats:
1. Provide for freeze protection of all air-handling unit coils using outside air. The
freezestat set point shall be determined as a function of outdoor air temperature,
amount of outdoor air being introduced to the air-handling unit, return air
temperature, and amount of return air to the unit.
1. Sensor shall have a local display, analog output, and relay output contacts.
2. Provide aspirated enclosure for duct mounting. Readings from 0 to 200 ppm, Kele
model WCO-1B or approved equal.
2. Provide duct mounted units only, readings 0 to 2000 ppm, Valtronics model
6289D-D or approved equal.
3. Provide liquid fill for gages on lines with vibrations and snubbers for pulsation
protection. Provide needle valve to isolate each gauge.
4. Transmitters:
b. Accuracy shall be plus or minus 0.5 percent of the range with overload
protection.
c. Provide three valve manifold assembly for zero and span calibration and
maintenance of sensor.
5. Pressure Gauges:
a. Bourdon tube type, and shall have a diaphragm actuated pointer, white dial
with black figures, and pointer zero adjustment.
b. Accuracy shall be plus or minus 0.5 percent of the range with overload
protection.
a. Switch of proof: Select range for minimum flow operations. Dwyer model
1910 with SPDT contacts or approved equal.
a. DP Switch: Brass bellow, enclosed SPDT snap acting switch, contact rating
per application. Penn P74 or approved equal.
T. Flow:
1. Provide flow elements in horizontal pipe runs in accordance with good metering
practices and in accordance to manufacturer’s requirements for upstream and
downstream pipe diameters. Coordinate installation requirements with manufacturer.
2. Transmitter:
a. Air: Averaging Pitot type with multiple sensors for static pressure
measurements distributed across the air stream. Kele KMS series or approved
equal.
b. Fluid: Electromagnetic (energy metering), Turbine insertion type, with dual
sensor for basic fluid measurements. Onicon F-1210 or approved equal.
3. Switch:
a. Air: Differential Pressure diaphragm type single snap action switch. Dwyer
model 1626 or approved equal.
b. Fluid: Thermal Dispersion type with adjustable setpoint from 15% to 90 of
flow range setting. Dwyer TFS or approved equal.
U. Water/Moisture/Flood Detector:
V. Level:
2. Enclosed Sumps:
a. Float type switch suitable for fluid in which immersed. Switch shall be
assembly mounted, designed, and located for ease of maintenance access,
removal and level adjustment. GEMS LS1750 stainless steel single station
level switch or approved equal.
3. Receiver Tanks:
a. UT Standard analog level sensor. Furnished by Owner and installed by
contractor.
W. Current:
2. Switches: Battery powered, solid state with adjustable trip. Provided for equipment
status feedback.
X. Voltage:
2. Transformers: UL listed rated for 600vac, with enclosed windings, and built-in
fuse protection
PART 3: EXECUTION
3.01 Installation:
B. Provide details for typical and special equipment installations on construction documents.
C. Provide power surge and transient suppression for power circuits from an electrical panel,
located on the incoming power circuit serving the equipment. Kele model DTK-120HW or
approved equal.
D. Install field instruments in such a manner and at such a height as to allow convenient
access for readings, calibration and maintenance.
E. Install instruments in steam, liquid and liquid sealed service below their process
connection point. Slope connections down to the instrument with a slope of 1 inch per
foot.
F. Install instruments in gas and non-condensable vapor service above their process
connection point. Slope connections up to the instrument with a slope of one inch per foot.
G. Support instruments and tubing to relieve strain on connections and to prevent excess
vibration or movement.
H. Install piping and tubing in a neat appearance, protected from being stepped on, and
include provisions for expansion, drainage and without interference to access to valves or
other equipment. Tubing bends are to be made with a tool; hand bends are not acceptable.
I. Provide identification tags for field devices using engraved plastic laminated labels (use
stainless steel tags for high temperature service conditions). Secure labels to devices using
double sided tape for panels or stainless steel ties for field instruments. Nomenclature shall
utilize the UT standard abbreviations and codes and include the following information:
1. Building
3.02 Training:
END OF STANDARD