Notes On Transformer
Notes On Transformer
Again for an ideal transformer, the input power is equal to the output power.
V1 I1 = V2 I2 𝑜𝑟 E1 I1 = E2 I2
Or
E2 I1 N2
K= = =
E1 I2 N1
Where
I1 is the primary current in amperes
I2 is the secondary current in amperes
Which are inversely proportional to their respective turns
example3: The core of 1000kVA, 11000/550 V, 50Hz, single phase transformer has a cross-section of
20cm x 20 cm. If the maximum core density is not to exceed 1.3 tesla, calculate (i) the number of h.v.
and l.v. turns per phase and emf per turn. Assume a stacking factor of 0.9. ANS N1=1059, N2=53 and
10.387V/turn