Earth Ground Resistance Tester Kit Model 382252: User Manual
Earth Ground Resistance Tester Kit Model 382252: User Manual
Model 382252
Additional User Manual Translations available at www.extech.com
Introduction
Congratulations on your purchase of the Extech 382252 Earth Ground Resistance Tester Kit. This
device can measure Earth Ground Resistance (in 3 ranges), Earth Voltage and Resistance (up to
200kand AC and DC voltage. This device was designed to meet EN61010-1 safety standards.
Careful care and use of this meter will provide years of reliable service.
Safety
Please read the following safety information carefully before attempting to operate the meter and
use the meter only as specified in this manual.
Environmental safety information
Do not use meter outdoors when precipitation is likely
Installation Category III
Pollution degree 2
Altitude: 2000 meters max.
Ambient conditions: 32 to 104oF (0 to 40oC); RH: 80% max
Observe the following international safety warning symbols
Safety Symbols
Dangerous Voltages
2 382252-en-GB_V1.5 1/17
Meter Description
1. Digital Display – See Display Description below
2. HOLD key – Freezes measurement value on display
3. Zero ADJ control- Adjusts Zero value on display 1
Top View
2. P Input (Yellow)
Display Description 1 2 3
6
8. Low Battery Icon
9. HOLD Icon
3 382252-en-GB_V1.5 1/17
Operation
ZERO Adjustment of Earth Resistance Ranges
1. Connect the long test leads to the meter as follows:
a. Green lead to the 'E' terminal (Green jack)
b. Yellow lead to the 'P' terminal (Yellow jack)
c. Red lead to the 'C' terminal (Red jack)
2. Set the function selector switch to the desired measurement range. (20, 200, 2000Ω)
3. Short the 3 test leads together by clipping them all to a single earth ground rod.
4. Press the TEST key.
5. Use the 0-Adjust knob to adjust the displayed reading to 000
6. Press to TEST key again to end the Zero adjustment process.
7. Perform this adjustment for each range.
4 382252-en-GB_V1.5 1/17
Earth Ground Resistance test
If the auxiliary bars are placed in close proximity to the ground stake, measurement
inaccuracies will result.
(Minimum distance between rods should be no less than 10 feet (3m).
3. Connect the alligator clip end of the test leads to the Earth bars and existing ground rod
connection as shown above:
Green lead (2) to the existing ground rod (5)
Yellow lead (3) to Earth Bar P1 (6)
Red lead (4) to the Earth Bar C1 (7)
4. Set the meter's function switch to the desired resistance range. (20, 200, 2000Ω).
5. Zero the range as described in the Zero adjustment procedure above.
6. Press the TEST button. . The “ “ icon will flash and the audible signal will sound.
7. Note the displayed reading.
8. If high resistance is detected, note the value and take appropriate steps to correct the ground
connection if necessary.
9. Press to TEST key to end the test.
10. Readings of “1”……. are typical when the test leads are not connected to the meter.
HOLD Function
The Hold function freezes the latest measurement reading on the LCD.
1. Press the HOLD key to freeze the reading on the LCD
2. Press the HOLD key again to exit the HOLD function.
3. The HOLD function does not retain measurement data if the meter is turned off.
Backlight
1. Press the “ “ key to turn on the backlight.
2. The backlight will turn off after approximately 15 seconds.
5 382252-en-GB_V1.5 1/17
200k Resistance Measurement
1. Connect the red test lead to the V(C) connector and the black test lead to the COM (E)
connector.
2. Set the function selector switch to the 200kposition.
3. Connect the test probes to the circuit under test.
4. Note the displayed Resistance value.
AC Voltage Measurement
5. Connect the red test lead to the V(C) connector and the black test lead to the COM (E)
connector.
1. Set the function selector switch to the 750V AC position.
2. Connect the test probes to the circuit under test.
3. Note the displayed Voltage value.
DC Voltage Measurement
1. Connect the red test lead to the V(C) connector and the black test lead to the COM (E)
connector.
2. Set the function selector switch to the 1000V DC position.
3. Connect the test probes to the circuit under test.
4. Note the displayed Voltage value.
4. Press TEST button. The “ “ icon will flash and the audible signal will sound.
5. Note the resistance reading on the display.
6. Press the TEST button to stop the test.
4 5
1 2 3
6 382252-en-GB_V1.5 1/17
Maintenance
Battery Replacement
When the low battery icon ' ' appears on the LCD, the meter's batteries must be changed.
1. Remove power and disconnect the test leads from the meter.
2. Remove the tilt stand from the rear of the meter.
3. Remove the 4 battery compartment screws with a Phillips head screwdriver.
4. Remove the battery compartment cover and replace the six 1.5V 'AA' batteries.
5. Affix compartment cover and tighten screw.
6. Reattach the tilt stand.
You, as the end user, are legally bound (Battery ordinance) to return all
used batteries and accumulators; disposal in the household garbage is
prohibited!
You can hand over your used batteries / accumulators at collection points
in your community or wherever batteries / accumulators are sold!
Disposal: Follow the valid legal stipulations in respect of the disposal of the device at the
end of its lifecycle
Specifications
General Specifications
Measurements Earth Ground Resistance (in 3 ranges), Earth Voltage,
AC Voltage to 750V and DC Voltage to 1000V and resistance.
Display Large LCD with dual display
Sampling Time 2.5 times per second
Test lead length Red lead: 50' (15m), Yellow: 33' (10m), Green: 16' (5m)
Over-range indication '1' displayed as most significant digit
Power supply Six 1.5V 'AA' batteries (included)
Low battery indication LCD displays icon
Auto Power Off After approximately 15 minutes of use
Safety EN-61010-1 category III
Weight 700g (24.7oz) with batteries
Dimensions 200 x 92 x 50 mm (7.9 x 3.62 x 2")
Operating Conditions 0ºC to 40ºC (32ºF to 104ºF), with < 80% RH
Storage Conditions -10ºC to 60ºC (14ºF to 140ºF), with < 70% RH
7 382252-en-GB_V1.5 1/17
Measurement Specifications
Measurement Range Resolution Accuracy
20 0.01 ± (2% reading + 10 digits)
Earth Ground
200 0.1
Resistance ± (2% reading + 3 digits)
2000 1
Earth Voltage 0 to 200VAC
Frequency: 40 to 0.1V ± (3% reading +3digits)
500Hz
Kit contents
382252 Earth Ground Resistance Meter
2 Ground rods - zinc plated iron (22cm)
6 - AA alkaline batteries
3 Ground rod test cables - Red (15m), Yellow (10m), Green(5m)
2 Test leads for Ground Resistance with alligator clips (Red and Green) (1.5m)
2 Test leads for Voltage/Resistance (Black and Red) (1m)
User’s manual
Cloth Carrying case
Copyright © 2014‐2017 FLIR Systems, Inc.
All rights reserved including the right of reproduction in whole or in part in any form
ISO‐9001 Certified
www.extech.com
8 382252-en-GB_V1.5 1/17