Fire Pump Design Calculate
Fire Pump Design Calculate
Frank Application
Manual For Application
Select the speed of the flow in the pipe line. = 2.5 m/s
FLOW PUMP= 160 m3/h
CALCULATE HEAD LOSSES DARCY-WELSNCH EQUATION
Select the speed of the flow in the pipe line. = 2.5 m/s
CALCULATE HEAD LOSS OF FLUID VALVE & FITTING
Example2. Calculate the flow rate (Q). And water pressure (P). Minimum sprinkler system,
sprinkler Want POINT A For Ordinary Hazard 2
1. Calculate the area of 139 square meter Ordinary 2
2. K-factor Distribution of sprinkler heads. 5.6 ((gpm/psi)1/2)= 80 (L/min/(bar)1/2)
3. Black Pipe Schedule 40 (C Value 120).
4. S = distance between the sprinkler head on a Branch Line is 3 meters.
5. A = area coverage per sprinkler is 10.8 square meters.
\
Calculate Number sprinkler (Nozzle) and Number sprinkler per Branch Line Ordinary 2
\
d
NSB
S
CALCULATE 1
CALCULATE 2
d
Density
= 8.1 ((L/min)m2)
Flow Start sprinkler = 87.48 (L/min)
C Value Table
Dimeter of Pipe = 25 mm.
Nozzle Sprinkler
CALCULATE FIRE PUMP DESIGN
Example3. Calculate Fire Pump and Jackey Pump By Area Hazard For NFPA
=418.74 GPM