Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018

The document is a test report for a SEL 710 motor protection relay. It summarizes tests of the relay's protection functions including: [1] Phase overcurrent protection tripped as expected for currents above set thresholds within 0.029 seconds. [2] 50N/51N earth fault protection tripped for currents above 5A within 0.031 seconds. [3] Jam protection tripped for currents above 1.2A with a 5 second delay within 5.21 seconds. [4] Current imbalance protection tripped for imbalances above 10% with a 5 second delay within 5.12 seconds. [5] Undervoltage protection tripped for voltages below 0.7 per unit within 2.03 seconds

Uploaded by

Jayam kondan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
333 views3 pages

Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018

The document is a test report for a SEL 710 motor protection relay. It summarizes tests of the relay's protection functions including: [1] Phase overcurrent protection tripped as expected for currents above set thresholds within 0.029 seconds. [2] 50N/51N earth fault protection tripped for currents above 5A within 0.031 seconds. [3] Jam protection tripped for currents above 1.2A with a 5 second delay within 5.21 seconds. [4] Current imbalance protection tripped for imbalances above 10% with a 5 second delay within 5.12 seconds. [5] Undervoltage protection tripped for voltages below 0.7 per unit within 2.03 seconds

Uploaded by

Jayam kondan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

TEST REPORT FOR

SEL MOTOR PROTECTION SEL 710


RELAY-SEL 710
DATE: 21.06.2018

Project : SINGARENI THERMAL POWER PLANT, TELANGANA

Client : M/s STEAG ENEGY SERVICES PVT LTD

End Client : M/S SINGARENI

Panel Ref : 1A-COMPRESSOR

Relay Make & Model : SEL-710

Serial No : 3140060035

CT & VT Ratio : 150/50A

1. Phase Over Current TOC – Non Directional Current (I) – 4XFLA A , TD- 0s ,FLA:0.6

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 2.4 2.4 0 0.023

Y-N 2.4 2.4 0 0.022

B-N 2.4 2.4 0 0.029

2. [50N ] Current (I) – 5A : Time Delay- 0 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 5 5 0 0.024

Y-N 5 5 0 0.029

B-N 5 5 0 0.031

3. JAM Current (I) – 2XFLA A ,Time Delay- 5 s FLA:0.6

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 1.2 1.2 5 5.21

Y-N 1.2 1.2 5 5.19

B-N 1.2 1.2 5 5.16

4. CURRENT IMBALANCE Current (I) – 10%A ,Time Delay- 5 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.54 0.54 5 5.01

Y-N 0.54 0.54 5 5.02

B-N 0.54 0.54 5 5.12

5. UNDER VOLTAGE Voltage (I) – 0.7xVnm ,Time Delay- 2 s

Phase Sett Voltage (v) Inj. Voltage(v) Actual Tripping Trip Time(s)
Time (s)

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

R-N 45 45 2 2.00

Y-N 45 45 2 2.03

B-N 45 45 2 2.01

6. THERMAL OVER LOAD

Phase Inj. Current(A) Trip Time(s)

R,Y,B 1.33 749

R,Y,B 1.5 630

R,Y,B 1.6 420

Check List:

1. LED Functions has been checked and found ok.


2. Relay operations has been found satisfied and fit for service.

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR