0% found this document useful (0 votes)
604 views

II 08 Instrumentation PDF

This document provides design guidelines for instrumentation items for a project to revamp fire protection systems at 18 ONGC facilities in Mehsana Asset, India. It covers environmental design criteria, applicable codes and standards, design requirements, and specifications for various instrumentation components. The firefighting systems will be upgraded at group gathering stations, early production stations, and effluent treatment plants to improve safety.

Uploaded by

abdulkidwai2009
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
604 views

II 08 Instrumentation PDF

This document provides design guidelines for instrumentation items for a project to revamp fire protection systems at 18 ONGC facilities in Mehsana Asset, India. It covers environmental design criteria, applicable codes and standards, design requirements, and specifications for various instrumentation components. The firefighting systems will be upgraded at group gathering stations, early production stations, and effluent treatment plants to improve safety.

Uploaded by

abdulkidwai2009
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 235

REVAMPING OF FIRE PROTECTION SYSTEM AT

INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 2 of 18

Table of Content

1.0 Introduction ................................................................................................................... 4


1.1 Scope .................................................................................................................. 4
1.2 Definitions of Terms ............................................................................................. 5
1.3 Abbreviations ....................................................................................................... 5

2.0 ENVIRONMENTAL DESIGN CRITERIA ......................................................................... 6


2.1 Climatic Conditions .............................................................................................. 6
2.2 Design Life .......................................................................................................... 6
2.3 Area Classification ............................................................................................... 7

3.0 CODES, STANDARDS AND REFERENCE DOCUMENTS ............................................ 7


3.1 Reference Project Document ............................................................................... 7
3.2 International Codes and Standards...................................................................... 7

4.0 DESIGN CRITERIA......................................................................................................... 8


4.1 General................................................................................................................ 8
4.2 Hazardous Area Classification and Certification .................................................. 8
4.3 Ingress protection ................................................................................................ 9
4.4 Spare capacity ..................................................................................................... 9
4.5 Standardization .................................................................................................... 9
4.6 SIL Study ............................................................................................................. 9

5.0 FIRE FIGHTING SYSTEM .............................................................................................. 9


5.1 Fusible Plug Loop Fire Detection ....................................................................... 10
5.2 Deluge Valve Operation Philosophy .................................................................. 10
5.3 Fire Water Pump Control Philosophy ................................................................. 11
5.4 Fire Water Tank Monitoring ............................................................................... 11

6.0 FIELD INSTRUMENTS ................................................................................................. 12


6.1 General.............................................................................................................. 12
6.2 Flow Instruments ............................................................................................... 12
6.3 Level Instruments .............................................................................................. 13
6.4 Pressure and Differential Pressure Instruments ................................................. 13
6.5 Solenoid Valves ................................................................................................. 14

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 3 of 18

6.6 Manual Call Points ............................................................................................. 14

7.0 ACCURACY OF INSTRUMENTS ................................................................................. 14

8.0 INSTRUMENT AIR SUPPLY AND DISTRIBUTION ...................................................... 14

9.0 INSTRUMENT CABLES AND CABLE TRAYS ............................................................ 15

10.0 INSTRUMENT JUNCTION BOX ................................................................................... 16

11.0 INSTRUMENT CABLE GLANDS.................................................................................. 17

12.0 INSTRUMENT INSTALLATION .................................................................................... 17

13.0 POWER SUPPLY ......................................................................................................... 18

14.0 INSTRUMENT NAMEPLATES AND TAG PLATES ..................................................... 18

15.0 MULTI-CABLE TRANSITS ........................................................................................... 18

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 4 of 18

1.0 INTRODUCTION
Oil and Natural Gas Corporation Ltd. (ONGC) is planning to revamp their existing
firefighting facilities of Mehsana Asset in the state of Gujarat under the project ‘Revamping
of fire protection system at Installations of Mehsana Asset. The Firefighting system of
surface facilities includes Group Gathering Stations (GGS), Early Production Stations
(EPS) and Effluent Treatment Plants (ETP).
ONGC has contracted Petro6 Engineering and Construction Pvt. Ltd. as Design
Engineering Consultant (DEC) for for the above mentioned project. The facilities covered
under this project are as follows:
a) North Kadi GGS-III
b) North Kadi GGS-I
c) North Kadi GGS-II
d) North Kadi GGS-IV
e) Jotana GGS
f) Sobhasan GGS-I
g) Sobhasan GGS-II
h) Balol GGS-I
i) Balol GGS-IV
j) Balol GGS-II
k) Balol GGS-III
l) Bechraji GGS-I
m) Bechraji GGS-II
n) Lanwa GGS-I
o) Lanwa GGS-II
p) Lanwa GGS-III
q) Sobhasan WWTP
r) Langhnaj EPS
1.1 Scope
The purpose of this document is to define the Design Basis/Guidelines to be used for
selection of instrumentation items proposed under this project.
These specifications are to be considered as minimum requirements and CONTRACTOR
may submit to the COMPANY, for agreement, all calculations sheets and possible
solutions that could give technical and/or economic improvement.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 5 of 18

Any omission in this requirement shall not relieve the CONTRACTOR of his responsibility
to deliver the equipment along with other associated items, which are complete, of proven
design, and conforms to the Performance Requirements.
1.2 Definitions of Terms
The CLIENT / COMPANY / OWNER where used in this specification shall mean the
ultimate user / owner of the plant and facilities.

The CONTRACTOR / PURCHASER where used in this specification shall mean the party,
who undertake LSTK / EPC contract for the above project.

The VENDOR / SUPPLIER where used in this specification shall mean the party, who
manufactures or supplies the equipment and services specified.

The INSPECTOR / TPA where used in this specification shall mean the PURCHASER /
COMPANY or their authorized agency for carrying out the inspection.

The ENGINEER / DEC where used in this specification shall mean the party, who perform
Design Engineering Consultancy and Project Management for the Company.

1.3 Abbreviations
API American Petroleum Institute
AISI American Iron and Steel Institute
ASME American Society of Mechanical Engineers
ATEX ATmosphere EXplosives
BIS Bureau of Indian standards
BS British Standards
CCOE Chief Controller of Explosives
CCR Central Control Room
CENELEC European committee for Electro technical Standardization
CMRI Central Institute of Mining and Fuels Research
DC Direct Current
DGMS Directorate General of Mines Safety
DP Differential Pressure
D(S)PD(S)T Double (Single) Pole Double (Single) Throw
EEMUA Engineering Equipment Manufacturers and Users Associations

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 6 of 18

FAT Factory Acceptance Test


FM Factory Mutual
HART Highway Addressable Remote Transducer
HMI Human Machine Interface
IEC International Electro technical Commission
ISA International Society for Automation
ISO International Standards Organization
I/O Input or Output
JB Junction Box
MAWP Maximum Allowable Working Pressure
MFR STD Manufacturer’s Standard
NPT(M),(F) National Pipe Thread (Male screw), (Female screw).
PLC Programmable Logic Controller
P&ID Piping and Instrumentation Drawing
PVL Preferred Vendor List
RTU Remote Terminal Unit
SAT Site Acceptance Test
SDV Shutdown valve
SIL Safety Integrity Level
UL Underwriters Laboratory
UPS Uninterrupted Power Supply System

2.0 ENVIRONMENTAL DESIGN CRITERIA


2.1 Climatic Conditions
The equipment shall be designed for out-door location, suited to corrosive, desert / salt
laden and marine environment. Climatic conditions under which equipment designed /
operated shall be as per Project Design Basis and Equipment Datasheet.
2.2 Design Life
Equipment shall be designed and constructed for continuous operation, outdoor and for a
minimum service life of 25 years or as per Project Design Basis and Equipment Datasheet
whichever is more.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 7 of 18

2.3 Area Classification


Electrical and Instrumentation equipment supplied part of mechanical equipment and
packages shall be suitable for the applicable Hazardous Area Classification as specified in
equipment datasheet.

3.0 CODES, STANDARDS AND REFERENCE DOCUMENTS


3.1 Reference Project Document
The latest revision of following project specification / documents shall form integral part of
this design basis,
P6EC-STD-PP-S-1001 : Piping Material Specification
5085-COMM-EL-L-1001 : Electrical Design Basis
P6EC-STD-IN-E-1001 : Instrument Installation Standards
P6EC-STD-IN-S-1001 : Standard Specification for Instrument Installation
P6EC-STD-IN-S-1004 : Standard Specification for Orifice Flange Assembly
P6EC-STD-IN-S-1005 : Standard Specification for Orifice Plate
P6EC-STD-IN-S-1008 : Standard Specification for Level Transmitter
P6EC-STD-IN-S-1011 : Standard Specification for Pressure Gauge and Differential
Pressure Gauge
P6EC-STD-IN-S-1012 : Standard Specification for Pressure Transmitter and
Differential Pressure Transmitter
P6EC-STD-IN-S-1019 : Standard Specification for Firewater Pump Control Panel
P6EC-STD-IN-S-1024 : Standard Specification for Deluge Valve
3.2 International Codes and Standards
The design, materials, fabrication, inspection and testing of equipment and packages shall
be in accordance with this specification and the latest edition (including addenda / errata)
of applicable codes and standards as listed below.

EN 10204 : Certificates on Material tests

IEC 60079 : Electrical Apparatus for Explosive Gas Atmospheres


(various parts as applicable)
IEC 60529 : Degrees of protection provided by enclosures (IP code)

IEC 60654 : Industrial-process measurement and control equipment


operating conditions
IEC 60228 : Conductors for insulated cables

IEC 60331 : Fire resisting characteristics of electric cables

IEC 60332 : Tests for electric cables under fire conditions

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 8 of 18

IEC 60754 : Test on gases evolved during combustion of electric


cables
IEC 61034 : Measurement of smoke density of cables burning under
defined conditions
ISO 5167 Measurement of fluid flow by means of pressure
: differential devices inserted in circular cross-section
conduits running full
API STD 598 : Valve Inspection and Testing
ASME B 16.5 : Pipe Flanges and Flange fittings
ASME B16.10 : Face to Face and End Dimensions of Valves

NFPA 13 : Standard for the Installation of Sprinkler Systems


Standard for Installation of Stationary Pumps for Fire
NFPA 20 :
Protection
NFPA 72 : National Fire Alarm Code
OMR : Oil Mines Regulations
OISD : Oil Industries Safety Directorate regulations
TAC : Tariff Advisory Committee
DGMS : Directorate General of Mines Safety
IER : Indian Electricity Rules
CPCB : Central Pollution Control Board of India
GSPCB : Gujarat State Pollution Control Board

4.0 DESIGN CRITERIA


4.1 General
The design of the firefighting system for all the installations shall be designed to meet
applicable OISD and NFPA requirements.
4.2 Hazardous Area Classification and Certification
All instruments installed in this project shall be certified as mentioned below.

 Field Instruments such as transmitters and switches used shall be Ex’i certified

 Solenoid valves shall be Ex’d certified


Instrumentation used in classified area shall be as per OMR 2017.
All instruments and individual electrical/electronic components such as transmitters,
switches and solenoid valves shall be selected based on DGMS Gazette notification no
GSR 1359(E) dated 18.10.2017 for Electrical appliances, equipment, machinery or other

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 9 of 18

material that are used or may be used in Hazardous area of oil mines. Relevant explosion
proof certificates shall be provided for all equipment used.
4.3 Ingress protection
All field instruments shall have a minimum Ingress Protection to IP 65 as per IEC 60529.
All electrical/electronic equipment mounted in the Fire Water Pump Shed such as the Fire
Water Pump Control Panel and compressor shed shall be IP 55 certified as a minimum.
Any other equipment mounted in the control rooms and other indoor non-classified areas
shall have ingress protection to IP 42 as a minimum.
Suitable protection from the weather such as canopy or sun shades shall be provided for
local control panels installed in outdoor locations.
4.4 Spare capacity
Spare capacity for the installed system shall be as follows:

 Multi-core cable - Provision for adding at least 2 Field Instruments, installed and wired
from field to I/O racks.

 Cable trays and cable ladders - minimum of 30% installed spare space.

 Minimum 20% wired terminals in Unit control panel/control room panels / control room
equipment

 Minimum 20% space for additional terminals in future in unit control panel / control
room panel/control room equipment
4.5 Standardization
Selected instruments in various skids, tube size, cables and fittings make & model shall be
the same and shall be standardized throughout for all the equipment.
4.6 SIL Study
No SIL study is envisaged for the firefighting system unless regulatory norms/applicable
codes and standards specify otherwise.

5.0 FIRE FIGHTING SYSTEM


The following firefighting systems are envisaged for this project.

 New Fusible plug loop detection systems

 New Deluge valve systems

 New Firewater Pump Control Panel

 New Manual Alarm Points

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 10 of 18

 Modification of RTU/SCADA in CCR


5.1 Fusible Plug Loop Fire Detection
Fusible plug loops shall be installed on all tanks for fire detection. The detection system
shall be designed in accordance to the relevant OISD standards.
The fusible plugs shall be of SS 316 material and the temperature rating of the fusible plug
shall be designed to suit factors such as peak ambient temperatures, relative humidity and
installation height above the tank roof.
The response time of the system shall be designed to incur minimum time delay. The
design shall ensure that false fire detection shall be minimized as far as possible in
accordance with NFPA approved practices.
Instrument air shall be used to pressurize the fusible plug loop and each fusible plug loop
shall be provided with an Instrument air charging arrangement which will contain an
isolation valve, restriction orifice, check valve and a pressure switch downstream of this
arrangement to monitor the pressure of the fusible plug loop.
A common pressure switch shall be installed for actuation of both deluge valves of a tank.
Pressure Switch installed on the fusible plug loops shall be monitored from the RTU and a
pressure low detection shall actuate the deluge valves by energizing the solenoid valves
on the deluge valves. The Logic to open the relevant deluge valves will be implemented in
the RTU. The deluge valves of the tank on fire shall open to contain the fire and the deluge
valve of the adjacent tanks shall open for cooling of the adjacent tanks.
LSTK CONTRACTOR shall modify/upgrade the existing RTU/SCADA to incorporate above
monitoring and logics.
5.2 Deluge Valve Operation Philosophy
The deluge valve system shall be designed in accordance with the Standard Specification
for Deluge Valve, P6EC-STD-IN-S-1024.
The deluge valves shall be installed outside the dyke area of hydrocarbon storing tanks of
all the installations covered in this project as shown on the P&IDs. The deluge valve
system shall be a standalone system that shall automatically open upon loss of pneumatic
pressure in the fusible plug loops.
In Jotana GGS and North Kadi GGS-IV, where deluge valves are to be installed in the
compressor house the deluge valves shall not have the facility to open automatically on
fire detection as specified in OISD 189. It shall be opened manually from the SCADA by
the operator.
In general all other deluge valves shall be actuated from the plant RTU/SCADA based on
fire detection by fusible loop.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 11 of 18

A manual valve shall be provided on the deluge valve to open the deluge valve from the
field.
A pressure switch shall be provided at the discharge of all deluge valves to detect status of
the deluge valve which shall be displayed in the RTU/SCADA in the CCR.
The deluge valve shall be UL listed/ FM approved.
The deluge valve shall be manual reset type and shall have facility to close manually after
all the alarm conditions return to normal.
5.3 Firewater Pump Control Philosophy
The Firewater Pump control panel shall be Micro PLC based and shall be installed outdoor
in the Fire water Pump shed.
In General for all fields the Fire Water jockey pumps and Main Fire water pumps will start
automatically based on fire water ring main pressure or shall have a capability to be
started manually from the local fire water pump panel in the fire water pump house.
In case of Balol GGS-1 since the SCADA control room is far away from the fire water
pump house the Fire water jockey pumps and fire water main pumps shall be provided
with the capability to be started from the SCADA control room.
The Firewater Pump Control Panel (FWPCP) shall be designed in accordance with the
Standard Specification for Fire Water Pump Control Panel, P6EC-STD-IN-S-1019.
The Firewater Pump control panel shall do the following functions

 Maintain the Firewater header pressure by automatically starting and stopping the
jockey pumps based on pressure transmitter installed on the header.

 Start the Main Diesel driven Fire water pump based on pressure Low Low alarm on the
Fire water header.

 Start the Electrical driven Fire water pump based on pressure Low Low alarm on the
Fire water header and/or failure of Diesel driven firewater pump

 Monitor the status of the Jockey pumps and main fire water pumps

 Serial communication with the plant RTU system for remote control/monitoring of
relevant functions, alarms and status.
5.4 Firewater Tank Monitoring
Each of the 18 installation has existing plant RTU which monitors plant instruments in the
respective CCR.
Additionally, new level instruments shall be provided in all locations including the existing
fire water tanks and the indication of firewater tank levels shall be made available in the
CCR.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 12 of 18

Firewater tank level shall be interfaced to the existing RTU and monitored on the SCADA
system.
5.5 Instruments for Firewater Testing
As a minimum, local DP type orifice flowmeters and pressure gauges shall be provided for
firewater pump testing. These instruments shall be designed in line with NFPA 20
requirements.

6.0 FIELD INSTRUMENTS


6.1 General
Instruments shall be chosen based on intended service, required rangeability, required
accuracy and the installation/maintenance requirements.
All process fluid properties and likely operating scenarios shall be considered during
instrument selection and specification including normal, start up and abnormal situations.
Field instruments shall generally operate from nominal 24 VDC power supplies generated
from within the RTU or the FWPCP.
Electronic transmitters shall be in general 2 wire SMART type with 4 to 20 mA output
superimposed with digital communications using HART protocol. All electronic transmitters
shall be SIL 2 certified.
The transmitters shall be supplied complete with integral output meter (digital, LCD
indicator) capable of displaying the measured variable in engineering units as well as a
percentage value.
Mounting brackets, fixtures and body bolts and nuts for transmitters shall be carbon steel &
shall be supplied with the instruments unless or otherwise specified.
The use of mercury, asbestos, cadmium plated components and other prohibited materials
will not be accepted.
For specific requirements requiring PWHT, Ultrasonic test, Radiography etc., piping
material specification shall be referred.
6.2 Flow Instruments
Orifice plate material shall be AISI Type 316 stainless steel as a minimum unless special
materials are required for a particular service.
Beta ratio for orifice shall be in the range of 0.2 to 0.75.
Orifice meters the flow range-ability shall not exceed 3:1.
Standard DP ranges shall be (0 – 500 mm WC, 0 – 1250 mm WC, 0 – 2500 mm WC, 0 –
5000 mm WC).

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 13 of 18

Orifice flanges shall be weld neck type in accordance with ANSI B16.36.
In general DP type flow meters employing square edge concentric orifice plates as primary
sensing element shall normally be used where the piping sizes are 50mm or larger and
integral orifice shall be used for line sizes below 50mm.
The supplier shall carry out orifice calculations including calculations for the thickness of
the orifice plates. This shall include both orifice plates used for flow measurements and
restriction orifice.
Differential pressure instruments shall be fitted with five valve manifold for isolate and
equalize. Bleed ports shall be fitted with plugs.
Differential pressure gauges used for flow measurement shall have dual scale showing DP
as well as Flow (Square root scale)
Marking shall be done on orifice plates with Tag number, diameter (mm) of orifice, nominal
pipe size (in.), flange rating, materials.
6.3 Level Instruments
Level transmitter used shall be of float and tape type with local LCD display as well as 4-20
mA HART protocol and shall be hardwired to the existing RTU in each location.
Guide wires shall be provided to prevent horizontal swaying of the float.
On existing RCC tanks carbon steel plates shall be fixed on top of the tank and nozzles for
the tape and guide wires shall be installed on the plate.
The instrument shall be installed on the side wall of the tanks at visible height.
6.4 Pressure and Differential Pressure Instruments
Pressure gauges shall have a circular dial and shall be of the direct sensing type with
Bourdon element.
Gauges shall have 150 mm dial and movement and casing shall be of AISI 316 stainless
steel construction and shall have 1/2” NPT (M) bottom process connections.
Pressure gauges shall be of the safety pattern construction and shall be fitted with full
blow-out backs and shatterproof lens (laminated safety glass) and gauge protector if
required. Pressure gauges shall have scales calibrated in kg/cm2, white background with
black lettering.
Over range protector (gauge saver) shall be provided where a pressure instrument is
required to withstand protuberant pressure due to unavoidable operation. All pressure
instruments shall have over-range protection up to at least system design pressure without
temporary or permanent damage.
Glycerin filed gauges shall be provided for pulsating service, (e.g. discharge piping of

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 14 of 18

reciprocating Pumps).
Pressure switches shall have environmentally sealed micro switches wired to screw type
terminals. Mercury actuated switches shall not be acceptable. Pressure switches contact
type shall be hermetically sealed SPDT type.
All pressure instruments shall be fitted with integral two valve isolate and bleed manifold.
The bleed port shall be fitted with plug. All differential pressure instruments shall have
block, bleed, and vent and isolation facility.
6.5 Solenoid Valves
Solenoid valve coil shall be rated 24 VDC for continuous operation under the specified
ambient conditions. Coil power shall not exceed 10 Watts and a lower rating shall be
preferred.
Coils shall be capable of permanent energization at the maximum specified solar radiation
temperature unless supplied with permanent attached sunshade.
Solenoid valve body material shall be of 316 stainless steel.
Solenoid valve coils shall be fitted with a suppression diode by the vendor.
Solenoid valves shall be designed for direct operation of their pneumatic ports in response
to their coil voltage. Pilot operated solenoid valves shall not be used.
Universal type solenoid shall be used.
6.6 Manual Call Points
Manual Call Points (MCP) shall be provided at strategic locations around tank and process
areas of all installations for raising alarms to the control room. The quantity of MCP
required shall be selected based on NFPA 72 requirements.
Push Buttons with Push to Activate, twist-to-release red mushroom style head with
protection cover to prevent accidental operation shall be used.
Two sets of contacts, one each of the normally open and normally closed.
The MCP circuit shall be designed based on normally energized and open to alarm fail
safe philosophy.
Contact rating shall be 24 VDC, 0.5 A.
Red/white label engraved “Fire Alarm” in 25mm upper-case characters shall be provided.

7.0 ACCURACY OF INSTRUMENTS


Accuracy shall be as specified in the datasheets of each instrument.

8.0 INSTRUMENT AIR SUPPLY AND DISTRIBUTION

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 15 of 18

Instrument impulse tubing and Instrument air supply tubing material shall conform to ASTM
A269 TP 316L with a minimum Molybdenum content of 2.5% and shall be ½” size. All
instrumentation tube fittings shall be of the double ferrule 316 SS compression type.
The connection from each take off point to the individual user shall be stainless steel
tubes.
Each air supply take off from main header and connection to each instrument air consumer
shall be fitted with isolation valve.
The air supply to instruments shall be through individual isolating valves and filter/regulator
sets shall be supplied.

9.0 INSTRUMENT CABLES AND CABLE TRAYS


DGMS vide its circular no. DGMS technical Circular( Electrical) , (Approval), No.17
Dhanbad dt 25.5.2015 has done away with specific approval of electrical cables. However
standards and parameters prescribed in above mentioned circular are to be adhered
during manufacturing process and use of cables in mines.
All cables shall be Fire Resistant in accordance with IEC 60331-1.
Signal cables shall be multi stranded Copper conductor twisted pair, PVC inner jacket,
galvanized steel wire armored, XLPE or PVC outer sheath, 300/500 V rating, with overall
screen, pair identification blue, black numbered, suitable for direct burial.
Core cable shall be single stranded, PVC inner jacket, galvanized steel wire armored,
XLPE or PVC outer sheath, 300/500 V rating, cores shall be identified with colors with
numbering and shall be suitable for direct burial.
All cables shall be UV resistant and Rodent Resistant
All cables shall be color coded for easy for easy identification as per the below criteria
- All hardwired cables shall have Grey colored outer sheath
- All power cables shall have Black colored outer sheath
Standardization of cables can be done as follows
- All analog cables shall be 1P x 1.5 Sq.mm
- Main cable for analog signals shall be 10P x 1.5 Sq.mm
- Digital signals shall have 2C x 1.5 Sq.mm
- Solenoids shall have 2C x 2.5 Sq.mm
- Main cable for Digital Signals shall be 20C x 2.5 Sq.mm
All cables shall be in general run above ground on FRP cable trays. Main cables shall be
run on ladder trays and branch cables shall be run on perforated trays.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 16 of 18

The cables may be dropped into concrete trenches close to the control room/rack room if
required.
Power and signals shall be run on separate trays/Trench.

10.0 INSTRUMENT JUNCTION BOX


Junction Boxes shall also be segregated according to the I/O types as below

 Analog
 Digital Input
 Digital Output
 Pulse
All junction boxes shall be of copper free die cast Aluminum.
Each terminal rail and terminal shall be clearly identified as detailed on wiring diagrams.
Terminals shall be suitable to terminate wires of up to 2.5 sq.mm. Screens from single pair
cable and multi-pair cable shall be terminated on terminals.
Terminal shall be copper or other suitable alloy, spring loaded, vibration resistant, snap
mounted on nickel plated rails complete with end cover mounted either vertically or
horizontally.
Adequate space shall be provided inside junction box for pulling single pair cables and
multipair cables and termination.
Cable shall enter from bottom of junction box. Side entries shall be avoided and top entries
shall not be used. The Junction box shall be provided with removable gland plates at the
bottom and sides
Junction box shall be suitable for surface mounting and provided with tag number,
nameplate, mounting clamps, earthing terminal and non- removable manufacturer
nameplate containing as a minimum type of name of manufacturer, explosion protection if
applicable, hazardous area classification certificate, certifying authority, IP rating and
number of terminals.
Each terminal rail and terminal shall be clearly identified as detailed on wiring diagrams.
All unused cable entries shall be sealed by the use of appropriate screwed plugs. For
hazardous areas, certified ex-proof plugs shall be used.
All Junction box shall be supplied an earth boss and a drain plug.
Junction box terminals shall be standardized to 20 and 40 terminals.
Junction boxes shall be provided with required number of cable entries with additional 20%
spare certified plugs.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 17 of 18

11.0 INSTRUMENT CABLE GLANDS


Cable glands for field instruments and junction boxes shall be nickel plated brass double
compression type and Ex-proof.

12.0 INSTRUMENT INSTALLATION


All field instrumentation and valves shall be installed so as to be readily accessible from
grade or permanent platforms. Good access for operation and maintenance shall be
provided for all valves and field instruments.
Cables from junction boxes to control room equipment shall be installed without
splices/intermediate terminations.
Instrument signal & electrical control/power cables shall be laid on separate trays
physically separated by a distance to prevent electrical interference. Where intersection
between different types of cables is required, it shall be routed such that these cable
crossovers shall be at right angles.
Routing of cables shall avoid the installation risks due to high voltage cable installed in the
vicinity, high temperature lines, corrosive fluid spillage and direct solar radiation and
provide mechanical protection wherever necessary. Instrument cable tray shall be installed
with a space of minimum 300 mm from Electrical cable trays
All cables shall be installed in cable trays/ladders next to each other in a neat manner and
bunching of cables shall not be acceptable.
Cable tray supports, instrument tubing supports shall not depend on process piping or the
equipment to which they are attached.
Buried cable in the trench shall be marked and protected by warning marker tape and
concrete cover. The warning and lettering on the covers shall be specifically to instrument
buried cables and a general purpose cover shall not be acceptable.
Cable route markers should be installed at intervals of not more than 15m on straight runs
of cables and at deviations in the cable route in case the cables are buried.
Cable tags embossed on AISI 316 strips shall be wired in a staggered manner on each
cable at 5 meter interval in the trench and in the cable tray.
Cable trays and cable tray covers and fixing material shall be hot dip galvanized for
outdoor and indoor locations.
Branch cable trays shall be perforated without tray cover.
Main cable tray above ground shall be on cable ladders and shall be supported at every
1.5m.
Double compression cable glands shall be used for terminating cables.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Instrumentation Design Basis Rev: 1


Doc No: 5085-COMM-IN-L-1001 Page: 18 of 18

Cable glands material shall be nickel plated brass double compression type and Ex-proof
as per area classification.
Cable glands installed in hazardous areas shall be suitable for the hazardous area
classifications.
Instrument Air/Process tubing shall be supported rigidly and Installed on Hot dipped
Galvanized perforated tray.

13.0 POWER SUPPLY


The following power supply shall be considered.
- UPS 230 V AC, 50 Hz
- Non UPS 230 V AC, 50 Hz
All other power supplies as required shall be generated within the equipment by using
certified transformers /converters.

14.0 INSTRUMENT NAMEPLATES AND TAG PLATES


Instruments shall be provided with an identification plate, with all data clearly stamped on a
corrosion-resistant plate permanently attached by means of rivets or pins by the vendor.
The following data must be stamped on the identification plate: Tag Number, Name of
Manufacturer or Trade Mark, Model Number, Serial Number, Hazardous Area
Classification and Certificate Number, other relevant details such as range, wetted
material, and pressure rating as applicable for each instrument.
Field instruments shall carry traffolyte nameplate black letter on white background
indicating tag number and short description of service.
In addition all Instruments and cables shall be fitted with a Stainless steel tag plate tied to
the instrument by a SS wire.
All cables shall be tied with identification tags as per cable schedule at each end of the
cable, at both sides of MCTs/ Pipe sleeves, at regular intervals along with routings and at
every bend or change of direction.
Clips or tie-wraps (nylon) securing cables to angles or tray shall preferably be corrosion
resistant material compatible with the cable outer jacket & the tray.

15.0 MULTI-CABLE TRANSITS

All cables entering into safe areas such as the CCR shall have Multi Cable Transits to
ensure proper sealing of the safe areas and shall be of fire safe design.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 2 of 18

Table of Content

1.0 INTRODUCTION ............................................................................................................. 4


1.1 Definitions ............................................................................................................ 4
1.2 Scope .................................................................................................................. 5
1.3 Abbreviations ....................................................................................................... 5

2.0 SCOPE OF SUPPLY ...................................................................................................... 5

3.0 SCOPE OF WORK ......................................................................................................... 6


3.1 General ................................................................................................................ 6
3.2 Detailed Engineering............................................................................................ 8
3.3 Field Instruments ................................................................................................. 8
3.4 Fire Water Pump Control Panel ........................................................................... 9
3.5 RTU/SCADA Modifications ................................................................................ 10
3.6 Control Room Modification ................................................................................. 10
3.7 Fire Detection System........................................................................................ 10
3.8 Deluge Valves.................................................................................................... 11
3.9 Interface with MCC ............................................................................................ 11
3.10 Installation and Demolition ................................................................................. 11

4.0 PROCUREMENT .......................................................................................................... 13


4.1 General .............................................................................................................. 13
4.2 Commissioning Spares ...................................................................................... 14
4.3 2 year Spares .................................................................................................... 15

5.0 INSPECTION AND TESTING ....................................................................................... 15


5.1 Field Instruments ............................................................................................... 15
5.2 Control System Factory Acceptance Testing ..................................................... 16
5.3 Control Systems Site Acceptance Testing ......................................................... 16
5.4 Control Systems Integrated Site Acceptance Testing......................................... 16

6.0 PRE-COMMISSIONING ................................................................................................ 16

7.0 COMMISSIONING ........................................................................................................ 17

8.0 QUALITY CONTROL REQUIREMENTS....................................................................... 18

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 3 of 18

9.0 ENVIRONMENT, HEALTH AND SAFETY REQUIREMENTS ....................................... 18

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 4 of 18

1.0 INTRODUCTION
Oil and Natural Gas Corporation Ltd. (ONGC) is planning to revamp their existing
firefighting facilities of Mehsana Asset in the state of Gujarat under the project
„Revamping of fire protection system at Installations of Mehsana Asset. The Firefighting
system of surface facilities includes Group Gathering Stations (GGS), Early Production
Stations (EPS) and Effluent Treatment Plants (ETP).
ONGC has contracted Petro6 Engineering and Construction Pvt. Ltd. as Design
Engineering Consultant (DEC) for the above mentioned project. The facilities covered
under this project are as follows:
a) North Kadi GGS-III
b) North Kadi GGS-I
c) North Kadi GGS-II
d) North Kadi GGS-IV
e) Jotana GGS
f) Sobhasan GGS-I
g) Sobhasan GGS-II
h) Balol GGS-I
i) Balol GGS-IV
j) Balol GGS-II
k) Balol GGS-III
l) Bechraji GGS-I
m) Bechraji GGS-II
n) Lanwa GGS-I
o) Lanwa GGS-II
p) Lanwa GGS-III
q) Sobhasan WWTP
r) Langhnaj EPS

1.1 Definitions
The COMPANY / CLIENT / OWNER where used in this specification shall mean the
ultimate user / COMPANY of the plant and facilities.
The CONTRACTOR / PURCHASER where used in this specification shall mean the
party, who undertake LSTK / EPC contract for the above project.
The VENDOR / SUPPLIER where used in this specification shall mean the party, who
manufactures or supplies the equipment and services specified.
TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 5 of 18

The INSPECTOR / TPA where used in this specification shall mean the PURCHASER /
COMPANY or their authorized agency for carrying out the inspection.
The ENGINEER / DEC where used in this specification shall mean the party, who
perform Design Engineering Consultancy and Project Management for Company

1.2 Scope
The purpose of this document is to define the Scope of Work that needs to be carried out
by the LSTK contractor in all the fields.

These specifications are to be considered as minimum requirements and VENDOR may


submit to the COMPANY, for agreement, all calculations sheets and possible solutions
that could give technical and/or economic improvement.

Any omission in this requirement shall not relieve the VENDOR of his responsibility to
deliver the equipment along with other associated items, which are complete, of proven
design, and conforms to the Performance Requirements.

1.3 Abbreviations
CCR Central Control Room
FAT Factory Acceptance Test
GUI Graphic User Interface
ISO International Standard Organization
I/O Input / Output
MCC Motor Control Centre
PGTR Performance Guarentee Test Run
QA Quality Assurance
QC Quality Control
SAT Site Acceptance Test
UPS Uninterruptible Power Supply
RTU Remote terminal unit

2.0 SCOPE OF SUPPLY


The scope of supply shall include but not limited to the following:

a) All Field instruments including switches, transmitters and gauges

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 6 of 18

b) Supply of one dedicated brand new laptop for each installation with interface cables
and softwares for configuration, storage & restoration of backups, troubleshooting
and modifications including all software license‟s for the Fire Water Pump Control
Panel PLCs.

c) All additional hardware and software including software licenses required to connect
the field instrumentation to the existing RTU

d) Supply of fusible plug loop detection system including fusible plugs, tubing and
accessories such as Restriction orifice, Check valve, isolation for each loop.

e) Supply of Deluge valves with all accessories

f) Supply of Fire Water Pump Control Panel for each field

g) Supply of at least five sets of portable multi-function Electro pneumatic calibrator


with in-built pneumatic pump for calibration of field instruments to cater to all
installations.

h) Junction boxes as required

i) Main and branch cables, cables trays and cable glands

j) Tubing trays

k) Multi cable transits for all cable entry in to buildings

l) Supply of all tubings and fittings as required

m) All mounting stands for field instruments, Junction boxes and other detectors

n) Pre-fabricated FRP canopies /Sun shields for all field instruments and panels

o) Support steel for cable trays, tubing trays

p) Supply of all other installation and erection materials and consumables such as
earthing cables, cable tags, ferrules, lugs and all other accessories for mounting of
all instruments and local panels.

q) Commissioning spare parts as per the section 4.2 as a minimum

r) 2 year spare parts list as per vendor recommendation in line with section 4.3

3.0 SCOPE OF WORK


3.1 General
The CONTRACTOR shall develop the Basic Engineering Design package provided as
part of tender package into “Approved for Construction (AFC)” status, taking into account

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 7 of 18

of the detailed requirements as specified in the tender package, including;

 Process Basic Design Package

 Process Flow Diagrams and Piping & Instrumentation Diagrams

 Equipment Datasheets and Specifications

 Design Basis of various disciplines

 Project Specifications

 Standard Specifications

 Installation Standards etc.


It is the responsibility of the CONTRACTOR to meet all the requirements of following
central and state laws and regulatory requirements, including, but not limited to

 Oil Mines Regulations

 Oil Industries Safety Directorate regulations (OISD)

 Directorate General of Mines Safety (DGMS)

 Central Pollution Control Boards standards

 Indian Electricity Rules etc.


The scope of work of CONTRACTOR shall include, but not limited to, residual
engineering design, detailed engineering design, procurement of materials manufacture /
fabricate, inspection, testing, painting, and packing, transportation to site and supply of all
equipment / packages as listed in the equipment list / P&ID.
The CONTRACTOR‟s scope of work shall also include, unloading of the equipment /
packages at site, storage, moving to site, installation / erection, hooking up, inspection,
testing, and mechanical completion of work, pre-commissioning, commissioning and
handing over to COMPANY ready for start-up.
CONTRACTOR shall ensure the presence of equipment manufacturer (VENDOR) at site
for supervision of pre-commissioning and commissioning as required. CONTRACTOR
shall also ensure that equipment manufacturer (VENDOR) checks the correctness of
erection of all critical equipment prior to pre-commissioning.
Equipment which is transported by sea shall have sea-worthy packing and shall be sent
with nitrogen filling. Recommended preservation procedures shall be strictly followed by
the CONTRACTOR during the period of storage for all equipment.
The requirements of this specification are to be considered as minimum requirements
and CONTRACTOR may submit to the COMPANY for agreement, any better solutions,
with supporting document that could give technical and / or economic improvement.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 8 of 18

Any omission in this requirement shall not relieve the CONTRACTOR of his responsibility
to deliver the WORK with proven design, safe to operate and conforms to the
performance requirements as specified in the CONTRACT documents facilities.
3.2 Detailed Engineering
CONTRACTOR shall perform site visits in order to understand site conditions and project
requirements clearly prior to start of engineering work.

It is expected that CONTRACTOR shall utilize uniform data sheet formats, for preparing
specifications for various instruments, including those, which are being prepared by
package/sub package vendors. Items for which no format has been attached with the
document, CONTRACTOR may use standard ISA formats. Use of manufacturer standard
formats shall be avoided. In case package data sheets differ from the standard formats, it
is CONTRACTOR‟s responsibility to convert it into standard formats.

CONTRACTOR shall be responsible for all coordination with CONTRACTOR's own inter-
departments like Mechanical, Piping, Electrical, Process and Civil/Structural.

This shall include furnishing all necessary engineering data in the form of drawings and
documents and inter discipline review of drawings and data prepared by other
departments

CONTRACTOR shall also be responsible for all the coordination with the DEC,
COMPANY and all vendors.

3.3 Field Instruments


CONTRACTOR shall be responsible for the engineering required for installation of new
Field Instruments as per approved P&ID.

CONTRACTOR shall perform a site survey prior to start of Engineering in order to


understand the site conditions in line with the project requriements.

CONTRACTOR to note that the existing Fire Water tank dimensions are not quantified in
some of the fields and CONTRACTOR shall be responsible for selecting level instrument
range suitably during the site survey.

CONTRACTOR shall be responsible for the following for field instruments during the
engineering phase.

 Prepare/Update Instrument Index

 Prepare/Update Instrument Data sheets

 Perform Sizing calculations for Flow meters

 Selection of suitable instruments and valves

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 9 of 18

 Prepare/Update Instrument Location plan

 Coordination with system vendors for modification of the hardware and software
for the existing SCADA/RTU systems

 Normal Junction box grouping and preparation of Junction box schedule and
Wiring drawings as required

 Site Survey to identify the cable routing for all instruments

 Prepare/Update Instrument Cable block diagram

 Prepare/Update Main and branch cable tray and cable routing

 Preparation of Hook up drawings

 Prepare/Update of Instrument air Manifold layout

 Preparation of Instrument Typical Installation details

 Preparation of Instrumentation Bulk MTO


3.4 Fire Water Pump Control Panel
CONTRACTOR shall be responsible for design, engineering, procurement, installation,
Inspection, Testing, commissioning and handover of the Fire water Pump Control panel
as per P6EC-STD-IN-S-1019, Standard Specification for Fire Water Pump Control Panel.

In General for all fields the Fire Water jockey pumps and Main Fire water pumps will start
automatically based on fire water ring main pressure or shall have a capability to be
started manually from the local fire water pump panel in the fire water pump house.
In case of Balol GGS-1 since the SCADA control room is far away from the fire water
pump house the Fire water jockey pumps and fire water main pumps shall be provided
with the capability to start / stop from the SCADA control room.
CONTRACTOR shall also be responsible for the following

1. Interfacing the pressure transmitters on the Fire water header to the Fire water Pump
Control panel

2. Interfacing between the Fire water pump control panel and the MCC for the Fire water
jockey pumps and Electrical driven fire water main pumps located inside the Fire
water pump shed.

3. Interfacing between the Fire water pump control panel and the Diesel engine driven
fire water main pump control panel located inside the Fire water pump shed.

4. Interfacing between the Fire water control panel and the RTU in each of the site
through serial communication interface.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 10 of 18

3.5 RTU/SCADA Modifications


CONTRACTOR shall be responsible for the performing all modifications required for the
RTU/SCADA in each of the field mentioned in this project to accommodate the additional
inputs and outputs which are added part of this project.

CONTRACTOR shall perform site visits and identify the spares available, type of I/O
cards available and all other relevant aspects of the existing control system and
coordinate with the control system vendor (ABB) to supply any hardware and software
required to accommodate the additional I/O‟s relating this project.

CONTRACTOR shall ensure that the 24V DC power supply part of the RTU system are
adequate and if found inadequate shall augment the power supply as required. The
proposed modification shall be submitted to DEC/Company for review and approval.

The above modification of the RTU system will also include the serial communication with
the Fire Water Pump Control Panel in each of the sites for seamless exchange of data
between the RTU and the Fire water Pump Control panel.

Modification of graphics of the SCADA to include the new facilities which are added in
this project shall be carried out by CONTRACTOR. Sufficient license for instrument tags
shall be ensured by the CONTRACTOR and where required new licenses shall be
procured from the RTU/SCADA system vendor.

All modifications including hardware and software required to provide the start / stop
facility for fire water jockey pumps and Main fire water pumps from the SCADA control
room only in Balol GGS-1

The CONTRACTOR shall be responsible for the implementation, Testing and


commissioning of all the logic modifications required to open the relevant Deluge valves
on fire detection on the appropriate tanks.

CONTRACTOR shall be responsible to add barriers suitable for instrinsically safe (Ex‟i)
field instruments.

3.6 Control Room Modification


It is not envisaged to do any modification to the existing control rooms. However
CONTRACTOR shall be responsible for any modifications required to the control room in
order to lay and terminate new cables which are part of this project. CONTRACTOR shall
include all the engineering services, procurement, construction activities related with the
above work.

3.7 Fire Detection System


CONTRACTOR shall be responsible for the design, procurement, installation, testing,

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 11 of 18

pre-commissioning and commissioning of all components of the Fusible Plug loop type
fire detection as per the P&ID diagrams for each of the fields. The design of the Fusible
plug loop shall conform to the relvant OISD codes.

LSTK CONTRACTOR shall be responsible for extension of Instrument Air headers to all
areas where Fusible plug loops and deluge valves are to be installed.

3.8 Deluge Valves


CONTRACTOR shall be responsible for design, procurement, testing, installation and
commissioning of the deluge valve system and its interface with the pneumatic fusible
plug loop fire detection system and the electronic interface to the RTU system.

The CONTRACTOR shall be responsible for the followings

1. Interfacing the Fusible plug loop for each tank with the appropriate Deluge valves

2. Interfacing between the deluge valves and the RTU

3.9 Interface with MCC


CONTRACTOR shall be responsible for the design Procurement, Installation, Testing,
Precommissioning and commissioning activities required to interface all the signals such
as running indication, Fault indication, Auto/Manual status indication, Start/Stop
Command for each Jockey pump and main Fire water pump Motor in the MCC to the Fire
water pump control panel as per section 3.4

3.10 Installation and Demolition


The CONTRACTOR shall include the scope of installation of all items required for
handover of a complete working fire fighting system on turnkey basis as covered in
Scope of work.

CONTRACTOR shall be responsible for the dismantling of all existing instruments,


cables, trays, panels and supports for instrumentation items that will no longer be used.
All items which are dismantled shall be handed over to Authorised client personnel or
disposed of in line with environmental norms after COMPANY approval.

CONTRACTOR shall carryout installation of all instrument items as per the Installation
standards and specification included part of this bid documents. If any referred standards
are not available, the same will be prepared by the CONTRACTOR and submitted for
approval prior to implementation.

Installation shall include but not limited to the following

 Installation of instrument stanchions and all field instruments

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 12 of 18

 Installation of local control panels and local gauge boards as applicable

 Installation of new system cabinets, marshaling cabinets and power


distribution cabinets as required

 Installation of any hardware required within the control system


supplied by contractor like PLC consoles

 Installation of all system cables, power supply cables and grounding


cables

 Installation of junction box supports and Junction boxes

 Installation of all main cable tray supports and main cable trays

 Main cable and branch cable laying and dressing

 Cable glanding, ferruling, crimping and termination

 Installation of Instrument Air manifolds and air supply tubing

 Installation of Process Impulse tubing and Tubing supports

 Laying and termination of Instrument Earthing cables

 Painting and Touch up painting for instrument supports

CONTRACTOR shall be fully responsible for providing completely integrated unit wise
earthing system for which Instrument earthing system is a part. CONTRACTOR‟s scope
of work shall include earth pits, earthing cable, cable strips (as applicable) as per the
requirements with various system oriented items and interface with SCADA earthing.
SCADA earthing shall also be done by LSTK.

For special instruments, the installation may be carried out as per vendor/ manufacturer's
recommendations however all such installation standards shall be subject to DEC /
COMPANY review. CONTRACTOR shall be fully responsible to meet any and every
installation related requirements.

Painting of instrument supports, junction box supports cable tray supports and tubing
supports shall be done immediately after the installation of the support and shall be
inspected by COMPANY representative

CONTRACTOR shall be equipped with all tools and necessary equipment for the safe
installation and safety checks of all items.

Existing cable routing layout, cable trays, supports, instrument mounting stands can be
reused provided that the design and general arrangement of the plant uses prudent use

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 13 of 18

of space and construction materials. CONTRACTOR is encouraged to perform site visit


before submission of the bid to ascertain the same.

CONTRACTOR shall be responsible for supply of manpower for the duration of the
project based on the demand for skilled manpower and the time frame to meet project
deadlines. CONTRACTOR shall be responsible for the welfare and safety which shall
include but not be limited to their accommodation, transportation, food and safety as per
COMPANY‟s HSE norms. CONTRACTOR shall also have an emergency response unit
on standby to manage all possible situations.

4.0 PROCUREMENT
4.1 General
CONTRACTOR shall be responsible for the procurement of all items listed in the Scope
of Supply

As part of the procurement scope of work the CONTRACTOR shall be responsible for the
following activities

 Preparation of RFQ packages for all instrumentation items including Vendor


Document requirement list, Inspection and Test plan and spare parts
requirements

 Floating of RFQ packages to at least 3 vendors from the COMPANYs Vendor


list

 Technical Bid evaluation and Commercial bid evaluation

 Conducting technical clarification meetings as required with the different


vendors

 Order Placement and issue of Purchase order

 Vendor Document review and incorporation

 Expediting and Inspection including Factory acceptance test

 Packing, Transportation, Preservation and Storage at Site.

 Site acceptance test and integrated Site acceptance test

 Handover of spare parts and handover of dismantled items

It shall be CONTRACTORs responsibility to liase with vendors to obtain vendor


documentation. CONTRACTOR shall be responsible for a technical bid evaluation (TBE)
to ensure that vendor supplied items are technically acceptable before submitting the

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 14 of 18

documents to DEC for review and approval. CONTRACTOR to note that supply of all
items shall be as per CLIENT approved vendor list only and shall meet all certification
requirements.

The CONTRACTOR shall thoroughly review and approve vendor drawings for all
instruments including sub-package items, before forwarding to DEC. Approved drawings
that are duly stamped and signed by a competent representative/ engineer of Contractor
shall be accepted for review by DEC.

The CONTRACTOR shall also review documents provided by sub-vendors for system
oriented items. The CONTRACTOR shall review documents such as (but not limited to)
I/O assignments, loop wiring diagram, software documentation, and dynamic graphical
display drawings supplied by system vendors of SCADA and package PLCs. These
documents shall be reviewed and approved by CONTRACTOR based on
philosophy specified / agreed for the engineering of control systems before forwarding to
DEC /CLIENT.

All multidisciplinary fabrication and construction drawings shall be reviewed and signed
by CONTRACTOR‟s respective departmental representatives before forwarding to DEC
/CLIENT for review/approval/record.

Coordination with all sub-package unit suppliers for uniformity in engineering and
documentation and documentation supplied by them including P&ID's, instrument
specifications, installation standards etc. and obtaining all requisite drawing and
documents for review, record and final documentation.

Coordination with all instrument item suppliers including suppliers/manufacturers of


various system oriented items shall be a LSTK contractor scope.

CONTRACTOR shall be responsible for all the coordination with the vendors for all
factory Inspection and Testing during the manufacturing.

CONTRACTOR shall be responsible for the timely arrival of goods to site and storage
shall be in CONTRACTORs yard.

CONTRACTOR shall be responsible for storage of goods and transportation to site. Any
associated cost including taxes, insurance, freight and other tariffs shall in
CONTRACTORs accounts.

CONTRACTOR shall be responsible for the warranty/guarantee of all items supplied by


all vendors.

4.2 Commissioning Spares


The CONTRACTOR shall supply commissioning spare parts required for all instruments

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 15 of 18

and control systems, PLC etc.

As a minimum the contractor shall supply the following spare parts as a minimum as
commissioning spare parts

Fuses and Lamps 100%

Electronic Transmitter (Complete set) 1 per type for each installation

All Control system cards 1 per type for each installation

4.3 2 year Spares


CONTRACTOR shall ensure that all the sub vendors and vendors of package units
provide a list of recommended 2 year spare parts which will be submitted to the
DEC/COMPANY for review .

Each of the vendors shall prepare a detailed spare parts inter changeability record to
arrive at the common parts used in the project and shall prepare a list of recommended
quantity of 2 year spare parts list.

This list shall be handed over to the COMPANY with unit price and COMPANY will order
it directly with the vendor.

5.0 INSPECTION AND TESTING

5.1 Field Instruments


All Field Instruments shall be inspected and tested at the factory prior to shipment to site.

CONTRACTOR shall prepare Inspection and test plan together with the vendors and
coordinate all the Inspection activities with the vendor.

CONTRACTOR shall select a qualified sub-contractor to do the Site inspection activities


such as calibration, continuity testing, perform pre-commissioning checks etc.

The calibration equipment required for calibration of all instruments shall be supplied by
the sub-contractor and these equipment shall have a calibration certificate which is
traceable to national/International standards.

Calibration of all instruments shall be performed and documented at site before


installation. Complete documentation including certificates, datasheets, GA drawings,
calibration checks shall be suitably filed and handed over to COMPANY.

The megger testing and continuity testing of cables shall be carried out before and after
laying of cables. Cable test certificates and supplier documentation shall be filed and
handed over to COMPANY.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 16 of 18

Cold loop checks shall be conducted to ensure continuity of the cables before system
power up.

All Impulse tubing shall be pressure tested in line with standard requirements.

All Air tubing shall be leak tested at maximum operating pressure.

All test results shall be documented and handed over to the COMPANY.

5.2 Control System Factory Acceptance Testing


The CONTRACTOR shall be responsible for submitting an FAT checklist and procedure
for the Fire Water Pump Control Panels for approval to the DEC well in advance of FAT
visits.

The system shall undergo a 100% Factory acceptance test.

All I/O‟s will be simulated and a loop check shall be performed and all control and
Shutdown functions shall be checked 100% before accepting the control system

5.3 Control Systems Site Acceptance Testing


All Fire Water Pump Contro Panels shall undergo a 100% site acceptance test. The
CONTRACTOR shall be responsible for submitting an SAT checklist and procedure for
approval to the DEC well in advance of commencement of site activities.

All I/O‟s will be simulated and a loop check shall be performed and all control and
Shutdown functions shall be checked 100% before accepting the control system.

5.4 Control Systems Integrated Site Acceptance Testing


The CONTRACTOR shall be responsible for submitting an ISAT checklist and procedure
for approval to the DEC well in advance of commencement of site activities.

The integrated site acceptance test shall cover interface to all other systems and
subsystems shall perform to the satisfaction of DEC/COMPANY before approval of the
same can be awarded.

6.0 PRE-COMMISSIONING
Hot loop checks shall be conducted after power up of control system and completion of
all Site acceptance testing of the control system and electronic instruments shall be
simulated from the field and verified in the control room. All checks shall be duly recorded
and signed off by the performing engineer before submission to COMPANY.

Correct functioning of control and shutdown devices such as Deluge Valves shall be
ensured before start-up.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 17 of 18

Desired response of the plant as per approved Cause and Effect shall be verified and
signed off. CONTRACTOR shall be responsible for certifying the logic diagrams for all
units and utilities as final and in conformance with approved documents.

Preparation of Punch Lists and closing out of punch points shall be CONTRACTORs
responsibility.

Contractor scope of work shall include loop checking and pre-commissioning of


completely integrated instrumentation and control system including RTU, sub-package
system items in line with specification given elsewhere in this package. The co-ordination
necessary with SCADA vendor shall be in Contractor's scope of work.

Contractor shall make all modification and/or changes found necessary during loop
testing/ pre-commissioning/ commissioning. All such changes shall be approved by the
representative of DEC/COMPANY as per the procedure set up at site by engineer in-
charge/COMPANY. All changes found necessary in the shutdown logics/ interlock logics
of the plant and Pre-Commissioning/Loop testing/ Commissioning shall be certified by
Contractor, package sub-supplier, machinery supplier, COMPANY operator.

In case of system oriented items, Contractor shall be fully responsible to demonstrate to


DEC/ COMPANY all functional requirements specified in this document including their
performance in the actual plant environment activity shall also be coordinated by
Contractor with COMPANY and other package supplier as necessary

7.0 COMMISSIONING
The start-up, commissioning and stabilization of plant including any co-ordination with
COMPANY /DEC, sub-vendors and SCADA/PLC vendor, Analyzers, Machine monitoring
system, etc. shall be the total responsibility of CONTRACTOR/ LSTK vendor.

In case of system-oriented items like Analyzer systems, Machine Monitoring Systems and
any other special instrument items, the installation shall be done under the supervision of
that system/instrument vendor's personnel. It is the responsibility of the Contractor to co-
ordinate and to make available the specialist's services with qualified engineers and
technicians from the original suppliers of all control system at the time of installation,
testing and commissioning.

After successful completion of the plant construction and commissioning activities,


CONTRACTOR shall be responsible for preparing red line mark-ups and subsequently
the submission of As-Built Drawings in hard and soft copies along with native files to the
Owner.

CONTRACTOR shall include in his scope the supply of manpower for a period of 3
months after plant start-up to ensure smooth operation of the plant and handing over to

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

Scope of Work for Instrumentation- LSTK Contract Rev: 1

Doc No: 5085-COMM-IN-L-1002 Page: 18 of 18

Owner.

Contractor scope of work shall include loop checking and pre-commissioning of


completely integrated instrumentation and control system including DCS, sub-package
system items in line with specification given elsewhere in this package. The co-ordination
necessary with SCADA vendor shall be in Contractor's scope of work.

Contractor shall make all modification and/or changes found necessary during loop
testing/ pre-commissioning/ commissioning. All such changes shall be approved by the
representative of DEC/ COMPANY as per the procedure set up at site by engineer in-
charge/ COMPANY. All changes found necessary in the shutdown logics/ interlock logics
of the plant and Pre-Commissioning/Loop testing/ Commissioning shall be certified by
Contractor, package sub-supplier, machinery supplier, COMPANY operator.

In case of system oriented items, Contractor shall be fully responsible to demonstrate to


DEC / COMPANY all functional requirements specified in this document including their
performance in the actual plant environment activity shall also be coordinated by
Contractor with COMPANY and other package supplier as necessary

8.0 QUALITY CONTROL REQUIREMENTS


All materials before being incorporated in the work shall be inspected and if necessary
tested before approval by COMPANY‟s representative. Any work, on which such
materials are used without prior inspection (and when necessary testing) and without
approval and written permission of COMPANY‟s representative is liable to be considered
as defective and not acceptable. All Consumable test certificates need to be submitted to
COMPANY for review before commencing the work.

9.0 ENVIRONMENT, HEALTH AND SAFETY REQUIREMENTS


The CONTRACTOR shall adhere to the policies, guidelines and practices referred by the
company. The Contractor shall also submit his HSE policies and HSE plan for the project.
CONTRACTOR shall supply and install all types of area barricading / protective shielding
/ sheeting up to require for carrying out testing activities within the existing plant and pipe
rack and other facilities when the plant is in operation or having shut down.
CONTRACTOR shall seek any hot work permit and other necessary permits from the
COMPANY and strictly observe plant safety guide lines as imposed from time to time by
the COMPANY.

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - BALOL GGS - I
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BAG1-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 3"-FW-BAG1-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BAG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 2"-FW-BAG1-6019-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6017-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6017-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6017-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BAG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 2"-FW-BAG1-6019-AA3
13 HS-0102A-START PUMP START COMMAND BAG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BAG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BAG1-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BAG1-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 3"-FW-BAG1-6008-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BAG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 2"-FW-BAG1-6020-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BAG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 2"-FW-BAG1-6020-AA3
23 HS-0102B-START PUMP START COMMAND BAG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BAG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BAG1-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION BAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BAG1-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6009-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE BAG1-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6013-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BAG1-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BAG1-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BAG1-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6010-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE BAG1-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6014-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BAG1-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BAG1-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 10"-FW-BAG1-6015-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 10"-FW-BAG1-6015-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 10"-FW-BAG1-6015-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG1-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 8"-FW-BAG1-6042-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 8"-FW-BAG1-6024-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 8"-FW-BAG1-6042-AA3 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 8"-FW-BAG1-6042-AA3 5085-COMM-IN-J-1003
61 RO-1003 RESTRICTION ORIFICE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
62 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1003
63 DPI-1003A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1004
64 DV-1003A DELUGE VALVE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1001
65 XSY-1003A SOLENOID VALVE BAL1-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
66 PSL-1003 PRESSURE SWITCH BAL1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
67 PAL-1003 PRESSURE ALARM LOW BAL1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
68 PSH-1003A PRESSURE SWITCH BAL1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
69 PAH-1003A PRESSURE ALARM HIGH BAL1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
70 RO-1003A RESTRICTION ORIFICE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 -
71 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1003
72 DPI-1003B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1004
73 DV-1003B DELUGE VALVE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1001
74 XSY-1003B SOLENOID VALVE BAL1-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
75 PSH-1003B PRESSURE SWITCH BAL1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 5085-COMM-IN-J-1006
76 PAH-1003B PRESSURE ALARM HIGH BAL1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
77 RO-1003B RESTRICTION ORIFICE BAL1-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 -
78 RO-1002 RESTRICTION ORIFICE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
79 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1003
80 DPI-1002A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1004
81 DV-1002A DELUGE VALVE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1001
82 XSY-1002A SOLENOID VALVE BAL1-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
83 PSL-1002 PRESSURE SWITCH BAL1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
84 PAL-1002 PRESSURE ALARM LOW BAL1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
85 PSH-1002A PRESSURE SWITCH BAL1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
86 PAH-1002A PRESSURE ALARM HIGH BAL1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
87 RO-1002A RESTRICTION ORIFICE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 -
88 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1003
89 DPI-1002B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1004
90 DV-1002B DELUGE VALVE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1001
91 XSY-1002B SOLENOID VALVE BAL1-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
92 PSH-1002B PRESSURE SWITCH BAL1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 5085-COMM-IN-J-1006
93 PAH-1002B PRESSURE ALARM HIGH BAL1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
94 RO-1002B RESTRICTION ORIFICE BAL1-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 -
95 RO-1004 RESTRICTION ORIFICE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
96 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1003
97 DPI-1004A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1004 REFER DELUGE VALVE SCHEMATIC FOR TANKS
98 DV-1004A DELUGE VALVE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1001 5085-COMM-PR-D-1003

99 XSY-1004A SOLENOID VALVE BAL1-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
100 PSL-1004 PRESSURE SWITCH BAL1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
101 PAL-1004 PRESSURE ALARM LOW BAL1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
102 PSH-1004A PRESSURE SWITCH BAL1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1006
103 PAH-1004A PRESSURE ALARM HIGH BAL1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
104 RO-1004A RESTRICTION ORIFICE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 -
105 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1003
REFER DELUGE VALVE SCHEMATIC FOR TANKS
106 DPI-1004B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1004
5085-COMM-PR-D-1003
107 DV-1004B DELUGE VALVE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 5085-COMM-IN-J-1001
108 XSY-1004B SOLENOID VALVE BAL1-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
109 PSH-1004B PRESSURE SWITCH BAL1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6032-AM3 5085-COMM-IN-J-1006
110 PAH-1004B PRESSURE ALARM HIGH BAL1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
111 RO-1004B RESTRICTION ORIFICE BAL1-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6032-AM3 -
112 RO-1001 RESTRICTION ORIFICE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
113 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 5085-COMM-IN-J-1003
114 DPI-1001A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 5085-COMM-IN-J-1004
115 DV-1001A DELUGE VALVE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 5085-COMM-IN-J-1001
116 XSY-1001A SOLENOID VALVE BAL1-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
117 PSL-1001 PRESSURE SWITCH BAL1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
118 PAL-1001 PRESSURE ALARM LOW BAL1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
119 PSH-1001A PRESSURE SWITCH BAL1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
120 PAH-1001A PRESSURE ALARM HIGH BAL1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
121 RO-1001A RESTRICTION ORIFICE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 -
122 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 5085-COMM-IN-J-1003
123 DPI-1001B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 5085-COMM-IN-J-1004
124 DV-1001B DELUGE VALVE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 5085-COMM-IN-J-1001
125 XSY-1001B SOLENOID VALVE BAL1-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
126 PSH-1001B PRESSURE SWITCH BAL1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 5085-COMM-IN-J-1006
127 PAH-1001B PRESSURE ALARM HIGH BAL1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
128 RO-1001B RESTRICTION ORIFICE BAL1-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 -
129 RO-2002 RESTRICTION ORIFICE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
130 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 5085-COMM-IN-J-1003
131 DPI-2002A DIFFERENTIAL PRESSURE GAUGE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 5085-COMM-IN-J-1004
132 DV-2002A DELUGE VALVE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 5085-COMM-IN-J-1001
133 XSY-2002A SOLENOID VALVE BAL1-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
134 PSL-2002 PRESSURE SWITCH BAL1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
135 PAL-2002 PRESSURE ALARM LOW BAL1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
136 PSH-2002A PRESSURE SWITCH BAL1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
137 PAH-2002A PRESSURE ALARM HIGH BAL1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
138 RO-2002A RESTRICTION ORIFICE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 -
139 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 5085-COMM-IN-J-1003
140 DPI-2002B DIFFERENTIAL PRESSURE GAUGE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 5085-COMM-IN-J-1004
141 DV-2002B DELUGE VALVE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 5085-COMM-IN-J-1001
142 XSY-2002B SOLENOID VALVE BAL1-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
143 PSH-2002B PRESSURE SWITCH BAL1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 5085-COMM-IN-J-1006
144 PAH-2002B PRESSURE ALARM HIGH BAL1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
145 RO-2002B RESTRICTION ORIFICE BAL1-TT-02 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 -
146 RO-2003 RESTRICTION ORIFICE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
147 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 5085-COMM-IN-J-1003
148 DPI-2003A DIFFERENTIAL PRESSURE GAUGE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 5085-COMM-IN-J-1004
149 DV-2003A DELUGE VALVE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 5085-COMM-IN-J-1001
150 XSY-2003A SOLENOID VALVE BAL1-TT-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
151 PSL-2003 PRESSURE SWITCH BAL1-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
152 PAL-2003 PRESSURE ALARM LOW BAL1-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
153 PSH-2003A PRESSURE SWITCH BAL1-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
154 PAH-2003A PRESSURE ALARM HIGH BAL1-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
155 RO-2003A RESTRICTION ORIFICE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 -
156 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 5085-COMM-IN-J-1003
157 DPI-2003B DIFFERENTIAL PRESSURE GAUGE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 5085-COMM-IN-J-1004
158 DV-2003B DELUGE VALVE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 5085-COMM-IN-J-1001
159 XSY-2003B SOLENOID VALVE BAL1-TT-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
160 PSH-2003B PRESSURE SWITCH BAL1-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 5085-COMM-IN-J-1006
161 PAH-2003B PRESSURE ALARM HIGH BAL1-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 - -
162 RO-2003B RESTRICTION ORIFICE BAL1-TT-03 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 -
163 RO-1005 RESTRICTION ORIFICE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
164 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 5085-COMM-IN-J-1003
165 DPI-1005A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 5085-COMM-IN-J-1004
166 DV-1005A DELUGE VALVE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 5085-COMM-IN-J-1001
167 XSY-1005A SOLENOID VALVE BAL1-OST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
168 PSL-1005 PRESSURE SWITCH BAL1-OST-05 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
169 PAL-1005 PRESSURE ALARM LOW BAL1-OST-05 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
170 PSH-1005A PRESSURE SWITCH BAL1-OST-05 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
171 PAH-1005A PRESSURE ALARM HIGH BAL1-OST-05 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
5085-COMM-PR-D-1003
172 RO-1005A RESTRICTION ORIFICE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 -
173 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 5085-COMM-IN-J-1003
174 DPI-1005B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 5085-COMM-IN-J-1004
175 DV-1005B DELUGE VALVE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 5085-COMM-IN-J-1001
176 XSY-1005B SOLENOID VALVE BAL1-OST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
177 PSH-1005B PRESSURE SWITCH BAL1-OST-05 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 5085-COMM-IN-J-1006
178 PAH-1005B PRESSURE ALARM HIGH BAL1-OST-05 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
179 RO-1005B RESTRICTION ORIFICE BAL1-OST-05 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 -
180 RO-1006 RESTRICTION ORIFICE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
181 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 5085-COMM-IN-J-1003
182 DPI-1006A DIFFERENTIAL PRESSURE GAUGE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 5085-COMM-IN-J-1004
183 DV-1006A DELUGE VALVE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 5085-COMM-IN-J-1001
184 XSY-1006A SOLENOID VALVE BAL1-OST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
185 PSL-1006 PRESSURE SWITCH BAL1-OST-06 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
186 PAL-1006 PRESSURE ALARM LOW BAL1-OST-06 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
187 PSH-1006A PRESSURE SWITCH BAL1-OST-06 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
188 PAH-1006A PRESSURE ALARM HIGH BAL1-OST-06 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
5085-COMM-PR-D-1003
189 RO-1006A RESTRICTION ORIFICE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 -
190 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 5085-COMM-IN-J-1003
191 DPI-1006B DIFFERENTIAL PRESSURE GAUGE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 5085-COMM-IN-J-1004
192 DV-1006B DELUGE VALVE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 5085-COMM-IN-J-1001
193 XSY-1006B SOLENOID VALVE BAL1-OST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
194 PSH-1006B PRESSURE SWITCH BAL1-OST-06 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 5085-COMM-IN-J-1006
195 PAH-1006B PRESSURE ALARM HIGH BAL1-OST-06 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
196 RO-1006B RESTRICTION ORIFICE BAL1-OST-06 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 -
197 RO-2001 RESTRICTION ORIFICE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
REFER DELUGE VALVE SCHEMATIC FOR TANKS
198 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 5085-COMM-IN-J-1003
5085-COMM-PR-D-1003
199 DPI-2001A DIFFERENTIAL PRESSURE GAUGE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 5085-COMM-IN-J-1004
200 DV-2001A DELUGE VALVE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 5085-COMM-IN-J-1001
201 XSY-2001A SOLENOID VALVE BAL1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
202 PSL-2001 PRESSURE SWITCH BAL1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
203 PAL-2001 PRESSURE ALARM LOW BAL1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
204 PSH-2001A PRESSURE SWITCH BAL1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 5085-COMM-IN-J-1006
205 PAH-2001A PRESSURE ALARM HIGH BAL1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
206 RO-2001A RESTRICTION ORIFICE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 - REFER DELUGE VALVE SCHEMATIC FOR TANKS
207 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 5085-COMM-IN-J-1003 5085-COMM-PR-D-1003

208 DPI-2001B DIFFERENTIAL PRESSURE GAUGE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 5085-COMM-IN-J-1004
209 DV-2001B DELUGE VALVE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 5085-COMM-IN-J-1001
210 XSY-2001B SOLENOID VALVE BAL1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
211 PSH-2001B PRESSURE SWITCH BAL1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 5085-COMM-IN-J-1006
212 PAH-2001B PRESSURE ALARM HIGH BAL1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 - -
213 RO-2001B RESTRICTION ORIFICE BAL1-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 -

SHEET 2 OF 2
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BAG1-IN-K-1002 Page: 2 of 2

BALOL GGS-1
AI DI DO DOP

RTU 2 27 6 18

RTU WITH 30%


3 35 8 23
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - BALOL GGS - II
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BAG2-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 3"-FW-BAG2-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BAG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 2"-FW-BAG2-6019-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6017-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6017-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6017-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BAG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 2"-FW-BAG2-6019-AA3
13 HS-0102A-START PUMP START COMMAND BAG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BAG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BAG2-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BAG2-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 3"-FW-BAG2-6008-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BAG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 2"-FW-BAG2-6020-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BAG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 2"-FW-BAG2-6020-AA3
23 HS-0102B-START PUMP START COMMAND BAG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BAG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BAG2-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION BAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BAG2-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6008-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE BAG2-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6012-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BAG2-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BAG2-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BAG2-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6009-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE BAG2-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6013-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BAG2-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BAG2-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6015-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6015-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6015-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG2-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 8"-FW-BAG2-6023-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 8"-FW-BAG2-6038-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 8"-FW-BAG2-6024-AA3 5085-COMM-IN-J-1003
60 RO-1002 RESTRICTION ORIFICE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
61 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 5085-COMM-IN-J-1003
62 DPI-1002A DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 5085-COMM-IN-J-1004
63 DV-1002A DELUGE VALVE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 5085-COMM-IN-J-1001
64 XSY-1002A SOLENOID VALVE BALGGS2-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
65 PSL-1002 PRESSURE SWITCH BALGGS2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
66 PAL-1002 PRESSURE ALARM LOW BALGGS2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
67 PSH-1002A PRESSURE SWITCH BALGGS2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
68 PAH-1002A PRESSURE ALARM HIGH BALGGS2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
69 RO-1002A RESTRICTION ORIFICE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 -
70 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 5085-COMM-IN-J-1003
71 DPI-1002B DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 5085-COMM-IN-J-1004
72 DV-1002B DELUGE VALVE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 5085-COMM-IN-J-1001
73 XSY-1002B SOLENOID VALVE BALGGS2-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
74 PSH-1002B PRESSURE SWITCH BALGGS2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 5085-COMM-IN-J-1006
75 PAH-1002B PRESSURE ALARM HIGH BALGGS2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
76 RO-1002B RESTRICTION ORIFICE BALGGS2-OST-02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 -
77 RO-1001 RESTRICTION ORIFICE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
78 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 5085-COMM-IN-J-1003
79 DPI-1001A DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 5085-COMM-IN-J-1004
80 DV-1001A DELUGE VALVE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 5085-COMM-IN-J-1001
81 XSY-1001A SOLENOID VALVE BALGGS2-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
82 PSL-1001 PRESSURE SWITCH BALGGS2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
83 PAL-1001 PRESSURE ALARM LOW BALGGS2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
84 PSH-1001A PRESSURE SWITCH BALGGS2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
85 PAH-1001A PRESSURE ALARM HIGH BALGGS2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
86 RO-1001A RESTRICTION ORIFICE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 -
87 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 5085-COMM-IN-J-1003
88 DPI-1001B DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 5085-COMM-IN-J-1004
89 DV-1001B DELUGE VALVE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 5085-COMM-IN-J-1001
90 XSY-1001B SOLENOID VALVE BALGGS2-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
91 PSH-1001B PRESSURE SWITCH BALGGS2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 5085-COMM-IN-J-1006
92 PAH-1001B PRESSURE ALARM HIGH BALGGS2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
93 RO-1001B RESTRICTION ORIFICE BALGGS2-OST-01 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 -
94 RO-1004 RESTRICTION ORIFICE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
95 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 5085-COMM-IN-J-1003
96 DPI-1004A DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 5085-COMM-IN-J-1004
REFER DELUGE VALVE SCHEMATIC FOR TANKS
97 DV-1004A DELUGE VALVE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 5085-COMM-IN-J-1001
5085-COMM-PR-D-1003
98 XSY-1004A SOLENOID VALVE BALGGS2-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
99 PSL-1004 PRESSURE SWITCH BALGGS2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
100 PAH-1004 PRESSURE ALARM LOW BALGGS2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -

SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - BALOL GGS - II
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PSH-1004A PRESSURE SWITCH BALGGS2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 5085-COMM-IN-J-1006
102 PAH-1004A PRESSURE ALARM HIGH BALGGS2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
103 RO-1004A RESTRICTION ORIFICE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 -
104 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 5085-COMM-IN-J-1003
105 DPI-1004B DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 5085-COMM-IN-J-1004 REFER DELUGE VALVE SCHEMATIC FOR TANKS
106 DV-1004B DELUGE VALVE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 5085-COMM-IN-J-1001 5085-COMM-PR-D-1003
107 XSY-1004B SOLENOID VALVE BALGGS2-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
108 PSH-1004B PRESSURE SWITCH BALGGS2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 5085-COMM-IN-J-1006
109 PAH-1004B PRESSURE ALARM HIGH BALGGS2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
110 RO-1004B RESTRICTION ORIFICE BALGGS2-OST-04 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 -
111 RO-1003 RESTRICTION ORIFICE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
112 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 5085-COMM-IN-J-1003
113 DPI-1003A DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 5085-COMM-IN-J-1004
114 DV-1003A DELUGE VALVE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 5085-COMM-IN-J-1001
115 XSY-1003A SOLENOID VALVE BALGGS2-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
116 PSL-1003 PRESSURE SWITCH BALGGS2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
117 PAL-1003 PRESSURE ALARM LOW BALGGS2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
118 PSH-1003A PRESSURE SWITCH BALGGS2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
119 PAH-1003A PRESSURE ALARM HIGH BALGGS2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
120 RO-1003A RESTRICTION ORIFICE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 -
121 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 5085-COMM-IN-J-1003
122 DPI-1003B DIFFERENTIAL PRESSURE GAUGE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 5085-COMM-IN-J-1004
123 DV-1003B DELUGE VALVE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 5085-COMM-IN-J-1001
124 XSY-1003B SOLENOID VALVE BALGGS2-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
125 PSH-1003B PRESSURE SWITCH BALGGS2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 5085-COMM-IN-J-1006
126 PAH-1003B PRESSURE ALARM HIGH BALGGS2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
127 RO-1003B RESTRICTION ORIFICE BALGGS2-OST-03 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 -
128 RO-2001 RESTRICTION ORIFICE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
129 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 5085-COMM-IN-J-1003
130 DPI-2001A DIFFERENTIAL PRESSURE GAUGE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 5085-COMM-IN-J-1004
131 DV-2001A DELUGE VALVE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 5085-COMM-IN-J-1001
132 XSY-2001A SOLENOID VALVE BALGGS2-TT-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
133 PSL-2001 PRESSURE SWITCH BALGGS2-TT-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
134 PAL-2001 PRESSURE ALARM LOW BALGGS2-TT-01/02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
135 PSH-2001A PRESSURE SWITCH BALGGS2-TT-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
136 PAH-2001A PRESSURE ALARM HIGH BALGGS2-TT-01/02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
137 RO-2001A RESTRICTION ORIFICE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 -
138 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 5085-COMM-IN-J-1003
139 DPI-2001B DIFFERENTIAL PRESSURE GAUGE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 5085-COMM-IN-J-1004
140 DV-2001B DELUGE VALVE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 5085-COMM-IN-J-1001
141 XSY-2001B SOLENOID VALVE BALGGS2-TT-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
142 PSH-2001B PRESSURE SWITCH BALGGS2-TT-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 5085-COMM-IN-J-1006
143 PAH-2001B PRESSURE ALARM HIGH BALGGS2-TT-01/02 CCR - SOFT FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 - -
144 RO-2001B RESTRICTION ORIFICE BALGGS2-TT-01/02 FIELD - - FIRE WATER NETWORK 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BAG2-IN-K-1002 Page: 2 of 2

BALOL GGS-2
AI DI DO DOP

RTU 2 15 6 10

RTU WITH 30%


3 20 8 13
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BALOL GGS - III
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BAG3-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 3"-FW-BAG3-6006-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BAG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 2"-FW-BAG3-6010-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6016-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6016-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6016-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BAG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 2"-FW-BAG3-6017-AA3
13 HS-0102A-START PUMP START COMMAND BAG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BAG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BAG3-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BAG3-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 3"-FW-BAG3-6007-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BAG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 2"-FW-BAG3-6011-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BAG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 2"-FW-BAG3-6011-AA3
23 HS-0102B-START PUMP START COMMAND BAG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BAG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BAG3-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION BAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BAG3-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6008-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE BAG3-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6012-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BAG3-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BAG3-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BAG3-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6009-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE BAG3-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6013-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BAG3-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BAG3-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6014-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6014-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6014-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG3-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 8"-FW-BAG3-6015-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 8"-FW-BAG3-6023-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 8"-FW-BAG3-6023-AA3 5085-COMM-IN-J-1003
59 RO-2001 RESTRICTION ORIFICE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
60 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1003
61 DPI-2001A DIFFERENTIAL PRESSURE GAUGE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1004
62 DV-2001A DELUGE VALVE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1001
63 XSY-2001A SOLENOID VALVE T-504 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
64 PSL-2001 PRESSURE SWITCH T-504 FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAL-2001 PRESSURE ALARM LOW T-504 CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
66 PSH-2001A PRESSURE SWITCH T-504 FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
67 PAH-2001A PRESSURE ALARM HIGH T-504 CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
68 RO-2001A RESTRICTION ORIFICE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 -
69 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1003
70 DPI-2001B DIFFERENTIAL PRESSURE GAUGE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1004
71 DV-2001B DELUGE VALVE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1001
72 XSY-2001B SOLENOID VALVE T-504 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
73 PSH-2001B PRESSURE SWITCH T-504 FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1006
74 PAH-2001B PRESSURE ALARM HIGH T-504 CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
75 RO-2001B RESTRICTION ORIFICE T-504 FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 -
76 RO-1003 RESTRICTION ORIFICE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
77 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1003
78 DPI-1003A DIFFERENTIAL PRESSURE GAUGE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1004
79 DV-1003A DELUGE VALVE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1001
80 XSY-1003A SOLENOID VALVE T-501C FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
81 PSL-1003 PRESSURE SWITCH T-501C FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
82 PAL-1003 PRESSURE ALARM LOW T-501C CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
83 PSH-1003A PRESSURE SWITCH T-501C FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
84 PAH-1003A PRESSURE ALARM HIGH T-501C CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
85 RO-1003A RESTRICTION ORIFICE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 -
86 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1003
87 DPI-1003B DIFFERENTIAL PRESSURE GAUGE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1004
88 DV-1003B DELUGE VALVE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1001
89 XSY-1003B SOLENOID VALVE T-501C FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
90 PSH-1003B PRESSURE SWITCH T-501C FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 5085-COMM-IN-J-1006
91 PAH-1003B PRESSURE ALARM HIGH T-501C CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
92 RO-1003B RESTRICTION ORIFICE T-501C FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 -
93 RO-1004 RESTRICTION ORIFICE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
94 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 5085-COMM-IN-J-1003
95 DPI-1004A DIFFERENTIAL PRESSURE GAUGE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 5085-COMM-IN-J-1004
96 DV-1004A DELUGE VALVE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 5085-COMM-IN-J-1001
97 XSY-1004A SOLENOID VALVE T-501D FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
98 PSL-1004 PRESSURE SWITCH T-501D FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
99 PAL-1004 PRESSURE ALARM LOW T-501D CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
100 PSH-1004A PRESSURE SWITCH T-501D FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
5085-COMM-PR-D-1003
SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BALOL GGS - III
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks
REFER DELUGE VALVE SCHEMATIC FOR TANKS
101 PAH-1004A PRESSURE ALARM HIGH T-501D CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
102 RO-1004A RESTRICTION ORIFICE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 -
103 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 5085-COMM-IN-J-1003
104 DPI-1004B DIFFERENTIAL PRESSURE GAUGE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 5085-COMM-IN-J-1004
105 DV-1004B DELUGE VALVE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 5085-COMM-IN-J-1001
106 XSY-1004B SOLENOID VALVE T-501D FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
107 PSH-1004B PRESSURE SWITCH T-501D FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 5085-COMM-IN-J-1006
108 PAH-1004B PRESSURE ALARM HIGH T-501D CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
109 RO-1004B RESTRICTION ORIFICE T-501D FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 -
110 RO-1001 RESTRICTION ORIFICE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
111 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 5085-COMM-IN-J-1003
112 DPI-1001A DIFFERENTIAL PRESSURE GAUGE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 5085-COMM-IN-J-1004
113 DV-1001A DELUGE VALVE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 5085-COMM-IN-J-1001
114 XSY-1001A SOLENOID VALVE T-501A FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
115 PSL-1001 PRESSURE SWITCH T-501A FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
116 PAL-1001 PRESSURE ALARM LOW T-501A CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
117 PSH-1001A PRESSURE SWITCH T-501A FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
118 PAH-1001A PRESSURE ALARM HIGH T-501A CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
119 RO-1001A RESTRICTION ORIFICE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 -
120 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 5085-COMM-IN-J-1003
121 DPI-1001B DIFFERENTIAL PRESSURE GAUGE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 5085-COMM-IN-J-1004
122 DV-1001B DELUGE VALVE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 5085-COMM-IN-J-1001
123 XSY-1001B SOLENOID VALVE T-501A FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
124 PSH-1001B PRESSURE SWITCH T-501A FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 5085-COMM-IN-J-1006
125 PAH-1001B PRESSURE ALARM HIGH T-501A CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
126 RO-1001B RESTRICTION ORIFICE T-501A FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 -
127 RO-1002 RESTRICTION ORIFICE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
128 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 5085-COMM-IN-J-1003
129 DPI-1002A DIFFERENTIAL PRESSURE GAUGE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 5085-COMM-IN-J-1004
130 DV-1002A DELUGE VALVE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 5085-COMM-IN-J-1001
131 XSY-1002A SOLENOID VALVE T-501B FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
132 PSL-1002 PRESSURE SWITCH T-501B FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
133 PAL-1002 PRESSURE ALARM LOW T-501B CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
134 PSH-1002A PRESSURE SWITCH T-501B FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
135 PAH-1002A PRESSURE ALARM HIGH T-501B CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
136 RO-1002A RESTRICTION ORIFICE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 -
137 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 5085-COMM-IN-J-1003
138 DPI-1002B DIFFERENTIAL PRESSURE GAUGE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 5085-COMM-IN-J-1004
139 DV-1002B DELUGE VALVE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 5085-COMM-IN-J-1001
140 XSY-1002B SOLENOID VALVE T-501B FIELD RTU DOP FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
141 PSH-1002B PRESSURE SWITCH T-501B FIELD RTU DI FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 5085-COMM-IN-J-1006
142 PAH-1002B PRESSURE ALARM HIGH T-501B CCR - SOFT FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 - -
143 RO-1002B RESTRICTION ORIFICE T-501B FIELD - - FIRE WATER NETWORK 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BAG3-IN-K-1002 Page: 2 of 2

BALOL GGS-III
AI DI DO DOP

RTU 2 15 6 10

RTU WITH 30%


3 20 8 13
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BALOL GGS - IV
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG4-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BAG4-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 3"-FW-BAG4-6006-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BAG4-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 2"-FW-BAG4-6010-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6016-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6016-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6016-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BAG4-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 2"-FW-BAG4-6018-AA3
13 HS-0102A-START PUMP START COMMAND BAG4-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BAG4-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BAG4-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BAG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BAG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BAG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BAG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BAG4-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 3"-FW-BAG4-6007-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BAG4-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 2"-FW-BAG4-6011-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BAG4-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 2"-FW-BAG4-6020-AA3
23 HS-0102B-START PUMP START COMMAND BAG4-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BAG4-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BAG4-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BAG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BAG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
28 28/02/2018 AUTO INDICATION BAG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BAG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BAG4-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6008-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE BAG4-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6012-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BAG4-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BAG4-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BAG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BAG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BAG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BAG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BAG4-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6009-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE BAG4-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6013-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BAG4-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BAG4-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BAG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BAG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BAG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BAG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6015-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6015-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6015-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BAG4-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 8"-FW-BAG4-6024-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 8"-FW-BAG4-6024-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 8"-FW-BAG4-6024-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 8"-FW-BAG4-6024-AA3 5085-COMM-IN-J-1003
60 RO-1001 RESTRICTION ORIFICE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
61 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 5085-COMM-IN-J-1003
62 DPI-1001A DIFFERENTIAL PRESSURE GAUGE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 5085-COMM-IN-J-1004
63 DV-1001A DELUGE VALVE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 5085-COMM-IN-J-1001
64 XSY-1001A SOLENOID VALVE BAL IV-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
65 PSL-1001 PRESSURE SWITCH BAL IV-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - 5085-COMM-IN-J-1006
66 PAL-1001 PRESSURE ALARM LOW BAL IV-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
67 PSH-1001A PRESSURE SWITCH BAL IV-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
68 PAH-1001A PRESSURE ALARM HIGH BAL IV-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
5085-COMM-PR-D-1003
69 RO-1001A RESTRICTION ORIFICE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 -
70 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 5085-COMM-IN-J-1003
71 DPI-1001B DIFFERENTIAL PRESSURE GAUGE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 5085-COMM-IN-J-1004
72 DV-1001B DELUGE VALVE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 5085-COMM-IN-J-1001
73 XSY-1001B SOLENOID VALVE BAL IV-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
74 PSH-1001B PRESSURE SWITCH BAL IV-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 5085-COMM-IN-J-1006
75 PAH-1001B PRESSURE ALARM HIGH BAL IV-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
76 RO-1001B RESTRICTION ORIFICE BAL IV-ST-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 -
77 RO-1002 RESTRICTION ORIFICE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
78 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 5085-COMM-IN-J-1003
79 DPI-1002A DIFFERENTIAL PRESSURE GAUGE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 5085-COMM-IN-J-1004
80 DV-1002A DELUGE VALVE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 5085-COMM-IN-J-1001
81 XSY-1002A SOLENOID VALVE BAL IV-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
82 PSL-1002 PRESSURE SWITCH BAL IV-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - 5085-COMM-IN-J-1006
83 PAL-1002 PRESSURE ALARM LOW BAL IV-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
84 PSH-1002A PRESSURE SWITCH BAL IV-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
85 PAH-1002A PRESSURE ALARM HIGH BAL IV-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
5085-COMM-PR-D-1003
86 RO-1002A RESTRICTION ORIFICE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 -
87 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 5085-COMM-IN-J-1003
88 DPI-1002B DIFFERENTIAL PRESSURE GAUGE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 5085-COMM-IN-J-1004
89 DV-1002B DELUGE VALVE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 5085-COMM-IN-J-1001
90 XSY-1002B SOLENOID VALVE BAL IV-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
91 PSH-1002B PRESSURE SWITCH BAL IV-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 5085-COMM-IN-J-1006
92 PAH-1002B PRESSURE ALARM HIGH BAL IV-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
93 RO-1002B RESTRICTION ORIFICE BAL IV-ST-02 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 -
94 RO-2001 RESTRICTION ORIFICE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
95 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 5085-COMM-IN-J-1003
96 DPI-2001A DIFFERENTIAL PRESSURE GAUGE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 5085-COMM-IN-J-1004
97 DV-2001A DELUGE VALVE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 5085-COMM-IN-J-1001
98 XSY-2001A SOLENOID VALVE BAL IV-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
99 PSL-2001 PRESSURE SWITCH BAL IV-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - 5085-COMM-IN-J-1006
100 PAL-2001 PRESSURE ALARM LOW BAL IV-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -

REFER DELUGE VALVE SCHEMATIC FOR TANKS


SHEET 2 OF 3 5085-COMM-PR-D-1003
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BALOL GGS - IV
Document Title : INSTRUMENT INDEX
Document No : 5085-BAG4-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PSH-2001A PRESSURE SWITCH BAL IV-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
102 PAH-2001A PRESSURE ALARM HIGH BAL IV-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
5085-COMM-PR-D-1003
103 RO-2001A RESTRICTION ORIFICE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 -
104 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 5085-COMM-IN-J-1003
105 DPI-2001B DIFFERENTIAL PRESSURE GAUGE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 5085-COMM-IN-J-1004
106 DV-2001B DELUGE VALVE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 5085-COMM-IN-J-1001
107 XSY-2001B SOLENOID VALVE BAL IV-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
108 PSH-2001B PRESSURE SWITCH BAL IV-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 5085-COMM-IN-J-1006
109 PAH-2001B PRESSURE ALARM HIGH BAL IV-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 - -
110 RO-2001B RESTRICTION ORIFICE BAL IV-TT-01 FIELD - - FIRE WATER NETWORK 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BAG4-IN-K-1002 Page: 2 of 2

BALOL GGS-IV
AI DI DO DOP

RTU 2 9 6 6

RTU WITH 30%


3 12 8 8
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BECHRAJI GGS - 1
Document Title : INSTRUMENT INDEX
Document No : 5085-BEG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
7 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BEG1-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 3"-FW-BEG1-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BEG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 2"-FW-BEG1-6012-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6015-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6015-AA3 5085-COMM-IN-J-1005
11 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6017-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BEG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 2"-FW-BEG1-6018-AA3
13 HS-0102A-START PUMP START COMMAND BEG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BEG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BEG1-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BEG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BEG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BEG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BEG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
20 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BEG1-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 3"-FW-BEG1-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BEG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 2"-FW-BEG1-6013-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BEG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 2"-FW-BEG1-6019-AA3
23 HS-0102B-START PUMP START COMMAND BEG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BEG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BEG1-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BEG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BEG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION BEG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BEG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
30 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BEG1-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6006-AA3 5085-COMM-IN-J-1004
31 PI-0101 PRESSURE INDICATOR-MANIFOLD TYPE BEG1-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6010-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BEG1-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BEG1-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BEG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BEG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BEG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BEG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
38 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BEG1-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6007-AA3 5085-COMM-IN-J-1004
39 PI-0102 PRESSURE INDICATOR-MANIFOLD TYPE BEG1-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6011-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BEG1-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BEG1-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BEG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BEG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BEG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BEG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 10"-FW-BEG1-6014-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 10"-FW-BEG1-6014-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 10"-FW-BEG1-6014-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG1-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 8"-FW-BEG1-6024-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 8"-FW-BEG1-6021-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 8"-FW-BEG1-6028-AA3 5085-COMM-IN-J-1003
61 PI-0206 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
62 PI-0207 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 8"-FW-BEG1-6049-AA3 5085-COMM-IN-J-1003
63 PI-0208 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 8"-FW-BEG1-6047-AA3 5085-COMM-IN-J-1003
64 PI-0209 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 8"-FW-BEG1-6025-AA3 5085-COMM-IN-J-1003
65 RO-1004 RESTRICTION ORIFICE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
66 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 5085-COMM-IN-J-1003
67 DPI-1004A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 5085-COMM-IN-J-1004
68 DV-1004A DELUGE VALVE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 5085-COMM-IN-J-1001
69 XSY-1004A SOLENOID VALVE BC-1-E.ST-TK-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
70 PSL-1004 PRESSURE SWITCH BC-1-E.ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
71 PAL-1004 PRESSURE ALARM LOW BC-1-E.ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
72 PSH-1004A PRESSURE SWITCH BC-1-E.ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
73 PAH-1004A PRESSURE ALARM HIGH BC-1-E.ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
74 RO-1004A RESTRICTION ORIFICE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 -
75 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 5085-COMM-IN-J-1003
76 DPI-1004B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 5085-COMM-IN-J-1004
77 DV-1004B DELUGE VALVE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 5085-COMM-IN-J-1001
78 XSY-1004B SOLENOID VALVE BC-1-E.ST-TK-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
79 PSH-1004B PRESSURE SWITCH BC-1-E.ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 5085-COMM-IN-J-1006
80 PAH-1004B PRESSURE ALARM HIGH BC-1-E.ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
81 RO-1004B RESTRICTION ORIFICE BC-1-E.ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 -
82 RO-1002 RESTRICTION ORIFICE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
83 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 5085-COMM-IN-J-1003
84 DPI-1002A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 5085-COMM-IN-J-1004
85 DV-1002A DELUGE VALVE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 5085-COMM-IN-J-1001
86 XSY-1002A SOLENOID VALVE BC-1-E.ST-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
87 PSL-1002 PRESSURE SWITCH BC-1-E.ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
88 PAL-1002 PRESSURE ALARM LOW BC-1-E.ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
89 PSH-1002A PRESSURE SWITCH BC-1-E.ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
90 PAH-1002A PRESSURE ALARM HIGH BC-1-E.ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
91 RO-1002A RESTRICTION ORIFICE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 -
92 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 5085-COMM-IN-J-1003
93 DPI-1002B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 5085-COMM-IN-J-1004
94 DV-1002B DELUGE VALVE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 5085-COMM-IN-J-1001
95 XSY-1002B SOLENOID VALVE BC-1-E.ST-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
96 PSH-1002B PRESSURE SWITCH BC-1-E.ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 5085-COMM-IN-J-1006
97 PAH-1002B PRESSURE ALARM HIGH BC-1-E.ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
98 RO-1002B RESTRICTION ORIFICE BC-1-E.ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 -
99 RO-2001 RESTRICTION ORIFICE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
100 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 5085-COMM-IN-J-1003

SHEET 2 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BECHRAJI GGS - 1
Document Title : INSTRUMENT INDEX
Document No : 5085-BEG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 DPI-2001A DIFFERENTIAL PRESSURE GAUGE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 5085-COMM-IN-J-1004
102 DV-2001A DELUGE VALVE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 5085-COMM-IN-J-1001
103 XSY-2001A SOLENOID VALVE BC-1-TS-TK FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
104 PSL-2001 PRESSURE SWITCH BC-1-TS-TK FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
105 PAL-2001 PRESSURE ALARM LOW BC-1-TS-TK CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
106 PSH-2001A PRESSURE SWITCH BC-1-TS-TK FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
107 PAH-2001A PRESSURE ALARM HIGH BC-1-TS-TK CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
108 RO-2001A RESTRICTION ORIFICE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 -
109 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 5085-COMM-IN-J-1003
110 DPI-2001B DIFFERENTIAL PRESSURE GAUGE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 5085-COMM-IN-J-1004
111 DV-2001B DELUGE VALVE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 5085-COMM-IN-J-1001
112 XSY-2001B SOLENOID VALVE BC-1-TS-TK FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
113 PSH-2001B PRESSURE SWITCH BC-1-TS-TK FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 5085-COMM-IN-J-1006
114 PAH-2001B PRESSURE ALARM HIGH BC-1-TS-TK CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
115 RO-2001B RESTRICTION ORIFICE BC-1-TS-TK FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 -
116 RO-1003 RESTRICTION ORIFICE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
117 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 5085-COMM-IN-J-1003
118 DPI-1003A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 5085-COMM-IN-J-1004
119 DV-1003A DELUGE VALVE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 5085-COMM-IN-J-1001
120 XSY-1003A SOLENOID VALVE BC-1-E.ST-TK-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
121 PSL-1003 PRESSURE SWITCH BC-1-E.ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
122 PAL-1003 PRESSURE ALARM LOW BC-1-E.ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
123 PSH-1003A PRESSURE SWITCH BC-1-E.ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
124 PAH-1003A PRESSURE ALARM HIGH BC-1-E.ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
125 RO-1003A RESTRICTION ORIFICE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 -
126 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 5085-COMM-IN-J-1003
127 DPI-1003B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 5085-COMM-IN-J-1004
128 DV-1003B DELUGE VALVE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 5085-COMM-IN-J-1001
129 XSY-1003B SOLENOID VALVE BC-1-E.ST-TK-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
130 PSH-1003B PRESSURE SWITCH BC-1-E.ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 5085-COMM-IN-J-1006
131 PAH-1003B PRESSURE ALARM HIGH BC-1-E.ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
132 RO-1003B RESTRICTION ORIFICE BC-1-E.ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 -
133 RO-1001 RESTRICTION ORIFICE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
134 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 5085-COMM-IN-J-1003
135 DPI-1001A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 5085-COMM-IN-J-1004
136 DV-1001A DELUGE VALVE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 5085-COMM-IN-J-1001
137 XSY-1001A SOLENOID VALVE BC-1-E.ST-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
138 PSL-1001 PRESSURE SWITCH BC-1-E.ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
139 PAL-1001 PRESSURE ALARM LOW BC-1-E.ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
140 PSH-1001A PRESSURE SWITCH BC-1-E.ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
141 PAH-1001A PRESSURE ALARM HIGH BC-1-E.ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
142 RO-1001A RESTRICTION ORIFICE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 -
143 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 5085-COMM-IN-J-1003
144 DPI-1001B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 5085-COMM-IN-J-1004
145 DV-1001B DELUGE VALVE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 5085-COMM-IN-J-1001
146 XSY-1001B SOLENOID VALVE BC-1-E.ST-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
147 PSH-1001B PRESSURE SWITCH BC-1-E.ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 5085-COMM-IN-J-1006
148 PAH-1001B PRESSURE ALARM HIGH BC-1-E.ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
149 RO-1001B RESTRICTION ORIFICE BC-1-E.ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 -
150 RO-1005 RESTRICTION ORIFICE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
151 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 5085-COMM-IN-J-1003
152 DPI-1005A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 5085-COMM-IN-J-1004
153 DV-1005A DELUGE VALVE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 5085-COMM-IN-J-1001
154 XSY-1005A SOLENOID VALVE BC-1-E.ST-TK-05 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
155 PSL-1005 PRESSURE SWITCH BC-1-E.ST-TK-05 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
156 PAL-1005 PRESSURE ALARM LOW BC-1-E.ST-TK-05 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
157 PSH-1005A PRESSURE SWITCH BC-1-E.ST-TK-05 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
158 PAH-1005A PRESSURE ALARM HIGH BC-1-E.ST-TK-05 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
159 RO-1005A RESTRICTION ORIFICE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 -
160 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 5085-COMM-IN-J-1003
161 DPI-1005B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 5085-COMM-IN-J-1004
162 DV-1005B DELUGE VALVE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 5085-COMM-IN-J-1001
163 XSY-1005B SOLENOID VALVE BC-1-E.ST-TK-05 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
164 PSH-1005B PRESSURE SWITCH BC-1-E.ST-TK-05 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 5085-COMM-IN-J-1006
165 PAH-1005B PRESSURE ALARM HIGH BC-1-E.ST-TK-05 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
166 RO-1005B RESTRICTION ORIFICE BC-1-E.ST-TK-05 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 -
167 RO-1006 RESTRICTION ORIFICE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
168 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 5085-COMM-IN-J-1003
169 DPI-1006A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 5085-COMM-IN-J-1004
170 DV-1006A DELUGE VALVE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 5085-COMM-IN-J-1001
171 XSY-1006A SOLENOID VALVE BC-1-E.ST-TK-06 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
172 PSL-1006 PRESSURE SWITCH BC-1-E.ST-TK-06 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
173 PAL-1006 PRESSURE ALARM LOW BC-1-E.ST-TK-06 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
174 PSH-1006A PRESSURE SWITCH BC-1-E.ST-TK-06 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
175 PAH-1006A PRESSURE ALARM HIGH BC-1-E.ST-TK-06 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
176 RO-1006A RESTRICTION ORIFICE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 -
177 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 5085-COMM-IN-J-1003
178 DPI-1006B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 5085-COMM-IN-J-1004
179 DV-1006B DELUGE VALVE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 5085-COMM-IN-J-1001
180 XSY-1006B SOLENOID VALVE BC-1-E.ST-TK-06 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
181 PSH-1006B PRESSURE SWITCH BC-1-E.ST-TK-06 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 5085-COMM-IN-J-1006
182 PAH-1006B PRESSURE ALARM HIGH BC-1-E.ST-TK-06 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
183 RO-1006B RESTRICTION ORIFICE BC-1-E.ST-TK-06 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 -
184 RO-1007 RESTRICTION ORIFICE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
185 PI-1007A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 5085-COMM-IN-J-1003
186 DPI-1007A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 5085-COMM-IN-J-1004
187 DV-1007A DELUGE VALVE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 5085-COMM-IN-J-1001
188 XSY-1007A SOLENOID VALVE BC-1-E.ST-TK-07 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
189 PSL-1007 PRESSURE SWITCH BC-1-E.ST-TK-07 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
190 PAL-1007 PRESSURE ALARM LOW BC-1-E.ST-TK-07 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
191 PSH-1007A PRESSURE SWITCH BC-1-E.ST-TK-07 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
192 PAH-1007A PRESSURE ALARM HIGH BC-1-E.ST-TK-07 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
193 RO-1007A RESTRICTION ORIFICE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 -
194 PI-1007B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 5085-COMM-IN-J-1003
195 DPI-1007B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 5085-COMM-IN-J-1004
196 DV-1007B DELUGE VALVE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 5085-COMM-IN-J-1001
197 XSY-1007B SOLENOID VALVE BC-1-E.ST-TK-07 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
198 PSH-1007B PRESSURE SWITCH BC-1-E.ST-TK-07 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 5085-COMM-IN-J-1006
199 PAH-1007B PRESSURE ALARM HIGH BC-1-E.ST-TK-07 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
200 RO-1007B RESTRICTION ORIFICE BC-1-E.ST-TK-07 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 -

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BECHRAJI GGS - 1
Document Title : INSTRUMENT INDEX
Document No : 5085-BEG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

201 RO-1008 RESTRICTION ORIFICE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
202 PI-1008A PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 5085-COMM-IN-J-1003
203 DPI-1008A DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 5085-COMM-IN-J-1004
204 DV-1008A DELUGE VALVE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 5085-COMM-IN-J-1001
205 XSY-1008A SOLENOID VALVE BC-1-E.ST-TK-08 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
206 PSL-1008 PRESSURE SWITCH BC-1-E.ST-TK-08 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
207 PAL-1008 PRESSURE ALARM LOW BC-1-E.ST-TK-08 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
208 PSH-1008A PRESSURE SWITCH BC-1-E.ST-TK-08 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
209 PAH-1008A PRESSURE ALARM HIGH BC-1-E.ST-TK-08 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
210 RO-1008A RESTRICTION ORIFICE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 -
211 PI-1008B PRESSURE INDICATOR-MANIFOLD TYPE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 5085-COMM-IN-J-1003
212 DPI-1008B DIFFERENTIAL PRESSURE GAUGE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 5085-COMM-IN-J-1004
213 DV-1008B DELUGE VALVE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 5085-COMM-IN-J-1001
214 XSY-1008B SOLENOID VALVE BC-1-E.ST-TK-08 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
215 PSH-1008B PRESSURE SWITCH BC-1-E.ST-TK-08 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 5085-COMM-IN-J-1006
216 PAH-1008B PRESSURE ALARM HIGH BC-1-E.ST-TK-08 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 - -
217 RO-1008B RESTRICTION ORIFICE BC-1-E.ST-TK-08 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 -
218 RO-1010 RESTRICTION ORIFICE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
219 PI-1010A PRESSURE INDICATOR-MANIFOLD TYPE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 5085-COMM-IN-J-1003
220 DPI-1010A DIFFERENTIAL PRESSURE GAUGE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 5085-COMM-IN-J-1004
221 DV-1010A DELUGE VALVE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 5085-COMM-IN-J-1001
222 XSY-1010A SOLENOID VALVE BE-ETP-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
223 PSL-1010 PRESSURE SWITCH BE-ETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
224 PAL-1010 PRESSURE ALARM LOW BE-ETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
225 PSH-1010A PRESSURE SWITCH BE-ETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
226 PAH-1010A PRESSURE ALARM HIGH BE-ETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
5085-COMM-PR-D-1003
227 RO-1010A RESTRICTION ORIFICE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 -
228 PI-1010B PRESSURE INDICATOR-MANIFOLD TYPE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 5085-COMM-IN-J-1003
229 DPI-1010B DIFFERENTIAL PRESSURE GAUGE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 5085-COMM-IN-J-1004
230 DV-1010B DELUGE VALVE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 5085-COMM-IN-J-1001
231 XSY-1010B SOLENOID VALVE BE-ETP-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
232 PSH-1010B PRESSURE SWITCH BE-ETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 5085-COMM-IN-J-1006
233 PAH-1010B PRESSURE ALARM HIGH BE-ETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
234 RO-1010B RESTRICTION ORIFICE BE-ETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 -
235 RO-1009 RESTRICTION ORIFICE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
236 PI-1009A PRESSURE INDICATOR-MANIFOLD TYPE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 5085-COMM-IN-J-1003
237 DPI-1009A DIFFERENTIAL PRESSURE GAUGE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 5085-COMM-IN-J-1004
238 DV-1009A DELUGE VALVE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 5085-COMM-IN-J-1001
239 XSY-1009A SOLENOID VALVE BE-ETP-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
240 PSL-1009 PRESSURE SWITCH BE-ETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
241 PAL-1009 PRESSURE ALARM LOW BE-ETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
242 PSH-1009A PRESSURE SWITCH BE-ETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
243 PAH-1009A PRESSURE ALARM HIGH BE-ETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
5085-COMM-PR-D-1003
244 RO-1009A RESTRICTION ORIFICE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 -
245 PI-1009B PRESSURE INDICATOR-MANIFOLD TYPE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 5085-COMM-IN-J-1003
246 DPI-1009B DIFFERENTIAL PRESSURE GAUGE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 5085-COMM-IN-J-1004
247 DV-1009B DELUGE VALVE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 5085-COMM-IN-J-1001
248 XSY-1009B SOLENOID VALVE BE-ETP-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
249 PSH-1009B PRESSURE SWITCH BE-ETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 5085-COMM-IN-J-1006
250 PAH-1009B PRESSURE ALARM HIGH BE-ETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 - -
251 RO-1009B RESTRICTION ORIFICE BE-ETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BEG1-IN-K-1002 Page: 2 of 2

BEG-GGS-1
AI DI DO DOP

RTU 2 39 6 26

RTU WITH 30%


3 51 8 34
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BECHRAJI GGS - II
Document Title : INSTRUMENT INDEX
Document No : 5085-BEG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE BEG2-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 3"-FW-BEG2-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE BEG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 2"-FW-BEG2-6010-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6016-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6016-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6016-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE BEG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 2"-FW-BEG2-6019-AA3
13 HS-0102A-START PUMP START COMMAND BEG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND BEG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND BEG2-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION BEG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION BEG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION BEG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION BEG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE BEG2-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 3"-FW-BEG2-6007-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE BEG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 2"-FW-BEG2-6011-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE BEG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 2"-FW-BEG2-6021-AA3
23 HS-0102B-START PUMP START COMMAND BEG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND BEG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND BEG2-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION BEG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION BEG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION BEG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION BEG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE BEG2-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6008-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE BEG2-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6012-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND BEG2-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND BEG2-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION BEG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION BEG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION BEG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION BEG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE BEG2-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6009-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE BEG2-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6013-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND BEG2-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND BEG2-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION BEG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION BEG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION BEG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION BEG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6014-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6014-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6014-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-BEG2-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 8"-FW-BEG2-6037-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 8"-FW-BEG2-6037-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 8"-FW-BEG2-6037-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 8"-FW-BEG2-6037-AA3 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 8"-FW-BEG2-6037-AA3 5085-COMM-IN-J-1003
61 RO-1004 RESTRICTION ORIFICE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
62 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 5085-COMM-IN-J-1003
63 DPI-1004A DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 5085-COMM-IN-J-1004
64 DV-1004A DELUGE VALVE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 5085-COMM-IN-J-1001
65 XSY-1004A SOLENOID VALVE BC-II-E-ST-TK-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
66 PSL-1004 PRESSURE SWITCH BC-II-E-ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
67 PAL-1004 PRESSURE ALARM LOW BC-II-E-ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
68 PSH-1004A PRESSURE SWITCH BC-II-E-ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
69 PAH-1004A PRESSURE ALARM HIGH BC-II-E-ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
70 RO-1004A RESTRICTION ORIFICE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 -
71 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 5085-COMM-IN-J-1003
72 DPI-1004B DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 5085-COMM-IN-J-1004
73 DV-1004B DELUGE VALVE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 5085-COMM-IN-J-1001
74 XSY-1004B SOLENOID VALVE BC-II-E-ST-TK-04 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
75 PSH-1004B PRESSURE SWITCH BC-II-E-ST-TK-04 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 5085-COMM-IN-J-1006
76 PAH-1004B PRESSURE ALARM HIGH BC-II-E-ST-TK-04 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
77 RO-1004B RESTRICTION ORIFICE BC-II-E-ST-TK-04 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 -
78 RO-1002 RESTRICTION ORIFICE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
79 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 5085-COMM-IN-J-1003
80 DPI-1002A DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 5085-COMM-IN-J-1004
81 DV-1002A DELUGE VALVE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 5085-COMM-IN-J-1001
82 XSY-1002A SOLENOID VALVE BC-II-E-ST-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
83 PSL-1002 PRESSURE SWITCH BC-II-E-ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
84 PAL-1002 PRESSURE ALARM LOW BC-II-E-ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
85 PSH-1002A PRESSURE SWITCH BC-II-E-ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
86 PAH-1002A PRESSURE ALARM HIGH BC-II-E-ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
87 RO-1002A RESTRICTION ORIFICE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 -
88 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 5085-COMM-IN-J-1003
89 DPI-1002B DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 5085-COMM-IN-J-1004
90 DV-1002B DELUGE VALVE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 5085-COMM-IN-J-1001
91 XSY-1002B SOLENOID VALVE BC-II-E-ST-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
92 PSH-1002B PRESSURE SWITCH BC-II-E-ST-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 5085-COMM-IN-J-1006
93 PAH-1002B PRESSURE ALARM HIGH BC-II-E-ST-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
94 RO-1002B RESTRICTION ORIFICE BC-II-E-ST-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 -
95 RO-2002 RESTRICTION ORIFICE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
96 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 5085-COMM-IN-J-1003
97 DPI-2002A DIFFERENTIAL PRESSURE GAUGE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 5085-COMM-IN-J-1004
98 DV-2002A DELUGE VALVE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 5085-COMM-IN-J-1001
99 XSY-2002A SOLENOID VALVE BC-II-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
100 PSL-2002 PRESSURE SWITCH BC-II-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006

SHEET 2 OF 3 REFER DELUGE VALVE SCHEMATIC FOR TANKS


Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- BECHRAJI GGS - II
Document Title : INSTRUMENT INDEX
Document No : 5085-BEG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PAL-2002 PRESSURE ALARM LOW BC-II-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
102 PSH-2002A PRESSURE SWITCH BC-II-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
103 PAH-2002A PRESSURE ALARM HIGH BC-II-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
104 RO-2002A RESTRICTION ORIFICE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 -
105 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 5085-COMM-IN-J-1003
106 DPI-2002B DIFFERENTIAL PRESSURE GAUGE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 5085-COMM-IN-J-1004
107 DV-2002B DELUGE VALVE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 5085-COMM-IN-J-1001
108 XSY-2002B SOLENOID VALVE BC-II-TK-02 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
109 PSH-2002B PRESSURE SWITCH BC-II-TK-02 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 5085-COMM-IN-J-1006
110 PAH-2002B PRESSURE ALARM HIGH BC-II-TK-02 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
111 RO-2002B RESTRICTION ORIFICE BC-II-TK-02 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 -
112 RO-1003 RESTRICTION ORIFICE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
113 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 5085-COMM-IN-J-1003
114 DPI-1003A DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 5085-COMM-IN-J-1004
115 DV-1003A DELUGE VALVE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 5085-COMM-IN-J-1001
116 XSY-1003A SOLENOID VALVE BC-II-E-ST-TK-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
117 PSL-1003 PRESSURE SWITCH BC-II-E-ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
118 PAL-1003 PRESSURE ALARM LOW BC-II-E-ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
119 PSH-1003A PRESSURE SWITCH BC-II-E-ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
120 PAH-1003A PRESSURE ALARM HIGH BC-II-E-ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
121 RO-1003A RESTRICTION ORIFICE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 -
122 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 5085-COMM-IN-J-1003
123 DPI-1003B DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 5085-COMM-IN-J-1004
124 DV-1003B DELUGE VALVE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 5085-COMM-IN-J-1001
125 XSY-1003B SOLENOID VALVE BC-II-E-ST-TK-03 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
126 PSH-1003B PRESSURE SWITCH BC-II-E-ST-TK-03 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 5085-COMM-IN-J-1006
127 PAH-1003B PRESSURE ALARM HIGH BC-II-E-ST-TK-03 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
128 RO-1003B RESTRICTION ORIFICE BC-II-E-ST-TK-03 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 -
129 RO-1001 RESTRICTION ORIFICE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
130 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 5085-COMM-IN-J-1003
131 DPI-1001A DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 5085-COMM-IN-J-1004
132 DV-1001A DELUGE VALVE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 5085-COMM-IN-J-1001
133 XSY-1001A SOLENOID VALVE BC-II-E-ST-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
134 PSL-1001 PRESSURE SWITCH BC-II-E-ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
135 PAL-1001 PRESSURE ALARM LOW BC-II-E-ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
136 PSH-1001A PRESSURE SWITCH BC-II-E-ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
137 PAH-1001A PRESSURE ALARM HIGH BC-II-E-ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
138 RO-1001A RESTRICTION ORIFICE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 -
139 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 5085-COMM-IN-J-1003
140 DPI-1001B DIFFERENTIAL PRESSURE GAUGE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 5085-COMM-IN-J-1004
141 DV-1001B DELUGE VALVE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 5085-COMM-IN-J-1001
142 XSY-1001B SOLENOID VALVE BC-II-E-ST-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
143 PSH-1001B PRESSURE SWITCH BC-II-E-ST-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 5085-COMM-IN-J-1006
144 PAH-1001B PRESSURE ALARM HIGH BC-II-E-ST-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
145 RO-1001B RESTRICTION ORIFICE BC-II-E-ST-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 -
146 RO-2001 RESTRICTION ORIFICE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
147 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 5085-COMM-IN-J-1003
148 DPI-2001A DIFFERENTIAL PRESSURE GAUGE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 5085-COMM-IN-J-1004
149 DV-2001A DELUGE VALVE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 5085-COMM-IN-J-1001
150 XSY-2001A SOLENOID VALVE BC-II-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
151 PSL-2001 PRESSURE SWITCH BC-II-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
152 PAL-2001 PRESSURE ALARM LOW BC-II-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
153 PSH-2001A PRESSURE SWITCH BC-II-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
154 PAH-2001A PRESSURE ALARM HIGH BC-II-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
155 RO-2001A RESTRICTION ORIFICE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 -
156 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 5085-COMM-IN-J-1003
157 DPI-2001B DIFFERENTIAL PRESSURE GAUGE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 5085-COMM-IN-J-1004
158 DV-2001B DELUGE VALVE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 5085-COMM-IN-J-1001
159 XSY-2001B SOLENOID VALVE BC-II-TK-01 FIELD RTU DOP FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
160 PSH-2001B PRESSURE SWITCH BC-II-TK-01 FIELD RTU DI FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 5085-COMM-IN-J-1006
161 PAH-2001B PRESSURE ALARM HIGH BC-II-TK-01 CCR - SOFT FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 - -
162 RO-2001B RESTRICTION ORIFICE BC-II-TK-01 FIELD - - FIRE WATER NETWORK 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-BEG2-IN-K-1002 Page: 2 of 2

BEG-GGS-II
AI DI DO DOP

RTU 2 18 6 12

RTU WITH 30%


3 23 8 16
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
TAG NOS / REVISIONS
PAGE NO REMARKS
DESCRIPTION
0 1

1 Cover Sheet X X

2 Revision Sheet X X

3 DV-XXXX X X

4 Schematic X X

5 Annexure-BAG1 X X

6 Annexure-BAG2 X X

7 Annexure-BAG3 X X

8 Annexure-BAG4 X X

9 Annexure-BEG1 X X

10 Annexure-BEG2 X X

11 Annexure-JOG X X

12 Annexure-LAG2 X X

13 Annexure-LAG3 X X

14 Annexure-LGE X X

15 Annexure-NKG1 X X

16 Annexure-NKG2 X X

17 Annexure-NKG3 X X

18 Annexure-NKG4 X X

19 Annexure-SOG1 X X

20 Annexure-SOG2 X X

21 Annexure-SOW X X

22 Annexure-LAG1 X X

Document No:

5085-COMM-IN-J-1001
SHEET : 02 of 22
1 Tag No See Annexures
2 Service Location See Annexures Field
3 P&ID No Equipment/ Line No See Annexures See Annexures
GENERAL
4 Area Classification Certification Zone 2, Gas Gr IIA/IIB, T3 Ex'd, IP65
5 Ambient Temperature Min Max °C -2 50
6 Line Size and Schedule Inlet Outlet See Annexures See Annexures
7 Fluid Fire Water
8 Fluid Type Phase Water Liquid
9 Design Pressure Kg/cm2g Design Temperature °C 18.85 75
10 Flow Min Norm Max m3/hr -- -- Note-3
PROCESS
11 Operating Pressure Kg/cm2g See Annexures
CONDITIONS
12 Operating Temperature °C 25-50
13 Max. Differential Pressure Kg/cm2g 18.5
14 Shut off back pressure Kg/cm2g --
15 Viscosity cP 0.7 - 1.0
16 Valve Type Diaphragm Type
17 Body Size See Annexures (Note-3)
18 End Connections Rating, Finish Flanged 150#
19 Body Material Diaphragm Material Cast Iron or Ductile Iron or Cast Steel Neoprene

VALVE BODY 20 Packing Seals * *


21 Seat Material Stem Material SS316 *
22 Bolt / Nut Material ASTM A 193 GRADE B7, ASTM A 194 GRADE 2H
23 Paint Leakage Class MFR STD CLASS VI, Tight Shut Off
4.5mm thick, SS316L Spiral wound gasket with flexible graphite filler, CS
24 Gasket
center and inner ring to ASME B16.20
25 Actuator Type Diaphragm
26 Actuator Orientation Actuator Material - Cast Iron
27 Ingress Protection Actuator Size IP 65 *
ACTUATOR
28 Operating Meduim Fire Water
29 Fire Water Supply Pressure Kg/cm2g Norm Max 7 12
30 Full Stroke Time <10 Sec
31 Solenoid Valve Supply Reverse acting 2 way type 24 VDC
32 Solenoid Valve Certification Solenoid Valve Material Ex 'd SS316
SOLENOID VALVE
33 Solenoid Valve Pn. Connection Solenoid Valve Elec connection 1/2" NPTM 1/2" NPTF
34 Action on Power Failure Open
35 Air Operated Valve Type 2 Way Spring Return Type Reverse Acting
36 Air Operated Valve Material Supply SS316 1/2" NPTF
AIR OPERATED
37 Air Operated Valve End Connection *
VALVE
38 Action on Air Failure Pneumatic Connection Size Open 1/2" NPTF (*)
2
39 Air Supply Pressure Kg/cm g Min Norm Max 4 6 10.5

AIR FILTER 40 Air Filter Regulator Speed Control * *


REGULATOR 41 Air Consumption *
42 Valve Manufacturer Valve Model * *
43 Actuator Manufacturer Actuator Model * *
PURCHASE 44 Limit Switch Manufacturer Limit Switch Model * *
45 Purchase Order Number *
46 Price Item Number * *

NOTES :
1. '*' - Vendor to Confirm
2. Typical deluge valve setup is shown in general notes sheet.
3. Flow rate and size of deluge valve to be finalised by the engineering contractor.

DATASHEET FOR
DELUGE VALVE
1 AP 28.02.18 Re-issued for Bid
0 AMV 17.08.16 Issued for Bid SHEET 03 OF 22
REV BY DATE DESCRIPTION Doc No: 5085-COMM-IN-J-1001 CODE : 5085 REV. 1
TYPICAL DELUGE VALVE SCHEMATIC

GENERAL NOTES
DELUGE VALVE
1 PA 28.02.2018 Re-issued for Bid
0 AMV 05.10.2016 Issued for Bid SHEET 04 OF 22
REV BY DATE DESCRIPTION 5085-COMM-IN-J-1001 CODE : 5085 REV. 1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 05 OF 22
BALOL GGS-I
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1003A BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 3", Sch 80 3" 11.0

2 DV-1003B BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6028-AM3 3", Sch 80 3" 11.0

3 DV-1002A BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 3", Sch 80 3" 11.0

4 DV-1002B BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6029-AM3 3", Sch 80 3" 11.0

5 DV-1004A BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 3", Sch 80 3" 11.0

6 DV-1004B BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6032-AM3 3", Sch 80 3" 11.0

7 DV-1001A BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 3", Sch 80 3" 11.0

8 DV-1001B BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 3", Sch 80 3" 11.0

9 DV-2002A BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 2", Sch 80 2" 11.0

10 DV-2002B BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 2", Sch 80 2" 11.0

11 DV-2003A BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 2", Sch 80 2" 11.0

12 DV-2003B BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 2", Sch 80 2" 11.0

13 DV-1005A BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 3", Sch 80 3" 11.0

14 DV-1005B BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 3", Sch 80 3" 11.0

15 DV-1006A BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 3", Sch 80 3" 11.0

16 DV-1006B BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 3", Sch 80 3" 11.0

17 DV-2001A BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 2", Sch 80 2" 11.0

18 DV-2001B BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 2", Sch 80 2" 11.0

Notes:

1 All tag numbers shall be prefixed with area code BAG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 06 OF 22
BALOL GGS-II
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1002A BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 3", Sch 80 3" 10.5

2 DV-1002B BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 3", Sch 80 3" 10.5

3 DV-1001A BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 3", Sch 80 3" 10.5

4 DV-1001B BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 3", Sch 80 3" 10.5

5 DV-1004A BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 3", Sch 80 3" 10.5

6 DV-1004B BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 3", Sch 80 3" 10.5

7 DV-1003A BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 3", Sch 80 3" 10.5

8 DV-1003B BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 3", Sch 80 3" 10.5

9 DV-2001A BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 3", Sch 80 3" 10.5

10 DV-2001B BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code BAG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 07 OF 22
BALOL GGS-III
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-2001A T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 2", Sch 80 2" 10.5

2 DV-2001B T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 2", Sch 80 2" 10.5

3 DV-1003A T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 2", Sch 80 2" 10.5

4 DV-1003B T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 2", Sch 80 2" 10.5

5 DV-1004A T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 3", Sch 80 3" 10.5

6 DV-1004B T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 3", Sch 80 3" 10.5

7 DV-1001A T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 3", Sch 80 3" 10.5

8 DV-1001B T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 3", Sch 80 3" 10.5

9 DV-1002A T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 3", Sch 80 3" 10.5

10 DV-1002B T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code BAG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 08 OF 22
BALOL GGS-IV
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 3", Sch 80 3" 10.5

2 DV-1001B BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 3", Sch 80 3" 10.5

3 DV-1002A BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 3", Sch 80 3" 10.5

4 DV-1002B BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 3", Sch 80 3" 10.5

5 DV-2001A BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 2", Sch 80 2" 10.5

6 DV-2001B BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 2", Sch 80 2" 10.5

Notes:

1 All tag numbers shall be prefixed with area code BAG4


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 09 OF 22
BECHRAJI GGS-I
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1004A BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 3", Sch 80 3" 10.5

2 DV-1004B BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 3", Sch 80 3" 10.5

3 DV-1002A BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 3", Sch 80 3" 10.5

4 DV-1002B BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 3", Sch 80 3" 10.5

5 DV-2001A BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 2", Sch 80 2" 10.5

6 DV-2001B BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 2", Sch 80 2" 10.5

7 DV-1003A BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 3", Sch 80 3" 10.5

8 DV-1003B BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 3", Sch 80 3" 10.5

9 DV-1001A BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 3", Sch 80 3" 10.5

10 DV-1001B BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 3", Sch 80 3" 10.5

11 DV-1005A BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 3", Sch 80 3" 10.5

12 DV-1005B BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 3", Sch 80 3" 10.5

13 DV-1006A BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 3", Sch 80 3" 10.5

14 DV-1006B BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 3", Sch 80 3" 10.5

15 DV-1007A BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 3", Sch 80 3" 10.5

16 DV-1007B BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 3", Sch 80 3" 10.5

17 DV-1008A BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 3", Sch 80 3" 10.5

18 DV-1008B BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 3", Sch 80 3" 10.5

19 DV-1010A BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 4", Sch STD 4" 10.5

20 DV-1010B BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 4", Sch STD 4" 10.5

21 DV-1009A BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 4", Sch STD 4" 10.5

22 DV-1009B BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 4", Sch STD 4" 10.5

Notes:

1 All tag numbers shall be prefixed with area code BEG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 10 OF 22
BECHRAJI GGS-II
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1004A BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 3", Sch 80 3" 10.5

2 DV-1004B BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 3", Sch 80 3" 10.5

3 DV-1002A BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 3", Sch 80 3" 10.5

4 DV-1002B BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 3", Sch 80 3" 10.5

5 DV-2002A BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 2", Sch 80 2" 10.5

6 DV-2002B BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 2", Sch 80 2" 10.5

7 DV-1003A BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 3", Sch 80 3" 10.5

8 DV-1003B BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 3", Sch 80 3" 10.5

9 DV-1001A BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 3", Sch 80 3" 10.5

10 DV-1001B BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 3", Sch 80 3" 10.5

11 DV-2001A BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 2", Sch 80 2" 10.5

12 DV-2001B BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 2", Sch 80 2" 10.5

Notes:

1 All tag numbers shall be prefixed with area code BEG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 11 OF 22
JOTANA GGS
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-2001A JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AM3 2", Sch 80 2" 10.5

2 DV-2001B JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AM3 2", Sch 80 2" 10.5

3 DV-2002A JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AM3 2", Sch 80 2" 10.5

4 DV-2002B JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AM3 2", Sch 80 2" 10.5

5 DV-1001A JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AM3 3", Sch 80 3" 10.5

6 DV-1001B JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AM3 3", Sch 80 3" 10.5

7 DV-1002A JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 3", Sch 80 3" 10.5

8 DV-1002B JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 3", Sch 80 3" 10.5

9 DV-1003A JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 3", Sch 80 3" 10.5

10 DV-1003B JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 3", Sch 80 3" 10.5

11 DV-1004A JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 3", Sch 80 3" 10.5

12 DV-1004B JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 3", Sch 80 3" 10.5

13 DV-3001A COMPRESSOR 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 3", Sch 80 3" 10.5

14 DV-3001B COMPRESSOR 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code JOG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 22 OF 22
LANWA GGS-I
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 3", Sch 80 3" 10.5

2 DV-1001B LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 3", Sch 80 3" 10.5

3 DV-1002A LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 3", Sch 80 3" 10.5

4 DV-1002B LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 3", Sch 80 3" 10.5

5 DV-1003A LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 3", Sch 80 3" 10.5

6 DV-1003B LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code LAG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 12 OF 22
LANWA GGS-II
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A LGN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 3", Sch 80 3" 10.5

2 DV-1001B LGN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6038-AM3 3", Sch 80 3" 10.5

3 DV-1002A LGN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 3", Sch 80 3" 10.5

4 DV-1002B LGN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 3", Sch 80 3" 10.5

5 DV-1003A LGN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 3", Sch 80 3" 10.5

6 DV-1003B LGN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6039-AM3 3", Sch 80 3" 10.5

7 DV-1004A LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 3", Sch 80 3" 10.5

8 DV-1004B LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 3", Sch 80 3" 10.5

9 DV-2001A LGN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 3", Sch 80 3" 10.5

10 DV-2001B LGN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code LAG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 13 OF 22
LANWA GGS-III
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 3", Sch 80 3" 11.0

2 DV-1001B LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 3", Sch 80 3" 11.0

3 DV-1002A LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 3", Sch 80 3" 11.0

4 DV-1002B LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 3", Sch 80 3" 11.0

5 DV-1003A LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 3", Sch 80 3" 11.0

6 DV-1003B LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 3", Sch 80 3" 11.0

7 DV-1004A LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 3", Sch 80 3" 11.0

8 DV-1004B LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 3", Sch 80 3" 11.0

9 DV-2001A LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 2", Sch 80 2" 11.0

10 DV-2001B LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 2", Sch 80 2" 11.0

11 DV-2002A LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 2", Sch 80 2" 11.0

12 DV-2002B LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 2", Sch 80 2" 11.0

13 DV-2003A LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 2", Sch 80 2" 11.0

14 DV-2003B LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 2", Sch 80 2" 11.0

Notes:

1 All tag numbers shall be prefixed with area code LAG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 14 OF 22
LANGHNAJ EPS
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

Notes:

1 All tag numbers shall be prefixed with area code LGE


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 15 OF 22
NORTH KADI GGS-I
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 3", Sch 80 3" 10.5

2 DV-1001B NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 3", Sch 80 3" 10.5

3 DV-1002A NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 3", Sch 80 3" 10.5

4 DV-1002B NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 3", Sch 80 3" 10.5

5 DV-1003A NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 3", Sch 80 3" 10.5

6 DV-1003B NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 3", Sch 80 3" 10.5

7 DV-1004A NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 3", Sch 80 3" 10.5

8 DV-1004B NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 3", Sch 80 3" 10.5

9 DV-2001A NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 2", Sch 80 2" 10.5

10 DV-2001B NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 2", Sch 80 2" 10.5

11 DV-2002A NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 2", Sch 80 2" 10.5

12 DV-2002B NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 2", Sch 80 2" 10.5

13 DV-2003A NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 2", Sch 80 2" 10.5

14 DV-2003B NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 2", Sch 80 2" 10.5

15 DV-1005A NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 3", Sch 80 3" 10.5

16 DV-1005B NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 3", Sch 80 3" 10.5

17 DV-1006A NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 3", Sch 80 3" 10.5

18 DV-1006B NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code NKG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 16 OF 22
NORTH KADI GGS-II
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 3", Sch 80 3" 10.5

2 DV-1001B NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 3", Sch 80 3" 10.5

3 DV-1002A NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 3", Sch 80 3" 10.5

4 DV-1002B NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 3", Sch 80 3" 10.5

5 DV-1003A NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 3", Sch 80 3" 10.5

6 DV-1003B NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 3", Sch 80 3" 10.5

7 DV-1004A NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 3", Sch 80 3" 10.5

8 DV-1004B NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 3", Sch 80 3" 10.5

9 DV-1005A NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 3", Sch 80 3" 10.5

10 DV-1005B NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 3", Sch 80 3" 10.5

11 DV-1006A NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 3", Sch 80 3" 10.5

12 DV-1006B NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 3", Sch 80 3" 10.5

13 DV-2001A NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 2", Sch 80 2" 10.5

14 DV-2001B NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 2", Sch 80 2" 10.5

15 DV-2002A NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 2", Sch 80 2" 10.5

16 DV-2002B NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 2", Sch 80 2" 10.5

17 DV-2003A NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 3", Sch 80 3" 10.5

18 DV-2003B NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code NKG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 17 OF 22
NORTH KADI GGS-III
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 3", Sch 80 3" 10.5

2 DV-1001B NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 3", Sch 80 3" 10.5

3 DV-1002A NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 3", Sch 80 3" 10.5

4 DV-1002B NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 3", Sch 80 3" 10.5

5 DV-1003A NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 3", Sch 80 3" 10.5

6 DV-1003B NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 3", Sch 80 3" 10.5

7 DV-1004A NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 3", Sch 80 3" 10.5

8 DV-1004B NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 3", Sch 80 3" 10.5

9 DV-2001A NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 2", Sch 80 2" 10.5

10 DV-2001B NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 2", Sch 80 2" 10.5

11 DV-2002A NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 2", Sch 80 2" 10.5

12 DV-2002B NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 2", Sch 80 2" 10.5

13 DV-2003A NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 2", Sch 80 2" 10.5

14 DV-2003B NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 2", Sch 80 2" 10.5

15 DV-2004A NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6036-AM3 3", Sch 80 3" 10.5

16 DV-2004B NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 3", Sch 80 3" 10.5

17 DV-1005A NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 3", Sch 80 3" 10.5

18 DV-1005B NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 3", Sch 80 3" 10.5

19 DV-1006A NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 3", Sch 80 3" 10.5

20 DV-1006B NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code NKG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 18 OF 22
NORTH KADI GGS-IV
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-3001A LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 4", Sch STD 4" 10.5

2 DV-3001B LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 4", Sch STD 4" 10.5

3 DV-1001A 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6031-AM3 3", Sch 80 3" 10.5

4 DV-1001B 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 3", Sch 80 3" 10.5

5 DV-1002A 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 3", Sch 80 3" 10.5

6 DV-1002B 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 3", Sch 80 3" 10.5

7 DV-1003A 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 3", Sch 80 3" 10.5

8 DV-1003B 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 3", Sch 80 3" 10.5

9 DV-1004A 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 3", Sch 80 3" 10.5

10 DV-1004B 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 3", Sch 80 3" 10.5

11 DV-2001A 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 3", Sch 80 3" 10.5

12 DV-2001B 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 3", Sch 80 3" 10.5

13 DV-2002A 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 3", Sch 80 3" 10.5

14 DV-2002B 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 3", Sch 80 3" 10.5

15 DV-2003A 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 3", Sch 80 3" 10.5

16 DV-2003B 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 3", Sch 80 3" 10.5

17 DV-1005A 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 3", Sch 80 3" 10.5

18 DV-1005B 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 3", Sch 80 3" 10.5

19 DV-1006A 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 3", Sch 80 3" 10.5

20 DV-1006B 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code NKG4


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 19 OF 22
SOBHASAN GGS-I
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6029-AM3 3", Sch 80 3" 10.5

2 DV-1001B SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 3", Sch 80 3" 10.5

3 DV-1002A SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 3", Sch 80 3" 10.5

4 DV-1002B SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 3", Sch 80 3" 10.5

5 DV-1003A SOB1-ST-01/02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 3", Sch 80 3" 10.5

6 DV-1003B SOB1-ST-01/02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 3", Sch 80 3" 10.5

7 DV-2001A SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6035-AM3 3", Sch 80 3" 10.5

8 DV-2001B SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6027-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code SOG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 20 OF 22
SOBHASAN GGS-II
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 2", Sch 80 2" 10.5

2 DV-1001B SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 2", Sch 80 2" 10.5

3 DV-1008A SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 2", Sch 80 2" 10.5

4 DV-1008B SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 2", Sch 80 2" 10.5

5 DV-2002A SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 3", Sch 80 3" 10.5

6 DV-2002B SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 3", Sch 80 3" 10.5

7 DV-2001A SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 3", Sch 80 3" 10.5

8 DV-2001B SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 3", Sch 80 3" 10.5

9 DV-1009A SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 3", Sch 80 3" 10.5

10 DV-1009B SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 3", Sch 80 3" 10.5

11 DV-1005A SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 3", Sch 80 3" 10.5

12 DV-1005B SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 3", Sch 80 3" 10.5

13 DV-1007A SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 3", Sch 80 3" 10.5

14 DV-1007B SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 3", Sch 80 3" 10.5

15 DV-1002A SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 3", Sch 80 3" 10.5

16 DV-1002B SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 3", Sch 80 3" 10.5

17 DV-1003A SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 3", Sch 80 3" 10.5

18 DV-1003B SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 3", Sch 80 3" 10.5

19 DV-1004A SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 3", Sch 80 3" 10.5

20 DV-1004B SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 3", Sch 80 3" 10.5

21 DV-1006A SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 3", Sch 80 3" 10.5

22 DV-1006B SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code SOG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 21 OF 22
SOBHASAN WWTP
DOC.NO : 5085-COMM-IN-J-1001

Operating
S.No Tag Number Service PID Number Equipment / Line Number Line Size and Schedule Body Size Pressure Remarks
kg/cm2

1 DV-1001A SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 3", Sch 80 3" 10.5

2 DV-1001B SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 3", Sch 80 3" 10.5

3 DV-1002A SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 3", Sch 80 3" 10.5

4 DV-1002B SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 3", Sch 80 3" 10.5

9 DV-1003A SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6050-AM3 4", Sch STD 4" 10.5

10 DV-1003B SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6053-AM3 4", Sch STD 4" 10.5

11 DV-1004A SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6037-AM3 3", Sch 80 3" 10.5

12 DV-1004B SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6038-AM3 3", Sch 80 3" 10.5

Notes:

1 All tag numbers shall be prefixed with area code SOW


REVISIONS
TAG NOS /
PAGE NO REMARKS
DESCRIPTION
0 1

1 Cover Sheet X X

2 Revision Sheet X X

3 PIT- XXXX X X

4 General Notes X X

5 Annexure-BAG1 X X

6 Annexure-BAG2 X X

7 Annexure-BAG3 X X

8 Annexure-BAG4 X X

9 Annexure-BEG1 X X

10 Annexure-BEG2 X X

11 Annexure-JOG X X

12 Annexure-LAG2 X X

13 Annexure-LAG3 X X

14 Annexure-LGE X X

15 Annexure-NKG1 X X

16 Annexure-NKG2 X X

17 Annexure-NKG3 X X

18 Annexure-NKG4 X X

19 Annexure-SOG1 X X

20 Annexure-SOG2 X X

21 Annexure-SOW X X

22 Annexure-LAG1 X X

Document No:

5085-COMM-IN-J-1002
SHEET : 02 OF 22
1 Tag Number See Annexure-1
2 Service See Annexure-1
3 Location Field
4 Equipment / Line Number See Annexure-1
GENERAL
5 P&ID Number See Annexure-1
6 Ambient Temperature Min Max °C -2 50
7 Ingress Protection Area Classification IP 65 Zone 2, Gas Group IIA/IIB, T3
8 Certification Ex'i
9 Fluid Fluid State See Annexure-1 See Annexure-1
10 Design Pressure Kg/cm2 g Design Temperature °C See Annexure-1 See Annexure-1
PROCESS
11 Operating Pressure Kg/cm2 g See Annexure-1
CONDITION
12 Operating Temperature °C See Annexure-1
13 Oper. Spec. Gravity Oper. Viscosity cP See Annexure-1 See Annexure-1
14 Type of Transmitter Electronic - Smart Type Pressure Transmitter with Manifold
15 Type of Communication 4-20mA, Analog, 2 Wire, HART
16 Instrument Range Min. Max Kg/cm2 g * *
17 Calibration Range Min. Max Kg/cm2 g 0 15
18 Elevation Suppresion NA NA
19 Element Type Element Material Diaphragm SS316
20 Body Material Body Rating SS316 150#
TRANSMITTER
21 Electronic Housing Material Wetted o-rings Material MFR Std MFR Std
22 Bolts Paint Carbon Steel MFR Std
23 Process Connection Electrical Connection ½” NPT ½” NPTF
24 Power Supply Load driving capacity 24 VDC (+/-10%) 600 ohm @ 24 VDC
25 Repeatability Output Signal ± 0.05 % 4-20mA Loop Powered+HART
26 Accuracy Response Time ± 0.05 % 100 ms
27 Mounting Mounting Accessories Direct Required
28 Process Connection & Rating NA
29 Diaphragm Material Flange Material NA NA
30 Housing Material NA
DIAPHRAGM SEAL 31 Fill Fluid NA
32 Capillary Material NA
33 Capillary Type Capillary Length NA NA
34 Flushing Connection NA
35 Manifold Type 2 Valve (Isolation & Vent), 1/2" NPTM x 1/2" NPTF
36 Material of Manifold SS316
37 Maximum Pressure Rating *
MANIFOLD 38 Process Connection Size & Rating 1/2" NPTF --
39 Vent / Drain connection Size and Type 1/4" NPT
40 Manifold Mounting -
41 Manufacturer Model * *
42 Communication Type HART Communication (with 4-20mA)
COMMUNICATION & 43 Baud-Rate *
SOFTWARE 44 Communication With: Internal Diagnostics -- Yes
45 Hand Held Terminal No
46 Integral Meter Scale Required, LCD Display Kg/cm2 g
47 Hydrostatic Testing Yes
OPTIONS 48 Tag plate SS 316
49 Over range Protection Required
50 Mounting Brackets Material Required Carbon steel
51 Manufacturer *
52 Model *
PURCHASE 53 Purchase order Number *
54 Price *
55 Serial Number Item Number * *

NOTES:
1. * - VENDOR to specify / furnish
2. Transmitter shall be DGMS certified.
3. Transmitter tag numbers shall be prefixed with the area code of the installation

DATASHEET
FOR
PRESSURE TRANSMITTTER-MANIFOLD
1 AP 28.02.18 Re-issued For Bid TYPE
0 AMV 13.10.16 Issued For Bid SHEET : 03 OF 22
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1002 CODE : 5085 REV.1
GENERAL NOTES - PRESSURE TRANSMITTER

1) Pressure elements must be able to withstand over range pressure equivalent to 130% of maximum span.
2) Transmitters exposed to vacuum shall have under range protection to full vacuum.
3) The range shall be as specified in the datasheets and errors are expressed as a percentage of the calibrated span, unless otherwise stated.
The transmitter accuracy including the combined effects of linearity, hysteresis and repeatability will be equal to or better than ± 0.05% of
calibrated span or better , temperature effects at calibrated span per 50 Deg C.
4) VENDOR shall furnish tagging for Field instruments as per the datasheets. Tagging shall be via nameplates that are mounted on the unit
with 316 SS hardware. Adhesives shall not be used. The above information is in addition to manufacturer's standard tagging information,
such as model number and serial number.
5) VENDOR shall prepare Inspection and Test Plan and submit for approval by COMPANY / Detailed, component wise Inspection and testing
activities by the VENDOR, INSPECTOR and verification/ witness activities by the COMPANY shall be specified, identified and controlled
by a VENDOR’s Inspection and Test Plan.
6) All Tag names starting with PSIT shall be SIL-2 certified

INSPECTION

7) Inspection shall be carried out for the following, as a minimum:


(i) Visual examination and dimensional check;
(ii) Verification of testing as mentioned under factory testing;
(iii) Verification of material certificates;
(iv) Verification of Electrical compliance certificates & IP rating certification
(v) Calibration.

DOCUMENT

8) The Manufacturer shall submit the following certificates in accordance with EN 10204 3.1B:
(i) Mill test certificates relevant to the chemical analysis and mechanical properties of the materials used for the transmitter construction
as per the relevant standards, as applicable.
(ii) Report on heat treatment carried out, as applicable.
(iii) Test certificates for hydrostatic complete with duration and pressure records of each test.
(iv) Test reports of radiography, ultrasonic & MPI inspection
(v) Electrical area classification
(vi) Ingress protection rating compliance certificates.
(vii) Calibration certificate.
(viii) Data sheets.
(ix) Installation, operation and maintenance manual.

DATASHEET
FOR
1 AP 28.02.18 Re-issued For Bid PRESSURE TRANSMITTTER

0 AMV 13.10.16 Issued For Bid SHEET : 04 OF 22


REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1002 CODE : 5085 REV. 1
ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 05 OF 22
BALOL GGS-I
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 10"-FW-BAG1-6015-AA3 5085-BAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 10"-FW-BAG1-6015-AA3 5085-BAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 10"-FW-BAG1-6015-AA3 5085-BAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BAG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 06 OF 22
BALOL GGS-II
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-BAG2-6015-AA3 5085-BAG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-BAG2-6015-AA3 5085-BAG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-BAG2-6015-AA3 5085-BAG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BAG2


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 07 OF 22
BALOL GGS-III
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-BAG3-6014-AA3 5085-BAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-BAG3-6014-AA3 5085-BAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-BAG3-6014-AA3 5085-BAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BAG3


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 08 OF 22
BALOL GGS-IV
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-BAG4-6015-AA3 5085-BAG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-BAG4-6015-AA3 5085-BAG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-BAG4-6015-AA3 5085-BAG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BAG4


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 09 OF 22
BECHRAJI GGS-I
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 10"-FW-BEG1-6014-AA3 5085-BEG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 10"-FW-BEG1-6014-AA3 5085-BEG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 10"-FW-BEG1-6014-AA3 5085-BEG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BEG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 10 OF 22
BECHRAJI GGS-II
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-BEG2-6014-AA3 5085-BEG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-BEG2-6014-AA3 5085-BEG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-BEG2-6014-AA3 5085-BEG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code BEG2


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 11 OF 22
JOTANA GGS
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-JOG-6016-AA3 5085-JOG-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-JOG-6016-AA3 5085-JOG-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-JOG-6016-AA3 5085-JOG-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code JOG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 22 OF 22
LANWA GGS-I
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-LAG1-6018-AA3 5085-LAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-LAG1-6018-AA3 5085-LAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-LAG1-6018-AA3 5085-LAG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code LAG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 12 OF 22
LANWA GGS-II
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-LAG2-6018-AA3 5085-LAG2-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-LAG2-6018-AA3 5085-LAG2-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-LAG2-6018-AA3 5085-LAG2-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code LAG2


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 13 OF 22
LANWA GGS-III
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-LAG3-6014-AA3 5085-LAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-LAG3-6014-AA3 5085-LAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-LAG3-6014-AA3 5085-LAG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code LAG3


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 14 OF 22
LANGHNAJ EPS
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-LGE-6015-AA3 5085-LGE-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-LGE-6015-AA3 5085-LGE-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-LGE-6015-AA3 5085-LGE-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code LGE


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 15 OF 22
NORTH KADI GGS-I
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-NKG1-6012-AA3 5085-NKG1-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-NKG1-6012-AA3 5085-NKG1-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-NKG1-6012-AA3 5085-NKG1-PR-D-1001-01 Water/Liquid 18.85 75 12.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code NKG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 16 OF 22
NORTH KADI GGS-II
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER - 5085-NKG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER - 5085-NKG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER - 5085-NKG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code NKG2


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 17 OF 22
NORTH KADI GGS-III
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-NKG3-6023-AA3 5085-NKG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-NKG3-6023-AA3 5085-NKG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-NKG3-6023-AA3 5085-NKG3-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code NKG3


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 18 OF 22
NORTH KADI GGS-IV
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 10"-FW-NKG4-6020-AA3 5085-NKG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 10"-FW-NKG4-6020-AA3 5085-NKG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 10"-FW-NKG4-6020-AA3 5085-NKG4-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code NKG4


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 19 OF 22
SOBHASAN GGS-I
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-SOG1-6017-AA3 5085-SOG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-SOG1-6017-AA3 5085-SOG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-SOG1-6017-AA3 5085-SOG1-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code SOG1


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 20 OF 22
SOBHASAN GGS-II
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER 8"-FW-SOG2-6003-AA3 5085-SOG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER 8"-FW-SOG2-6003-AA3 5085-SOG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER 8"-FW-SOG2-6003-AA3 5085-SOG2-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code SOG2


ANNEXURE
FIRE FIGHTING SYSTEM UPGRADATION OF 17 INSTALLATIONS AT MEHSANA ASSET
SHEET 21 OF 22
SOBHASAN WWTP
DOC.NO 5085-COMM-IN-J-1002

Process Condition

S.No Tag Number Service Equipment / Line Number PID Number Operating Remarks
Design Pressure Design Temp Operating Temp Oper. Spec. Oper.
Fluid/Fluid state Pressure
Kg/cm2g °C °C Gravity Viscosity
Kg/cm2g
1 PIT-0110 PUMP DISCHARGE HEADER - 5085-SOW-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

2 PIT-0111 PUMP DISCHARGE HEADER - 5085-SOW-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

3 PIT-0112 PUMP DISCHARGE HEADER - 5085-SOW-PR-D-1001-01 Water/Liquid 18.85 75 10.5 25-50 0.9-1 0.5-1

Notes:

1 All instruments shall be prefixed by area code SOW


TAG NO / REVISIONS
PAGE NO REMARKS
DESCRIPTIION 0 1

1 Cover Sheet X X
2 Revision Sheet X X
3 PI-XXXX X X
4 General Notes X X
5 Annexure X X
6 Annexure X X

Document No:

5085-COMM-IN-J-1003
Sheet: 02 of 06
1 Tag Number PI-XXXX
2 Service Refer P&ID
3 Location Field
GENERAL 4 Equipment / Line Number Refer P&ID
5 P&ID Number See Annexure-1
6 Ambient Temperature Min Max °C -2 50
7 Ingress Protection IP 65
8 Fluid Fluid State Water Liquid
9 Design Pressure Kg/cm2 g Design Temperature °C 18.85 75
PROCESS CONDITION
10 Operating Pressure Kg/cm2 g 10.5-12.5
11 Operating Temperature °C 25-50
12 Type Pressure Gauge - Manifold Type
13 Calibration Range Min Max. Kg/cm2 g See Annexure-1
kPag See Annexure-1
14 Figure Interval As per EN 837
15 Minor Graduation As per EN 837
16 Mounting Direct Mounted
17 Dial Size Dial Color 150mm White with Black Lettering
18 Scale Unit Kg/cm2 g
19 Case Material SS316
20 Ring Construction Ring Material Bayonet SS316
21 Blow-Out Protection Yes
GAUGE
22 Lens Material Shatter- Proof Front Glass
23 Pressure Element Type Pressure Element Material Bourdon Type SS316
24 Socket Material SS 316
25 Connection Size 1/2" NPT(M)
26 Connection Location Bottom
27 Movement Material SS 316
28 Nominal Accuracy ± 1% of Full Scale Division (Min.)
29 NACE MR0175 Compliance No
30 Solid Front --
31 Zero Set Required (Micrometer Pointer - External)
32 Type NA
33 Process Connection Size & Rating NA
34 Diaphragm Material NA
35 Bottom Housing Material NA
DIAPHRAGM SEAL
36 Fill Fluid NA
37 Flushing Connection (Drip ring) NA
38 Top Housing Material NA
39 Connection to Instrument NA
40 Manifold Type 2 Valve (Isolation & Vent), 1/2" NPTM x 1/2" NPTF
41 Material of Manifold SS316
42 Maximum Pressure Rating *
MANIFOLD 43 Process Connection Size & Rating 1/2" NPTF --
44 Vent / Drain connection Size and Type 1/4" NPT
45 Manifold Mounting -
46 Manufacturer Model * *
47 Syphon: Type Snubber: Type No No
48 Over range Protection 130% of Full Scale Deflection without accuracy loss
OPTIONS 49 Movement Damping *
50 Gauge Protector *
51 Tag Plate SS316
52 Manufacturer *
53 Model *
PURCHASE 54 Purchase order Number *
55 Price *
56 Serial Number Item Number * *

NOTES:
1. * - VENDOR to specify / furnish

DATASHEET
FOR
1 AP 28.02.18 Re-issued for Bid PRESSURE GAUGE-MANIFOLD TYPE

0 AMV 10/06/16 Issued for Bid SHEET : 03 OF 06


REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1003 CODE : 5085 REV.1
GENERAL NOTES - PRESSURE INDICATORS

1) Pressure elements must be able to withstand over range pressure equivalent to 130% of maximum span.
2) Gauges exposed to vacuum shall have under range protection to full vacuum.
3) VENDOR shall furnish tagging for Field instruments as per the datasheets. Tagging shall be via nameplates that are mounted on the
unit with 316 SS hardware. Adhesives shall not be used. The above information is in addition to manufacturer's standard tagging
information, such as model number and serial number.

INSPECTION

4) Inspection shall be carried out for the following, as a minimum:


(i) Visual examination and dimensional check
(ii) Verification of testing as mentioned under factory testing
(iii) Verification of material certificates
(iv) Verification of IP rating certification
(v) Calibration

DOCUMENTS

5) The Manufacturer shall submit the following certificates in accordance with EN 10204 3.1B:
(i) Mill test certificates relevant to the chemical analysis and mechanical properties of the materials used for the gauges/seal
construction as per the relevant standards, as applicable
(ii) Report on heat treatment carried out, as applicable
(iii) Test certificates for hydrostatic complete with duration and pressure records of each test
(iv) Test reports of radiography, ultrasonic & MPI inspection
(v) Ingress protection rating compliance certificates
(vi) Calibration certificate
(vii) Data sheets
(viii) Installation, operation and maintenance manual
(ix) Certified general arrangement

GENERAL NOTES
FOR
1 AP 28.02.18 Re-issued for Bid PRESSURE GAUGE

0 AMV 10/06/16 Issued for Bid SHEET : 04 OF 06


REV BY DATE DESCRIPTION DOC.NO : 5085-COMM-IN-J-1003 CODE: 5085 REV.1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET SHEET 05 OF 06

DOC.NO : 5085-COMM-IN-J-1003

Calibration Range
S.No Area Code Installation Name PID Number Quantity Min Max Remarks
kg/cm2g kg/cm2g

5085-BAG1-PR-D-1001-01 5 0 25
1 BAG1 Balol GGS-I
5085-BAG1-PR-D-1002-01/02 23 0 18
5085-BAG2-PR-D-1001-01 5 0 25
2 BAG2 Balol GGS-II
5085-BAG2-PR-D-1002-01 14 0 18
5085-BAG3-PR-D-1001-01 5 0 25
3 BAG3 Balol GGS-III
5085-BAG3-PR-D-1002-01 13 0 18
5085-BAG4-PR-D-1001-01 5 0 25
4 BAG4 Balol GGS-IV
5085-BAG4-PR-D-1002-01 10 0 18
5085-BEG1-PR-D-1001-01 5 0 25
5 BEG1 Bechraji GGS-I
5085-BEG1-PR-D-1002-01/02 35 0 18
5085-BEG2-PR-D-1001-01 5 0 25
6 BEG2 Bechraji GGS-II
5085-BEG2-PR-D-1002-01 13 0 18
5085-JOG-PR-D-1001-01 5 0 25
7 JOG1 Jotana GGS
5085-JOG-PR-D-1002-01 21 0 18
5085-LAG2-PR-D-1001-01 5 0 25
8 LAG2 Lanwa GGS-II
5085-LAG2-PR-D-1002-01 13 0 18
5085-LAG3-PR-D-1001-01 5 0 25
9 LAG3 Lanwa GGS-III
5085-LAG3-PR-D-1002-01 17 0 18
5085-LGE-PR-D-1001-01 5 0 25
10 LGE Langhnaj EPS
5085-LGE-PR-D-1002-01 4 0 18
5085-NKG1-PR-D-1001-01 5 0 25
11 NKG1 North Kadi GGS-I
5085-NKG1-PR-D-1002-01/02 23 0 18
5085-NKG2-PR-D-1001-01 5 0 25
12 NKG2 North Kadi GGS-II
5085-NKG2-PR-D-1002-01/02 23 0 18
5085-NKG3-PR-D-1001-01 5 0 25
13 NKG3 North Kadi GGS-III
5085-NKG3-PR-D-1002-01/02 25 0 18
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET SHEET 06 OF 06

DOC.NO : 5085-COMM-IN-J-1003

Calibration Range
S.No Area Code Installation Name PID Number Quantity Min Max Remarks
kg/cm2g kg/cm2g

5085-NKG4-PR-D-1001-01 5 0 25
14 NKG4 North Kadi GGS-IV
5085-NKG4-PR-D-1002-01/02 27 0 18
5085-SOG1-PR-D-1001-01 5 0 25
15 SOG1 Sobhasan GGS-I
5085-SOG1-PR-D-1002-01 11 0 18
5085-SOG2-PR-D-1001-01 5 0 25
16 SOG2 Sobhasan GGS-II
5085-SOG2-PR-D-1002-01/02 27 0 18
5085-SOW-PR-D-1001-01 5 0 25
17 SOW Sobhasan WWTP
5085-SOW-PR-D-1002-01/02 16 0 18
5085-LAG1-PR-D-1001-01 5 0 25
18 LAG1 Lanwa GGS-I
5085-LAG1-PR-D-1001-01 9 0 18

Notes:
1 All tag numbers shall be provided as per P&ID
2 All tag numbers shall be prefixed by area code
TAG NO / REVISIONS
PAGE NO REMARKS
DESCRIPTIION 0 1

1 Cover Sheet X X
2 Revision Sheet X X
3 DPI-XXXX X X
4 General Notes X X
5 Annexure - BAG1 X X
6 Annexure - BAG2 X X
7 Annexure - BAG3 X X
8 Annexure - BAG4 X X
9 Annexure - BEG1 X X
10 Annexure - BEG2 X X
11 Annexure - JOG X X
12 Annexure - LAG2 X X
13 Annexure - LAG3 X X
14 Annexure - LGE X X
15 Annexure - NKG1 X X
16 Annexure - NKG2 X X
17 Annexure - NKG3 X X
18 Annexure - NKG4 X X
19 Annexure - SOG1 X X
20 Annexure - SOG2 X X
21 Annexure - SOW X X
22 Annexure - LAG1 X X

Document No:

5085-COMM-IN-J-1004
Sheet: 02 of 22
1 Tag Number See Annexure-1
2 Service See Annexure-1
3 Location Field
GENERAL 4 Equipment / Line Number See Annexure-1
5 P&ID Number See Annexure-1
6 Ambient Temperature Min Max °C -2 50
7 Ingress Protection IP 65
8 Fluid Fluid State Water Liquid
9 Design Pressure Kg/cm2 g Design Temperature °C 18.85 75
PROCESS CONDITION 10 Operating Pressure Kg/cm2 g See Annexure-1
11 Operating Temperature °C 25 - 50
12 Differential Pressure Maximum mmWC 1100
13 Type Differential Pressure Gauge
14 Calibration Range mmWC 2500
15 Figure Interval *
16 Minor Graduation *
17 Mounting 2" Pipe Stanchion, 316SS mounting hardware to be included
18 Dial Size Dial Background color 150mm White with Black Lettering
19 Scale Unit mmWC
20 Case Material SS316
21 Ring construction Ring Material Bayonet SS316
22 Blow-Out Protection Yes
GAUGE
23 Lens Material Shatter - Proof Front Glass
24 Pressure Element Type Diaphragm Type
25 Pressure Element Material SS316
26 Socket Material --
27 Gauge Connection Size 1/2" NPT(M)
28 Connection Location *
29 Movement Material SS316
30 Nominal Accuracy ±2% Full Scale (Minimum)
31 NACE MR0175 Compliance --
32 Zero Adjustment Required (Micrometer Pointer-External)
33 Type NA
34 Process Connection Size & Rating NA
35 Diaphragm Material NA
36 Bottom Housing Material NA
DIAPHRAGM SEAL
37 Fill Fluid NA
38 Flushing Connection (Drip ring) NA
39 Top Housing Material NA
40 Connection to Instrument NA
41 Manifold Type 5 Valve (Isolation & Vent), 1/2" NPTM x 1/2" NPTF
42 Material of Manifold SS316
43 Maximum Pressure Rating *
MANIFOLD 44 Process Connection Size & Rating 1/2" NPTF *
45 Vent / Drain connection Size and Type 1/4" NPT
46 Manifold Mounting -
47 Manufacturer Model * *
48 Syphon: Type Snubber: Type No No
49 Over range Protection 130% of Full Scale Deflection without accuracy loss
OPTIONS 50 Movement Damping *
51 Gauge Protector --
52 Tag Plate SS316
53 Manufacturer *
54 Model *
PURCHASE 55 Purchase order Number *
56 Price *
57 Serial Number Item Number * *

NOTES:
1. * - VENDOR to specify / furnish

DATASHEET
FOR
DIFFERENTIAL PRESSURE GAUGE-
1 AP 28.02.18 Re-issued for Bid MANIFOLD TYPE
0 AMV 06.10.16 Issued for Bid SHEET : 03 OF 22
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1004 CODE : 5085 REV. 1
GENERAL NOTES - DIFFERENTIAL PRESSURE INDICATOR

1) VENDOR shall furnish tagging for Field instruments as per the datasheets. Tagging shall be via nameplates that are mounted on the unit with
316 SS hardware. Adhesives shall not be used. The above information is in addition to manufacturer's standard tagging information, such as model
number and serial number.
2) Each side of the DP Indicator should be able to take complete static pressure

INSPECTION

3) Inspection shall be carried out for the following, as a minimum:


(i) Visual examination and dimensional check
(ii) Verification of testing as mentioned under factory testing
(iii) Verification of material certificates
(iv) Verification of IP rating certification
(v) Calibration

DOCUMENTS

4) The Manufacturer shall submit the following certificates in accordance with EN 10204 3.1B:

(i) Mill test certificates relevant to the chemical analysis and mechanical properties of the materials used for the gauges/seal construction as per
the relevant standards, as applicable
(ii) Report on heat treatment carried out, as applicable
(iii) Test certificates for hydrostatic complete with duration and pressure records of each test
(iv) Ingress protection rating compliance certificates
(v) Calibration certificate
(vi) Data sheets
(vii) Installation, operation and maintenance manual
(viii) Certified general arrangement

DATASHEET
FOR
1 AP 28.02.18 Re-issued for Bid DIFFERENTIAL PRESSURE GAUGE
0 AMV 06.10.16 Issued for Bid SHEET : 04 OF 22
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1004 CODE : 5085 REV. 1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 05 OF 22
BALOL GGS - I
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 BAG1-P-102A PUMP SUCTION 5085-BAG1-PR-D-1001-01 3"-FW-BAG1-6007-AA3 0.1


2 DPI-0102 BAG1-P-102B PUMP SUCTION 5085-BAG1-PR-D-1001-01 3"-FW-BAG1-6008-AA3 0.1
3 DPI-0103 BAG1-P-101A PUMP SUCTION 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6009-AA3 0.1
4 DPI-0104 BAG1-P-101B PUMP SUCTION 5085-BAG1-PR-D-1001-01 8"-FW-BAG1-6010-AA3 0.1
5 DPI-1003A BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 8.0
6 DPI-1003B BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6028-AM3 8.0
7 DPI-1002A BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 8.0
8 DPI-1002B BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6029-AM3 8.0
9 DPI-1004A BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 8.0
10 DPI-1004B BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6032-AM3 8.0
11 DPI-1001A BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 8.0
12 DPI-1001B BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 8.0
13 DPI-2002A BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 8.0
14 DPI-2002B BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 8.0
15 DPI-2003A BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 8.0
16 DPI-2003B BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 8.0
17 DPI-1005A BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 8.0
18 DPI-1005B BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 8.0
19 DPI-1006A BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 8.0
20 DPI-1006B BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 8.0
21 DPI-2001A BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 8.0
22 DPI-2001B BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BAG1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 06 OF 22
BALOL GGS - II
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 BAG2-P-102A PUMP SUCTION 5085-BAG2-PR-D-1001-01 3"-FW-BAG2-6007-AA3 0.1


2 DPI-0102 BAG2-P-102B PUMP SUCTION 5085-BAG2-PR-D-1001-01 3"-FW-BAG2-6008-AA3 0.1
3 DPI-0103 BAG2-P-101A PUMP SUCTION 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6008-AA3 0.1
4 DPI-0104 BAG2-P-101B PUMP SUCTION 5085-BAG2-PR-D-1001-01 8"-FW-BAG2-6009-AA3 0.1
5 DPI-1002A BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 8.0
6 DPI-1002B BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 8.0
7 DPI-1001A BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 8.0
8 DPI-1001B BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 8.0
9 DPI-1004A BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 8.0
10 DPI-1004B BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 8.0
11 DPI-1003A BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 8.0
12 DPI-1003B BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 8.0
13 DPI-2001A BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 8.0
14 DPI-2001B BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BAG2
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 07 OF 22
BALOL GGS - III
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 BAG3-P-102A PUMP SUCTION 5085-BAG3-PR-D-1001-01 3"-FW-BAG3-6006-AA3 0.1


2 DPI-0102 BAG3-P-102B PUMP SUCTION 5085-BAG3-PR-D-1001-01 3"-FW-BAG3-6007-AA3 0.1
3 DPI-0103 BAG3-P-101A PUMP SUCTION 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6008-AA3 0.1
4 DPI-0104 BAG3-P-101B PUMP SUCTION 5085-BAG3-PR-D-1001-01 8"-FW-BAG3-6009-AA3 0.1
5 DPI-2001A T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 8.0
6 DPI-2001B T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 8.0
7 DPI-1003A T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 8.0
8 DPI-1003B T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 8.0
9 DPI-1004A T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 8.0
10 DPI-1004B T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 8.0
11 DPI-1001A T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 8.0
12 DPI-1001B T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 8.0
13 DPI-1002A T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 8.0
14 DPI-1002B T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BAG3
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 08 OF 22
BALOL GGS - IV
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 BAG4-P-102A PUMP SUCTION 5085-BAG4-PR-D-1001-01 3"-FW-BAG4-6006-AA3 0.1


2 DPI-0102 BAG4-P-102B PUMP SUCTION 5085-BAG4-PR-D-1001-01 3"-FW-BAG4-6007-AA3 0.1
3 DPI-0103 BAG4-P-101A PUMP SUCTION 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6008-AA3 0.1
4 DPI-0104 BAG4-P-101B PUMP SUCTION 5085-BAG4-PR-D-1001-01 8"-FW-BAG4-6009-AA3 0.1
5 DPI-1001A BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 8.0
6 DPI-1001B BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 8.0
7 DPI-1002A BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 8.0
8 DPI-1002B BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 8.0
9 DPI-2001A BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 8.0
10 DPI-2001B BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BAG4
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 09 OF 22
BECHRAJI GGS-I
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)
1 DPI-0103 BEG1-P-102A PUMP SUCTION 5085-BEG1-PR-D-1001-01 3"-FW-BEG1-6008-AA3 0.1
2 DPI-0104 BEG1-P-102B PUMP SUCTION 5085-BEG1-PR-D-1001-01 3"-FW-BEG1-6009-AA3 0.1
3 DPI-0101 BEG1-P-101A PUMP SUCTION 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6006-AA3 0.1
4 DPI-0102 BEG1-P-101B PUMP SUCTION 5085-BEG1-PR-D-1001-01 8"-FW-BEG1-6007-AA3 0.1
5 DPI-1004A BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 8.0
6 DPI-1004B BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 8.0
7 DPI-1002A BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 8.0
8 DPI-1002B BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 8.0
9 DPI-2001A BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 8.0
10 DPI-2001B BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 8.0
11 DPI-1003A BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 8.0
12 DPI-1003B BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 8.0
13 DPI-1001A BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 8.0
14 DPI-1001B BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 8.0
15 DPI-1005A BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 8.0
16 DPI-1005B BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 8.0
17 DPI-1006A BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 8.0
18 DPI-1006B BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 8.0
19 DPI-1007A BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 8.0
20 DPI-1007B BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 8.0
21 DPI-1008A BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 8.0
22 DPI-1008B BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 8.0
23 DPI-1010A BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 8.0
24 DPI-1010B BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 8.0
25 DPI-1009A BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 8.0
26 DPI-1009B BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BEG1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 10 OF 22
BECHRAJI GGS - II
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 BEG2-P-102A PUMP SUCTION 5085-BEG2-PR-D-1001-01 3"-FW-BEG2-6007-AA3 0.1


2 DPI-0102 BEG2-P-102B PUMP SUCTION 5085-BEG2-PR-D-1001-01 3"-FW-BEG2-6007-AA3 0.1
3 DPI-0103 BEG2-P-101A PUMP SUCTION 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6008-AA3 0.1
4 DPI-0104 BEG2-P-101B PUMP SUCTION 5085-BEG2-PR-D-1001-01 8"-FW-BEG2-6009-AA3 0.1
5 DPI-1004A BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 8.0
6 DPI-1004B BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 8.0
7 DPI-1002A BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 8.0
8 DPI-1002B BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 8.0
9 DPI-2002A BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 8.0
10 DPI-2002B BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 8.0
11 DPI-1003A BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 8.0
12 DPI-1003B BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 8.0
13 DPI-1001A BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 8.0
14 DPI-1001B BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 8.0
15 DPI-2001A BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 8.0
16 DPI-2001B BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code BEG2
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 11 OF 22
JOTANA GGS
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 JOT-JOCKEY-01 PUMP SUCTION 5085-JOG-PR-D-1001-01 3"-FW-JOG-6008-AA3 0.1


2 DPI-0102 JOT-JOCKEY-02 PUMP SUCTION 5085-JOG-PR-D-1001-01 3"-FW-JOG-6009-AA3 0.1
3 DPI-0103 JOG-P-101A PUMP SUCTION 5085-JOG-PR-D-1001-01 8"-FW-JOG-6010-AA3 0.1
4 DPI-0104 JOG-P-101B PUMP SUCTION 5085-JOG-PR-D-1001-01 8"-FW-JOG-6011-AA3 0.1
5 DPI-2001A JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AM3 8.0
6 DPI-2001B JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AM3 8.0
7 DPI-2002A JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AM3 8.0
8 DPI-2002B JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AM3 8.0
9 DPI-1001A JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AM3 8.0
10 DPI-1001B JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AM3 8.0
11 DPI-1002A JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 8.0
12 DPI-1002B JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 8.0
13 DPI-1003A JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 8.0
14 DPI-1003B JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 8.0
15 DPI-1004A JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 8.0
16 DPI-1004B JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 8.0
17 DPI-3001A COMPRESSOR 5085-JOG-PR-D-1002-01 8"-FW-JOG-6038-AM3 8.0
18 DPI-3001B COMPRESSOR 5085-JOG-PR-D-1002-01 8"-FW-JOG-6038-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code JOG
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 22 OF 22
LANWA GGS - 1
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 LAG1-P-102A PUMP SUCTION 5085-LAG1-PR-D-1001-01 3"-FW-LAG1-6008-AA3 0.1


2 DPI-0102 LAG1-P-102B PUMP SUCTION 5085-LAG1-PR-D-1001-01 3"-FW-LAG1-6009-AA3 0.1
3 DPI-0103 LAG1-P-101A PUMP SUCTION 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6010-AA3 0.1
4 DPI-0104 LAG1-P-101B PUMP SUCTION 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6011-AA3 0.1
5 DPI-1001A LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 8.0
6 DPI-1001B LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 8.0
7 DPI-1002A LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 8.0
8 DPI-1002B LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 8.0
9 DPI-1003A LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 8.0
10 DPI-1003B LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code LAG1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 12 OF 22
LANWA GGS-II
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 LAG2-P-102A PUMP SUCTION 5085-LAG2-PR-D-1001-01 3"-FW-LAG2-6008-AA3 0.1


2 DPI-0102 LAG2-P-102B PUMP SUCTION 5085-LAG2-PR-D-1001-01 3"-FW-LAG2-6009-AA3 0.1
3 DPI-0103 LAG2-P-101A PUMP SUCTION 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6010-AA3 0.1
4 DPI-0104 LAG2-P-101B PUMP SUCTION 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6011-AA3 0.1
5 DPI-1001A LAN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 8.0
6 DPI-1001B LAN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6038-AM3 8.0
7 DPI-1002A LAN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 8.0
8 DPI-1002B LAN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 8.0
9 DPI-1003A LAN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 8.0
10 DPI-1003B LAN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6039-AM3 8.0
11 DPI-1004A LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 8.0
12 DPI-1004B LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 8.0
13 DPI-2001A LAN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 8.0
14 DPI-2001B LAN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code LAG2
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 13 OF 22
LANWA GGS-III
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 LAG3-P-102A PUMP SUCTION 5085-LAG3-PR-D-1001-01 3"-FW-LAG3-6007-AA3 0.1


2 DPI-0102 LAG3-P-102B PUMP SUCTION 5085-LAG3-PR-D-1001-01 3"-FW-LAG3-6008-AA3 0.1
3 DPI-0103 LAG3-P-101A PUMP SUCTION 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6008-AA3 0.1
4 DPI-0104 LAG3-P-101B PUMP SUCTION 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6009-AA3 0.1
5 DPI-1001A LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 8.0
6 DPI-1001B LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 8.0
7 DPI-1002A LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 8.0
8 DPI-1002B LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 8.0
9 DPI-1003A LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 8.0
10 DPI-1003B LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 8.0
11 DPI-1004A LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 8.0
12 DPI-1004B LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 8.0
13 DPI-2001A LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 8.0
14 DPI-2001B LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 8.0
15 DPI-2002A LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 8.0
16 DPI-2002B LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 8.0
17 DPI-2003A LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 8.0
18 DPI-2003B LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code LAG3
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 14 OF 22
LAGHNAJ EPS
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 LGE-P-102A PUMP SUCTION 5085-LGE-PR-D-1001-01 3"-FW-LGE-6007-AA3 0.1


2 DPI-0102 LGE-P-102B PUMP SUCTION 5085-LGE-PR-D-1001-01 3"-FW-LGE-6008-AA3 0.1
3 DPI-0103 LGE-P-101A PUMP SUCTION 5085-LGE-PR-D-1001-01 8"-FW-LGE-6009-AA3 0.1
4 DPI-0104 LGE-P-101B PUMP SUCTION 5085-LGE-PR-D-1001-01 8"-FW-LGE-6010-AA3 0.1

Notes
1 All instrument tag numbers shall be prefixed by area code LGE
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 15 OF 22
NORTH KADI GGS-I
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 NK1-JP-01 PUMP SUCTION 5085-NKG1-PR-D-1001-01 3"-FW-NKG1-6007-AA3 0.1


2 DPI-0102 NK1-JP-02 PUMP SUCTION 5085-NKG1-PR-D-1001-01 3"-FW-NKG1-6006-AA3 0.1
3 DPI-0103 NK1-FWP-MEC-01 PUMP SUCTION 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6004-AA3 0.1
4 DPI-0104 NK1-FWP-MEC-02 PUMP SUCTION 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6005-AA3 0.1
5 DPI-1001A NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 8.0
6 DPI-1001B NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 8.0
7 DPI-1002A NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 8.0
8 DPI-1002B NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 8.0
9 DPI-1003A NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 8.0
10 DPI-1003B NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 8.0
11 DPI-1004A NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 8.0
12 DPI-1004B NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 8.0
13 DPI-2001A NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 8.0
14 DPI-2001B NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 8.0
15 DPI-2002A NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 8.0
16 DPI-2002B NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 8.0
17 DPI-2003A NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 8.0
18 DPI-2003B NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 8.0
19 DPI-1005A NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 8.0
20 DPI-1005B NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 8.0
21 DPI-1006A NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 8.0
22 DPI-1006B NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code NKG1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 16 OF 22
NORTH KADI GGS-II
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 NK2-JP-01 PUMP SUCTION 5085-NKG2-PR-D-1001-01 3"-FW-NKG2-6008-AA3 0.1


2 DPI-0102 NK2-JP-02 PUMP SUCTION 5085-NKG2-PR-D-1001-01 3"-FW-NKG2-6009-AA3 0.1
3 DPI-0103 NKG2-P-101A PUMP SUCTION 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6010-AA3 0.1
4 DPI-0104 NKG2-P-101B PUMP SUCTION 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6011-AA3 0.1
5 DPI-1001A NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 8.0
6 DPI-1001B NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 8.0
7 DPI-1002A NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 8.0
8 DPI-1002B NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 8.0
9 DPI-1003A NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 8.0
10 DPI-1003B NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 8.0
11 DPI-1004A NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 8.0
12 DPI-1004B NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 8.0
13 DPI-1005A NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 8.0
14 DPI-1005B NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 8.0
15 DPI-1006A NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 8.0
16 DPI-1006B NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 8.0
17 DPI-2001A NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 8.0
18 DPI-2001B NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 8.0
19 DPI-2002A NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 8.0
20 DPI-2002B NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 8.0
21 DPI-2003A NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 8.0
22 DPI-2003B NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code NKG2
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 17 OF 22
NORTH KADI GGS-III
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 NKG3-P-102A PUMP SUCTION 5085-NKG3-PR-D-1001-01 3"-FW-NKG3-6007-AA3 0.1


2 DPI-0102 NKG3-P-102B PUMP SUCTION 5085-NKG3-PR-D-1001-01 3"-FW-NKG3-6008-AA3 0.1
3 DPI-0103 NKG3-P-101A PUMP SUCTION 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6009-AA3 0.1
4 DPI-0104 NKG3-P-101B PUMP SUCTION 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6010-AA3 0.1
5 DPI-1001A NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 8.0
6 DPI-1001B NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 8.0
7 DPI-1002A NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 8.0
8 DPI-1002B NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 8.0
9 DPI-1003A NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 8.0
10 DPI-1003B NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 8.0
11 DPI-1004A NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 8.0
12 DPI-1004B NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 8.0
13 DPI-2001A NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 8.0
14 DPI-2001B NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 8.0
15 DPI-2002A NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 8.0
16 DPI-2002B NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 8.0
17 DPI-2003A NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 8.0
18 DPI-2003B NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 8.0
19 DPI-2004A NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6036-AM3 8.0
20 DPI-2004B NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 8.0
21 DPI-1005A NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 8.0
22 DPI-1005B NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 8.0
23 DPI-1006A NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 8.0
24 DPI-1006B NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code NKG3
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 18 OF 22
NORTH KADI GGS-IV
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 NKG4-P-102A PUMP SUCTION 5085-NKG4-PR-D-1001-01 3"-FW-NKG4-6003-AA3 0.1


2 DPI-0102 NKG4-P-102B PUMP SUCTION 5085-NKG4-PR-D-1001-01 3"-FW-NKG4-6004-AA3 0.1
3 DPI-0103 NKG4-P-101A PUMP SUCTION 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6009-AA3 0.1
4 DPI-0104 NKG4-P-101B PUMP SUCTION 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6010-AA3 0.1
5 DPI-3001A LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 8.0
6 DPI-3001B LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 8.0
7 DPI-1001A 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6031-AM3 8.0
8 DPI-1001B 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 8.0
9 DPI-1002A 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 8.0
10 DPI-1002B 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 8.0
11 DPI-1003A 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 8.0
12 DPI-1003B 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 8.0
13 DPI-1004A 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 8.0
14 DPI-1004B 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 8.0
15 DPI-2001A 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 8.0
16 DPI-2001B 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 8.0
17 DPI-2002A 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 8.0
18 DPI-2002B 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 8.0
19 DPI-2003A 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 8.0
20 DPI-2003B 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 8.0
21 DPI-1005A 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 8.0
22 DPI-1005B 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 8.0
23 DPI-1006A 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 8.0
24 DPI-1006B 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code NKG4
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 19 OF 22
SOBHASAN GGS-I
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)

1 DPI-0101 SOG1-P-102A PUMP SUCTION 5085-SOG1-PR-D-1001-01 3"-FW-SOG1-6009-AA3 0.1


2 DPI-0102 SOG1-P-102B PUMP SUCTION 5085-SOG1-PR-D-1001-01 3"-FW-SOG1-6010-AA3 0.1
3 DPI-0103 SOG1-P-101A PUMP SUCTION 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6011-AA3 0.1
4 DPI-0104 SOG1-P-101B PUMP SUCTION 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6012-AA3 0.1
5 DPI-1001A SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 8.0
6 DPI-1001B SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6037-AM3 8.0
7 DPI-1002A SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6035-AM3 8.0
8 DPI-1002B SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6036-AM3 8.0
9 DPI-1003A SOB1-ST-01 / 02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 8.0
10 DPI-1003B SOB1-ST-01 / 02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 8.0
11 DPI-2001A SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6035-AM3 8.0
12 DPI-2001B SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6027-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code SOG1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 20 OF 22
SOBHASAN GGS-II
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)
1 DPI-0101 SOG2-P-102A PUMP SUCTION 5085-SOG2-PR-D-1001-01 3"-FW-SOG2-6008-AA3 0.1
2 DPI-0102 SOG2-P-102B PUMP SUCTION 5085-SOG2-PR-D-1001-01 3"-FW-SOG2-6009-AA3 0.1
3 DPI-0103 SOG2-P-101A PUMP SUCTION 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6010-AA3 0.1
4 DPI-0104 SOG2-P-101B PUMP SUCTION 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6011-AA3 0.1
5 DPI-1001A SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 8.0
6 DPI-1001B SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 8.0
7 DPI-1008A SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 8.0
8 DPI-1008B SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 8.0
9 DPI-2002A SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 8.0
10 DPI-2002B SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 8.0
11 DPI-2001A SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 8.0
12 DPI-2001B SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 8.0
13 DPI-1009A SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 8.0
14 DPI-1009B SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 8.0
15 DPI-1005A SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 8.0
16 DPI-1005B SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 8.0
17 DPI-1007A SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 8.0
18 DPI-1007B SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 8.0
19 DPI-1002A SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 8.0
20 DPI-1002B SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 8.0
21 DPI-1003A SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 8.0
22 DPI-1003B SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 8.0
23 DPI-1004A SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 8.0
24 DPI-1004B SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 8.0
25 DPI-1006A SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 8.0
26 DPI-1006B SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 8.0
Notes
1 All instrument tag numbers shall be prefixed by area code SOG2
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 21 OF 22
SOBHASAN WWTP
DOC.NO : 5085-COMM-IN-J-1004

Operating Pressure
S.No Tag Number Service PID Number Line Number Remarks
(kg/cm2g)
1 DPI-0101 SOW-P-102A PUMP SUCTION 5085-SOW-PR-D-1001-01 3"-FW-SOW-6007-AA3 0.1
2 DPI-0102 SOW-P-102B PUMP SUCTION 5085-SOW-PR-D-1001-01 3"-FW-SOW-6006-AA3 0.1
3 DPI-0103 SOWETP-FW-02 PUMP SUCTION 5085-SOW-PR-D-1001-01 8"-FW-SOW-6004-AA3 0.1
4 DPI-0104 SOWETP-FW-01 PUMP SUCTION 5085-SOW-PR-D-1001-01 8"-FW-SOW-6005-AA3 0.1
5 DPI-1001A SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 8.0
6 DPI-1001B SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 8.0
7 DPI-1002A SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 8.0
8 DPI-1002B SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 8.0
9 DPI-1003A SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6050-AM3 8.0
10 DPI-1003B SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6053-AM3 8.0
11 DPI-1004A SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6037-AM3 8.0
12 DPI-1004B SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6038-AM3 8.0

Notes
1 All instrument tag numbers shall be prefixed by area code SOW
REVISIONS
TAG NOS /
PAGE NO REMARKS
DESCRIPTION
0 1

1 Cover Sheet X X

2 Revision Sheet X X

3 FE-XXXX X X

4 FI-XXXX X X

5 NOTES-ORIFICE X X

6 Annexure X X

Document No:
5085-COMM-IN-J-1005
SHEET : 02 OF 06
1 Tag Number See Annexure-1
2 Service See Annexure-1
3 Location Field
GENERAL 4 Equipment / Line Number See Annexure-1
5 P&ID Number See Annexure-1
6 Ambient Temperature Min Max °C -2 50
7 Inlet Line ID SCH Outlet Line ID SCH 8", Sch Std 8", Sch Std
8 Diff Range 0 - 2500 mmWC (*)
METER
9 Meter Maximum See Annexure-1
10 Fluid Fluid State Water Liquid
11 Design Pressure Kg/cm2 g Design Temperature °C 18.85 75
12 Flow Minimum Normal Maximum Sm3/hr See Annexure-2
13 Operating Pressure Kg/cm2 g See Annexure-2
14 Operating Temperature °C See Annexure-2
PROCESS CONDITION 15 Density at Oper. Temp Kg/m3
16 Molecular Weight 18
17 Operating Viscosity (cP) 0.7-1
18 Cp/Cv --
19
20
21 Type Concentric Square edge
22 Sizing As Per AGA 3 / ISO 5167
23 Material SS316
24 Thickness"W" In mm *
PLATE
25 Beta Ratio d/D Between 0.2 and 0.7
26 Bore Diameter 'd' *
27 Vent / Drain Yes
28
29 Type Orifice Flanges, WN as per ASME B.16.5
30 Tap Type Flange Type
31 Number Of Taps Per Flange 2
32 Material ASTM A106 GR B
33 Size & Rating 8",150#
34 Facing & Finish RF WN
FLANGES 35 Gasket Thickness mm *
4.5 MM THK, SS 316L SPIRAL WOUND GASKET WITH FLEXIBLE
36 Gasket Material
GRAPHITE FILLER
37 Plate Holder Not required
38 Plate Holder Material Not required
39 Bolt Material ALLOY STEEL ASTM A 193 B7
40 Nut Material ALLOY STEEL ASTM A 194 2H
41 Straightning Vanes Not required
OPTIONS 42 Connection Not required
43 Material Not required
44 Manufacturer *
45 Model *
PURCHASE 46 Purchase order Number *
47 Price *
48 Serial Number Item Number * *

NOTES:
1) '*' - Vendor to Specify

DATASHEET
FOR
1 PA 28.02.2018 Re-Issued for Bid FLOW ELEMENT
0 AMV 06.10.2016 Issued for Bid SHEET : 03 OF 06
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1005 CODE : 5085 REV.1
15 Type DP Flow Indicator
16 Calibration Range Kg/cm2 *
17 Figure Interval *
18 Minor Graduation *
19 Mounting 2" Pipe Stanchion, 316SS mounting hardware to be included
20 Dial Size Dial Background color 150mm White with Black Lettering
21 Scale Unit Dual scale (mmWC and Sm3/hr)
22 Case Material SS316
23 Ring construction Ring Material Bayonet SS316
24 Blow-Out Protection Yes
GAUGE
25 Lens Material Shatter - Proof Front Glass
26 Pressure Element Type Diaphragm Type
27 Pressure Element Material SS316
28 Socket Material --
29 Gauge Connection Size 1/2" NPT(M)
30 Connection Location *
31 Movement Material SS316
32 Nominal Accuracy ±2% Full Scale (Minimum)
33 NACE MR0175 Compliance --
34 Zero Adjustment Required(Micrometer Pointer-External)
35 Type NA
36 Process Connection Size & Rating NA
37 Diaphragm Material NA
38 Bottom Housing Material NA
DIAPHRAGM SEAL
39 Fill Fluid NA
40 Flushing Connection (Drip ring) NA
41 Top Housing Material NA
42 Connection to Instrument NA
43 Manifold Type 5 Valve, 1/2" NPTM x 1/2" NPTF
44 Material of Manifold SS316
45 Maximum Pressure Rating *
MANIFOLD 46 Process Connection Size & Rating 1/2" NPTF --
47 Vent / Drain connection Size and Type 1/4" NPT
48 Manifold Mounting -
49 Manufacturer Model * *
50 Syphon: Type Snubber: Type No No
51 Over range Protection 130% of Full Scale Deflection without accuracy loss
OPTIONS 52 Movement Damping *
53 Gauge Protector --
54 Tag Plate SS316
55 Manufacturer *
56 Model *
PURCHASE 57 Purchase order Number *
58 Price *
59 Serial Number Item Number * *

NOTES:
1. * - VENDOR to specify / furnish

DATASHEET
FOR
1 PA 28.02.2018 Re-Issued for Bid FLOW INDICATOR
0 AMV 06.10.2016 Issued for Bid SHEET : 04 OF 06
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1005 CODE : 5085 REV.1
GENERAL NOTES - ORIFICE FLOW METER

1) Vendor to provide flow orifice calculations as per ISO 5167 / AGA 3 or equivalent.
2) Orifice fitting shall be supplied complete with handle, grease, jack screw, etc.
3) The Supplier shall carry out orifice calculations including calculations for the thickness of the orifice plates.
4) Range shall be sized so that design flow is around 70% to 80% of maximum flow for a differential pressure of 2500 mmwc (0-100 in WC).
5) Other preferred ranges shall be 500, 1000, 5000 mm WC
6) The plate construction shall be as per ISO 5167 Part 2, Sec 5.
7) Orifice Flanges shall comply with ASME B16.5
8) Orifice Plate shall have the following information engraved on the upstream side of Orifice Tab:
(i) Tag numbers,
(ii) Orifice bore diameter,
(iii) ID of pipe,
(iv) Material,

TEST AND INSPECTION


9) The following tests shall be performed as applicableand results provided as part of documentation
(i) Hydrostatic test
(ii) Non-destructive test ( 100% radiograph is mandatory, ultrasonic test or dye penetrant test as applicable)
(iii) PWHT where applicable
(iv) Visual Inspection
(v) Dimensional and flange finish check

DOCUMENTS
10) The following documents shall be provided.
(i) Material certificates as per ISO 10474 type 3.1 B
(ii) Certified outline dimensional / Internal drawings.
(iii) Assembly and disassembly procedures
(iv) Testing and inspection certificates
(v) Element sizing calculations
(vi) Data sheet

GENERAL NOTES FOR


ORIFICE FLOW METER
1 PA 28.02.2018 Re-Issued for Bid
0 AMV 06.10.2016 Issued for Bid SHEET : 05 OF 06
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1005 CODE : 5085 REV.1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET SHEET 06 OF 06

DOC.NO : 5085-COMM-IN-J-1005
Operating Operating
Area Flow (Sm3/hr) Meter Max
S.No Field Tag Number Instrument Description Equipment / Line Number PID Number Pressure Temperature Remarks
Code Max (Sm3/hr)
kg/cm2g Deg.C
1 BALOL GGS-I BAG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BAG1-6017-AA3 5085-BAG1-PR-D-1001-01 10.5 25-50 288 500

2 BALOL GGS-I BAG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BAG1-6017-AA3 5085-BAG1-PR-D-1001-01 10.5 25-50 - -

3 BALOL GGS-II BAG2 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BAG2-6016-AA3 5085-BAG2-PR-D-1001-01 10.5 25-50 288 500

4 BALOL GGS-II BAG2 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BAG2-6016-AA3 5085-BAG2-PR-D-1001-01 10.5 25-50 - -

5 BALOL GGS-III BAG3 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BAG3-6016-AA3 5085-BAG3-PR-D-1001-01 10.5 25-50 288 500

6 BALOL GGS-III BAG3 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BAG3-6016-AA3 5085-BAG3-PR-D-1001-01 10.5 25-50 - -

7 BALOL GGS-IV BAG4 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BAG4-6016-AA3 5085-BAG4-PR-D-1001-01 10.5 25-50 288 500

8 BALOL GGS-IV BAG4 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BAG4-6016-AA3 5085-BAG4-PR-D-1001-01 10.5 25-50 - -

9 BECHRAJI GGS-I BEG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BEG1-6015-AA3 5085-BEG1-PR-D-1001-01 10.5 25-50 290 500

10 BECHRAJI GGS-I BEG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BEG1-6015-AA3 5085-BEG1-PR-D-1001-01 10.5 25-50 - -

11 BECHRAJI GGS-II BEG2 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-BEG2-6016-AA3 5085-BEG2-PR-D-1001-01 10.5 25-50 290 500

12 BECHRAJI GGS-II BEG2 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-BEG2-6016-AA3 5085-BEG2-PR-D-1001-01 10.5 25-50 - -

13 JOTANA GGS JOG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-JOG1-6019-AA3 5085-JOG1-PR-D-1001-01 10.5 25-50 288 500

14 JOTANA GGS JOG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-JOG1-6019-AA3 5085-JOG1-PR-D-1001-01 10.5 25-50 - -

15 LANWA GGS-II LAG2 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-LAG2-6017-AA3 5085-LAG2-PR-D-1001-01 10.5 25-50 288 500

16 LANWA GGS-II LAG2 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-LAG2-6017-AA3 5085-LAG2-PR-D-1001-01 10.5 25-50 - -

17 LANWA GGS-III LAG3 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-LAG3-6016-AA3 5085-LAG3-PR-D-1001-01 10.5 25-50 288 500

18 LANWA GGS-III LAG3 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-LAG3-6016-AA3 5085-LAG3-PR-D-1001-01 10.5 25-50 - -

19 LANGHNAJ EPS LGE FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-LGE-6016-AA3 5085-LGE-PR-D-1001-01 10.5 25-50 288 500

20 LANGHNAJ EPS LGE FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-LGE-6016-AA3 5085-LGE-PR-D-1001-01 10.5 25-50 - -

21 NORTH KADI GGS-I NKG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-NKG1-6013-AA3 5085-NKG1-PR-D-1001-01 10.5 25-50 288 500

22 NORTH KADI GGS-I NKG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-NKG1-6013-AA3 5085-NKG1-PR-D-1001-01 10.5 25-50 - -

23 NORTH KADI GGS-II NKG2 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-NKG2-6018-AA3 5085-NKG2-PR-D-1001-01 10.5 25-50 288 500

24 NORTH KADI GGS-II NKG2 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-NKG2-6018-AA3 5085-NKG2-PR-D-1001-01 10.5 25-50 - -

25 NORTH KADI GGS-III NKG3 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-NKG3-6022-AA3 5085-NKG3-PR-D-1001-01 10.5 25-50 288 500

26 NORTH KADI GGS-III NKG3 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-NKG3-6022-AA3 5085-NKG3-PR-D-1001-01 10.5 25-50 - -

27 NORTH KADI GGS-IV NKG4 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-NKG4-6014-AA3 5085-NKG4-PR-D-1001-01 10.5 25-50 288 500

28 NORTH KADI GGS-IV NKG4 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-NKG4-6014-AA3 5085-NKG4-PR-D-1001-01 10.5 25-50 - -

29 SOBHASAN GGS-I SOG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-SOG1-6020-AA3 5085-SOG1-PR-D-1001-01 10.5 25-50 288 500

30 SOBHASAN GGS-I SOG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-SOG1-6020-AA3 5085-SOG1-PR-D-1001-01 10.5 25-50 - -

31 SOBHASAN GGS-II SOG2 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-SOG2-6024-AA3 5085-SOG2-PR-D-1001-01 10.5 25-50 288 500

32 SOBHASAN GGS-II SOG2 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-SOG2-6024-AA3 5085-SOG2-PR-D-1001-01 10.5 25-50 - -

33 SOBHASAN WWTP SOW FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-SOW-6013-AA3 5085-SOW-PR-D-1001-01 10.5 25-50 288 500

34 SOBHASAN WWTP SOW FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-SOW-6013-AA3 5085-SOW-PR-D-1001-01 10.5 25-50 - -

35 LANWA GGS-I LAG1 FE-0101 FLOW ELEMENT - ORIFICE TYPE 8"-FW-LAG1-6017-AA3 5085-LAG1-PR-D-1001-01 10.5 25-50 288 500

36 LANWA GGS-I LAG1 FI-0101 LOCAL DP TYPE FLOW INDICATOR 8"-FW-LAG1-6017-AA3 5085-LAG1-PR-D-1001-01 10.5 25-50 - -
REVISIONS
TAG NOS /
PAGE NO REMARKS
DESCRIPTION
0 1

1 Cover Sheet X X

2 Revision Sheet X X

3 PSH- XXXX X X

4 PSL- XXXX X X

5 Annexure-BAG1 X X

6 Annexure-BAG2 X X

7 Annexure-BAG3 X X

8 Annexure-BAG4 X X

9 Annexure-BEG1 X X

10 Annexure-BEG2 X X

11 Annexure-JOG X X

12 Annexure-LAG1 X X

13 Annexure-LAG2 X X

14 Annexure-LAG3 X X

15 Annexure-LGE X X

16 Annexure-NKG1 X X

17 Annexure-NKG2 X X

18 Annexure-NKG3 X X

19 Annexure-NKG4 X X

20 Annexure-SOG1 X X

21 Annexure-SOG2 X X

22 Annexure-SOW X X

Document No:

5085-COMM-IN-J-1006
SHEET : 02 OF 22
1 Tag Number PSH-XXXX

2 Service Deluge Valve discharge

3 Location Field

GENERAL 4 Equipment / Line Number See Annexure

5 P&ID Number See Annexure

6 Ambient Temperature Min Max °C -2 50

7 Area Classification Enclosure Type Zone 2, Group IIA&B, T3 Ex'i, IP 65

8 Design Pressure kg/cm2g Design Temperature °C 18.85 75

PROCESS 9 Operating Pressure kg/cm2g Temperature °C See Annexure 25 - 50


CONDITION 10 Setpoint kg/cm2g 5-6.5

11

12 Type Blind type

13 Process Connection 1/2" NPT (M)

14 Electrical connection 1/2" NPT (F)

15 Set Point Deviation ±1%

16 Dead Band 10% of Range

17 Switch Diff: Setpoint adjustable between 10% and 90%

18 Switch type Snap acting microswitch

19 No. of switching setpoints 2 NO + 2 NC

20 Switch rating 24VDC, 0.5 A

21 Repeatability ±1%
PRESSURE SWITCH
22 Accuracy ±1%

23 Sensor Type Sensor Material Diaphgram 316 SS

24 External Zero adjustment -

25 Body Material Die cast aluminium

26 Spring *

27 Materials Lock Ring *

28 Spring Plate *

29 O ring *

30 Accessories Tag plate , Block and Bleed valve (2 - way valve)

31 Steady state air consumption N/A

32 Manufacturer *

33 Model *

PURCHASE 34 Purchase order Number *

35 Price *

36 Serial Number Item Number * *

NOTES :

1. * - VENDOR to specify / furnish

DATASHEET
FOR
PRESSURE SWITCH
1 AP 28.02.2018 Re-issued for Bid
0 AMV 07.10.2016 Issued for Bid SHEET : 03 OF 22

REV BY DATE DESCRIPTION DOC.NO : 5085-COMM-IN-J-1006 CODE : 5085 REV. 1


1 Tag Number PSL-XXXX

2 Service Deluge Valve discharge

3 Location Field

GENERAL 4 Equipment / Line Number See Annexure

5 P&ID Number See Annexure

6 Ambient Temperature Min Max °C -2 50

7 Area Classification Enclosure Type Zone 2, Group IIA&B, T3 Ex'i, IP 65

8 Design Pressure kg/cm2g Design Temperature °C 18.85 75

PROCESS 9 Operating Pressure kg/cm2g Temperature °C See Annexure 25 - 50


CONDITION 10 Setpoint kg/cm2g 2.5

11

12 Type Blind type

13 Process Connection 1/2" NPT (M)

14 Electrical connection 1/2" NPT (F)

15 Set Point Deviation ±1%

16 Dead Band 10% of Range

17 Switch Diff: Setpoint adjustable between 10% and 90%

18 Switch type Snap acting microswitch

19 No. of switching setpoints 2 NO + 2 NC

20 Switch rating 24VDC, 0.5 A

21 Repeatability ±1%
PRESSURE SWITCH
22 Accuracy ±1%

23 Sensor Type Sensor Material Diaphgram 316 SS

24 External Zero adjustment -

25 Body Material Die cast aluminium

26 Spring *

27 Materials Lock Ring *

28 Spring Plate *

29 O ring *

30 Accessories Tag plate , Block and Bleed valve (2 - way valve)

31 Steady state air consumption N/A

32 Manufacturer *

33 Model *

PURCHASE 34 Purchase order Number *

35 Price *

36 Serial Number Item Number * *

NOTES :

1. * - VENDOR to specify / furnish

DATASHEET
FOR
PRESSURE SWITCH
1 AP 28.02.2018 Re-issued for Bid
0 AMV 07.10.2016 Issued for Bid SHEET : 04 OF 22

REV BY DATE DESCRIPTION DOC.NO : 5085-COMM-IN-J-1006 CODE : 5085 REV. 1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 05 OF 22
BALOL GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1003A BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6026-AM3 11.0

2 PSH-1003B BAL1-OST-03 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6028-AM3 11.0

3 PSH-1002A BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6027-AM3 11.0

4 PSH-1002B BAL1-OST-02 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6029-AM3 11.0

5 PSH-1004A BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6030-AM3 11.0

6 PSH-1004B BAL1-OST-04 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6032-AM3 11.0

7 PSH-1001A BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6031-AM3 11.0

8 PSH-1001B BAL1-OST-01 5085-BAG1-PR-D-1002-01 3"-FW-BAG1-6033-AM3 11.0

9 PSH-2002A BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6034-AM3 11.0

10 PSH-2002B BAL1-TT-02 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6036-AM3 11.0

11 PSH-2003A BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6035-AM3 11.0

12 PSH-2003B BAL1-TT-03 5085-BAG1-PR-D-1002-01 2"-FW-BAG1-6037-AM3 11.0

13 PSH-1005A BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6038-AM3 11.0

14 PSH-1005B BAL1-OST-05 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6040-AM3 11.0

15 PSH-1006A BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6039-AM3 11.0

16 PSH-1006B BAL1-OST-06 5085-BAG1-PR-D-1002-02 3"-FW-BAG1-6041-AM3 11.0

17 PSH-2001A BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6043-AM3 11.0

18 PSH-2001B BAL1-TT-01 5085-BAG1-PR-D-1002-02 2"-FW-BAG1-6044-AM3 11.0

19 PSL-1003 BAL1-OST-03 5085-BAG1-PR-D-1002-01 - 7

20 PSL-1002 BAL1-OST-02 5085-BAG1-PR-D-1002-01 - 7

21 PSL-1004 BAL1-OST-04 5085-BAG1-PR-D-1002-01 - 7

22 PSL-1001 BAL1-OST-01 5085-BAG1-PR-D-1002-01 - 7

23 PSL-2002 BAL1-TT-02 5085-BAG1-PR-D-1002-01 - 7

24 PSL-2003 BAL1-TT-03 5085-BAG1-PR-D-1002-01 - 7

25 PSL-1005 BAL1-OST-05 5085-BAG1-PR-D-1002-02 - 7

26 PSL-1006 BAL1-OST-06 5085-BAG1-PR-D-1002-02 - 7

27 PSL-2001 BAL1-TT-01 5085-BAG1-PR-D-1002-02 - 7

Notes:

1 All tag numbers shall be prefixed by area code BAG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 06 OF 22
BALOL GGS-II
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1002A BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6034-AM3 10.5

2 PSH-1002B BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6035-AM3 10.5

3 PSH-1001A BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6036-AM3 10.5

4 PSH-1001B BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6033-AM3 10.5

5 PSH-1004A BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6030-AM3 10.5

6 PSH-1004B BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6031-AM3 10.5

7 PSH-1003A BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6032-AM3 10.5

8 PSH-1003B BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6029-AM3 10.5

9 PSH-2001A BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6041-AM3 10.5

10 PSH-2001B BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 3"-FW-BAG2-6042-AM3 10.5

11 PSL-1002 BALGGS2-OST-02 5085-BAG2-PR-D-1002-01 - 7

12 PSL-1001 BALGGS2-OST-01 5085-BAG2-PR-D-1002-01 - 7

13 PSL-1004 BALGGS2-OST-04 5085-BAG2-PR-D-1002-01 - 7

14 PSL-1003 BALGGS2-OST-03 5085-BAG2-PR-D-1002-01 - 7

15 PSL-2001 BALGGS2-TT-01/02 5085-BAG2-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code BAG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 07 OF 22
BALOL GGS-III
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-2001A T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 10.5

2 PSH-2001B T-504 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 10.5

3 PSH-1003A T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6024-AM3 10.5

4 PSH-1003B T-501C 5085-BAG3-PR-D-1002-01 2"-FW-BAG3-6029-AM3 10.5

5 PSH-1004A T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6031-AM3 10.5

6 PSH-1004B T-501D 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6026-AM3 10.5

7 PSH-1001A T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6027-AM3 10.5

8 PSH-1001B T-501A 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6032-AM3 10.5

9 PSH-1002A T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6028-AM3 10.5

10 PSH-1002B T-501B 5085-BAG3-PR-D-1002-01 3"-FW-BAG3-6033-AM3 10.5

11 PSL-2001 T-504 5085-BAG3-PR-D-1002-01 - 7

12 PSL-1003 T-501C 5085-BAG3-PR-D-1002-01 - 7

13 PSL-1004 T-501D 5085-BAG3-PR-D-1002-01 - 7

14 PSL-1001 T-501A 5085-BAG3-PR-D-1002-01 - 7

15 PSL-1002 T-501B 5085-BAG3-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code BAG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 08 OF 22
BALOL GGS-IV
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6028-AM3 10.5

2 PSH-1001B BAL IV-ST-01 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6025-AM3 10.5

3 PSH-1002A BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6029-AM3 10.5

4 PSH-1002B BAL IV-ST-02 5085-BAG4-PR-D-1002-01 3"-FW-BAG4-6026-AM3 10.5

5 PSH-2001A BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6030-AM3 10.5

6 PSH-2001B BAL IV-TT-01 5085-BAG4-PR-D-1002-01 2"-FW-BAG4-6027-AM3 10.5

7 PSL-1001 BAL IV-ST-01 5085-BAG4-PR-D-1002-01 - 7

8 PSL-1002 BAL IV-ST-02 5085-BAG4-PR-D-1002-01 - 7

9 PSL-2001 BAL IV-TT-01 5085-BAG4-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code BAG4


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 09 OF 22
BECHRAJI GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1004A BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6029-AM3 10.5

2 PSH-1004B BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6031-AM3 10.5

3 PSH-1002A BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6033-AM3 10.5

4 PSH-1002B BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6030-AM3 10.5

5 PSH-2001A BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6032-AM3 10.5

6 PSH-2001B BC-1-TS-TK 5085-BEG1-PR-D-1002-01 2"-FW-BEG1-6059-AM3 10.5

7 PSH-1003A BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6037-AM3 10.5

8 PSH-1003B BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6035-AM3 10.5

9 PSH-1001A BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6036-AM3 10.5

10 PSH-1001B BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6034-AM3 10.5

11 PSH-1005A BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6045-AM3 10.5

12 PSH-1005B BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6042-AM3 10.5

13 PSH-1006A BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6044-AM3 10.5

14 PSH-1006B BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6043-AM3 10.5

15 PSH-1007A BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6040-AM3 10.5

16 PSH-1007B BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6039-AM3 10.5

17 PSH-1008A BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6041-AM3 10.5

18 PSH-1008B BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 3"-FW-BEG1-6038-AM3 10.5

19 PSH-1010A BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6051-AM3 10.5

20 PSH-1010B BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6058-AM3 10.5

21 PSH-1009A BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6050-AM3 10.5

22 PSH-1009B BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 4"-FW-BEG1-6057-AM3 10.5

23 PSL-1004 BC-1-E.ST-TK-04 5085-BEG1-PR-D-1002-01 - 7

24 PSL-1002 BC-1-E.ST-TK-02 5085-BEG1-PR-D-1002-01 - 7

25 PSL-2001 BC-1-TS-TK 5085-BEG1-PR-D-1002-01 - 7

26 PSL-1003 BC-1-E.ST-TK-03 5085-BEG1-PR-D-1002-01 - 7

27 PSL-1001 BC-1-E.ST-TK-01 5085-BEG1-PR-D-1002-01 - 7

28 PSL-1005 BC-1-E.ST-TK-05 5085-BEG1-PR-D-1002-01 - 7

29 PSL-1006 BC-1-E.ST-TK-06 5085-BEG1-PR-D-1002-01 - 7

30 PSL-1007 BC-1-E.ST-TK-07 5085-BEG1-PR-D-1002-01 - 7

31 PSL-1008 BC-1-E.ST-TK-08 5085-BEG1-PR-D-1002-01 - 7

32 PSL-1010 BE-ETP-WT-02 5085-BEG1-PR-D-1002-02 - 7

33 PSL-1009 BE-ETP-WT-01 5085-BEG1-PR-D-1002-02 - 7

Notes:

1 All tag numbers shall be prefixed by area code BEG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 10 OF 22
BECHRAJI GGS-II
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1004A BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6027-AM3 10.5

2 PSH-1004B BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6026-AM3 10.5

3 PSH-1002A BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6025-AM3 10.5

4 PSH-1002B BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6028-AM3 10.5

5 PSH-2002A BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6024-AM3 10.5

6 PSH-2002B BC-II-TK-02 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6029-AM3 10.5

7 PSH-1003A BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6032-AM3 10.5

8 PSH-1003B BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6033-AM3 10.5

9 PSH-1001A BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6031-AM3 10.5

10 PSH-1001B BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 3"-FW-BEG2-6034-AM3 10.5

11 PSH-2001A BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6035-AM3 10.5

12 PSH-2001B BC-II-TK-01 5085-BEG2-PR-D-1002-01 2"-FW-BEG2-6030-AM3 10.5

13 PSL-1004 BC-II-E-ST-TK-04 5085-BEG2-PR-D-1002-01 - 7

14 PSL-1002 BC-II-E-ST-TK-02 5085-BEG2-PR-D-1002-01 - 7

15 PSL-2002 BC-II-TK-02 5085-BEG2-PR-D-1002-01 - 7

16 PSL-1003 BC-II-E-ST-TK-03 5085-BEG2-PR-D-1002-01 - 7

17 PSL-1001 BC-II-E-ST-TK-01 5085-BEG2-PR-D-1002-01 - 7

18 PSL-2001 BC-II-TK-01 5085-BEG2-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code BEG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 11 OF 22
JOTANA GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-2001A JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AM3 10.5

2 PSH-2001B JOT-ST-01 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AM3 10.5

3 PSH-2002A JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AM3 10.5

4 PSH-2002B JOT-ST-02 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AM3 10.5

5 PSH-1001A JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AM3 10.5

6 PSH-1001B JOT-ST-03 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AM3 10.5

7 PSH-1002A JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 10.5

8 PSH-1002B JOT-ST-04 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 10.5

9 PSH-1003A JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 10.5

10 PSH-1003B JOT-ST-05 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 10.5

11 PSH-1004A JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 10.5

12 PSH-1004B JOT-ST-06 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 10.5

13 PSH-3001A COMPRESSOR 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 10.5

14 PSH-3001B COMPRESSOR 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 10.5

15 PSL-2001 JOT-ST-01 5085-JOG-PR-D-1002-01 - 7

16 PSL-2002 JOT-ST-02 5085-JOG-PR-D-1002-01 - 7

17 PSL-1001 JOT-ST-03 5085-JOG-PR-D-1002-01 - 7

18 PSL-1002 JOT-ST-04 5085-JOG-PR-D-1002-01 - 7

19 PSL-1003 JOT-ST-05 5085-JOG-PR-D-1002-01 - 7

20 PSL-1004 JOT-ST-06 5085-JOG-PR-D-1002-01 - 7

21 PSL-3001 COMPRESSOR 5085-JOG-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code JOG


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 12 OF 22
LANWA GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 10.5

2 PSH-1001B LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 10.5

3 PSH-1002A LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 10.5

4 PSH-1002B LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 10.5

5 PSH-1003A LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 10.5

6 PSH-1003B LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 10.5

7 PSL-1001 LAN1-ST-01/02 5085-LAG1-PR-D-1002-01 - 7

8 PSL-1002 LAN1-ST-03/04 5085-LAG1-PR-D-1002-01 - 7

9 PSL-1003 LAN1-ST-05/06 5085-LAG1-PR-D-1002-01 - 7

10 PSL-1004 LAN1-ST-07/08 5085-LAG1-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code LAG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 13 OF 22
LANWA GGS-II
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A LAN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 10.5

2 PSH-1001B LAN2-ST-01 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6038-AM3 10.5

3 PSH-1002A LAN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 10.5

4 PSH-1002B LAN2-ST-02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 10.5

5 PSH-1003A LAN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 10.5

6 PSH-1003B LAN2-ST-03 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6039-AM3 10.5

7 PSH-1004A LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 10.5

8 PSH-1004B LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 10.5

9 PSH-2001A LAN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6041-AM3 10.5

10 PSH-2001B LAN2-ST-04 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6042-AM3 10.5

11 PSL-1001 LAN2-ST-01 5085-LAG2-PR-D-1002-01 - 7

12 PSL-1002 LAN2-ST-02 5085-LAG2-PR-D-1002-01 - 7

13 PSL-1003 LAN2-ST-03 5085-LAG2-PR-D-1002-01 - 7

14 PSL-1004 LAN2-EFLTK-01/02 5085-LAG2-PR-D-1002-01 - 7

15 PSL-2001 LAN2-ST-04 5085-LAG2-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code LAG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 14 OF 22
LANWA GGS-III
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 11.0

2 PSH-1001B LW3-ST-01 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 11.0

3 PSH-1002A LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 11.0

4 PSH-1002B LW3-ST-02 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 11.0

5 PSH-1003A LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 11.0

6 PSH-1003B LW3-ST-03 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 11.0

7 PSH-1004A LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 11.0

8 PSH-1004B LW3-ST-04 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 11.0

9 PSH-2001A LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 11.0

10 PSH-2001B LW3-TT-05 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 11.0

11 PSH-2002A LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 11.0

12 PSH-2002B LW3-TT-06 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 11.0

13 PSH-2003A LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 11.0

14 PSH-2003B LW3-TT-07 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 11.0

15 PSL-1001 LW3-ST-01 5085-LAG3-PR-D-1002-01 - 7

16 PSL-1002 LW3-ST-02 5085-LAG3-PR-D-1002-01 - 7

17 PSL-1003 LW3-ST-03 5085-LAG3-PR-D-1002-01 - 7

18 PSL-1004 LW3-ST-04 5085-LAG3-PR-D-1002-01 - 7

19 PSL-2001 LW3-TT-05 5085-LAG3-PR-D-1002-01 - 7

20 PSL-2002 LW3-TT-06 5085-LAG3-PR-D-1002-01 - 7

21 PSL-2003 LW3-TT-07 5085-LAG3-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code LAG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 15 OF 22
LANGHNAJ EPS
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSL-1001 LANGH-T-02/04 5085-LGE-PR-D-1002-01 - 7

2 PSL-1002 LANGH-T-01/03 5085-LGE-PR-D-1002-01 - 7

3 PSL-1003 LANGH-T-05/06 5085-LGE-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code LGE


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 16 OF 22
NORTH KADI GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 10.5

2 PSH-1001B NK1-OST-01 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 10.5

3 PSH-1002A NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 10.5

4 PSH-1002B NK1-OST-02 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 10.5

5 PSH-1003A NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 10.5

6 PSH-1003B NK1-OST-03 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 10.5

7 PSH-1004A NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 10.5

8 PSH-1004B NK1-OST-04 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 10.5

9 PSH-2001A NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 10.5

10 PSH-2001B NK1-TT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 10.5

11 PSH-2002A NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 10.5

12 PSH-2002B NK1-TT-02 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 10.5

13 PSH-2003A NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 10.5

14 PSH-2003B NK1-AT-01 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 10.5

15 PSH-1005A NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 10.5

16 PSH-1005B NK1-ET-01 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 10.5

17 PSH-1006A NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 10.5

18 PSH-1006B NK1-ET-02 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 10.5

19 PSL-1001 NK1-OST-01 5085-NKG1-PR-D-1002-01 - 7

20 PSL-1002 NK1-OST-02 5085-NKG1-PR-D-1002-01 - 7

21 PSL-1003 NK1-OST-03 5085-NKG1-PR-D-1002-01 - 7

22 PSL-1004 NK1-OST-04 5085-NKG1-PR-D-1002-01 - 7

23 PSL-2001 NK1-TT-01 5085-NKG1-PR-D-1002-01 - 7

24 PSL-2002 NK1-TT-02 5085-NKG1-PR-D-1002-01 - 7

25 PSL-2003 NK1-AT-01 5085-NKG1-PR-D-1002-01 - 7

26 PSL-1005 NK1-ET-01 5085-NKG1-PR-D-1002-02 - 7

26 PSL-1006 NK1-ET-02 5085-NKG1-PR-D-1002-02 - 7

Notes:

1 All tag numbers shall be prefixed by area code NKG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 17 OF 22
NORTH KADI GGS-II
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 10.5

2 PSH-1001B NK2-OST-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 10.5

3 PSH-1002A NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 10.5

4 PSH-1002B NK2-OST-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 10.5

5 PSH-1003A NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 10.5

6 PSH-1003B NK2-OST-03 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 10.5

7 PSH-1004A NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 10.5

8 PSH-1004B NK2-OST-04 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 10.5

9 PSH-1005A NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 10.5

10 PSH-1005B NK2-WT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 10.5

11 PSH-1006A NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 10.5

12 PSH-1006B NK2-WT-02 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 10.5

13 PSH-2001A NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 10.5

14 PSH-2001B NK2-TT-01 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 10.5

15 PSH-2002A NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 10.5

16 PSH-2002B NK2-TT-02 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 10.5

17 PSH-2003A NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 10.5

18 PSH-2003B NK2-AT-01 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 10.5

19 PSL-1001 NK2-OST-01 5085-NKG2-PR-D-1002-01 - 7

20 PSL-1002 NK2-OST-02 5085-NKG2-PR-D-1002-01 - 7

21 PSL-1003 NK2-OST-03 5085-NKG2-PR-D-1002-01 - 7

22 PSL-1004 NK2-OST-04 5085-NKG2-PR-D-1002-01 - 7

23 PSL-1005 NK2-WT-01 5085-NKG2-PR-D-1002-01 - 7

24 PSL-1006 NK2-WT-02 5085-NKG2-PR-D-1002-01 - 7

25 PSL-2001 NK2-TT-01 5085-NKG2-PR-D-1002-01 - 7

26 PSL-2002 NK2-TT-02 5085-NKG2-PR-D-1002-01 - 7

27 PSL-2003 NK2-AT-01 5085-NKG2-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code NKG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 18 OF 22
NORTH KADI GGS-III
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 10.5

2 PSH-1001B NK3-OST-01 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 10.5

3 PSH-1002A NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 10.5

4 PSH-1002B NK3-OST-02 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 10.5

5 PSH-1003A NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 10.5

6 PSH-1003B NK3-OST-03 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 10.5

7 PSH-1004A NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 10.5

8 PSH-1004B NK3-OST-04 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 10.5

9 PSH-2001A NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 10.5

10 PSH-2001B NK3-TT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 10.5

11 PSH-2002A NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 10.5

12 PSH-2002B NK3-TT-2 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 10.5

13 PSH-2003A NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 10.5

14 PSH-2003B NK3-AT-1 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 10.5

15 PSH-2004A NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6036-AM3 10.5

16 PSH-2004B NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 10.5

17 PSH-1005A NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 10.5

18 PSH-1005B NK3-ET-01 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 10.5

19 PSH-1006A NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 10.5

20 PSH-1006B NK3-ET-02 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 10.5

21 PSL-1001 NK3-OST-01 5085-NKG3-PR-D-1002-01 - 7

22 PSL-1002 NK3-OST-02 5085-NKG3-PR-D-1002-01 - 7

23 PSL-1003 NK3-OST-03 5085-NKG3-PR-D-1002-01 - 7

24 PSL-1004 NK3-OST-04 5085-NKG3-PR-D-1002-01 - 7

25 PSL-2001 NK3-TT-1 5085-NKG3-PR-D-1002-01 - 7

26 PSL-2002 NK3-TT-2 5085-NKG3-PR-D-1002-01 - 7

27 PSL-2003 NK3-AT-1 5085-NKG3-PR-D-1002-01 - 7

28 PSL-2004 NK3-HOEC-1/2 5085-NKG3-PR-D-1002-02 - 7

29 PSL-1005 NK3-ET-01 5085-NKG3-PR-D-1002-02 - 7

30 PSL-1006 NK3-ET-02 5085-NKG3-PR-D-1002-02 - 7

Notes:

1 All tag numbers shall be prefixed by area code NKG3


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 19 OF 22
NORTH KADI GGS-IV
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-3001A LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 10.5

2 PSH-3001B LP COMPRESSOR 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 10.5

3 PSH-1001A 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6031-AM3 10.5

4 PSH-1001B 10-TT-102A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 10.5

5 PSH-1002A 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 10.5

6 PSH-1002B 10-TT-102B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 10.5

7 PSH-1003A 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 10.5

8 PSH-1003B 10-TT-102C 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 10.5

9 PSH-1004A 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 10.5

10 PSH-1004B 10-TT-102D 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 10.5

11 PSH-2001A 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 10.5

12 PSH-2001B 10-TT-101B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 10.5

13 PSH-2002A 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 10.5

14 PSH-2002B 10-TT-101A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 10.5

15 PSH-2003A 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 10.5

16 PSH-2003B 10-AT-101A/B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 10.5

17 PSH-1005A 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 10.5

18 PSH-1005B 10-TT-103A 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 10.5

19 PSH-1006A 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 10.5

20 PSH-1006B 10-TT-103B 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 10.5

21 PSL-1001 10-TT-102A 5085-NKG4-PR-D-1002-02 - 7

22 PSL-1002 10-TT-102B 5085-NKG4-PR-D-1002-02 - 7

23 PSL-1003 10-TT-102C 5085-NKG4-PR-D-1002-02 - 7

24 PSL-1004 10-TT-102D 5085-NKG4-PR-D-1002-02 - 7

25 PSL-2001 10-TT-101B 5085-NKG4-PR-D-1002-02 - 7

26 PSL-2002 10-TT-101A 5085-NKG4-PR-D-1002-02 - 7

27 PSL-2003 10-AT-101A/B 5085-NKG4-PR-D-1002-02 - 7

28 PSL-1005 10-TT-103A 5085-NKG4-PR-D-1002-02 - 7

29 PSL-1006 10-TT-103B 5085-NKG4-PR-D-1002-02 - 7

30 PSL-3001 LP COMPRESSOR 5085-NKG4-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code NKG4


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 20 OF 22
SOBHASAN GGS-I
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 10.5

2 PSH-1001B SOB1-ST-05 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6037-AM3 10.5

3 PSH-1002A SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6035-AM3 10.5

4 PSH-1002B SOB1-ST-06 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6036-AM3 10.5

5 PSH-1003A SOB1-ST-01 / SS-02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6036-AM3 10.5

6 PSH-1003B SOB1-ST-01 / SS-02 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6036-AM3 10.5

7 PSH-2001A SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 10.5

8 PSH-2001B SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6028-AM3 10.5

9 PSL-1001 SOB1-ST-05 5085-SOG1-PR-D-1002-01 - 7

10 PSL-1002 SOB1-ST-06 5085-SOG1-PR-D-1002-01 - 7

11 PSL-1003 SOB1-ST-01/02 5085-SOG1-PR-D-1002-01 - 7

12 PSL-2001 SOB1-TT-01 / ST-03 5085-SOG1-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code SOG1


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 21 OF 22
SOBHASAN GGS-II
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 10.5

2 PSH-1001B SOB2-ST-01 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 10.5

3 PSH-1008A SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 10.5

4 PSH-1008B SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 10.5

5 PSH-2002A SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 10.5

6 PSH-2002B SOB2-ACT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 10.5

7 PSH-2001A SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 10.5

8 PSH-2001B SOB2-TT-03 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 10.5

9 PSH-1009A SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 10.5

10 PSH-1009B SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 10.5

11 PSH-1005A SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 10.5

12 PSH-1005B SOB2-ST-08 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 10.5

13 PSH-1007A SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 10.5

14 PSH-1007B SOB2-WT-02 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 10.5

15 PSH-1002A SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 10.5

16 PSH-1002B SOB2-ST-05 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 10.5

17 PSH-1003A SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 10.5

18 PSH-1003B SOB2-ST-06 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 10.5

19 PSH-1004A SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 10.5

20 PSH-1004B SOB2-ST-07 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 10.5

21 PSH-1006A SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 10.5

22 PSH-1006B SOB2-WT-01 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 10.5

27 PSL-1001 SOB2-ST-01 5085-SOG2-PR-D-1002-01 - 7

28 PSL-1008 SOB2-CU-T-02 5085-SOG2-PR-D-1002-01 - 7

29 PSL-2002 SOB2-ACT-01 5085-SOG2-PR-D-1002-01 - 7

30 PSL-2001 SOB2-TT-03 5085-SOG2-PR-D-1002-01 - 7

31 PSL-1009 SOB2-CU-T-04 5085-SOG2-PR-D-1002-01 - 7

32 PSL-1005 SOB2-ST-08 5085-SOG2-PR-D-1002-01 - 7

33 PSL-1007 SOB2-WT-02 5085-SOG2-PR-D-1002-01 - 7

34 PSL-1002 SOB2-ST-05 5085-SOG2-PR-D-1002-01 - 7

35 PSL-1003 SOB2-ST-06 5085-SOG2-PR-D-1002-01 - 7

36 PSL-1004 SOB2-ST-07 5085-SOG2-PR-D-1002-01 - 7

37 PSL-1006 SOB2-WT-01 5085-SOG2-PR-D-1002-01 - 7

Notes:

1 All tag numbers shall be prefixed by area code SOG2


ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET
SHEET 22 OF 22
SOBHASAN WWTP
DOC.NO : 5085-COMM-IN-J-1006

Operating Pressure
S.No Tag Number Service PID Number Equipment / Line Number Remarks
kg/cm2g

1 PSH-1001A SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 10.5

2 PSH-1001B SOBETP-WT-101A 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 10.5

3 PSH-1002A SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 10.5

4 PSH-1002B SOBETP-WT-101B 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 10.5

5 PSH-1003A SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6050-AM3 10.5

6 PSH-1003B SOBETP-WT-01 5085-SOW-PR-D-1002-01 4"-FW-SOW-6053-AM3 10.5

7 PSH-1004A SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6037-AM3 10.5

8 PSH-1004B SOBETP-WT-02 5085-SOW-PR-D-1002-01 3"-FW-SOW-6038-AM3 10.5

9 PSL-1001 SOBETP-WT-101A 5085-SOW-PR-D-1002-01 - 7

10 PSL-1002 SOBETP-WT-101B 5085-SOW-PR-D-1002-01 - 7

13 PSL-1003 SOBETP-WT-01 5085-SOW-PR-D-1002-02 - 7

14 PSL-1004 SOBETP-WT-02 5085-SOW-PR-D-1002-02 - 7

Notes:

1 All tag numbers shall be prefixed by area code SOW


REVISIONS
TAG NOS /
PAGE NO REMARKS
DESCRIPTION
0 1

1 Cover Sheet X X

2 Revision Sheet X X

3 LIT- XXXX X X

4 Notes X X

5 Annexure X X

Document No:

5085-COMM-IN-J-1007
SHEET : 02 OF 5
1 Tag Number See Annexure

2 Service Fire Water Tank

3 Location Field

GENERAL 4 Equipment / Line Number See Annexure

5 P&ID Number See Annexure

6 Ambient Temperature Min Max °C -2 50

7 Area Classification Enclosure Type Zone 2, Group IIA&B, T3 IP 65, Instrinsically safe - Ex'i

8 Fluid Fluid State Water Liquid


9 Design Pressure kPag
kPag Design Temperature °C ATM AMB
10 Inlet Pressure Minimum Normal Maximum kPag ATM
PROCESS CONDITION 11 Temperature Minimum Normal Maximum °C AMB
12 Upper Fluid Lower Fluid Water --
13 Interface Oper. Specific Gravity NA 1
14 Corrosion NA
15 Type Float and Tape type Level transmitter
16 Measuring Principle Mounting Float and Tape Top
17 Output 4-20 mA HART PROTOCOL
18 Probe Material SS316
19 Measuring Range Min mm Max mm See Annexure See Annexure
TRANSMITTER
20 Process Connection Rating 2" Flanged 150#
21 Transmitter Orientation Enclosure material Top MFR Std
22 Electrical Connection 1/2 " NPTF
23 Power Supply Output/Protocol 24 VDC, Loop powered 4-20 mA/HART
24 Accuracy Integral Display ±0.1% Required
15 Type Orientation NA NA
16 Measuring Length mm Tank Height mm NA NA

17 Sections Required NA
18 Connection Size Rating NA NA
19 Connection Arrangement NA
GAUGE 20 Gauge Body Material NA
21 Float Material NA
22 Indication Assembly NA
23 Indication Type NA
24 Bolts and Nuts NA
25 Frost Extension Length NA NA
32 Manufacturer *
33 Model *

PURCHASE 34 Purchase order Number *

35 Price *

36 Serial Number Item Number * *

NOTES :

1. * - VENDOR to specify / furnish

DATASHEET
FOR
LEVEL TRANSMITTER - FLOAT AND TAPE
1 AP 18.01.2018 Re-Issued for Bid TYPE
0 AMV 06.10.2016 Issued for Bid SHEET : 03 OF 5

REV BY DATE DESCRIPTION DOC.NO : 5085-COMM-IN-J-1007 CODE : 5085 REV. 1


GENERAL NOTES - FLOAT AND TAPE TYPE LEVEL TRANSMITTER
1 Vendor shall provide all the mounting accessories for the board and guide wires .
2 Supplier shall provide probe which can be cut at site to suit the installation.
3 The level gauge will be designed to withstand loads induced by the connecting piping without affecting the sealing joints.
4 Stainless steel nameplates permanently bolted to the instrument containing Tag number, Serial number, Model Number shall be provided by
vendor in addition to manufacturer's standard tagging information.

ELECTRONICS
5 Zero and span shall be non-interactive and continuously adjustable externally.
6 Adjustments shall be possible using a HART hand held communicator unit or from the main control system. The smart facility shall be disabled,
once configured and installed, when applied in Safety shutdown services. Signal wiring terminals shall be of the screw type.
7 The specific gravity /dielectric constant adjustment will be easily accessible and built into the transmitter enclosure. Changes in dielectric constant/specific
gravity shall not affect instrument zero.
8 The transmitter shall have over-range protection provided up to the maximum chamber rating without temporary or permanent damage to the
measuring assembly.
9 The transmitter accuracy including the combined effects of linearity, hysterisis and repeatability will be equal to or better than ± 0.1% of calibrated span,
temperature effects at calibrated span per 50°C.
10 The transmitter housing material shall be of low copper aluminium and painted to manufacturer standard.
11 Unused entries shall be plugged off in compliance with the electrical safety certificate.
12 An integral digital output meter calibrated in engineering units (%) shall be fitted as specified in the data sheet.
13 The transmitter housing material shall be of low copper aluminium and painted to manufacturer standard.
14 Unused entries shall be plugged off in compliance with the electrical safety certificate.
15 An integral digital output meter calibrated in engineering units (%) shall be fitted as specified in the data sheet.

IDENTIFICATION
16 The transmitter shall be provided with a non-removable stainless steel nameplate engraved with the following.
(I) Instrument Tag number
(II) Manufacturer and Model No
(III) Manufacturer Serial No
(IV) Range including units of measure
(V) Service and Body Rating
(VI) End Connection
(VII) Electrical Certification

MATERIAL REQUIREMENTS
17 The materials of construction of the transmitters shall be suitable for the process conditions as detailed in the data sheets.

GENERAL NOTES
FOR
1 AP 18.01.2018 Re-Issued for Bid LEVEL TRANSMITTER
0 AMV 06.10.2016 Issued for Bid SHEET : 04 OF 05
REV BY DATE DESCRIPTION DOC.NO 5085-COMM-IN-J-1007 CODE : 5085 REV.1
ANNEXURE
REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET SHEET 05 OF 05

DOC.NO 5085-COMM-IN-J-1007

Measuring Range
Equipment / Line (mm)
S.No Area Code Installation Name Tag Number PID Number Remarks
Number
Min Max

1 BAG1 BALOL GGS-I LIT-0101 5085-BAG1-PR-D-1001-01 - 0 4200

2 BAG1 BALOL GGS-I LIT-0102 5085-BAG1-PR-D-1001-01 - 0 4200

3 BAG2 BALOL GGS-II LIT-0101 5085-BAG2-PR-D-1001-01 - 0 2600

4 BAG2 BALOL GGS-II LIT-0102 5085-BAG2-PR-D-1001-01 - 0 2600

5 BAG3 BALOL GGS-III LIT-0101 5085-BAG3-PR-D-1001-01 - Note 2

6 BAG3 BALOL GGS-III LIT-0102 5085-BAG3-PR-D-1001-01 - Note 2

7 BAG4 BALOL GGS-IV LIT-0101 5085-BAG4-PR-D-1001-01 - 0 2600

8 BAG4 BALOL GGS-IV LIT-0102 5085-BAG4-PR-D-1001-01 - 0 2600

9 BEG1 BECHRAJI GGS-I LIT-0101 5085-BEG1-PR-D-1001-01 - Note 2

10 BEG1 BECHRAJI GGS-I LIT-0102 5085-BEG1-PR-D-1001-01 - Note 2

11 BEG2 BECHRAJI GGS-II LIT-0101 5085-BEG2-PR-D-1001-01 - Note 2

12 BEG2 BECHRAJI GGS-II LIT-0102 5085-BEG2-PR-D-1001-01 - Note 2

13 JOG1 JOTANA GGS LIT-0101 5085-JOG1-PR-D-1001-01 - Note 2

14 JOG1 JOTANA GGS LIT-0102 5085-JOG1-PR-D-1001-01 - Note 2

15 LAG2 LANWA GGS-II LIT-0101 5085-LAG2-PR-D-1001-01 - Note 2

16 LAG2 LANWA GGS-II LIT-0102 5085-LAG2-PR-D-1001-01 - Note 2

17 LAG3 LANWA GGS-III LIT-0101 5085-LAG3-PR-D-1001-01 - Note 2

18 LAG3 LANWA GGS-III LIT-0102 5085-LAG3-PR-D-1001-01 - Note 2

19 LGE LANGHNAJ EPS LIT-0101 5085-LGE-PR-D-1001-01 - Note 2

20 LGE LANGHNAJ EPS LIT-0102 5085-LGE-PR-D-1001-01 - Note 2

21 NKG1 NORTH KADI GGS-I LIT-0101 5085-NKG1-PR-D-1001-01 - 0 2700

22 NKG1 NORTH KADI GGS-I LIT-0102 5085-NKG1-PR-D-1001-01 - 0 2700

23 NKG2 NORTH KADI GGS-II LIT-0101 5085-NKG2-PR-D-1001-01 - 0 4500

24 NKG2 NORTH KADI GGS-II LIT-0102 5085-NKG2-PR-D-1001-01 - 0 4500

25 NKG3 NORTH KADI GGS-III LIT-0101 5085-NKG3-PR-D-1001-01 - Note 2

26 NKG3 NORTH KADI GGS-III LIT-0102 5085-NKG3-PR-D-1001-01 - Note 2

27 NKG4 NORTH KADI GGS-IV LIT-0101 5085-NKG4-PR-D-1001-01 - Note 2

28 NKG4 NORTH KADI GGS-IV LIT-0102 5085-NKG4-PR-D-1001-01 - Note 2

29 SOG1 SOBHASAN GGS-I LIT-0101 5085-SOG1-PR-D-1001-01 - Note 2

30 SOG1 SOBHASAN GGS-I LIT-0102 5085-SOG1-PR-D-1001-01 - 0 5000

31 SOG2 SOBHASAN GGS-II LIT-0101 5085-SOG2-PR-D-1001-01 - Note 2

32 SOG2 SOBHASAN GGS-II LIT-0102 5085-SOG2-PR-D-1001-01 - Note 2

33 SOW SOBHASAN WWTP LIT-0101 5085-SOW-PR-D-1001-01 - Note 2

34 SOW SOBHASAN WWTP LIT-0102 5085-SOW-PR-D-1001-01 - Note 2

35 LAG1 LANWA GGS-I LIT-0101 5085-LAG1-PR-D-1001-01 - Note 2

36 LAG1 LANWA GGS-I LIT-0102 5085-LAG1-PR-D-1001-01 - Note 2

Notes:

1 All tag numbers shall be prefixed by area code

2 Tank height shall be checked and confirmed by Engineering Contractor during site survey
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - JOGANA GGS
Document Title : INSTRUMENT INDEX
Document No : 5085-JOG-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG1-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE JOG-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 3"-FW-JOG-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE JOG-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 2"-FW-JOG-6012-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6019-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6019-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6019-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE JOG-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 2"-FW-JOG-6021-AA3
13 HS-0102A-START PUMP START COMMAND JOG-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND JOG-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND JOG-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION JOG-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION JOG-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION JOG-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION JOG-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE JOG-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 3"-FW-JOG-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE JOG-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 2"-FW-JOG-6013-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE JOG-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 2"-FW-JOG-6023-AA3
23 HS-0102B-START PUMP START COMMAND JOG-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND JOG-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND JOG-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION JOG-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION JOG-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION JOG-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION JOG-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE JOG-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6010-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE JOG-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6014-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND JOG-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND JOG-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION JOG-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION JOG-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION JOG-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION JOG-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE JOG-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6011-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE JOG-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6015-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND JOG-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND JOG-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION JOG-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION JOG-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION JOG-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION JOG-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6016-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6016-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 8"-FW-JOG-6016-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-JOG-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6016-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6018-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6017-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6025-AA3 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6026-AA3 5085-COMM-IN-J-1003
61 PI-0206 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6027-AA3 5085-COMM-IN-J-1003
62 PI-0207 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 8"-FW-JOG1-6028-AA3 5085-COMM-IN-J-1003
63 RO-2001 RESTRICTION ORIFICE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
64 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AA3 5085-COMM-IN-J-1003
65 DPI-2001A DIFFERENTIAL PRESSURE GAUGE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AA3 5085-COMM-IN-J-1004
66 DV-2001A DELUGE VALVE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AA3 5085-COMM-IN-J-1001
67 XSY-2001A SOLENOID VALVE JOT-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
68 PSL-2001 PRESSURE SWITCH JOT-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
69 PAL-2001 PRESSURE ALARM LOW JOT-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
70 PSH-2001A PRESSURE SWITCH JOT-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AA3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
71 PAH-2001A PRESSURE ALARM HIGH JOT-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
72 RO-2001A RESTRICTION ORIFICE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6030-AA3 -
73 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AA3 5085-COMM-IN-J-1003
74 DPI-2001B DIFFERENTIAL PRESSURE GAUGE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AA3 5085-COMM-IN-J-1004
75 DV-2001B DELUGE VALVE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AA3 5085-COMM-IN-J-1001
76 XSY-2001B SOLENOID VALVE JOT-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
77 PSH-2001B PRESSURE SWITCH JOT-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AA3 5085-COMM-IN-J-1006
78 PAH-2001B PRESSURE ALARM HIGH JOT-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
79 RO-2001B RESTRICTION ORIFICE JOT-ST-01 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6036-AA3 -
80 RO-2002 RESTRICTION ORIFICE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
81 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AA3 5085-COMM-IN-J-1003
82 DPI-2002A DIFFERENTIAL PRESSURE GAUGE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AA3 5085-COMM-IN-J-1004
83 DV-2002A DELUGE VALVE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AA3 5085-COMM-IN-J-1001
84 XSY-2002A SOLENOID VALVE JOT-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
85 PSL-2002 PRESSURE SWITCH JOT-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
86 PAL-2002 PRESSURE ALARM LOW JOT-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
87 PSH-2002A PRESSURE SWITCH JOT-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AA3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
88 PAH-2002A PRESSURE ALARM HIGH JOT-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
89 RO-2002A RESTRICTION ORIFICE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6035-AA3 -
90 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AA3 5085-COMM-IN-J-1003
91 DPI-2002B DIFFERENTIAL PRESSURE GAUGE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AA3 5085-COMM-IN-J-1004
92 DV-2002B DELUGE VALVE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AA3 5085-COMM-IN-J-1001
93 XSY-2002B SOLENOID VALVE JOT-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
94 PSH-2002B PRESSURE SWITCH JOT-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AA3 5085-COMM-IN-J-1006
95 PAH-2002B PRESSURE ALARM HIGH JOT-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
96 RO-2002B RESTRICTION ORIFICE JOT-ST-02 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 2"-FW-JOG-6029-AA3 -
97 RO-1001 RESTRICTION ORIFICE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
98 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AA3 5085-COMM-IN-J-1003
99 DPI-1001A DIFFERENTIAL PRESSURE GAUGE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AA3 5085-COMM-IN-J-1004
100 DV-1001A DELUGE VALVE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AA3 5085-COMM-IN-J-1001

SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - JOGANA GGS
Document Title : INSTRUMENT INDEX
Document No : 5085-JOG-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 XSY-1001A SOLENOID VALVE JOT-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
102 PSL-1001 PRESSURE SWITCH JOT-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
103 PAL-1001 PRESSURE ALARM LOW JOT-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
104 PSH-1001A PRESSURE SWITCH JOT-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AA3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
105 PAH-1001A PRESSURE ALARM HIGH JOT-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
106 RO-1001A RESTRICTION ORIFICE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6032-AA3 -
107 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AA3 5085-COMM-IN-J-1003
108 DPI-1001B DIFFERENTIAL PRESSURE GAUGE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AA3 5085-COMM-IN-J-1004
109 DV-1001B DELUGE VALVE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AA3 5085-COMM-IN-J-1001
110 XSY-1001B SOLENOID VALVE JOT-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
111 PSH-1001B PRESSURE SWITCH JOT-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AA3 5085-COMM-IN-J-1006
112 PAH-1001B PRESSURE ALARM HIGH JOT-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
113 RO-1001B RESTRICTION ORIFICE JOT-ST-03 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6038-AA3 -
114 RO-1002 RESTRICTION ORIFICE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
115 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 5085-COMM-IN-J-1003
116 DPI-1002A DIFFERENTIAL PRESSURE GAUGE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 5085-COMM-IN-J-1004
117 DV-1002A DELUGE VALVE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 5085-COMM-IN-J-1001
118 XSY-1002A SOLENOID VALVE JOT-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
119 PSL-1002 PRESSURE SWITCH JOT-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
120 PAL-1002 PRESSURE ALARM LOW JOT-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
121 PSH-1002A PRESSURE SWITCH JOT-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
122 PAH-1002A PRESSURE ALARM HIGH JOT-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
123 RO-1002A RESTRICTION ORIFICE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6037-AM3 -
124 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 5085-COMM-IN-J-1003
125 DPI-1002B DIFFERENTIAL PRESSURE GAUGE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 5085-COMM-IN-J-1004
126 DV-1002B DELUGE VALVE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 5085-COMM-IN-J-1001
127 XSY-1002B SOLENOID VALVE JOT-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
128 PSH-1002B PRESSURE SWITCH JOT-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 5085-COMM-IN-J-1006
129 PAH-1002B PRESSURE ALARM HIGH JOT-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
130 RO-1002B RESTRICTION ORIFICE JOT-ST-04 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6031-AM3 -
131 RO-1003 RESTRICTION ORIFICE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
132 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 5085-COMM-IN-J-1003
133 DPI-1003A DIFFERENTIAL PRESSURE GAUGE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 5085-COMM-IN-J-1004
134 DV-1003A DELUGE VALVE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 5085-COMM-IN-J-1001
135 XSY-1003A SOLENOID VALVE JOT-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
136 PSL-1003 PRESSURE SWITCH JOT-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
137 PAL-1003 PRESSURE ALARM LOW JOT-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
138 PSH-1003A PRESSURE SWITCH JOT-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
139 PAH-1003A PRESSURE ALARM HIGH JOT-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
140 RO-1003A RESTRICTION ORIFICE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6034-AM3 -
141 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 5085-COMM-IN-J-1003
142 DPI-1003B DIFFERENTIAL PRESSURE GAUGE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 5085-COMM-IN-J-1004
143 DV-1003B DELUGE VALVE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 5085-COMM-IN-J-1001
144 XSY-1003B SOLENOID VALVE JOT-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
145 PSH-1003B PRESSURE SWITCH JOT-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 5085-COMM-IN-J-1006
146 PAH-1003B PRESSURE ALARM HIGH JOT-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
147 RO-1003B RESTRICTION ORIFICE JOT-ST-05 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6040-AM3 -
148 RO-1004 RESTRICTION ORIFICE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
149 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 5085-COMM-IN-J-1003
150 DPI-1004A DIFFERENTIAL PRESSURE GAUGE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 5085-COMM-IN-J-1004
151 DV-1004A DELUGE VALVE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 5085-COMM-IN-J-1001
152 XSY-1004A SOLENOID VALVE JOT-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
153 PSL-1004 PRESSURE SWITCH JOT-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
154 PAL-1004 PRESSURE ALARM LOW JOT-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
155 PSH-1004A PRESSURE SWITCH JOT-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
156 PAH-1004A PRESSURE ALARM HIGH JOT-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
157 RO-1004A RESTRICTION ORIFICE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6033-AM3 -
158 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 5085-COMM-IN-J-1003
159 DPI-1004B DIFFERENTIAL PRESSURE GAUGE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 5085-COMM-IN-J-1004
160 DV-1004B DELUGE VALVE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 5085-COMM-IN-J-1001
161 XSY-1004B SOLENOID VALVE JOT-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
162 PSH-1004B PRESSURE SWITCH JOT-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 5085-COMM-IN-J-1006
163 PAH-1004B PRESSURE ALARM HIGH JOT-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
164 RO-1004B RESTRICTION ORIFICE JOT-ST-06 FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6039-AM3 -
165 RO-3001 RESTRICTION ORIFICE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
166 PI-3001A PRESSURE INDICATOR-MANIFOLD TYPE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 5085-COMM-IN-J-1003
167 DPI-3001A DIFFERENTIAL PRESSURE GAUGE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 5085-COMM-IN-J-1004
168 DV-3001A DELUGE VALVE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 5085-COMM-IN-J-1001
169 XSY-3001A SOLENOID VALVE COMPRESSOR FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
170 PSL-3001 PRESSURE SWITCH COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - 5085-COMM-IN-J-1006
171 PAL-3001 PRESSURE ALARM LOW COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
172 PSH-3001A PRESSURE SWITCH COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
173 PAH-3001A PRESSURE ALARM HIGH COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
5085-COMM-PR-D-1003
174 RO-3001A RESTRICTION ORIFICE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6042-AM3 -
175 PI-3001B PRESSURE INDICATOR-MANIFOLD TYPE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 5085-COMM-IN-J-1003
176 DPI-3001B DIFFERENTIAL PRESSURE GAUGE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 5085-COMM-IN-J-1004
177 DV-3001B DELUGE VALVE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 5085-COMM-IN-J-1001
178 XSY-3001B SOLENOID VALVE COMPRESSOR FIELD RTU DOP FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
179 PSH-3001B PRESSURE SWITCH COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 5085-COMM-IN-J-1006
180 PAH-3001B PRESSURE ALARM HIGH COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 - -
181 RO-3001B RESTRICTION ORIFICE COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-JOG-PR-D-1002-01 3"-FW-JOG-6041-AM3 -

SHEET 3 OF 3
FIRE FIGHTING SYSTEM UPGRADATION OF 17
INSTALLATIONS AT MEHSANA ASSET

I/O List Rev: 1


Doc No:5085-JOG-IN-K-1002 Page: 2 of 2

JOTANA GGS
AI DI DO DOP

RTU 2 21 6 14

RTU SPARE WITH


3 27 8 18
30% CONTINGENCY

FWCP 3 16 4 -

FWCP SPARE WITH


4 21 5 -
30% CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - I
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (LAG1-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK (LAG1-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK (LAG1-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE LAG1-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 3"-FW-LAG1-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE LAG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 2"-FW-LAG1-6015-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6017-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6017-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6017-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE LAG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 2"-FW-LAG1-6021-AA3
13 HS-0102A-START PUMP START COMMAND LAG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND LAG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND LAG1-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION LAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION LAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION LAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION LAG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE LAG1-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 3"-FW-LAG1-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE LAG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 2"-FW-LAG1-6014-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE LAG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 2"-FW-LAG1-6022-AA3
23 HS-0102B-START PUMP START COMMAND LAG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND LAG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND LAG1-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION LAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION LAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION LAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION LAG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE LAG1-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6010-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE LAG1-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6013-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND LAG1-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND LAG1-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION LAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION LAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION LAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION LAG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE LAG1-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6011-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE LAG1-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6012-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND LAG1-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND LAG1-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION LAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION LAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION LAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION LAG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6018-AA3 5085-COMM-IN-J-1002

47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -

49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6018-AA3 5085-COMM-IN-J-1002

50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -

52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6018-AA3 5085-COMM-IN-J-1002

53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG1-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1001-01 8"-FW-LAG1-6023-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 8"-FW-LAG1-6019-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 8"-FW-LAG1-6019-AA3 5085-COMM-IN-J-1003
59 RO-1001 RESTRICTION ORIFICE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
60 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 5085-COMM-IN-J-1003
61 DPI-1001A DIFFERENTIAL PRESSURE GAUGE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 5085-COMM-IN-J-1004
62 DV-1001A DELUGE VALVE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 5085-COMM-IN-J-1001
63 XSY-1001A SOLENOID VALVE LAN1-ST-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
64 PSL-1001 PRESSURE SWITCH LAN1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAL-1001 PRESSURE ALARM LOW LAN1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
66 PSH-1001A PRESSURE SWITCH LAN1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
67 PAH-1001A PRESSURE ALARM HIGH LAN1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
68 RO-1001A RESTRICTION ORIFICE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6025-AM3 -
69 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 5085-COMM-IN-J-1003
70 DPI-1001B DIFFERENTIAL PRESSURE GAUGE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 5085-COMM-IN-J-1004
71 DV-1001B DELUGE VALVE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 5085-COMM-IN-J-1001
72 XSY-1001B SOLENOID VALVE LAN1-ST-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
73 PSH-1001B PRESSURE SWITCH LAN1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 5085-COMM-IN-J-1006
74 PAH-1001B PRESSURE ALARM HIGH LAN1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
75 RO-1001B RESTRICTION ORIFICE LAN1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6034-AM3 -
76 RO-1002 RESTRICTION ORIFICE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
77 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 5085-COMM-IN-J-1003
78 DPI-1002A DIFFERENTIAL PRESSURE GAUGE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 5085-COMM-IN-J-1004
79 DV-1002A DELUGE VALVE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 5085-COMM-IN-J-1001
80 XSY-1002A SOLENOID VALVE LAN1-ST-03/04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
81 PSL-1002 PRESSURE SWITCH LAN1-ST-03/04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
82 PAL-1002 PRESSURE ALARM LOW LAN1-ST-03/04 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
83 PSH-1002A PRESSURE SWITCH LAN1-ST-03/04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
84 PAH-1002A PRESSURE ALARM HIGH LAN1-ST-03/04 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
85 RO-1002A RESTRICTION ORIFICE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6033-AM3 -
86 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 5085-COMM-IN-J-1003
87 DPI-1002B DIFFERENTIAL PRESSURE GAUGE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 5085-COMM-IN-J-1004
88 DV-1002B DELUGE VALVE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 5085-COMM-IN-J-1001
89 XSY-1002B SOLENOID VALVE LAN1-ST-03/04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
90 PSH-1002B PRESSURE SWITCH LAN1-ST-03/04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 5085-COMM-IN-J-1006
91 PAH-1002B PRESSURE ALARM HIGH LAN1-ST-03/04 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
92 RO-1002B RESTRICTION ORIFICE LAN1-ST-03/04 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6026-AM3 -
93 RO-1003 RESTRICTION ORIFICE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
94 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 5085-COMM-IN-J-1003
95 DPI-1003A DIFFERENTIAL PRESSURE GAUGE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 5085-COMM-IN-J-1004
96 DV-1003A DELUGE VALVE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 5085-COMM-IN-J-1001
97 XSY-1003A SOLENOID VALVE LAN1-ST-05/06 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
98 PSL-1003 PRESSURE SWITCH LAN1-ST-05/06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006

REFER DELUGE VALVE SCHEMATIC FOR TANKS


SHEET 2 OF 3
5085-COMM-PR-D-1003
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - I
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

99 PAL-1003 PRESSURE ALARM LOW LAN1-ST-05/06 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
100 PSH-1003A PRESSURE SWITCH LAN1-ST-05/06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
101 PAH-1003A PRESSURE ALARM HIGH LAN1-ST-05/06 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
102 RO-1003A RESTRICTION ORIFICE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6030-AM3 -
103 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 5085-COMM-IN-J-1003
104 DPI-1003B DIFFERENTIAL PRESSURE GAUGE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 5085-COMM-IN-J-1004
105 DV-1003B DELUGE VALVE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 5085-COMM-IN-J-1001
106 XSY-1003B SOLENOID VALVE LAN1-ST-05/06 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
107 PSH-1003B PRESSURE SWITCH LAN1-ST-05/06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 5085-COMM-IN-J-1006
108 PAH-1003B PRESSURE ALARM HIGH LAN1-ST-05/06 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
109 RO-1003B RESTRICTION ORIFICE LAN1-ST-05/06 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 3"-FW-LAG1-6048-AM3 -
110 RO-1004 RESTRICTION ORIFICE LAN1-ST-07/08 FIELD - - FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -
111 PSL-1004 PRESSURE SWITCH LAN1-ST-07/08 FIELD RTU DI FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
112 PAL-1004 PRESSURE ALARM LOW LAN1-ST-07/08 CCR - SOFT FIRE WATER NETWORK 5085-LAG1-PR-D-1002-01 - -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-LAG1-IN-K-1002 Page: 2 of 2

LANWA-GGS-I
AI DI DO DOP

RTU 2 10 6 6

RTU WITH 30%


3 13 8 8
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - 2
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE LAG2-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 3"-FW-LAG2-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE LAG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 2"-FW-LAG2-6015-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6017-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6017-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6017-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE LAG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 2"-FW-LAG2-6021-AA3
13 HS-0102A-START PUMP START COMMAND LAG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND LAG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND LAG2-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION LAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION LAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION LAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION LAG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE LAG2-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 3"-FW-LAG2-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE LAG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 2"-FW-LAG2-6014-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE LAG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 2"-FW-LAG2-6022-AA3
23 HS-0102B-START PUMP START COMMAND LAG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND LAG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND LAG2-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION LAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION LAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION LAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION LAG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE LAG2-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6010-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE LAG2-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 10"-FW-LAG2-6013-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND LAG2-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND LAG2-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION LAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION LAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION LAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION LAG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE LAG2-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 8"-FW-LAG2-6011-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE LAG2-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 10"-FW-LAG2-6012-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND LAG2-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND LAG2-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION LAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION LAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION LAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION LAG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 10"-FW-LAG2-6018-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 10"-FW-LAG2-6018-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 10"-FW-LAG2-6018-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG2-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 8"-FW-LAG2-6019-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
59 RO-1001 RESTRICTION ORIFICE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
60 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 5085-COMM-IN-J-1003
61 DPI-1001A DIFFERENTIAL PRESSURE GAUGE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 5085-COMM-IN-J-1004
62 DV-1001A DELUGE VALVE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 5085-COMM-IN-J-1001
63 XSY-1001A SOLENOID VALVE LAN2-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
64 PSH-1001 PRESSURE SWITCH LAN2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAH-1001 PRESSURE ALARM HIGH LAN2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
66 PSH-1001A PRESSURE SWITCH LAN2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
67 PAH-1001A PRESSURE ALARM HIGH LAN2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
68 RO-1001A RESTRICTION ORIFICE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6034-AM3 -
69 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6032-AM3 5085-COMM-IN-J-1003
70 DPI-1001B DIFFERENTIAL PRESSURE GAUGE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6032-AM3 5085-COMM-IN-J-1004
71 DV-1001B DELUGE VALVE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6032-AM3 5085-COMM-IN-J-1001
72 XSY-1001B SOLENOID VALVE LAN2-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
73 PSH-1001B PRESSURE SWITCH LAN2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6032-AM3 5085-COMM-IN-J-1006
74 PAH-1001B PRESSURE ALARM HIGH LAN2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
75 RO-1001B RESTRICTION ORIFICE LAN2-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6032-AM3 -
76 RO-1002 RESTRICTION ORIFICE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
77 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 5085-COMM-IN-J-1003
78 DPI-1002A DIFFERENTIAL PRESSURE GAUGE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 5085-COMM-IN-J-1004
79 DV-1002A DELUGE VALVE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 5085-COMM-IN-J-1001
80 XSY-1002A SOLENOID VALVE LAN2-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
81 PSH-1002 PRESSURE SWITCH LAN2-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
82 PAH-1002 PRESSURE ALARM HIGH LAN2-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
83 PSH-1002A PRESSURE SWITCH LAN2-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
84 PAH-1002A PRESSURE ALARM HIGH LAN2-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
85 RO-1002A RESTRICTION ORIFICE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6036-AM3 -
86 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 5085-COMM-IN-J-1003
87 DPI-1002B DIFFERENTIAL PRESSURE GAUGE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 5085-COMM-IN-J-1004
88 DV-1002B DELUGE VALVE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 5085-COMM-IN-J-1001
89 XSY-1002B SOLENOID VALVE LAN2-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
90 PSH-1002B PRESSURE SWITCH LAN2-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 5085-COMM-IN-J-1006
91 PAH-1002B PRESSURE ALARM HIGH LAN2-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
92 RO-1002B RESTRICTION ORIFICE LAN2-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6037-AM3 -
93 RO-1003 RESTRICTION ORIFICE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
94 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 5085-COMM-IN-J-1003
95 DPI-1003A DIFFERENTIAL PRESSURE GAUGE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 5085-COMM-IN-J-1004
96 DV-1003A DELUGE VALVE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 5085-COMM-IN-J-1001
97 XSY-1003A SOLENOID VALVE LAN2-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
98 PSH-1003 PRESSURE SWITCH LAN2-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
99 PAH-1003 PRESSURE ALARM HIGH LAN2-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
100 PSH-1003A PRESSURE SWITCH LAN2-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
5085-COMM-PR-D-1003
SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - 2
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks
REFER DELUGE VALVE SCHEMATIC FOR TANKS
101 PAH-1003A PRESSURE ALARM HIGH LAN2-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
102 RO-1003A RESTRICTION ORIFICE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6035-AM3 -
103 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6031-AM3 5085-COMM-IN-J-1003
104 DPI-1003B DIFFERENTIAL PRESSURE GAUGE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6031-AM3 5085-COMM-IN-J-1004
105 DV-1003B DELUGE VALVE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6031-AM3 5085-COMM-IN-J-1001
106 XSY-1003B SOLENOID VALVE LAN2-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
107 PSH-1003B PRESSURE SWITCH LAN2-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6031-AM3 5085-COMM-IN-J-1006
108 PAH-1003B PRESSURE ALARM HIGH LAN2-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
109 RO-1003B RESTRICTION ORIFICE LAN2-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6031-AM3 -
110 RO-1004 RESTRICTION ORIFICE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
111 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6023-AM3 5085-COMM-IN-J-1003
112 DPI-1004A DIFFERENTIAL PRESSURE GAUGE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6023-AM3 5085-COMM-IN-J-1004
113 DV-1004A DELUGE VALVE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6023-AM3 5085-COMM-IN-J-1001
114 XSY-1004A SOLENOID VALVE LAN2-EFLTK-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
115 PSH-1004 PRESSURE SWITCH LAN2-EFLTK-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
116 PAH-1004 PRESSURE ALARM HIGH LAN2-EFLTK-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
117 PSH-1004A PRESSURE SWITCH LAN2-EFLTK-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6023-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
118 PAH-1004A PRESSURE ALARM HIGH LAN2-EFLTK-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
119 RO-1004A RESTRICTION ORIFICE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6023-AM3 -
120 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6028-AM3 5085-COMM-IN-J-1003
121 DPI-1004B DIFFERENTIAL PRESSURE GAUGE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6028-AM3 5085-COMM-IN-J-1004
122 DV-1004B DELUGE VALVE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6028-AM3 5085-COMM-IN-J-1001
123 XSY-1004B SOLENOID VALVE LAN2-EFLTK-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
124 PSH-1004B PRESSURE SWITCH LAN2-EFLTK-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6028-AM3 5085-COMM-IN-J-1006
125 PAH-1004B PRESSURE ALARM HIGH LAN2-EFLTK-01/02 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
126 RO-1004B RESTRICTION ORIFICE LAN2-EFLTK-01/02 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 3"-FW-LAG2-6028-AM3 -
127 RO-2001 RESTRICTION ORIFICE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
128 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6030-AM3 5085-COMM-IN-J-1003
129 DPI-2001A DIFFERENTIAL PRESSURE GAUGE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6030-AM3 5085-COMM-IN-J-1004
130 DV-2001A DELUGE VALVE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6030-AM3 5085-COMM-IN-J-1001
131 XSY-2001A SOLENOID VALVE LAN2-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
132 PSH-2001 PRESSURE SWITCH LAN2-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
133 PAH-2001 PRESSURE ALARM HIGH LAN2-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
134 PSH-2001A PRESSURE SWITCH LAN2-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
135 PAH-2001A PRESSURE ALARM HIGH LAN2-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
136 RO-2001A RESTRICTION ORIFICE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6030-AM3 -
137 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6029-AM3 5085-COMM-IN-J-1003
138 DPI-2001B DIFFERENTIAL PRESSURE GAUGE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6029-AM3 5085-COMM-IN-J-1004
139 DV-2001B DELUGE VALVE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6029-AM3 5085-COMM-IN-J-1001
140 XSY-2001B SOLENOID VALVE LAN2-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
141 PSH-2001B PRESSURE SWITCH LAN2-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6029-AM3 5085-COMM-IN-J-1006
142 PAH-2001B PRESSURE ALARM HIGH LAN2-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 - -
143 RO-2001B RESTRICTION ORIFICE LAN2-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG2-PR-D-1002-01 2"-FW-LAG2-6029-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-LAG2-IN-K-1002 Page: 2 of 2

LANWA-GGS-II
AI DI DO DOP

RTU 2 15 6 10

RTU WITH 30%


3 20 8 13
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - III
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE LAG3-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 3"-FW-LAG3-6006-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE LAG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 2"-FW-LAG3-6010-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6016-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6016-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6016-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE LAG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 2"-FW-LAG3-6018-AA3
13 HS-0102A-START PUMP START COMMAND LAG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND LAG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND LAG3-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION LAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION LAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION LAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION LAG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE LAG3-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 3"-FW-LAG3-6007-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE LAG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 2"-FW-LAG3-6011-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE LAG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 2"-FW-LAG3-6020-AA3
23 HS-0102B-START PUMP START COMMAND LAG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND LAG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND LAG3-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION LAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION LAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION LAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION LAG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE LAG3-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6008-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE LAG3-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6012-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND LAG3-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND LAG3-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION LAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION LAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION LAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION LAG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE LAG3-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6009-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE LAG3-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6013-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND LAG3-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND LAG3-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION LAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION LAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION LAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION LAG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6014-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6014-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 8"-FW-LAG3-6014-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LAG3-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 8"-FW-LAG3-6015-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 8"-FW-LAG3-6024-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 8"-FW-LAG3-6025-AA3 5085-COMM-IN-J-1003
59 RO-1001 RESTRICTION ORIFICE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
60 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 5085-COMM-IN-J-1003
61 DPI-1001A DIFFERENTIAL PRESSURE GAUGE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 5085-COMM-IN-J-1004
62 DV-1001A DELUGE VALVE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 5085-COMM-IN-J-1001
63 XSY-1001A SOLENOID VALVE LW3-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
64 PSL-1001 PRESSURE SWITCH LW3-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAL-1001 PRESSURE ALARM LOW LW3-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
66 PSH-1001A PRESSURE SWITCH LW3-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
67 PAH-1001A PRESSURE ALARM HIGH LW3-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
68 RO-1001A RESTRICTION ORIFICE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6032-AM3 -
69 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 5085-COMM-IN-J-1003
70 DPI-1001B DIFFERENTIAL PRESSURE GAUGE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 5085-COMM-IN-J-1004
71 DV-1001B DELUGE VALVE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 5085-COMM-IN-J-1001
72 XSY-1001B SOLENOID VALVE LW3-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
73 PSH-1001B PRESSURE SWITCH LW3-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 5085-COMM-IN-J-1006
74 PAH-1001B PRESSURE ALARM HIGH LW3-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
75 RO-1001B RESTRICTION ORIFICE LW3-ST-01 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6030-AM3 -
76 RO-1002 RESTRICTION ORIFICE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
77 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 5085-COMM-IN-J-1003
78 DPI-1002A DIFFERENTIAL PRESSURE GAUGE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 5085-COMM-IN-J-1004
79 DV-1002A DELUGE VALVE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 5085-COMM-IN-J-1001
80 XSY-1002A SOLENOID VALVE LW3-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
81 PSL-1002 PRESSURE SWITCH LW3-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
82 PAL-1002 PRESSURE ALARM LOW LW3-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
83 PSH-1002A PRESSURE SWITCH LW3-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
84 PAH-1002A PRESSURE ALARM HIGH LW3-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
85 RO-1002A RESTRICTION ORIFICE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6031-AM3 -
86 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 5085-COMM-IN-J-1003
87 DPI-1002B DIFFERENTIAL PRESSURE GAUGE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 5085-COMM-IN-J-1004
88 DV-1002B DELUGE VALVE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 5085-COMM-IN-J-1001
89 XSY-1002B SOLENOID VALVE LW3-ST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
90 PSH-1002B PRESSURE SWITCH LW3-ST-02 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 5085-COMM-IN-J-1006
91 PAH-1002B PRESSURE ALARM HIGH LW3-ST-02 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
92 RO-1002B RESTRICTION ORIFICE LW3-ST-02 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6029-AM3 -
93 RO-1003 RESTRICTION ORIFICE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
94 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 5085-COMM-IN-J-1003
95 DPI-1003A DIFFERENTIAL PRESSURE GAUGE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 5085-COMM-IN-J-1004
96 DV-1003A DELUGE VALVE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 5085-COMM-IN-J-1001
97 XSY-1003A SOLENOID VALVE LW3-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
98 PSL-1003 PRESSURE SWITCH LW3-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
99 PAL-1003 PRESSURE ALARM LOW LW3-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
100 PSH-1003A PRESSURE SWITCH LW3-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
5085-COMM-PR-D-1003
SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LANWA GGS - III
Document Title : INSTRUMENT INDEX
Document No : 5085-LAG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks
REFER DELUGE VALVE SCHEMATIC FOR TANKS
101 PAH-1003A PRESSURE ALARM HIGH LW3-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
102 RO-1003A RESTRICTION ORIFICE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6036-AM3 -
103 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 5085-COMM-IN-J-1003
104 DPI-1003B DIFFERENTIAL PRESSURE GAUGE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 5085-COMM-IN-J-1004
105 DV-1003B DELUGE VALVE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 5085-COMM-IN-J-1001
106 XSY-1003B SOLENOID VALVE LW3-ST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
107 PSH-1003B PRESSURE SWITCH LW3-ST-03 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 5085-COMM-IN-J-1006
108 PAH-1003B PRESSURE ALARM HIGH LW3-ST-03 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
109 RO-1003B RESTRICTION ORIFICE LW3-ST-03 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6034-AM3 -
110 RO-1004 RESTRICTION ORIFICE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
111 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 5085-COMM-IN-J-1003
112 DPI-1004A DIFFERENTIAL PRESSURE GAUGE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 5085-COMM-IN-J-1004
113 DV-1004A DELUGE VALVE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 5085-COMM-IN-J-1001
114 XSY-1004A SOLENOID VALVE LW3-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
115 PSL-1004 PRESSURE SWITCH LW3-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
116 PAL-1004 PRESSURE ALARM LOW LW3-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
117 PSH-1004A PRESSURE SWITCH LW3-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
118 PAH-1004A PRESSURE ALARM HIGH LW3-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
119 RO-1004A RESTRICTION ORIFICE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6035-AM3 -
120 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 5085-COMM-IN-J-1003
121 DPI-1004B DIFFERENTIAL PRESSURE GAUGE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 5085-COMM-IN-J-1004
122 DV-1004B DELUGE VALVE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 5085-COMM-IN-J-1001
123 XSY-1004B SOLENOID VALVE LW3-ST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
124 PSH-1004B PRESSURE SWITCH LW3-ST-04 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 5085-COMM-IN-J-1006
125 PAH-1004B PRESSURE ALARM HIGH LW3-ST-04 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
126 RO-1004B RESTRICTION ORIFICE LW3-ST-04 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 3"-FW-LAG3-6033-AM3 -
127 RO-2001 RESTRICTION ORIFICE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
128 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 5085-COMM-IN-J-1003
129 DPI-2001A DIFFERENTIAL PRESSURE GAUGE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 5085-COMM-IN-J-1004
130 DV-2001A DELUGE VALVE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 5085-COMM-IN-J-1001
131 XSY-2001A SOLENOID VALVE LW3-TT-05 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
132 PSL-2001 PRESSURE SWITCH LW3-TT-05 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
133 PAL-2001 PRESSURE ALARM LOW LW3-TT-05 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
134 PSH-2001A PRESSURE SWITCH LW3-TT-05 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
135 PAH-2001A PRESSURE ALARM HIGH LW3-TT-05 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
136 RO-2001A RESTRICTION ORIFICE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6039-AM3 -
137 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 5085-COMM-IN-J-1003
138 DPI-2001B DIFFERENTIAL PRESSURE GAUGE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 5085-COMM-IN-J-1004
139 DV-2001B DELUGE VALVE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 5085-COMM-IN-J-1001
140 XSY-2001B SOLENOID VALVE LW3-TT-05 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
141 PSH-2001B PRESSURE SWITCH LW3-TT-05 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 5085-COMM-IN-J-1006
142 PAH-2001B PRESSURE ALARM HIGH LW3-TT-05 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
143 RO-2001B RESTRICTION ORIFICE LW3-TT-05 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6040-AM3 -
144 RO-2002 RESTRICTION ORIFICE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
145 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 5085-COMM-IN-J-1003
146 DPI-2002A DIFFERENTIAL PRESSURE GAUGE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 5085-COMM-IN-J-1004
147 DV-2002A DELUGE VALVE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 5085-COMM-IN-J-1001
148 XSY-2002A SOLENOID VALVE LW3-TT-06 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
149 PSL-2002 PRESSURE SWITCH LW3-TT-06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
150 PAL-2002 PRESSURE ALARM LOW LW3-TT-06 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
151 PSH-2002A PRESSURE SWITCH LW3-TT-06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
152 PAH-2002A PRESSURE ALARM HIGH LW3-TT-06 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
153 RO-2002A RESTRICTION ORIFICE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6038-AM3 -
154 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 5085-COMM-IN-J-1003
155 DPI-2002B DIFFERENTIAL PRESSURE GAUGE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 5085-COMM-IN-J-1004
156 DV-2002B DELUGE VALVE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 5085-COMM-IN-J-1001
157 XSY-2002B SOLENOID VALVE LW3-TT-06 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
158 PSH-2002B PRESSURE SWITCH LW3-TT-06 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 5085-COMM-IN-J-1006
159 PAH-2002B PRESSURE ALARM HIGH LW3-TT-06 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
160 RO-2002B RESTRICTION ORIFICE LW3-TT-06 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6041-AM3 -
161 RO-2003 RESTRICTION ORIFICE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
162 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 5085-COMM-IN-J-1003
163 DPI-2003A DIFFERENTIAL PRESSURE GAUGE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 5085-COMM-IN-J-1004
164 DV-2003A DELUGE VALVE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 5085-COMM-IN-J-1001
165 XSY-2003A SOLENOID VALVE LW3-TT-07 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
166 PSL-2003 PRESSURE SWITCH LW3-TT-07 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
167 PAL-2003 PRESSURE ALARM LOW LW3-TT-07 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
168 PSH-2003A PRESSURE SWITCH LW3-TT-07 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
169 PAH-2003A PRESSURE ALARM HIGH LW3-TT-07 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
170 RO-2003A RESTRICTION ORIFICE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6037-AM3 -
171 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 5085-COMM-IN-J-1003
172 DPI-2003B DIFFERENTIAL PRESSURE GAUGE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 5085-COMM-IN-J-1004
173 DV-2003B DELUGE VALVE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 5085-COMM-IN-J-1001
174 XSY-2003B SOLENOID VALVE LW3-TT-07 FIELD RTU DOP FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
175 PSH-2003B PRESSURE SWITCH LW3-TT-07 FIELD RTU DI FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 5085-COMM-IN-J-1006
176 PAH-2003B PRESSURE ALARM HIGH LW3-TT-07 CCR - SOFT FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 - -
177 RO-2003B RESTRICTION ORIFICE LW3-TT-07 FIELD - - FIRE WATER NETWORK 5085-LAG3-PR-D-1002-01 2"-FW-LAG3-6042-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-LAG3-IN-K-1002 Page: 2 of 2

LANWA-GGS-III
AI DI DO DOP

RTU 2 21 6 14

RTU WITH 30%


3 27 8 18
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-LAGHNAJ EPS
Document Title : INSTRUMENT INDEX
Document No : 5085-LGE-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE LGE-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 3"-FW-LGE-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE LGE-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 2"-FW-LGE-6011-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6016-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6016-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6016-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE LGE-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 2"-FW-LGE-6018-AA3
13 HS-0102A-START PUMP START COMMAND LGE-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND LGE-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND LGE-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION LGE-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION LGE-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION LGE-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION LGE-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE LGE-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 3"-FW-LGE-6008-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE LGE-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 2"-FW-LGE-6012-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE LGE-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 2"-FW-LGE-6019-AA3
23 HS-0102B-START PUMP START COMMAND LGE-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND LGE-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND LGE-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION LGE-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION LGE-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION LGE-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION LGE-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE LGE-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6009-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE LGE-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6013-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND LGE-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND LGE-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION LGE-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION LGE-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION LGE-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION LGE-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE LGE-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6010-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE LGE-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6014-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND LGE-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND LGE-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION LGE-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION LGE-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION LGE-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION LGE-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6015-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6015-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 8"-FW-LGE-6015-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-LGE-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 8"-FW-LGE-6023-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 8"-FW-LGE-6022-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 8"-FW-LGE-6024-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 8"-FW-LGE-6021-AA3 5085-COMM-IN-J-1003
60 RO-1001 RESTRICTION ORIFICE LANGH-T-01/03 FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -
61 PSL-1001 PRESSURE SWITCH LANGH-T-01/03 FIELD RTU DI FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - 5085-COMM-IN-J-1006
62 PAL-1001 PRESSURE ALARM LOW LANGH-T-01/03 CCR - SOFT FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -
63 RO-1002 RESTRICTION ORIFICE LANGH-T-02/04 FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -
64 PSL-1002 PRESSURE SWITCH LANGH-T-02/04 FIELD RTU DI FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAL-1002 PRESSURE ALARM LOW LANGH-T-02/04 CCR - SOFT FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -
66 RO-1003 RESTRICTION ORIFICE LANGH-T-05/06 FIELD - - FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -
67 PSL-1003 PRESSURE SWITCH LANGH-T-05/06 FIELD RTU DI FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - 5085-COMM-IN-J-1006
68 PAL-1003 PRESSURE ALARM LOW LANGH-T-05/06 CCR - SOFT FIRE WATER NETWORK 5085-LGE-PR-D-1002-01 - -

SHEET 2 OF 2
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-LGE-IN-K-1002 Page: 2 of 2

LAGHNAJ EPS
AI DI DO DOP

RTU 2 3 6 -

RTU WITH 30%


3 4 8 -
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-1
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE NK1-JP-01 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 3"-FW-NKG1-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE NK1-JP-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 2"-FW-NKG1-6008-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6013-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6013-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6013-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE NK1-JP-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 2"-FW-NKG1-6015-AA3
13 HS-0102A-START PUMP START COMMAND NK1-JP-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND NK1-JP-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND NK1-JP-01 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION NK1-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION NK1-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION NK1-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION NK1-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE NK1-JP-02 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 3"-FW-NKG1-6006-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE NK1-JP-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 2"-FW-NKG1-6009-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE NK1-JP-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 2"-FW-NKG1-6024-AA3
23 HS-0102B-START PUMP START COMMAND NK1-JP-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND NK1-JP-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND NK1-JP-02 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION NK1-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION NK1-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION NK1-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION NK1-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE NK1-FWP-MEC-01 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6004-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE NK1-FWP-MEC-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6010-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND NK1-FWP-MEC-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
34 XS-0101A PUMP AUTO START COMMAND NK1-FWP-MEC-01 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
35 XA-0101A PUMP FAULT INDICATION NK1-FWP-MEC-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
36 XL-0101A PUMP RUNNING INDICATION NK1-FWP-MEC-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
37 XL-0101A-AUTO AUTO INDICATION NK1-FWP-MEC-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
38 XL-0101A-MANUAL MANUAL INDICATION NK1-FWP-MEC-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
39 DPI-0104 DIFFERENTIAL PRESSURE GAUGE NK1-FWP-MEC-02 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6005-AA3 5085-COMM-IN-J-1004
40 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE NK1-FWP-MEC-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6011-AA3 5085-COMM-IN-J-1003
41 HS-0101B-START PUMP START COMMAND NK1-FWP-MEC-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
42 XS-0101B PUMP AUTO START COMMAND NK1-FWP-MEC-02 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
43 XA-0101B PUMP FAULT INDICATION NK1-FWP-MEC-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
44 XL-0101B PUMP RUNNING INDICATION NK1-FWP-MEC-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
45 XL-0101B-AUTO AUTO INDICATION NK1-FWP-MEC-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
46 XL-0101B-MANUAL MANUAL INDICATION NK1-FWP-MEC-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
47 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6012-AA3 5085-COMM-IN-J-1002
48 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
49 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
50 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6012-AA3 5085-COMM-IN-J-1002
51 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
52 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
53 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 8"-FW-NKG1-6012-AA3 5085-COMM-IN-J-1002
54 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
55 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
56 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG1-PR-D-1001-01 -
57 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
58 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 8"-FW-NKG1-6017-AA3 5085-COMM-IN-J-1003
59 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 8"-FW-NKG1-6012-AA3 5085-COMM-IN-J-1003
60 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
61 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - 5085-COMM-IN-J-1003
62 RO-1001 RESTRICTION ORIFICE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
63 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 5085-COMM-IN-J-1003
64 DPI-1001A DIFFERENTIAL PRESSURE GAUGE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 5085-COMM-IN-J-1004
65 DV-1001A DELUGE VALVE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 5085-COMM-IN-J-1001
66 XSY-1001A SOLENOID VALVE NK1-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
67 PSL-1001 PRESSURE SWITCH NK1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
68 PAL-1001 PRESSURE ALARM LOW NK1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
69 PSH-1001A PRESSURE SWITCH NK1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
70 PAH-1001A PRESSURE ALARM HIGH NK1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
71 RO-1001A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-OST-01 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6039-AM3 -
72 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 5085-COMM-IN-J-1003
73 DPI-1001B DIFFERENTIAL PRESSURE GAUGE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 5085-COMM-IN-J-1004
74 DV-1001B DELUGE VALVE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 5085-COMM-IN-J-1001
75 XSY-1001B SOLENOID VALVE NK1-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
76 PSH-1001B PRESSURE SWITCH NK1-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 5085-COMM-IN-J-1006
77 PAH-1001B PRESSURE ALARM HIGH NK1-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
78 RO-1001B RESTRICTION ORIFICE NK1-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6038-AM3 -
79 RO-1002 RESTRICTION ORIFICE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
80 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 5085-COMM-IN-J-1003
81 DPI-1002A DIFFERENTIAL PRESSURE GAUGE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 5085-COMM-IN-J-1004
82 DV-1002A DELUGE VALVE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 5085-COMM-IN-J-1001
83 XSY-1002A SOLENOID VALVE NK1-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
84 PSL-1002 PRESSURE SWITCH NK1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
85 PAL-1002 PRESSURE ALARM LOW NK1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
86 PSH-1002A PRESSURE SWITCH NK1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
87 PAH-1002A PRESSURE ALARM HIGH NK1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
88 RO-1002A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-OST-02 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6036-AM3 -
89 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 5085-COMM-IN-J-1003
90 DPI-1002B DIFFERENTIAL PRESSURE GAUGE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 5085-COMM-IN-J-1004
91 DV-1002B DELUGE VALVE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 5085-COMM-IN-J-1001
92 XSY-1002B SOLENOID VALVE NK1-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
93 PSH-1002B PRESSURE SWITCH NK1-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 5085-COMM-IN-J-1006
94 PAH-1002B PRESSURE ALARM HIGH NK1-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
95 RO-1002B RESTRICTION ORIFICE NK1-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6037-AM3 -
96 RO-1003 RESTRICTION ORIFICE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
97 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 5085-COMM-IN-J-1003
98 DPI-1003A DIFFERENTIAL PRESSURE GAUGE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 5085-COMM-IN-J-1004
99 DV-1003A DELUGE VALVE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 5085-COMM-IN-J-1001
100 XSY-1003A SOLENOID VALVE NK1-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
101 PSL-1003 PRESSURE SWITCH NK1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
102 PAL-1003 PRESSURE ALARM LOW NK1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
103 PSH-1003A PRESSURE SWITCH NK1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
104 PAH-1003A PRESSURE ALARM HIGH NK1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
105 RO-1003A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-OST-03 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6043-AM3 -
106 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 5085-COMM-IN-J-1003

SHEET 2 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-1
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG1-IN-K-1001
Revision No :1 REFER DELUGE VALVE SCHEMATIC FOR
TANKS
5085-COMM-PR-D-1003
S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

107 DPI-1003B DIFFERENTIAL PRESSURE GAUGE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 5085-COMM-IN-J-1004
108 DV-1003B DELUGE VALVE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 5085-COMM-IN-J-1001
109 XSY-1003B SOLENOID VALVE NK1-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
110 PSH-1003B PRESSURE SWITCH NK1-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 5085-COMM-IN-J-1006
111 PAH-1003B PRESSURE ALARM HIGH NK1-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
112 RO-1003B RESTRICTION ORIFICE NK1-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6042-AM3 -
113 RO-1004 RESTRICTION ORIFICE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
114 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 5085-COMM-IN-J-1003
115 DPI-1004A DIFFERENTIAL PRESSURE GAUGE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 5085-COMM-IN-J-1004
116 DV-1004A DELUGE VALVE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 5085-COMM-IN-J-1001
117 XSY-1004A SOLENOID VALVE NK1-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
118 PSL-1004 PRESSURE SWITCH NK1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
119 PAL-1004 PRESSURE ALARM LOW NK1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
120 PSH-1004A PRESSURE SWITCH NK1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
121 PAH-1004A PRESSURE ALARM HIGH NK1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
122 RO-1004A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-OST-04 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6040-AM3 -
123 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 5085-COMM-IN-J-1003
124 DPI-1004B DIFFERENTIAL PRESSURE GAUGE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 5085-COMM-IN-J-1004
125 DV-1004B DELUGE VALVE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 5085-COMM-IN-J-1001
126 XSY-1004B SOLENOID VALVE NK1-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
127 PSH-1004B PRESSURE SWITCH NK1-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 5085-COMM-IN-J-1006
128 PAH-1004B PRESSURE ALARM HIGH NK1-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
129 RO-1004B RESTRICTION ORIFICE NK1-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 3"-FW-NKG1-6041-AM3 -
130 RO-2001 RESTRICTION ORIFICE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
131 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 5085-COMM-IN-J-1003
132 DPI-2001A DIFFERENTIAL PRESSURE GAUGE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 5085-COMM-IN-J-1004
133 DV-2001A DELUGE VALVE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 5085-COMM-IN-J-1001
134 XSY-2001A SOLENOID VALVE NK1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
135 PSL-2001 PRESSURE SWITCH NK1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
136 PAL-2001 PRESSURE ALARM LOW NK1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
137 PSH-2001A PRESSURE SWITCH NK1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
138 PAH-2001A PRESSURE ALARM HIGH NK1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
139 RO-2001A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-TT-01 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6034-AM3 -
140 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 5085-COMM-IN-J-1003
141 DPI-2001B DIFFERENTIAL PRESSURE GAUGE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 5085-COMM-IN-J-1004
142 DV-2001B DELUGE VALVE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 5085-COMM-IN-J-1001
143 XSY-2001B SOLENOID VALVE NK1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
144 PSH-2001B PRESSURE SWITCH NK1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 5085-COMM-IN-J-1006
145 PAH-2001B PRESSURE ALARM HIGH NK1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
146 RO-2001B RESTRICTION ORIFICE NK1-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6035-AM3 -
147 RO-2002 RESTRICTION ORIFICE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
148 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 5085-COMM-IN-J-1003
149 DPI-2002A DIFFERENTIAL PRESSURE GAUGE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 5085-COMM-IN-J-1004
150 DV-2002A DELUGE VALVE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 5085-COMM-IN-J-1001
151 XSY-2002A SOLENOID VALVE NK1-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
152 PSL-2002 PRESSURE SWITCH NK1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
153 PAL-2002 PRESSURE ALARM LOW NK1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
154 PSH-2002A PRESSURE SWITCH NK1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
155 PAH-2002A PRESSURE ALARM HIGH NK1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
156 RO-2002A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-TT-02 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6032-AM3 -
157 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 5085-COMM-IN-J-1003
158 DPI-2002B DIFFERENTIAL PRESSURE GAUGE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 5085-COMM-IN-J-1004
159 DV-2002B DELUGE VALVE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 5085-COMM-IN-J-1001
160 XSY-2002B SOLENOID VALVE NK1-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
161 PSH-2002B PRESSURE SWITCH NK1-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 5085-COMM-IN-J-1006
162 PAH-2002B PRESSURE ALARM HIGH NK1-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
163 RO-2002B RESTRICTION ORIFICE NK1-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6033-AM3 -
164 RO-2003 RESTRICTION ORIFICE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
165 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6028-AM3 5085-COMM-IN-J-1003
166 DPI-2003A DIFFERENTIAL PRESSURE GAUGE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6028-AM3 5085-COMM-IN-J-1004
167 DV-2003A DELUGE VALVE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6028-AM3 5085-COMM-IN-J-1001
168 XSY-2003A SOLENOID VALVE NK1-AT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
169 PSL-2003 PRESSURE SWITCH NK1-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
170 PAL-2003 PRESSURE ALARM LOW NK1-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
171 PSH-2003A PRESSURE SWITCH NK1-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6028-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
172 PAH-2003A PRESSURE ALARM HIGH NK1-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - - TANKS
173 RO-2003A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-AT-01 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6028-AM3 -
174 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6029-AM3 5085-COMM-IN-J-1003
175 DPI-2003B DIFFERENTIAL PRESSURE GAUGE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6029-AM3 5085-COMM-IN-J-1004
176 DV-2003B DELUGE VALVE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6029-AM3 5085-COMM-IN-J-1001
177 XSY-2003B SOLENOID VALVE NK1-AT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
178 PSH-2003B PRESSURE SWITCH NK1-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6029-AM3 5085-COMM-IN-J-1006
179 PAH-2003B PRESSURE ALARM HIGH NK1-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 - -
180 RO-2003B RESTRICTION ORIFICE NK1-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-01 2"-FW-NKG1-6029-AM3 -
181 RO-1005 RESTRICTION ORIFICE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
182 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 5085-COMM-IN-J-1003
183 DPI-1005A DIFFERENTIAL PRESSURE GAUGE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 5085-COMM-IN-J-1004
184 DV-1005A DELUGE VALVE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 5085-COMM-IN-J-1001
185 XSY-1005A SOLENOID VALVE NK1-ET-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
186 PSL-1005 PRESSURE SWITCH NK1-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
187 PAL-1005 PRESSURE ALARM LOW NK1-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
188 PSH-1005A PRESSURE SWITCH NK1-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
189 PAH-1005A PRESSURE ALARM HIGH NK1-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - - TANKS
190 RO-1005A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-ET-01 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6050-AM3 -
191 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 5085-COMM-IN-J-1003
192 DPI-1005B DIFFERENTIAL PRESSURE GAUGE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 5085-COMM-IN-J-1004
193 DV-1005B DELUGE VALVE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 5085-COMM-IN-J-1001
194 XSY-1005B SOLENOID VALVE NK1-ET-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
195 PSH-1005B PRESSURE SWITCH NK1-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 5085-COMM-IN-J-1006
196 PAH-1005B PRESSURE ALARM HIGH NK1-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
197 RO-1005B RESTRICTION ORIFICE NK1-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6046-AM3 -
198 RO-1006 RESTRICTION ORIFICE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
199 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 5085-COMM-IN-J-1003
200 DPI-1006A DIFFERENTIAL PRESSURE GAUGE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 5085-COMM-IN-J-1004
201 DV-1006A DELUGE VALVE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 5085-COMM-IN-J-1001
202 XSY-1006A SOLENOID VALVE NK1-ET-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
203 PSL-1006 PRESSURE SWITCH NK1-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - 5085-COMM-IN-J-1006
204 PAL-1006 PRESSURE ALARM LOW NK1-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
205 PSH-1006A PRESSURE SWITCH NK1-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 5085-COMM-IN-J-1006 REFER DELUGE VALVE SCHEMATIC FOR
206 PAH-1006A PRESSURE ALARM HIGH NK1-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - - TANKS
207 RO-1006A FIELD - - 5085-COMM-PR-D-1003
RESTRICTION ORIFICE NK1-ET-02 FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6051-AM3 -
208 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 5085-COMM-IN-J-1003
209 DPI-1006B DIFFERENTIAL PRESSURE GAUGE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 5085-COMM-IN-J-1004
210 DV-1006B DELUGE VALVE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 5085-COMM-IN-J-1001
211 XSY-1006B SOLENOID VALVE NK1-ET-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-1 REFER DELUGE VALVE SCHEMATIC FOR
Document Title : INSTRUMENT INDEX TANKS
Document No : 5085-NKG1-IN-K-1001 5085-COMM-PR-D-1003
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

212 PSH-1006B PRESSURE SWITCH NK1-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 5085-COMM-IN-J-1006
213 PAH-1006B PRESSURE ALARM HIGH NK1-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 - -
214 RO-1006B RESTRICTION ORIFICE NK1-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG1-PR-D-1002-02 3"-FW-NKG1-6047-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-NKG1-IN-K-1002 Page: 2 of 2

NORTH KADI GGS-1


AI DI DO DOP

RTU 2 27 6 18

RTU WITH 30%


3 35 8 23
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (NKG 2-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK (NKG 2-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK (NKG 2-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE NK2-JP-01 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 3"-FW-NKG2-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE NK2-JP-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 2"-FW-NKG2-6012-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6018-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6018-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6018-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE NK2-JP-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 2"-FW-NKG2-6021-AA3
13 HS-0102A-START PUMP START COMMAND NK2-JP-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND NK2-JP-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND NK2-JP-01 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION NK2-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION NK2-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION NK2-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION NK2-JP-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE NK2-JP-02 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 3"-FW-NKG2-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE NK2-JP-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 2"-FW-NKG2-6013-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE NK2-JP-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 2"-FW-NKG2-6019-AA3
23 HS-0102B-START PUMP START COMMAND NK2-JP-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND NK2-JP-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND NK2-JP-02 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION NK2-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION NK2-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION NK2-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION NK2-JP-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE NKG2-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6010-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE NKG2-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6014-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND NKG2-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND NKG2-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION NKG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION NKG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION NKG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION NKG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE NKG2-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6011-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE NKG2-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 8"-FW-NKG2-6015-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND NKG2-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND NKG2-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION NKG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION NKG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION NKG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION NKG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 - 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 - 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 - 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG2-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-02 8"-FW-NKG2-6025-AA3 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-02 8"-FW-NKG2-6046-AA3 5085-COMM-IN-J-1003
61 RO-1001 RESTRICTION ORIFICE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
62 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 5085-COMM-IN-J-1003
63 DPI-1001A DIFFERENTIAL PRESSURE GAUGE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 5085-COMM-IN-J-1004
64 DV-1001A DELUGE VALVE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 5085-COMM-IN-J-1001
65 XSY-1001A SOLENOID VALVE NK2-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
66 PSL-1001 PRESSURE SWITCH NK2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
67 PAL-1001 PRESSURE ALARM LOW NK2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
68 PSH-1001A PRESSURE SWITCH NK2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
69 PAH-1001A PRESSURE ALARM HIGH NK2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
70 RO-1001A RESTRICTION ORIFICE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6034-AM3 -
71 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 5085-COMM-IN-J-1003
72 DPI-1001B DIFFERENTIAL PRESSURE GAUGE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 5085-COMM-IN-J-1004
73 DV-1001B DELUGE VALVE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 5085-COMM-IN-J-1001
74 XSY-1001B SOLENOID VALVE NK2-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
75 PSH-1001B PRESSURE SWITCH NK2-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 5085-COMM-IN-J-1006
76 PAH-1001B PRESSURE ALARM HIGH NK2-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
77 RO-1001B RESTRICTION ORIFICE NK2-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6035-AM3 -
78 RO-1002 RESTRICTION ORIFICE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
79 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 5085-COMM-IN-J-1003
80 DPI-1002A DIFFERENTIAL PRESSURE GAUGE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 5085-COMM-IN-J-1004
81 DV-1002A DELUGE VALVE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 5085-COMM-IN-J-1001
82 XSY-1002A SOLENOID VALVE NK2-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
83 PSL-1002 PRESSURE SWITCH NK2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
84 PAL-1002 PRESSURE ALARM LOW NK2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
85 PSH-1002A PRESSURE SWITCH NK2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
86 PAH-1002A PRESSURE ALARM HIGH NK2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
87 RO-1002A RESTRICTION ORIFICE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6033-AM3 -
88 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 5085-COMM-IN-J-1003
89 DPI-1002B DIFFERENTIAL PRESSURE GAUGE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 5085-COMM-IN-J-1004
90 DV-1002B DELUGE VALVE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 5085-COMM-IN-J-1001
91 XSY-1002B SOLENOID VALVE NK2-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
92 PSH-1002B PRESSURE SWITCH NK2-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 5085-COMM-IN-J-1006
93 PAH-1002B PRESSURE ALARM HIGH NK2-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
94 RO-1002B RESTRICTION ORIFICE NK2-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6036-AM3 -
95 RO-1003 RESTRICTION ORIFICE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
96 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 5085-COMM-IN-J-1003
97 DPI-1003A DIFFERENTIAL PRESSURE GAUGE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 5085-COMM-IN-J-1004
98 DV-1003A DELUGE VALVE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 5085-COMM-IN-J-1001
99 XSY-1003A SOLENOID VALVE NK2-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
100 PSL-1003 PRESSURE SWITCH NK2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006

SHEET 2 OF 4 REFER DELUGE VALVE SCHEMATIC FOR TANKS


Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PAL-1003 PRESSURE ALARM LOW NK2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
102 PSH-1003A PRESSURE SWITCH NK2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
103 PAH-1003A PRESSURE ALARM HIGH NK2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
104 RO-1003A RESTRICTION ORIFICE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6037-AM3 -
105 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 5085-COMM-IN-J-1003
106 DPI-1003B DIFFERENTIAL PRESSURE GAUGE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 5085-COMM-IN-J-1004
107 DV-1003B DELUGE VALVE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 5085-COMM-IN-J-1001
108 XSY-1003B SOLENOID VALVE NK2-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
109 PSH-1003B PRESSURE SWITCH NK2-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 5085-COMM-IN-J-1006
110 PAH-1003B PRESSURE ALARM HIGH NK2-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
111 RO-1003B RESTRICTION ORIFICE NK2-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6038-AM3 -
112 RO-1004 RESTRICTION ORIFICE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
113 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 5085-COMM-IN-J-1003
114 DPI-1004A DIFFERENTIAL PRESSURE GAUGE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 5085-COMM-IN-J-1004
115 DV-1004A DELUGE VALVE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 5085-COMM-IN-J-1001
116 XSY-1004A SOLENOID VALVE NK2-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
117 PSL-1004 PRESSURE SWITCH NK2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
118 PAL-1004 PRESSURE ALARM LOW NK2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
119 PSH-1004A PRESSURE SWITCH NK2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
120 PAH-1004A PRESSURE ALARM HIGH NK2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
121 RO-1004A RESTRICTION ORIFICE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6039-AM3 -
122 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 5085-COMM-IN-J-1003
123 DPI-1004B DIFFERENTIAL PRESSURE GAUGE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 5085-COMM-IN-J-1004
124 DV-1004B DELUGE VALVE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 5085-COMM-IN-J-1001
125 XSY-1004B SOLENOID VALVE NK2-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
126 PSH-1004B PRESSURE SWITCH NK2-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 5085-COMM-IN-J-1006
127 PAH-1004B PRESSURE ALARM HIGH NK2-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
128 RO-1004B RESTRICTION ORIFICE NK2-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6040-AM3 -
129 RO-1005 RESTRICTION ORIFICE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
130 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 5085-COMM-IN-J-1003
131 DPI-1005A DIFFERENTIAL PRESSURE GAUGE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 5085-COMM-IN-J-1004
132 DV-1005A DELUGE VALVE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 5085-COMM-IN-J-1001
133 XSY-1005A SOLENOID VALVE NK2-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
134 PSL-1005 PRESSURE SWITCH NK2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
135 PAL-1005 PRESSURE ALARM LOW NK2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
136 PSH-1005A PRESSURE SWITCH NK2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
137 PAH-1005A PRESSURE ALARM HIGH NK2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
138 RO-1005A RESTRICTION ORIFICE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6041-AM3 -
139 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 5085-COMM-IN-J-1003
140 DPI-1005B DIFFERENTIAL PRESSURE GAUGE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 5085-COMM-IN-J-1004
141 DV-1005B DELUGE VALVE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 5085-COMM-IN-J-1001
142 XSY-1005B SOLENOID VALVE NK2-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
143 PSH-1005B PRESSURE SWITCH NK2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 5085-COMM-IN-J-1006
144 PAH-1005B PRESSURE ALARM HIGH NK2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
145 RO-1005B RESTRICTION ORIFICE NK2-WT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6042-AM3 -
146 RO-1006 RESTRICTION ORIFICE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
147 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 5085-COMM-IN-J-1003
148 DPI-1006A DIFFERENTIAL PRESSURE GAUGE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 5085-COMM-IN-J-1004
149 DV-1006A DELUGE VALVE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 5085-COMM-IN-J-1001
150 XSY-1006A SOLENOID VALVE NK2-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
151 PSL-1006 PRESSURE SWITCH NK2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
152 PAL-1006 PRESSURE ALARM LOW NK2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
153 PSH-1006A PRESSURE SWITCH NK2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
154 PAH-1006A PRESSURE ALARM HIGH NK2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
155 RO-1006A RESTRICTION ORIFICE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6043-AM3 -
156 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 5085-COMM-IN-J-1003
157 DPI-1006B DIFFERENTIAL PRESSURE GAUGE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 5085-COMM-IN-J-1004
158 DV-1006B DELUGE VALVE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 5085-COMM-IN-J-1001
159 XSY-1006B SOLENOID VALVE NK2-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
160 PSH-1006B PRESSURE SWITCH NK2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 5085-COMM-IN-J-1006
161 PAH-1006B PRESSURE ALARM HIGH NK2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
162 RO-1006B RESTRICTION ORIFICE NK2-WT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6044-AM3 -
163 RO-2001 RESTRICTION ORIFICE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
164 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 5085-COMM-IN-J-1003
165 DPI-2001A DIFFERENTIAL PRESSURE GAUGE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 5085-COMM-IN-J-1004
166 DV-2001A DELUGE VALVE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 5085-COMM-IN-J-1001
167 XSY-2001A SOLENOID VALVE NK2-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
168 PSL-2001 PRESSURE SWITCH NK2-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
169 PAL-2001 PRESSURE ALARM LOW NK2-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
170 PSH-2001A PRESSURE SWITCH NK2-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
171 PAH-2001A PRESSURE ALARM HIGH NK2-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
172 RO-2001A RESTRICTION ORIFICE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6029-AM3 -
173 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 5085-COMM-IN-J-1003
174 DPI-2001B DIFFERENTIAL PRESSURE GAUGE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 5085-COMM-IN-J-1004
175 DV-2001B DELUGE VALVE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 5085-COMM-IN-J-1001
176 XSY-2001B SOLENOID VALVE NK2-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
177 PSH-2001B PRESSURE SWITCH NK2-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 5085-COMM-IN-J-1006
178 PAH-2001B PRESSURE ALARM HIGH NK2-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
179 RO-2001B RESTRICTION ORIFICE NK2-TT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6031-AM3 -
180 RO-2002 RESTRICTION ORIFICE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
181 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 5085-COMM-IN-J-1003
182 DPI-2002A DIFFERENTIAL PRESSURE GAUGE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 5085-COMM-IN-J-1004
183 DV-2002A DELUGE VALVE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 5085-COMM-IN-J-1001
184 XSY-2002A SOLENOID VALVE NK2-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
185 PSL-2002 PRESSURE SWITCH NK2-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
186 PAL-2002 PRESSURE ALARM LOW NK2-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
187 PSH-2002A PRESSURE SWITCH NK2-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
188 PAH-2002A PRESSURE ALARM HIGH NK2-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
189 RO-2002A RESTRICTION ORIFICE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6030-AM3 -
190 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 5085-COMM-IN-J-1003
191 DPI-2002B DIFFERENTIAL PRESSURE GAUGE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 5085-COMM-IN-J-1004
192 DV-2002B DELUGE VALVE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 5085-COMM-IN-J-1001
193 XSY-2002B SOLENOID VALVE NK2-TT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
194 PSH-2002B PRESSURE SWITCH NK2-TT-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 5085-COMM-IN-J-1006
195 PAH-2002B PRESSURE ALARM HIGH NK2-TT-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
196 RO-2002B RESTRICTION ORIFICE NK2-TT-02 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 2"-FW-NKG2-6032-AM3 -
197 RO-2003 RESTRICTION ORIFICE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
198 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 5085-COMM-IN-J-1003
199 DPI-2003A DIFFERENTIAL PRESSURE GAUGE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 5085-COMM-IN-J-1004
200 DV-2003A DELUGE VALVE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 5085-COMM-IN-J-1001

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

201 XSY-2003A SOLENOID VALVE NK2-AT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
202 PSL-2003 PRESSURE SWITCH NK2-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
203 PAL-2003 PRESSURE ALARM LOW NK2-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
204 PSH-2003A PRESSURE SWITCH NK2-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
205 PAH-2003A PRESSURE ALARM HIGH NK2-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
206 RO-2003A RESTRICTION ORIFICE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6028-AM3 -
207 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 5085-COMM-IN-J-1003
208 DPI-2003B DIFFERENTIAL PRESSURE GAUGE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 5085-COMM-IN-J-1004
209 DV-2003B DELUGE VALVE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 5085-COMM-IN-J-1001
210 XSY-2003B SOLENOID VALVE NK2-AT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
211 PSH-2003B PRESSURE SWITCH NK2-AT-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 5085-COMM-IN-J-1006
212 PAH-2003B PRESSURE ALARM HIGH NK2-AT-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 - -
213 RO-2003A RESTRICTION ORIFICE NK2-AT-01 FIELD - - FIRE WATER NETWORK 5085-NKG2-PR-D-1002-01 3"-FW-NKG2-6027-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-NKG2-IN-K-1002 Page: 2 of 2

NORTH KADI GGS-2


AI DI DO DOP

RTU 2 27 6 18

RTU WITH 30%


3 35 8 23
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-3
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (NKG3-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK (NKG3-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK (NKG3-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE NKG3-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 3"-FW-NKG3-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE NKG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 2"-FW-NKG3-6011-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6022-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6022-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6022-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE NKG3-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 2"-FW-NKG3-6017-AA3
13 HS-0102A-START PUMP START COMMAND NKG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND NKG3-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND NKG3-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION NKG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION NKG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION NKG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION NKG3-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE NKG3-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 3"-FW-NKG3-6008-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE NKG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 2"-FW-NKG3-6012-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE NKG3-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 2"-FW-NKG3-6019-AA3
23 HS-0102B-START PUMP START COMMAND NKG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND NKG3-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND NKG3-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION NKG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION NKG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION NKG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION NKG3-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE NKG3-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6009-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE NKG3-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6013-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND NKG3-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND NKG3-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION NKG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION NKG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION NKG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION NKG3-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE NKG3-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6010-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE NKG3-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6014-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND NKG3-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND NKG3-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION NKG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION NKG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION NKG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION NKG3-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6023-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6023-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 8"-FW-NKG3-6023-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG3-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 8"-FW-NKG3-6044-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 8"-FW-NKG3-6016-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 8"-FW-NKG3-6046-AA3 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 8"-FW-NKG3-6049-AA3 5085-COMM-IN-J-1003
61 RO-1001 RESTRICTION ORIFICE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
62 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 5085-COMM-IN-J-1003
63 DPI-1001A DIFFERENTIAL PRESSURE GAUGE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 5085-COMM-IN-J-1004
64 DV-1001A DELUGE VALVE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 5085-COMM-IN-J-1001
65 XSY-1001A SOLENOID VALVE NK3-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
66 PSL-1001 PRESSURE SWITCH NK3-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
67 PAL-1001 PRESSURE ALARM LOW NK3-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
68 PSH-1001A PRESSURE SWITCH NK3-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
69 PAH-1001A PRESSURE ALARM HIGH NK3-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
70 RO-1001A RESTRICTION ORIFICE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6026-AM3 -
71 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 5085-COMM-IN-J-1003
72 DPI-1001B DIFFERENTIAL PRESSURE GAUGE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 5085-COMM-IN-J-1004
73 DV-1001B DELUGE VALVE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 5085-COMM-IN-J-1001
74 XSY-1001B SOLENOID VALVE NK3-OST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
75 PSH-1001B PRESSURE SWITCH NK3-OST-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 5085-COMM-IN-J-1006
76 PAH-1001B PRESSURE ALARM HIGH NK3-OST-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
77 RO-1001B RESTRICTION ORIFICE NK3-OST-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6032-AM3 -
78 RO-1002 RESTRICTION ORIFICE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
79 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 5085-COMM-IN-J-1003
80 DPI-1002A DIFFERENTIAL PRESSURE GAUGE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 5085-COMM-IN-J-1004
81 DV-1002A DELUGE VALVE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 5085-COMM-IN-J-1001
82 XSY-1002A SOLENOID VALVE NK3-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
83 PSL-1002 PRESSURE SWITCH NK3-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
84 PAL-1002 PRESSURE ALARM LOW NK3-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
85 PSH-1002A PRESSURE SWITCH NK3-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
86 PAH-1002A PRESSURE ALARM HIGH NK3-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
87 RO-1002A RESTRICTION ORIFICE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6027-AM3 -
88 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 5085-COMM-IN-J-1003
89 DPI-1002B DIFFERENTIAL PRESSURE GAUGE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 5085-COMM-IN-J-1004
90 DV-1002B DELUGE VALVE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 5085-COMM-IN-J-1001
91 XSY-1002B SOLENOID VALVE NK3-OST-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
92 PSH-1002B PRESSURE SWITCH NK3-OST-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 5085-COMM-IN-J-1006
93 PAH-1002B PRESSURE ALARM HIGH NK3-OST-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
94 RO-1002B RESTRICTION ORIFICE NK3-OST-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6033-AM3 -
95 RO-1003 RESTRICTION ORIFICE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
96 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 5085-COMM-IN-J-1003
97 DPI-1003A DIFFERENTIAL PRESSURE GAUGE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 5085-COMM-IN-J-1004
98 DV-1003A DELUGE VALVE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 5085-COMM-IN-J-1001
99 XSY-1003A SOLENOID VALVE NK3-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
100 PSL-1003 PRESSURE SWITCH NK3-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006

SHEET 2 OF 4 REFER DELUGE VALVE SCHEMATIC FOR TANKS


Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-3
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PAL-1003 PRESSURE ALARM LOW NK3-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
102 PSH-1003A PRESSURE SWITCH NK3-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
103 PAH-1003A PRESSURE ALARM HIGH NK3-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
104 RO-1003A RESTRICTION ORIFICE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6024-AM3 -
105 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 5085-COMM-IN-J-1003
106 DPI-1003B DIFFERENTIAL PRESSURE GAUGE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 5085-COMM-IN-J-1004
107 DV-1003B DELUGE VALVE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 5085-COMM-IN-J-1001
108 XSY-1003B SOLENOID VALVE NK3-OST-03 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
109 PSH-1003B PRESSURE SWITCH NK3-OST-03 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 5085-COMM-IN-J-1006
110 PAH-1003B PRESSURE ALARM HIGH NK3-OST-03 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
111 RO-1003B RESTRICTION ORIFICE NK3-OST-03 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6030-AM3 -
112 RO-1004 RESTRICTION ORIFICE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
113 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 5085-COMM-IN-J-1003
114 DPI-1004A DIFFERENTIAL PRESSURE GAUGE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 5085-COMM-IN-J-1004
115 DV-1004A DELUGE VALVE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 5085-COMM-IN-J-1001
116 XSY-1004A SOLENOID VALVE NK3-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
117 PSL-1004 PRESSURE SWITCH NK3-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
118 PAL-1004 PRESSURE ALARM LOW NK3-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
119 PSH-1004A PRESSURE SWITCH NK3-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
120 PAH-1004A PRESSURE ALARM HIGH NK3-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
121 RO-1004A RESTRICTION ORIFICE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6025-AM3 -
122 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 5085-COMM-IN-J-1003
123 DPI-1004B DIFFERENTIAL PRESSURE GAUGE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 5085-COMM-IN-J-1004
124 DV-1004B DELUGE VALVE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 5085-COMM-IN-J-1001
125 XSY-1004B SOLENOID VALVE NK3-OST-04 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
126 PSH-1004B PRESSURE SWITCH NK3-OST-04 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 5085-COMM-IN-J-1006
127 PAH-1004B PRESSURE ALARM HIGH NK3-OST-04 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
128 RO-1004B RESTRICTION ORIFICE NK3-OST-04 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 3"-FW-NKG3-6031-AM3 -
129 RO-2001 RESTRICTION ORIFICE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
130 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 5085-COMM-IN-J-1003
131 DPI-2001A DIFFERENTIAL PRESSURE GAUGE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 5085-COMM-IN-J-1004
132 DV-2001A DELUGE VALVE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 5085-COMM-IN-J-1001
133 XSY-2001A SOLENOID VALVE NK3-TT-1 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
134 PSL-2001 PRESSURE SWITCH NK3-TT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
135 PAL-2001 PRESSURE ALARM LOW NK3-TT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
136 PSH-2001A PRESSURE SWITCH NK3-TT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
137 PAH-2001A PRESSURE ALARM HIGH NK3-TT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
138 RO-2001A RESTRICTION ORIFICE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6028-AM3 -
139 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 5085-COMM-IN-J-1003
140 DPI-2001B DIFFERENTIAL PRESSURE GAUGE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 5085-COMM-IN-J-1004
141 DV-2001B DELUGE VALVE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 5085-COMM-IN-J-1001
142 XSY-2001B SOLENOID VALVE NK3-TT-1 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
143 PSH-2001B PRESSURE SWITCH NK3-TT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 5085-COMM-IN-J-1006
144 PAH-2001B PRESSURE ALARM HIGH NK3-TT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
145 RO-2001B RESTRICTION ORIFICE NK3-TT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6034-AM3 -
146 RO-2002 RESTRICTION ORIFICE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
147 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 5085-COMM-IN-J-1003
148 DPI-2002A DIFFERENTIAL PRESSURE GAUGE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 5085-COMM-IN-J-1004
149 DV-2002A DELUGE VALVE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 5085-COMM-IN-J-1001
150 XSY-2002A SOLENOID VALVE NK3-TT-2 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
151 PSL-2002 PRESSURE SWITCH NK3-TT-2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
152 PAL-2002 PRESSURE ALARM LOW NK3-TT-2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
153 PSH-2002A PRESSURE SWITCH NK3-TT-2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
154 PAH-2002A PRESSURE ALARM HIGH NK3-TT-2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
155 RO-2002A RESTRICTION ORIFICE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6029-AM3 -
156 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 5085-COMM-IN-J-1003
157 DPI-2002B DIFFERENTIAL PRESSURE GAUGE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 5085-COMM-IN-J-1004
158 DV-2002B DELUGE VALVE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 5085-COMM-IN-J-1001
159 XSY-2002B SOLENOID VALVE NK3-TT-2 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
160 PSH-2002B PRESSURE SWITCH NK3-TT-2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 5085-COMM-IN-J-1006
161 PAH-2002B PRESSURE ALARM HIGH NK3-TT-2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
162 RO-2002B RESTRICTION ORIFICE NK3-TT-2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6035-AM3 -
163 RO-2003 RESTRICTION ORIFICE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
164 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 5085-COMM-IN-J-1003
165 DPI-2003A DIFFERENTIAL PRESSURE GAUGE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 5085-COMM-IN-J-1004
166 DV-2003A DELUGE VALVE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 5085-COMM-IN-J-1001
167 XSY-2003A SOLENOID VALVE NK3-AT-1 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
168 PSL-2003 PRESSURE SWITCH NK3-AT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - 5085-COMM-IN-J-1006
169 PAL-2003 PRESSURE ALARM LOW NK3-AT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
170 PSH-2003A PRESSURE SWITCH NK3-AT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
171 PAH-2003A PRESSURE ALARM HIGH NK3-AT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
5085-COMM-PR-D-1003
172 RO-2003A RESTRICTION ORIFICE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6037-AM3 -
173 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 5085-COMM-IN-J-1003
174 DPI-2003B DIFFERENTIAL PRESSURE GAUGE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 5085-COMM-IN-J-1004
175 DV-2003B DELUGE VALVE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 5085-COMM-IN-J-1001
176 XSY-2003B SOLENOID VALVE NK3-AT-1 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
177 PSH-2003B PRESSURE SWITCH NK3-AT-1 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 5085-COMM-IN-J-1006
178 PAH-2003B PRESSURE ALARM HIGH NK3-AT-1 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 - -
179 RO-2003B RESTRICTION ORIFICE NK3-AT-1 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-01 2"-FW-NKG3-6036-AM3 -
180 RO-2004 RESTRICTION ORIFICE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
181 PI-2004A PRESSURE INDICATOR-MANIFOLD TYPE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6047-AM3 5085-COMM-IN-J-1003
182 DPI-2004A DIFFERENTIAL PRESSURE GAUGE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6047-AM3 5085-COMM-IN-J-1004
183 DV-2004A DELUGE VALVE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6047-AM3 5085-COMM-IN-J-1001
184 XSY-2004A SOLENOID VALVE NK3-HOEC-1/2 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
185 PSL-2004 PRESSURE SWITCH NK3-HOEC-1/2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - 5085-COMM-IN-J-1006
186 PAL-2004 PRESSURE ALARM LOW NK3-HOEC-1/2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
187 PSH-2004A PRESSURE SWITCH NK3-HOEC-1/2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6047-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
188 PAH-2004A PRESSURE ALARM HIGH NK3-HOEC-1/2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
5085-COMM-PR-D-1003
189 RO-2004A RESTRICTION ORIFICE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6047-AM3 -
190 PI-2004B PRESSURE INDICATOR-MANIFOLD TYPE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 5085-COMM-IN-J-1003
191 DPI-2004B DIFFERENTIAL PRESSURE GAUGE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 5085-COMM-IN-J-1004
192 DV-2004B DELUGE VALVE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 5085-COMM-IN-J-1001
193 XSY-2004B SOLENOID VALVE NK3-HOEC-1/2 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
194 PSH-2004B PRESSURE SWITCH NK3-HOEC-1/2 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 5085-COMM-IN-J-1006
195 PAH-2004B PRESSURE ALARM HIGH NK3-HOEC-1/2 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
196 RO-2004B RESTRICTION ORIFICE NK3-HOEC-1/2 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6038-AM3 -
197 RO-1005 RESTRICTION ORIFICE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
198 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 5085-COMM-IN-J-1003
199 DPI-1005A DIFFERENTIAL PRESSURE GAUGE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 5085-COMM-IN-J-1004
200 DV-1005A DELUGE VALVE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 5085-COMM-IN-J-1001

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-3
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG3-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

201 XSY-1005A SOLENOID VALVE NK3-ET-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
202 PSL-1005 PRESSURE SWITCH NK3-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - 5085-COMM-IN-J-1006
203 PAL-1005 PRESSURE ALARM LOW NK3-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
204 PSH-1005A PRESSURE SWITCH NK3-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
205 PAH-1005A PRESSURE ALARM HIGH NK3-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
5085-COMM-PR-D-1003
206 RO-1005A RESTRICTION ORIFICE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6042-AM3 -
207 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 5085-COMM-IN-J-1003
208 DPI-1005B DIFFERENTIAL PRESSURE GAUGE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 5085-COMM-IN-J-1004
209 DV-1005B DELUGE VALVE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 5085-COMM-IN-J-1001
210 XSY-1005B SOLENOID VALVE NK3-ET-01 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
211 PSH-1005B PRESSURE SWITCH NK3-ET-01 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 5085-COMM-IN-J-1006
212 PAH-1005B PRESSURE ALARM HIGH NK3-ET-01 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
213 RO-1005B RESTRICTION ORIFICE NK3-ET-01 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6043-AM3 -
214 RO-1006 RESTRICTION ORIFICE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
215 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 5085-COMM-IN-J-1003
216 DPI-1006A DIFFERENTIAL PRESSURE GAUGE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 5085-COMM-IN-J-1004
217 DV-1006A DELUGE VALVE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 5085-COMM-IN-J-1001
218 XSY-1006A SOLENOID VALVE NK3-ET-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
219 PSL-1006 PRESSURE SWITCH NK3-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - 5085-COMM-IN-J-1006
220 PAL-1006 PRESSURE ALARM LOW NK3-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
221 PSH-1006A PRESSURE SWITCH NK3-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
222 PAH-1006A PRESSURE ALARM HIGH NK3-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
5085-COMM-PR-D-1003
223 RO-1006A RESTRICTION ORIFICE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6040-AM3 -
224 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 5085-COMM-IN-J-1003
225 DPI-1006B DIFFERENTIAL PRESSURE GAUGE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 5085-COMM-IN-J-1004
226 DV-1006B DELUGE VALVE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 5085-COMM-IN-J-1001
227 XSY-1006B SOLENOID VALVE NK3-ET-02 FIELD RTU DOP FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
228 PSH-1006B PRESSURE SWITCH NK3-ET-02 FIELD RTU DI FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 5085-COMM-IN-J-1006
229 PAH-1006B PRESSURE ALARM HIGH NK3-ET-02 CCR - SOFT FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 - -
230 RO-1006B RESTRICTION ORIFICE NK3-ET-02 FIELD - - FIRE WATER NETWORK 5085-NKG3-PR-D-1002-02 3"-FW-NKG3-6041-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-NKG3-IN-K-1002 Page: 2 of 2

NORTH KADI GGS-3


AI DI DO DOP

RTU 2 30 6 20

RTU WITH 30%


3 39 8 26
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-4
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG4-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE NKG4-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 3"-FW-NKG4-6003-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE NKG4-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 2"-FW-NKG4-6007-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6014-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6014-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6014-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE NKG4-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 2"-FW-NKG4-6015-AA3
13 HS-0102A-START PUMP START COMMAND NKG4-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND NKG4-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND NKG4-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION NKG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION NKG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION NKG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION NKG4-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE NKG4-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 3"-FW-NKG4-6004-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE NKG4-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 2"-FW-NKG4-6008-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE NKG4-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 2"-FW-NKG4-6017-AA3
23 HS-0102B-START PUMP START COMMAND NKG4-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND NKG4-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND NKG4-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION NKG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION NKG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION NKG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION NKG4-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE NKG4-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 - 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE NKG4-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6009-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND NKG4-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND NKG4-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION NKG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION NKG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION NKG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION NKG4-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE NKG4-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 - 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE NKG4-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 8"-FW-NKG4-6010-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND NKG4-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND NKG4-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION NKG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION NKG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION NKG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION NKG4-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 10"-FW-NKG4-6020-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 10"-FW-NKG4-6020-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 10"-FW-NKG4-6020-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-NKG4-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 6"-FW-NKG4-6022-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 8"-FW-NKG4-6021-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 8"-FW-NKG4-6021-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1003
61 PI-0206 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1003
62 PI-0207 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 8"-FW-NKG4-6027-AA3 5085-COMM-IN-J-1003
63 RO-3001 RESTRICTION ORIFICE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
64 PI-3001A PRESSURE INDICATOR-MANIFOLD TYPE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 5085-COMM-IN-J-1003
65 DPI-3001A DIFFERENTIAL PRESSURE GAUGE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 5085-COMM-IN-J-1004
66 DV-3001A DELUGE VALVE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 5085-COMM-IN-J-1001
67 XSY-3001A SOLENOID VALVE LP COMPRESSOR FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
68 PSL-3001 PRESSURE SWITCH LP COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - 5085-COMM-IN-J-1006
69 PAL-3001 PRESSURE ALARM LOW LP COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
70 PSH-3001A PRESSURE SWITCH LP COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
71 PAH-3001A PRESSURE ALARM HIGH LP COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
5085-COMM-PR-D-1003
72 RO-3001A RESTRICTION ORIFICE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6025-AM3 -
73 PI-3001B PRESSURE INDICATOR-MANIFOLD TYPE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 5085-COMM-IN-J-1003
74 DPI-3001B DIFFERENTIAL PRESSURE GAUGE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 5085-COMM-IN-J-1004
75 DV-3001B DELUGE VALVE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 5085-COMM-IN-J-1001
76 XSY-3001B SOLENOID VALVE LP COMPRESSOR FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
77 PSH-3001B PRESSURE SWITCH LP COMPRESSOR FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 5085-COMM-IN-J-1006
78 PAH-3001B PRESSURE ALARM HIGH LP COMPRESSOR CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 - -
79 RO-3001B RESTRICTION ORIFICE LP COMPRESSOR FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-01 4"-FW-NKG4-6026-AM3 -
80 RO-1001 RESTRICTION ORIFICE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
81 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1003
82 DPI-1001A DIFFERENTIAL PRESSURE GAUGE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1004
83 DV-1001A DELUGE VALVE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1001
84 XSY-1001A SOLENOID VALVE 10-TT-102A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
85 PSL-1001 PRESSURE SWITCH 10-TT-102A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
86 PAL-1001 PRESSURE ALARM LOW 10-TT-102A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
87 PSH-1001A PRESSURE SWITCH 10-TT-102A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
88 PAH-1001A PRESSURE ALARM HIGH 10-TT-102A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
89 RO-1001A RESTRICTION ORIFICE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 -
90 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 5085-COMM-IN-J-1003
91 DPI-1001B DIFFERENTIAL PRESSURE GAUGE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 5085-COMM-IN-J-1004
92 DV-1001B DELUGE VALVE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 5085-COMM-IN-J-1001
93 XSY-1001B SOLENOID VALVE 10-TT-102A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
94 PSH-1001B PRESSURE SWITCH 10-TT-102A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 5085-COMM-IN-J-1006
95 PAH-1001B PRESSURE ALARM HIGH 10-TT-102A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
96 RO-1001B RESTRICTION ORIFICE 10-TT-102A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6032-AM3 -
97 RO-1002 RESTRICTION ORIFICE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
98 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1003
99 DPI-1002A DIFFERENTIAL PRESSURE GAUGE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1004
100 DV-1002A DELUGE VALVE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1001

SHEET 2 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-4
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG4-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 XSY-1002A SOLENOID VALVE 10-TT-102B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
102 PSL-1002 PRESSURE SWITCH 10-TT-102B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
103 PAL-1002 PRESSURE ALARM LOW 10-TT-102B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
104 PSH-1002A PRESSURE SWITCH 10-TT-102B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
105 PAH-1002A PRESSURE ALARM HIGH 10-TT-102B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
106 RO-1002A RESTRICTION ORIFICE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6030-AM3 -
107 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 5085-COMM-IN-J-1003
108 DPI-1002B DIFFERENTIAL PRESSURE GAUGE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 5085-COMM-IN-J-1004
109 DV-1002B DELUGE VALVE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 5085-COMM-IN-J-1001
110 XSY-1002B SOLENOID VALVE 10-TT-102B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
111 PSH-1002B PRESSURE SWITCH 10-TT-102B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 5085-COMM-IN-J-1006
112 PAH-1002B PRESSURE ALARM HIGH 10-TT-102B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
113 RO-1002B RESTRICTION ORIFICE 10-TT-102B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6033-AM3 -
114 RO-1003 RESTRICTION ORIFICE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
115 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 5085-COMM-IN-J-1003
116 DPI-1003A DIFFERENTIAL PRESSURE GAUGE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 5085-COMM-IN-J-1004
117 DV-1003A DELUGE VALVE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 5085-COMM-IN-J-1001
118 XSY-1003A SOLENOID VALVE 10-TT-102C FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
119 PSL-1003 PRESSURE SWITCH 10-TT-102C FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
120 PAL-1003 PRESSURE ALARM LOW 10-TT-102C CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
121 PSH-1003A PRESSURE SWITCH 10-TT-102C FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
122 PAH-1003A PRESSURE ALARM HIGH 10-TT-102C CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
123 RO-1003A RESTRICTION ORIFICE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6029-AM3 -
124 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 5085-COMM-IN-J-1003
125 DPI-1003B DIFFERENTIAL PRESSURE GAUGE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 5085-COMM-IN-J-1004
126 DV-1003B DELUGE VALVE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 5085-COMM-IN-J-1001
127 XSY-1003B SOLENOID VALVE 10-TT-102C FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
128 PSH-1003B PRESSURE SWITCH 10-TT-102C FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 5085-COMM-IN-J-1006
129 PAH-1003B PRESSURE ALARM HIGH 10-TT-102C CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
130 RO-1003B RESTRICTION ORIFICE 10-TT-102C FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6034-AM3 -
131 RO-1004 RESTRICTION ORIFICE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
132 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 5085-COMM-IN-J-1003
133 DPI-1004A DIFFERENTIAL PRESSURE GAUGE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 5085-COMM-IN-J-1004
134 DV-1004A DELUGE VALVE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 5085-COMM-IN-J-1001
135 XSY-1004A SOLENOID VALVE 10-TT-102D FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
136 PSL-1004 PRESSURE SWITCH 10-TT-102D FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
137 PAL-1004 PRESSURE ALARM LOW 10-TT-102D CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
138 PSH-1004A PRESSURE SWITCH 10-TT-102D FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
139 PAH-1004A PRESSURE ALARM HIGH 10-TT-102D CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
140 RO-1004A RESTRICTION ORIFICE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6028-AM3 -
141 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 5085-COMM-IN-J-1003
142 DPI-1004B DIFFERENTIAL PRESSURE GAUGE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 5085-COMM-IN-J-1004
143 DV-1004B DELUGE VALVE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 5085-COMM-IN-J-1001
144 XSY-1004B SOLENOID VALVE 10-TT-102D FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
145 PSH-1004B PRESSURE SWITCH 10-TT-102D FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 5085-COMM-IN-J-1006
146 PAH-1004B PRESSURE ALARM HIGH 10-TT-102D CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
147 RO-1004B RESTRICTION ORIFICE 10-TT-102D FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6035-AM3 -
148 RO-2001 RESTRICTION ORIFICE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
149 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 5085-COMM-IN-J-1003
150 DPI-2001A DIFFERENTIAL PRESSURE GAUGE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 5085-COMM-IN-J-1004
151 DV-2001A DELUGE VALVE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 5085-COMM-IN-J-1001
152 XSY-2001A SOLENOID VALVE 10-TT-101B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
153 PSL-2001 PRESSURE SWITCH 10-TT-101B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
154 PAL-2001 PRESSURE ALARM LOW 10-TT-101B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
155 PSH-2001A PRESSURE SWITCH 10-TT-101B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
156 PAH-2001A PRESSURE ALARM HIGH 10-TT-101B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
157 RO-2001A RESTRICTION ORIFICE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6042-AM3 -
158 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 5085-COMM-IN-J-1003
159 DPI-2001B DIFFERENTIAL PRESSURE GAUGE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 5085-COMM-IN-J-1004
160 DV-2001B DELUGE VALVE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 5085-COMM-IN-J-1001
161 XSY-2001B SOLENOID VALVE 10-TT-101B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
162 PSH-2001B PRESSURE SWITCH 10-TT-101B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 5085-COMM-IN-J-1006
163 PAH-2001B PRESSURE ALARM HIGH 10-TT-101B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
164 RO-2001B RESTRICTION ORIFICE 10-TT-101B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6036-AM3 -
165 RO-2002 RESTRICTION ORIFICE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
166 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1003
167 DPI-2002A DIFFERENTIAL PRESSURE GAUGE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1004
168 DV-2002A DELUGE VALVE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1001
169 XSY-2002A SOLENOID VALVE 10-TT-101A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
170 PSL-2002 PRESSURE SWITCH 10-TT-101A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
171 PAL-2002 PRESSURE ALARM LOW 10-TT-101A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
172 PSH-2002A PRESSURE SWITCH 10-TT-101A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
173 PAH-2002A PRESSURE ALARM HIGH 10-TT-101A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
174 RO-2002A RESTRICTION ORIFICE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 -
175 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 5085-COMM-IN-J-1003
176 DPI-2002B DIFFERENTIAL PRESSURE GAUGE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 5085-COMM-IN-J-1004
177 DV-2002B DELUGE VALVE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 5085-COMM-IN-J-1001
178 XSY-2002B SOLENOID VALVE 10-TT-101A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
179 PSH-2002B PRESSURE SWITCH 10-TT-101A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 5085-COMM-IN-J-1006
180 PAH-2002B PRESSURE ALARM HIGH 10-TT-101A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
181 RO-2002B RESTRICTION ORIFICE 10-TT-101A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6037-AM3 -
182 RO-2003 RESTRICTION ORIFICE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
183 PI-2003A PRESSURE INDICATOR-MANIFOLD TYPE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 5085-COMM-IN-J-1003
184 DPI-2003A DIFFERENTIAL PRESSURE GAUGE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 5085-COMM-IN-J-1004
185 DV-2003A DELUGE VALVE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 5085-COMM-IN-J-1001
186 XSY-2003A SOLENOID VALVE 10-AT-101A/B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
187 PSL-2003 PRESSURE SWITCH 10-AT-101A/B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
188 PAL-2003 PRESSURE ALARM LOW 10-AT-101A/B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
189 PSH-2003A PRESSURE SWITCH 10-AT-101A/B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
190 PAH-2003A PRESSURE ALARM HIGH 10-AT-101A/B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
191 RO-2003A RESTRICTION ORIFICE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6043-AM3 -
192 PI-2003B PRESSURE INDICATOR-MANIFOLD TYPE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1003
193 DPI-2003B DIFFERENTIAL PRESSURE GAUGE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1004
194 DV-2003B DELUGE VALVE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1001
195 XSY-2003B SOLENOID VALVE 10-AT-101A/B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
196 PSH-2003B PRESSURE SWITCH 10-AT-101A/B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 5085-COMM-IN-J-1006
197 PAH-2003B PRESSURE ALARM HIGH 10-AT-101A/B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
198 RO-2003B RESTRICTION ORIFICE 10-AT-101A/B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6046-AM3 -
199 RO-1005 RESTRICTION ORIFICE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
200 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 5085-COMM-IN-J-1003

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET- NORTH KADI GGS-4
Document Title : INSTRUMENT INDEX
Document No : 5085-NKG4-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

201 DPI-1005A DIFFERENTIAL PRESSURE GAUGE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 5085-COMM-IN-J-1004
202 DV-1005A DELUGE VALVE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 5085-COMM-IN-J-1001
203 XSY-1005A SOLENOID VALVE 10-TT-103A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
204 PSL-1005 PRESSURE SWITCH 10-TT-103A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
205 PAL-1005 PRESSURE ALARM LOW 10-TT-103A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
206 PSH-1005A PRESSURE SWITCH 10-TT-103A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
207 PAH-1005A PRESSURE ALARM HIGH 10-TT-103A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
208 RO-1005A RESTRICTION ORIFICE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6041-AM3 -
209 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 5085-COMM-IN-J-1003
210 DPI-1005B DIFFERENTIAL PRESSURE GAUGE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 5085-COMM-IN-J-1004
211 DV-1005B DELUGE VALVE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 5085-COMM-IN-J-1001
212 XSY-1005B SOLENOID VALVE 10-TT-103A FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
213 PSH-1005B PRESSURE SWITCH 10-TT-103A FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 5085-COMM-IN-J-1006
214 PAH-1005B PRESSURE ALARM HIGH 10-TT-103A CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
215 RO-1005B RESTRICTION ORIFICE 10-TT-103A FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6039-AM3 -
216 RO-1006 RESTRICTION ORIFICE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
217 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 5085-COMM-IN-J-1003
218 DPI-1006A DIFFERENTIAL PRESSURE GAUGE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 5085-COMM-IN-J-1004
219 DV-1006A DELUGE VALVE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 5085-COMM-IN-J-1001
220 XSY-1006A SOLENOID VALVE 10-TT-103B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
221 PSL-1006 PRESSURE SWITCH 10-TT-103B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - 5085-COMM-IN-J-1006
222 PAL-1006 PRESSURE ALARM LOW 10-TT-103B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
223 PSH-1006A PRESSURE SWITCH 10-TT-103B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
224 PAH-1006A PRESSURE ALARM HIGH 10-TT-103B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
5085-COMM-PR-D-1003
225 RO-1006A RESTRICTION ORIFICE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6040-AM3 -
226 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 5085-COMM-IN-J-1003
227 DPI-1006B DIFFERENTIAL PRESSURE GAUGE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 5085-COMM-IN-J-1004
228 DV-1006B DELUGE VALVE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 5085-COMM-IN-J-1001
229 XSY-1006B SOLENOID VALVE 10-TT-103B FIELD RTU DOP FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
230 PSH-1006B PRESSURE SWITCH 10-TT-103B FIELD RTU DI FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 5085-COMM-IN-J-1006
231 PAH-1006B PRESSURE ALARM HIGH 10-TT-103B CCR - SOFT FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 - -
232 RO-1006B RESTRICTION ORIFICE 10-TT-103B FIELD - - FIRE WATER NETWORK 5085-NKG4-PR-D-1002-02 3"-FW-NKG4-6038-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-NKG4-IN-K-1002 Page: 2 of 2

NORTH KADI GGS-4


AI DI DO DOP

RTU 2 30 6 20

RTU WITH 30%


3 39 8 26
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - SOBHASAN GGS-I
Document Title : INSTRUMENT INDEX
Document No : 5085-SOG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks
1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (SOG1-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 SOG1-D-100 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK (SOG1-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK (SOG1-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE SOG1-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 3"-FW-SOG1-6009-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE SOG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 2"-FW-SOG1-6013-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6020-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6020-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6020-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE SOG1-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 2"-FW-SOG1-6022-AA3
13 HS-0102A-START PUMP START COMMAND SOG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND SOG1-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND SOG1-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION SOG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION SOG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION SOG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION SOG1-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE SOG1-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 3"-FW-SOG1-6010-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE SOG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 2"-FW-SOG1-6014-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE SOG1-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 2"-FW-SOG1-6024-AA3
23 HS-0102B-START PUMP START COMMAND SOG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND SOG1-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND SOG1-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION SOG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION SOG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION SOG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION SOG1-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE SOG1-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6011-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE SOG1-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6015-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND SOG1-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND SOG1-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION SOG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION SOG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION SOG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION SOG1-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE SOG1-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6012-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE SOG1-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6016-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND SOG1-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND SOG1-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION SOG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION SOG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION SOG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION SOG1-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6017-AA3 5085-COMM-IN-J-1006
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6017-AA3 5085-COMM-IN-J-1006
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 8"-FW-SOG1-6017-AA3 5085-COMM-IN-J-1006
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG1-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 8"-FW-SOG1-6026-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER NETWORK FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 8"-FW-SOG1-6026-AA3 5085-COMM-IN-J-1003
59 RO-1001 RESTRICTION ORIFICE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
60 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 5085-COMM-IN-J-1003
61 DPI-1001A DIFFERENTIAL PRESSURE GAUGE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 5085-COMM-IN-J-1004
62 DV-1001A DELUGE VALVE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 5085-COMM-IN-J-1001
63 XSY-1001A SOLENOID VALVE SOB1-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
64 PSL-1001 PRESSURE SWITCH SOB1-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
65 PAL-1001 PRESSURE ALARM LOW SOB1-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
66 PSH-1001A PRESSURE SWITCH SOB1-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
67 PAH-1001A PRESSURE ALARM HIGH SOB1-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
68 RO-1001A RESTRICTION ORIFICE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6034-AM3 -
69 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 5085-COMM-IN-J-1003
70 DPI-1001B DIFFERENTIAL PRESSURE GAUGE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 5085-COMM-IN-J-1004
71 DV-1001B DELUGE VALVE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 5085-COMM-IN-J-1001
72 XSY-1001B SOLENOID VALVE SOB1-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
73 PSH-1001B PRESSURE SWITCH SOB1-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 5085-COMM-IN-J-1006
74 PAH-1001B PRESSURE ALARM HIGH SOB1-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
75 RO-1001B RESTRICTION ORIFICE SOB1-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6031-AM3 -
76 RO-1002 RESTRICTION ORIFICE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
77 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 5085-COMM-IN-J-1003
78 DPI-1002A DIFFERENTIAL PRESSURE GAUGE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 5085-COMM-IN-J-1004
79 DV-1002A DELUGE VALVE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 5085-COMM-IN-J-1001
80 XSY-1002A SOLENOID VALVE SOB1-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
81 PSL-1002 PRESSURE SWITCH SOB1-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
82 PAL-1002 PRESSURE ALARM LOW SOB1-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
83 PSH-1002A PRESSURE SWITCH SOB1-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
84 PAH-1002A PRESSURE ALARM HIGH SOB1-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
85 RO-1002A RESTRICTION ORIFICE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6033-AM3 -
86 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 5085-COMM-IN-J-1003
87 DPI-1002B DIFFERENTIAL PRESSURE GAUGE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 5085-COMM-IN-J-1004
88 DV-1002B DELUGE VALVE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 5085-COMM-IN-J-1001
89 XSY-1002B SOLENOID VALVE SOB1-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
90 PSH-1002B PRESSURE SWITCH SOB1-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 5085-COMM-IN-J-1006
91 PAH-1002B PRESSURE ALARM HIGH SOB1-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
92 RO-1002B RESTRICTION ORIFICE SOB1-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6032-AM3 -
93 RO-1003 RESTRICTION ORIFICE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
94 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 5085-COMM-IN-J-1003
95 DPI-1003A DIFFERENTIAL PRESSURE GAUGE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 5085-COMM-IN-J-1004
96 DV-1003A DELUGE VALVE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 5085-COMM-IN-J-1003
97 XSY-1003A SOLENOID VALVE SOB1-ST-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
98 PSL-1003 PRESSURE SWITCH SOB1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
99 PAL-1003 PRESSURE ALARM LOW SOB1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
100 PSH-1003A PRESSURE SWITCH SOB1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
101 PAH-1003A PRESSURE ALARM HIGH SOB1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
102 RO-1003A RESTRICTION ORIFICE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6038-AM3 -
103 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 5085-COMM-IN-J-1003
104 DPI-1003B DIFFERENTIAL PRESSURE GAUGE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 5085-COMM-IN-J-1004
105 DV-1003B DELUGE VALVE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 5085-COMM-IN-J-1003
106 XSY-1003B SOLENOID VALVE SOB1-ST-01/02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
107 PSH-1003B PRESSURE SWITCH SOB1-ST-01/02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 5085-COMM-IN-J-1006
108 PAH-1003B PRESSURE ALARM HIGH SOB1-ST-01/02 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
109 RO-1003B RESTRICTION ORIFICE SOB1-ST-01/02 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 3"-FW-SOG1-6043-AM3 -
110 RO-2001 RESTRICTION ORIFICE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -

SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - SOBHASAN GGS-I
Document Title : INSTRUMENT INDEX
Document No : 5085-SOG1-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks
111 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 5085-COMM-IN-J-1003
112 DPI-2001A DIFFERENTIAL PRESSURE GAUGE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 5085-COMM-IN-J-1004
113 DV-2001A DELUGE VALVE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 5085-COMM-IN-J-1001
114 XSY-2001A SOLENOID VALVE SOB1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
115 PSL-2001 PRESSURE SWITCH SOB1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - 5085-COMM-IN-J-1006
116 PAL-2001 PRESSURE ALARM LOW SOB1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
117 PSH-2001A PRESSURE SWITCH SOB1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
118 PAH-2001A PRESSURE ALARM HIGH SOB1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
5085-COMM-PR-D-1003
119 RO-2001A RESTRICTION ORIFICE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6027-AM3 -
120 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6030-AM3 5085-COMM-IN-J-1003
121 DPI-2001B DIFFERENTIAL PRESSURE GAUGE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6030-AM3 5085-COMM-IN-J-1004
122 DV-2001B DELUGE VALVE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6030-AM3 5085-COMM-IN-J-1001
123 XSY-2001B SOLENOID VALVE SOB1-TT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
124 PSH-2001B PRESSURE SWITCH SOB1-TT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6030-AM3 5085-COMM-IN-J-1006
125 PAH-2001B PRESSURE ALARM HIGH SOB1-TT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 - -
126 RO-2001B RESTRICTION ORIFICE SOB1-TT-01 FIELD - - FIRE WATER NETWORK 5085-SOG1-PR-D-1002-01 2"-FW-SOG1-6030-AM3 -

SHEET 3 OF 3
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-SOG1-IN-K-1002 Page: 2 of 2

SOBHASAN GGS-1
AI DI DO DOP

RTU 2 12 6 8

RTU SPARE WITH


3 16 8 10
30% CONTINGENCY

FWCP 3 16 4 -

FWCP SPARE WITH


4 21 5 -
30% CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - SOBHASAN GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-SOG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK-2 FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK-2 CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK-2 CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (SOG2-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK (SOG2-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK (SOG2-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE SOG2-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 3"-FW-SOG2-6008-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE SOG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 2"-FW-SOG2-6012-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6024-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6024-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6024-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE SOG2-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 2"-FW-SOG2-6022-AA3
13 HS-0102A-START PUMP START COMMAND SOG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND SOG2-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND SOG2-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION SOG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION SOG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION SOG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION SOG2-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE SOG2-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 3"-FW-SOG2-6009-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE SOG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 2"-FW-SOG2-6013-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE SOG2-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 2"-FW-SOG2-6020-AA3
23 HS-0102B-START PUMP START COMMAND SOG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND SOG2-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND SOG2-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION SOG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION SOG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION SOG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION SOG2-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE SOG2-P-101A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6010-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE SOG2-P-101A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6014-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND SOG2-P-101A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND SOG2-P-101A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION SOG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION SOG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION SOG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION SOG2-P-101A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE SOG2-P-101B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6011-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE SOG2-P-101B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6015-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND SOG2-P-101B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND SOG2-P-101B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION SOG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION SOG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION SOG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION SOG2-P-101B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6003-AA3 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6003-AA3 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 8"-FW-SOG2-6003-AA3 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOG2-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 8"-FW-SOG2-6019-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 8"-FW-SOG2-6016-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1003
60 PI-0301 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-02 - 5085-COMM-IN-J-1003
61 RO-1001 RESTRICTION ORIFICE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
62 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 5085-COMM-IN-J-1003
63 DPI-1001A DIFFERENTIAL PRESSURE GAUGE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 5085-COMM-IN-J-1004
64 DV-1001A DELUGE VALVE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 5085-COMM-IN-J-1001
65 XSY-1001A SOLENOID VALVE SOB2-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
66 PSL-1001 PRESSURE SWITCH SOB2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
67 PAL-1001 PRESSURE ALARM LOW SOB2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
68 PSH-1001A PRESSURE SWITCH SOB2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
69 PAH-1001A PRESSURE ALARM HIGH SOB2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
70 RO-1001A RESTRICTION ORIFICE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6044-AM3 -
71 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 5085-COMM-IN-J-1003
72 DPI-1001B DIFFERENTIAL PRESSURE GAUGE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 5085-COMM-IN-J-1004
73 DV-1001B DELUGE VALVE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 5085-COMM-IN-J-1001
74 XSY-1001B SOLENOID VALVE SOB2-ST-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
75 PSH-1001B PRESSURE SWITCH SOB2-ST-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 5085-COMM-IN-J-1006
76 PAH-1001B PRESSURE ALARM HIGH SOB2-ST-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
77 RO-1001B RESTRICTION ORIFICE SOB2-ST-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6045-AM3 -
78 RO-1008 RESTRICTION ORIFICE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
79 PI-1008A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 5085-COMM-IN-J-1003
80 DPI-1008A DIFFERENTIAL PRESSURE GAUGE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 5085-COMM-IN-J-1004
81 DV-1008A DELUGE VALVE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 5085-COMM-IN-J-1001
82 XSY-1008A SOLENOID VALVE SOB2-CU-T-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
83 PSL-1008 PRESSURE SWITCH SOB2-CU-T-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
84 PAL-1008 PRESSURE ALARM LOW SOB2-CU-T-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
85 PSH-1008A PRESSURE SWITCH SOB2-CU-T-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
86 PAH-1008A PRESSURE ALARM HIGH SOB2-CU-T-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
87 RO-1008A RESTRICTION ORIFICE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6043-AM3 -
88 PI-1008B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 5085-COMM-IN-J-1003
89 DPI-1008B DIFFERENTIAL PRESSURE GAUGE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 5085-COMM-IN-J-1004
90 DV-1008B DELUGE VALVE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 5085-COMM-IN-J-1001
91 XSY-1008B SOLENOID VALVE SOB2-CU-T-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
92 PSH-1008B PRESSURE SWITCH SOB2-CU-T-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 5085-COMM-IN-J-1006
93 PAH-1008B PRESSURE ALARM HIGH SOB2-CU-T-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
94 RO-1008B RESTRICTION ORIFICE SOB2-CU-T-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 2"-FW-SOG2-6042-AM3 -
95 RO-2002 RESTRICTION ORIFICE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
96 PI-2002A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 5085-COMM-IN-J-1003
97 DPI-2002A DIFFERENTIAL PRESSURE GAUGE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 5085-COMM-IN-J-1004
98 DV-2002A DELUGE VALVE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 5085-COMM-IN-J-1001
99 XSY-2002A SOLENOID VALVE SOB2-ACT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
100 PSL-2002 PRESSURE SWITCH SOB2-ACT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006

SHEET 2 OF 4 REFER DELUGE VALVE SCHEMATIC FOR TANKS


Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - SOBHASAN GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-SOG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PAL-2002 PRESSURE ALARM LOW SOB2-ACT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
102 PSH-2002A PRESSURE SWITCH SOB2-ACT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
103 PAH-2002A PRESSURE ALARM HIGH SOB2-ACT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
104 RO-2002A RESTRICTION ORIFICE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6047-AM3 -
105 PI-2002B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 5085-COMM-IN-J-1003
106 DPI-2002B DIFFERENTIAL PRESSURE GAUGE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 5085-COMM-IN-J-1004
107 DV-2002B DELUGE VALVE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 5085-COMM-IN-J-1001
108 XSY-2002B SOLENOID VALVE SOB2-ACT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
109 PSH-2002B PRESSURE SWITCH SOB2-ACT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 5085-COMM-IN-J-1006
110 PAH-2002B PRESSURE ALARM HIGH SOB2-ACT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
111 RO-2002B RESTRICTION ORIFICE SOB2-ACT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6046-AM3 -
112 RO-2001 RESTRICTION ORIFICE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
113 PI-2001A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 5085-COMM-IN-J-1003
114 DPI-2001A DIFFERENTIAL PRESSURE GAUGE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 5085-COMM-IN-J-1004
115 DV-2001A DELUGE VALVE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 5085-COMM-IN-J-1001
116 XSY-2001A SOLENOID VALVE SOB2-TT-03 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
117 PSL-2001 PRESSURE SWITCH SOB2-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
118 PAL-2001 PRESSURE ALARM LOW SOB2-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
119 PSH-2001A PRESSURE SWITCH SOB2-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
120 PAH-2001A PRESSURE ALARM HIGH SOB2-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
121 RO-2001A RESTRICTION ORIFICE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6054-AM3 -
122 PI-2001B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 5085-COMM-IN-J-1003
123 DPI-2001B DIFFERENTIAL PRESSURE GAUGE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 5085-COMM-IN-J-1004
124 DV-2001B DELUGE VALVE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 5085-COMM-IN-J-1001
125 XSY-2001B SOLENOID VALVE SOB2-TT-03 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
126 PSH-2001B PRESSURE SWITCH SOB2-TT-03 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 5085-COMM-IN-J-1006
127 PAH-2001B PRESSURE ALARM HIGH SOB2-TT-03 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
128 RO-2001B RESTRICTION ORIFICE SOB2-TT-03 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6041-AM3 -
129 RO-1009 RESTRICTION ORIFICE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
130 PI-1009A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6053-AM3 5085-COMM-IN-J-1003
131 DPI-1009A DIFFERENTIAL PRESSURE GAUGE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6053-AM3 5085-COMM-IN-J-1004
132 DV-1009A DELUGE VALVE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6053-AM3 5085-COMM-IN-J-1001
133 XSY-1009A SOLENOID VALVE SOB2-CU-T-04 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
134 PSL-1009 PRESSURE SWITCH SOB2-CU-T-04 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
135 PAL-1009 PRESSURE ALARM LOW SOB2-CU-T-04 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
136 PSH-1009A PRESSURE SWITCH SOB2-CU-T-04 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6053-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
137 PAH-1009A PRESSURE ALARM HIGH SOB2-CU-T-04 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
138 RO-1009A RESTRICTION ORIFICE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6053-AM3 -
139 PI-1009B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6040-AM3 5085-COMM-IN-J-1003
140 DPI-1009B DIFFERENTIAL PRESSURE GAUGE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6040-AM3 5085-COMM-IN-J-1004
141 DV-1009B DELUGE VALVE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6040-AM3 5085-COMM-IN-J-1001
142 XSY-1009B SOLENOID VALVE SOB2-CU-T-04 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
143 PSH-1009B PRESSURE SWITCH SOB2-CU-T-04 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6040-AM3 5085-COMM-IN-J-1006
144 PAH-1009B PRESSURE ALARM HIGH SOB2-CU-T-04 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
145 RO-1009B RESTRICTION ORIFICE SOB2-CU-T-04 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6040-AM3 -
146 RO-1005 RESTRICTION ORIFICE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
147 PI-1005A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 5085-COMM-IN-J-1003
148 DPI-1005A DIFFERENTIAL PRESSURE GAUGE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 5085-COMM-IN-J-1004
149 DV-1005A DELUGE VALVE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 5085-COMM-IN-J-1001
150 XSY-1005A SOLENOID VALVE SOB2-ST-08 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
151 PSL-1005 PRESSURE SWITCH SOB2-ST-08 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
152 PAL-1005 PRESSURE ALARM LOW SOB2-ST-08 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
153 PSH-1005A PRESSURE SWITCH SOB2-ST-08 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
154 PAH-1005A PRESSURE ALARM HIGH SOB2-ST-08 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
155 RO-1005A RESTRICTION ORIFICE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6033-AM3 -
156 PI-1005B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 5085-COMM-IN-J-1003
157 DPI-1005B DIFFERENTIAL PRESSURE GAUGE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 5085-COMM-IN-J-1004
158 DV-1005B DELUGE VALVE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 5085-COMM-IN-J-1001
159 XSY-1005B SOLENOID VALVE SOB2-ST-08 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
160 PSH-1005B PRESSURE SWITCH SOB2-ST-08 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 5085-COMM-IN-J-1006
161 PAH-1005B PRESSURE ALARM HIGH SOB2-ST-08 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
162 RO-1005B RESTRICTION ORIFICE SOB2-ST-08 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6039-AM3 -
163 RO-1007 RESTRICTION ORIFICE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
164 PI-1007A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 5085-COMM-IN-J-1003
165 DPI-1007A DIFFERENTIAL PRESSURE GAUGE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 5085-COMM-IN-J-1004
166 DV-1007A DELUGE VALVE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 5085-COMM-IN-J-1001
167 XSY-1007A SOLENOID VALVE SOB2-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
168 PSL-1007 PRESSURE SWITCH SOB2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
169 PAL-1007 PRESSURE ALARM LOW SOB2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
170 PSH-1007A PRESSURE SWITCH SOB2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
171 PAH-1007A PRESSURE ALARM HIGH SOB2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
172 RO-1007A RESTRICTION ORIFICE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6035-AM3 -
173 PI-1007B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 5085-COMM-IN-J-1003
174 DPI-1007B DIFFERENTIAL PRESSURE GAUGE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 5085-COMM-IN-J-1004
175 DV-1007B DELUGE VALVE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 5085-COMM-IN-J-1001
176 XSY-1007B SOLENOID VALVE SOB2-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
177 PSH-1007B PRESSURE SWITCH SOB2-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 5085-COMM-IN-J-1006
178 PAH-1007B PRESSURE ALARM HIGH SOB2-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
179 RO-1007B RESTRICTION ORIFICE SOB2-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6038-AM3 -
180 RO-1002 RESTRICTION ORIFICE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
181 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 5085-COMM-IN-J-1003
182 DPI-1002A DIFFERENTIAL PRESSURE GAUGE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 5085-COMM-IN-J-1004
183 DV-1002A DELUGE VALVE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 5085-COMM-IN-J-1001
184 XSY-1002A SOLENOID VALVE SOB2-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
185 PSL-1002 PRESSURE SWITCH SOB2-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
186 PAL-1002 PRESSURE ALARM LOW SOB2-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
187 PSH-1002A PRESSURE SWITCH SOB2-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
188 PAH-1002A PRESSURE ALARM HIGH SOB2-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
189 RO-1002A RESTRICTION ORIFICE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6028-AM3 -
190 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 5085-COMM-IN-J-1003
191 DPI-1002B DIFFERENTIAL PRESSURE GAUGE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 5085-COMM-IN-J-1004
192 DV-1002B DELUGE VALVE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 5085-COMM-IN-J-1001
193 XSY-1002B SOLENOID VALVE SOB2-ST-05 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
194 PSH-1002B PRESSURE SWITCH SOB2-ST-05 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 5085-COMM-IN-J-1006
195 PAH-1002B PRESSURE ALARM HIGH SOB2-ST-05 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
196 RO-1002B RESTRICTION ORIFICE SOB2-ST-05 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6030-AM3 -
197 RO-1003 RESTRICTION ORIFICE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
198 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 5085-COMM-IN-J-1003
199 DPI-1003A DIFFERENTIAL PRESSURE GAUGE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 5085-COMM-IN-J-1004
200 DV-1003A DELUGE VALVE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 5085-COMM-IN-J-1001

SHEET 3 OF 4
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET - SOBHASAN GGS-2
Document Title : INSTRUMENT INDEX
Document No : 5085-SOG2-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

201 XSY-1003A SOLENOID VALVE SOB2-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
202 PSL-1003 PRESSURE SWITCH SOB2-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
203 PAL-1003 PRESSURE ALARM LOW SOB2-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
204 PSH-1003A PRESSURE SWITCH SOB2-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
205 PAH-1003A PRESSURE ALARM HIGH SOB2-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
206 RO-1003A RESTRICTION ORIFICE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6029-AM3 -
207 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 5085-COMM-IN-J-1003
208 DPI-1003B DIFFERENTIAL PRESSURE GAUGE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 5085-COMM-IN-J-1004
209 DV-1003B DELUGE VALVE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 5085-COMM-IN-J-1001
210 XSY-1003B SOLENOID VALVE SOB2-ST-06 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
211 PSH-1003B PRESSURE SWITCH SOB2-ST-06 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 5085-COMM-IN-J-1006
212 PAH-1003B PRESSURE ALARM HIGH SOB2-ST-06 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
213 RO-1003B RESTRICTION ORIFICE SOB2-ST-06 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6031-AM3 -
214 RO-1004 RESTRICTION ORIFICE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
215 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 5085-COMM-IN-J-1003
216 DPI-1004A DIFFERENTIAL PRESSURE GAUGE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 5085-COMM-IN-J-1004
217 DV-1004A DELUGE VALVE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 5085-COMM-IN-J-1001
218 XSY-1004A SOLENOID VALVE SOB2-ST-07 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
219 PSL-1004 PRESSURE SWITCH SOB2-ST-07 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
220 PAL-1004 PRESSURE ALARM LOW SOB2-ST-07 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
221 PSH-1004A PRESSURE SWITCH SOB2-ST-07 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
222 PAH-1004A PRESSURE ALARM HIGH SOB2-ST-07 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
223 RO-1004A RESTRICTION ORIFICE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6032-AM3 -
224 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 5085-COMM-IN-J-1003
225 DPI-1004B DIFFERENTIAL PRESSURE GAUGE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 5085-COMM-IN-J-1004
226 DV-1004B DELUGE VALVE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 5085-COMM-IN-J-1001
227 XSY-1004B SOLENOID VALVE SOB2-ST-07 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
228 PSH-1004B PRESSURE SWITCH SOB2-ST-07 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 5085-COMM-IN-J-1006
229 PAH-1004B PRESSURE ALARM HIGH SOB2-ST-07 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
230 RO-1004B RESTRICTION ORIFICE SOB2-ST-07 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6036-AM3 -
231 RO-1006 RESTRICTION ORIFICE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
232 PI-1006A PRESSURE INDICATOR-MANIFOLD TYPE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 5085-COMM-IN-J-1003
233 DPI-1006A DIFFERENTIAL PRESSURE GAUGE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 5085-COMM-IN-J-1004
234 DV-1006A DELUGE VALVE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 5085-COMM-IN-J-1001
235 XSY-1006A SOLENOID VALVE SOB2-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
236 PSL-1006 PRESSURE SWITCH SOB2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - 5085-COMM-IN-J-1006
237 PAL-1006 PRESSURE ALARM LOW SOB2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
238 PSH-1006A PRESSURE SWITCH SOB2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
239 PAH-1006A PRESSURE ALARM HIGH SOB2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
5085-COMM-PR-D-1003
240 RO-1006A RESTRICTION ORIFICE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6034-AM3 -
241 PI-1006B PRESSURE INDICATOR-MANIFOLD TYPE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 5085-COMM-IN-J-1003
242 DPI-1006B DIFFERENTIAL PRESSURE GAUGE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 5085-COMM-IN-J-1004
243 DV-1006B DELUGE VALVE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 5085-COMM-IN-J-1001
244 XSY-1006B SOLENOID VALVE SOB2-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
245 PSH-1006B PRESSURE SWITCH SOB2-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 5085-COMM-IN-J-1006
246 PAH-1006B PRESSURE ALARM HIGH SOB2-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 - -
247 RO-1006B RESTRICTION ORIFICE SOB2-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOG2-PR-D-1002-01 3"-FW-SOG2-6037-AM3 -

SHEET 4 OF 4
REVAMPING OF FIRE PROTECTION SYSTEM AT
INSTALLATIONS OF MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-SOG2-IN-K-1002 Page: 2 of 2

SOBHASAN GGS-2
AI DI DO DOP

RTU 2 33 6 22

RTU WITH 30%


3 43 8 29
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-SOBHASAN WWTP
Document Title : INSTRUMENT INDEX
Document No : 5085-SOW-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

1 LIT-0101 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 - 5085-COMM-IN-J-1006
2 LI-0101 LEVEL INDICATION FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
3 LAL-0101 LEVEL ALARM LOW FIRE WATER TANK CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
4 LIT-0102 LEVEL TRANSMITTER-FLOAT AND TAPE LEVEL TYPE FIRE WATER TANK (SOW-D-100) FIELD RTU AI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 - 5085-COMM-IN-J-1006
5 LI-0102 LEVEL INDICATION FIRE WATER TANK (SOW-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
6 LAL-0102 LEVEL ALARM LOW FIRE WATER TANK (SOW-D-100) CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
7 DPI-0101 DIFFERENTIAL PRESSURE GAUGE SOW-P-102A PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 3"-FW-SOW-6007-AA3 5085-COMM-IN-J-1004
8 PI-0105 PRESSURE INDICATOR-MANIFOLD TYPE SOW-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 2"-FW-SOW-6008-AA3 5085-COMM-IN-J-1003
9 FE-0101 FLOW ELEMENT - ORIFICE TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6013-AA3 5085-COMM-IN-J-1005
10 FI-0101 LOCAL DP TYPE FLOW INDICATOR FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6013-AA3 5085-COMM-IN-J-1005
11 PI-0109 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER TANK OUTLET FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6013-AA3 5085-COMM-IN-J-1003
12 ARV-0102A AUTOMATIC RECIRCULATION VALVE SOW-P-102A PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 2"-FW-SOW-6019-AA3
13 HS-0102A-START PUMP START COMMAND SOW-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
14 HS-0102A-STOP PUMP STOP COMMAND SOW-P-102A PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
15 XS-0102A PUMP AUTO START/STOP COMMAND SOW-P-102A PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
16 XA-0102A PUMP FAULT INDICATION SOW-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
17 XI-0102A PUMP RUNNING INDICATION SOW-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
18 XL-0102A-AUTO AUTO INDICATION SOW-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
19 XL-0102A-MANUAL MANUAL INDICATION SOW-P-102A PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
20 DPI-0102 DIFFERENTIAL PRESSURE GAUGE SOW-P-102B PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 3"-FW-SOW-6006-AA3 5085-COMM-IN-J-1004
21 PI-0106 PRESSURE INDICATOR-MANIFOLD TYPE SOW-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 2"-FW-SOW-6009-AA3 5085-COMM-IN-J-1003
22 ARV-0102B AUTOMATIC RECIRCULATION VALVE SOW-P-102B PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 2"-FW-SOW-6020-AA3
23 HS-0102B-START PUMP START COMMAND SOW-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
24 HS-0102B-STOP PUMP STOP COMMAND SOW-P-102B PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
25 XS-0102B PUMP AUTO START/STOP COMMAND SOW-P-102B PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
26 XA-0102B PUMP FAULT INDICATION SOW-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
27 XI-0102B PUMP RUNNING INDICATION SOW-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
28 XL-0102B-AUTO AUTO INDICATION SOW-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
29 XL-0102B-MANUAL MANUAL INDICATION SOW-P-102B PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
30 DPI-0103 DIFFERENTIAL PRESSURE GAUGE SOWETP-FW-02 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6004-AA3 5085-COMM-IN-J-1004
31 PI-0107 PRESSURE INDICATOR-MANIFOLD TYPE SOWETP-FW-02 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6010-AA3 5085-COMM-IN-J-1003
32 HS-0101A-START PUMP START COMMAND SOWETP-FW-02 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
33 XS-0101A PUMP AUTO START COMMAND SOWETP-FW-02 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
34 XA-0101A PUMP FAULT INDICATION SOWETP-FW-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
35 XL-0101A PUMP RUNNING INDICATION SOWETP-FW-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
36 XL-0101A-AUTO AUTO INDICATION SOWETP-FW-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
37 XL-0101A-MANUAL MANUAL INDICATION SOWETP-FW-02 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
38 DPI-0104 DIFFERENTIAL PRESSURE GAUGE SOWETP-FW-01 PUMP SUCTION FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6005-AA3 5085-COMM-IN-J-1004
39 PI-0108 PRESSURE INDICATOR-MANIFOLD TYPE SOWETP-FW-01 PUMP DISCHARGE FIELD - - FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 8"-FW-SOW-6011-AA3 5085-COMM-IN-J-1003
40 HS-0101B-START PUMP START COMMAND SOWETP-FW-01 PUMP FIELD RTU DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
41 XS-0101B PUMP AUTO START COMMAND SOWETP-FW-01 PUMP FIELD FWP CP DO FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
42 XA-0101B PUMP FAULT INDICATION SOWETP-FW-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
43 XL-0101B PUMP RUNNING INDICATION SOWETP-FW-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
44 XL-0101B-AUTO AUTO INDICATION SOWETP-FW-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
45 XL-0101B-MANUAL MANUAL INDICATION SOWETP-FW-01 PUMP FIELD FWP CP DI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
46 PIT-0110 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 - 5085-COMM-IN-J-1002
47 PI-0110 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
48 PAL-0110 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
49 PIT-0111 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 - 5085-COMM-IN-J-1002
50 PI-0111 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
51 PAL-0111 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
52 PIT-0112 PRESSURE INDICATING TRANSMITTER-MANIFOLD TYPE PUMP DISCHARGE HEADER FIELD FWP CP AI FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 - 5085-COMM-IN-J-1002
53 PI-0112 PRESSURE INDICATION PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
54 PAH-0112 PRESSURE ALARM HIGH PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
55 PAL-0112 PRESSURE ALARM LOW PUMP DISCHARGE HEADER CCR - SOFT FIRE WATER TANKS AND PUMPS 5085-SOW-PR-D-1001-01 -
56 PI-0201 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6026-AA3 5085-COMM-IN-J-1003
57 PI-0202 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6017-AA3 5085-COMM-IN-J-1003
58 PI-0203 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6012-AA3 5085-COMM-IN-J-1003
59 PI-0204 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - 5085-COMM-IN-J-1003
60 PI-0205 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6030-AA3 5085-COMM-IN-J-1003
61 PI-0206 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6027-AA3 5085-COMM-IN-J-1003
62 PI-0207 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 8"-FW-SOW-6028-AA3 5085-COMM-IN-J-1003
63 PI-0208 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - 5085-COMM-IN-J-1003
64 PI-0209 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 8"-FW-SOW-6049-AA3 5085-COMM-IN-J-1003
65 PI-0210 PRESSURE INDICATOR-MANIFOLD TYPE FIRE WATER HEADER FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 8"-FW-SOW-6048-AA3 5085-COMM-IN-J-1003
66 RO-1001 RESTRICTION ORIFICE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
67 PI-1001A PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 5085-COMM-IN-J-1003
68 DPI-1001A DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 5085-COMM-IN-J-1004
69 DV-1001A DELUGE VALVE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 5085-COMM-IN-J-1001
70 XSY-1001A SOLENOID VALVE SOBETP-WT-101A FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
71 PSL-1001 PRESSURE SWITCH SOBETP-WT-101A FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - 5085-COMM-IN-J-1006
72 PAL-1001 PRESSURE ALARM LOW SOBETP-WT-101A CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
73 PSH-1001A PRESSURE SWITCH SOBETP-WT-101A FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
74 PAH-1001A PRESSURE ALARM HIGH SOBETP-WT-101A CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
5085-COMM-PR-D-1003
75 RO-1001A RESTRICTION ORIFICE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6039-AM3 -
76 PI-1001B PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 5085-COMM-IN-J-1003
77 DPI-1001B DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 5085-COMM-IN-J-1004
78 DV-1001B DELUGE VALVE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 5085-COMM-IN-J-1001
79 XSY-1001B SOLENOID VALVE SOBETP-WT-101A FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
80 PSH-1001B PRESSURE SWITCH SOBETP-WT-101A FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 5085-COMM-IN-J-1006
81 PAH-1001B PRESSURE ALARM HIGH SOBETP-WT-101A CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
82 RO-1001B RESTRICTION ORIFICE SOBETP-WT-101A FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6042-AM3 -
83 RO-1002 RESTRICTION ORIFICE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
84 PI-1002A PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 5085-COMM-IN-J-1003
85 DPI-1002A DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 5085-COMM-IN-J-1004
86 DV-1002A DELUGE VALVE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 5085-COMM-IN-J-1001
87 XSY-1002A SOLENOID VALVE SOBETP-WT-101B FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
88 PSL-1002 PRESSURE SWITCH SOBETP-WT-101B FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - 5085-COMM-IN-J-1006
89 PAL-1002 PRESSURE ALARM LOW SOBETP-WT-101B CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
90 PSH-1002A PRESSURE SWITCH SOBETP-WT-101B FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
91 PAH-1002A PRESSURE ALARM HIGH SOBETP-WT-101B CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
5085-COMM-PR-D-1003
92 RO-1002A RESTRICTION ORIFICE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6040-AM3 -
93 PI-1002B PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 5085-COMM-IN-J-1003
94 DPI-1002B DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 5085-COMM-IN-J-1004
95 DV-1002B DELUGE VALVE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 5085-COMM-IN-J-1001
96 XSY-1002B SOLENOID VALVE SOBETP-WT-101B FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
97 PSH-1002B PRESSURE SWITCH SOBETP-WT-101B FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 5085-COMM-IN-J-1006
98 PAH-1002B PRESSURE ALARM HIGH SOBETP-WT-101B CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 - -
99 RO-1002B RESTRICTION ORIFICE SOBETP-WT-101B FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-01 3"-FW-SOW-6041-AM3 -
100 RO-1003 RESTRICTION ORIFICE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -

SHEET 2 OF 3
Project : REVAMPING OF FIRE PROTECTION SYSTEM AT INSTALLATIONS OF MEHSANA ASSET-SOBHASAN WWTP
Document Title : INSTRUMENT INDEX
Document No : 5085-SOW-IN-K-1001
Revision No :1

S.No Tag No. Instrument Description Service Location System I/O Type P&ID Name P&ID Number Line/Equipment Number Instrument Datasheet No Remarks

101 PI-1003A PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6036-AM3 5085-COMM-IN-J-1003
102 DPI-1003A DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6036-AM3 5085-COMM-IN-J-1004
103 DV-1003A DELUGE VALVE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6036-AM3 5085-COMM-IN-J-1001
104 XSY-1003A SOLENOID VALVE SOBETP-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
105 PSL-1003 PRESSURE SWITCH SOBETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - 5085-COMM-IN-J-1006
106 PAL-1003 PRESSURE ALARM LOW SOBETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
107 PSH-1003A PRESSURE SWITCH SOBETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6036-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
108 PAH-1003A PRESSURE ALARM HIGH SOBETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
5085-COMM-PR-D-1003
109 RO-1003A RESTRICTION ORIFICE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6036-AM3 -
110 PI-1003B PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6035-AM3 5085-COMM-IN-J-1003
111 DPI-1003B DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6035-AM3 5085-COMM-IN-J-1004
112 DV-1003B DELUGE VALVE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6035-AM3 5085-COMM-IN-J-1001
113 XSY-1003B SOLENOID VALVE SOBETP-WT-01 FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
114 PSH-1003B PRESSURE SWITCH SOBETP-WT-01 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6035-AM3 5085-COMM-IN-J-1006
115 PAH-1003B PRESSURE ALARM HIGH SOBETP-WT-01 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
116 RO-1003B RESTRICTION ORIFICE SOBETP-WT-01 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6035-AM3 -
117 RO-1004 RESTRICTION ORIFICE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
118 PI-1004A PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6037-AM3 5085-COMM-IN-J-1003
119 DPI-1004A DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6037-AM3 5085-COMM-IN-J-1004
120 DV-1004A DELUGE VALVE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6037-AM3 5085-COMM-IN-J-1001
121 XSY-1004A SOLENOID VALVE SOBETP-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
122 PSL-1004 PRESSURE SWITCH SOBETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - 5085-COMM-IN-J-1006
123 PAL-1004 PRESSURE ALARM LOW SOBETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
124 PSH-1004A PRESSURE SWITCH SOBETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6037-AM3 5085-COMM-IN-J-1006
REFER DELUGE VALVE SCHEMATIC FOR TANKS
125 PAH-1004A PRESSURE ALARM HIGH SOBETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
5085-COMM-PR-D-1003
126 RO-1004A RESTRICTION ORIFICE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6037-AM3 -
127 DPI-1004B DIFFERENTIAL PRESSURE GAUGE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6038-AM3 5085-COMM-IN-J-1004
128 PI-1004B PRESSURE INDICATOR-MANIFOLD TYPE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6038-AM3 5085-COMM-IN-J-1003
129 DV-1004B DELUGE VALVE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6038-AM3 5085-COMM-IN-J-1001
130 XSY-1004B SOLENOID VALVE SOBETP-WT-02 FIELD RTU DOP FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
131 PSH-1004B PRESSURE SWITCH SOBETP-WT-02 FIELD RTU DI FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6038-AM3 5085-COMM-IN-J-1006
132 PAH-1004B PRESSURE ALARM HIGH SOBETP-WT-02 CCR - SOFT FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 - -
133 RO-1004B RESTRICTION ORIFICE SOBETP-WT-02 FIELD - - FIRE WATER NETWORK 5085-SOW-PR-D-1002-02 3"-FW-SOW-6038-AM3 -

SHEET 3 OF 3
FIRE FIGHTING SYSTEM UPGRADATION OF 17
INSTALLATIONS AT MEHSANA ASSET

I/O List Rev: 1


Doc No: 5085-SOW-IN-K-1002 Page: 2 of 2

SOBHASAN-WWTP
AI DI DO DOP

RTU 2 12 6 8

RTU WITH 30%


3 16 8 10
CONTINGENCY

FWPCP 3 16 4 -

FWPCP WITH 30%


4 21 5 -
CONTINGENCY

Notes:
1. All I/O counts are indicative