Fieldbus Connection
IRC5 <-> S500 IOs
IRC5 +
PN-SW
<->
CI50x-PNIO
+ S500 IOs
abb
Content
1 Disclaimer .................................................................................................................. 3
5 PROFINET Configurator............................................................................................ 8
This application manual describes the preconditions, tools and configuration steps to connect S500 IO
clusters to an IRC5 Profinet master.
The S500 IOs will be connected to either a CI501-PNIO or CI502-PNIO module.
Usage
This application manual should be used during design of an IRC5 system with attached S500 IO to
Profinet as well as during configuration and commissioning of the S500 IO clusters.
· System integrators
Prerequisites
- CI501 or CI502 + S500 IOs installation and documentation (chap. 4.2 Page 6)
- Add and configure CI50x modules: Device name, IO channels (chap. 5.2.4, page 13)
- Add and configure more S500 IO modules (chap. 5.2.6 page 16)
4. Copy the IPPNIO.xml file into the IRC5 configuration (chap. 6.1.1, page 18)
5. Adapt bus configuration and create or scan for EIO UNITS and IO Signals (chap 6.1.2, page.18)
oder
TU508-ETH 1SAP214000R0001
TU508-ETH
S500,Bus Terminal Unit
Spring
è Goto www.abb.com/PLC
è Select English as language and doubleclick on
Downloads \ Programmable Logic Controllers PLCs
è Select the AC500 control Builder Plus PS501 Documentation and download this
3ADR025078M0203.ZIP file.
è Unzip the file to a local folder on your Windows PC
è The AC500 Online Help can only be used on Windows PCs and must be stored
to a local folder.
Notice
è Doubleclick the file CAA-Merger-2.chm. The Online Help Chapter for AC500 / S500 Hardware will
open.
è In the chapter Hardware S500 the documentation of Bus Modules and IO-Moduls can be found.
Unzip the “PROFINET-IO Configurator Express.zip” file and start the setup with the “setup.exe” file. Then
follow the instructions of the Setup routine.
1. Extract the archive “ABB Automation Products GmbH.zip” into the FDCML directory for PROFINET
devices
a) On Windows 7 this directory is usually called
“C:\Users\Public\Documents\FDCML10\Profinet”
b) On Windows XP this directory is usually called
“C:\Documents and Settings\All Users\Documents\FDCML10\ Profinet”
After the import the folder “ABB Automation Products” will be selectable in the Device Catalog section.
The XC-versions of CI50x-PNIO are constructed for extrem conditions and therefore have
a separat order code.
There is no diffrence in configuration for the XC versions
NOTICE
The Device name of the CI50x-PNIO devices has to be set according the one of the following rules.
If the first rotary switch is set to 2 and the second to 0 the Device Name must be: ci501-pn-20
The last number of the device name must not have leading zeros.
If the address switches are not set to "00", the device name set via configuration
tool is also stored permanently. But after a restart, the stored device name is not
used; the device's behaviour is like described in section 5.2.3.1.1
Note
and outputs:
Do not select the IO-Modules “With Fast Counter” as the Fast Counter mostly is
only working with AC500 as the Profinet master.
NOTICE Please check in the S500 documentation (Online Help) if the Fast Counter is
available only for AC500 Profinet master.
This can be found in the Hardware documentation of the according IO Module in
the section “Internal Data Exchange”
See chapter 5.2.5.1.2
Request write permission from the connected controller by clicking the “Request Write Access” button in
menu. If the robto is in manual mode, answer the request for mastership at the FlexPendant.
Double click the Profinet_SW bus:
If you need to adapt signal naming or other settings, this has to be done after the first restart as described in
the following chapters.
In the PROFINET Configurator you can find the meaning of the signals and their slot-internal address as
described in chapter 5.2.5
The last entry + 1 gives the starting address for the next device.
DC522 itself has the following inputs:
CI501-PNIO Index: C1
CI502-PNIO Index: C2
DC532 Index B4
DC522 Index:B0
AX522 Index: B8
KW-Soft
1.10 Express (File version 1.10.22)
PROFINET Configurator
S500-CI501-PNIO_20121120_ci501-pn-00_DIM 1.xml
S500-CI501-PNIO_20121120_ci501-pn-00_DIM 2.xml
Xml-files for CI50x
S500-CI502-PNIO_20121120_ci502-pn-00_DIM 1.xml
S500-CI502-PNIO_20121120_ci502-pn-00_DIM 2.xml
Application Note 28
Title: Lang.: