Types of Wire

The document describes various types of wire insulation materials and their properties, including their temperature ratings and intended use locations. Some key insulation materials mentioned are moisture-resistant latex rubber rated for 167°F dry use, thermoplastic rated for 32°F to 150°F, moisture-resistant thermoplastic rated for 140°F and not for direct ground burial, underground feeder cable rated for 140°F for burial, and fluororesin insulated wire rated for 200°C with excellent heat, cold, oil and chemical resistance.

Uploaded by

MICHAEL
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
286 views

Types of Wire

The document describes various types of wire insulation materials and their properties, including their temperature ratings and intended use locations. Some key insulation materials mentioned are moisture-resistant latex rubber rated for 167°F dry use, thermoplastic rated for 32°F to 150°F, moisture-resistant thermoplastic rated for 140°F and not for direct ground burial, underground feeder cable rated for 140°F for burial, and fluororesin insulated wire rated for 200°C with excellent heat, cold, oil and chemical resistance.

Uploaded by

MICHAEL
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Moisture-Resistant Latex Rubber(RUW). Heat Resistant Latex Rubber 167°F.

, Dry only

Thermoplastic(T). Wire wrapped in thermoplastic insulation for protection from below 32° to 150°F.
Tinsel Cord 140̊F,(TP, TS, TPT, TST)

Moisture-Resistant Thermoplastic(TW). T-Wire with water-resistant insulation. Should not be buried


directly in ground. 140° Flame Retardant, Heat and Moisture resistant thermoplastic.

Underground feeder(UF). Underground Feeder and Branch Circuit Cable, 140°F. a water proof version of
NMC, rated for burial in the ground

Fluororesin Insulated Wire(FEPW). The maximum working temperature is 200℃.These wires have
excellent resistance to heat, cold, oil and chemicals, and do not burn.Wiring of electronic devices and
data devices.

Heat-Resistant Rubber(RH). Thermoset, 167°F. Dry and Damp only, Flame Retardant, and Moisture
Resistant. Best Quality, Better than RH and RP wire. For Factories and like. Moisture Res. & Flame
Retardant non-metallic Covering.

Moisture and Heat-Resistant Rubber(RHW). Flame, Ozone and Moisture Resistant, 167°F. For dry and
wet locations over 2,000 volts.

Heat-Resistant Latex Rubber(RUH). Heat Resistant Latex Rubber 167°F., Dry only.

Moisture and Heat-Resistant Thermoplastic(THW). TW-Wire 167°F. With heavier heat resistant
insulation. Dry and Wet Locations, Flame Retardant. (194°F. Special Applications within electric
discharge lighting equipment, 1,000w. open circuits or less.)

Thermoplastic Heat and Water-resistant Nylon-coated(THWN). Thermoplastic insulation, 167°F. with


outer nylon (or equivalent) jacket; Flame Retardant, Heat and Water Resistant.

Cross-Linked High Heat Water Resistant Insulated Wire(XHHW). Moisture Resistant Thermoset, 194°F.
For dry and Damp locations and 167°F. For wet locations. Flame Retardant, and moisture resistant.

Underground Service Entrance(USE). Underground Service Entrance Cable not fire resistant but high
temp. Wire 167°F. Replaces Lead shielded cable. Heavily rubber coated, with outer covering extra water
resistant, can also be type “T” with thermoplastic protection.

Flame-retardant and heat-resistant thermoplastic (ethylene tetrafluoroethylene) insulation(ZW). Type


ZW wire is suitable for use in dry locations at 90°C or wet locations at 75°C. It is also suitable for use in
dry locations at 150°C and lower temperatures for special applications.

Varnished Cambric(V). Varnished Cambric, #6 to MCM2000, 185°F., Dry use only.

Mineral Insulation (Metal Sheathed)(MI). Mineral Insulated, Metal Shielded cable. Magnesium Oxide,
194°F or 482°F., Dry or wet locations, with copper or Alloy Steel outer covering. Mineral insulated and
Metal Shielded.
Thermoplastic and Asbestos(TA). Thermoplastic and Asbestos, 194°F., Switchboard use only.

Thermoplastic and Fibrous Outer Braid(TBS). Thermoplastic with Fibrous outer braid, 194°F. Fire
Retardant (Switch Boards).

Silicone-Asbestos(SA). Silicone Rubber or Silicone Asbestos, 194°F. For dry and Damp Areas. Silicone
Rubber insulation with Glass or other Braided covering. (392°F. Special Applications).

Asbestos and Varnished Cambric(AVB). Asbestos and Varnished Cambric, 194-230°F., Dry use only.

Synthetic Heat Resistant(SIS). Switchboard wire 194°F. Thermoplastic Flame Resistant for Switchboards.
Synthetic Heat resistant Rubber. Dry only.

Fluorinated Ethylene Propylene(FEP). Fluorinated Ethylene Propylene Insulation, Rated over 194°F. Dry
only.

Fluorinated Ethylene Propylene with Glass Braid(FEPB). Same as FeP, but with glass braid or Asbestos
type outer covering. 392°F. Dry only.

Heat-Resistant Rubber(RHH). Thermoset, 194°F. Dry and Damp only, Flame Retardant, and Moisture
Resistant.

Heat-Resistant Thermoplastic(THHN). Thermoplastic 194°F. Insulation with outer nylon (or equivalent)
jacket Heat Resistant, Flame Retardant with nylon or equivalent jacket. Dry and Damp Locations.