0% found this document useful (0 votes)
248 views

4.1 Walk Way Slab

This document provides design calculations for reinforced concrete slabs in a water treatment plant project. It includes calculations for three slabs: a walkway slab over an aerator with a 0.75m span, a cover slab over a stilling chamber with a 1.2m span, and a cover slab over a flash mixer with a 1.9m span. For each slab, it calculates the loads, bending moments, required steel reinforcement, and checks deflection. The calculations follow the procedures in Indian code IS 456 to design reinforced concrete members.

Uploaded by

Seph Rjy
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
248 views

4.1 Walk Way Slab

This document provides design calculations for reinforced concrete slabs in a water treatment plant project. It includes calculations for three slabs: a walkway slab over an aerator with a 0.75m span, a cover slab over a stilling chamber with a 1.2m span, and a cover slab over a flash mixer with a 1.9m span. For each slab, it calculates the loads, bending moments, required steel reinforcement, and checks deflection. The calculations follow the procedures in Indian code IS 456 to design reinforced concrete members.

Uploaded by

Seph Rjy
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 12

PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Walkway Slab in Aerator

6.75 kN/m

0.75

Span of Slab l = 0.75 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 3 kN/m

Total load acting on the beam = 6.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 1.9 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 5.06 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x1.9= 2.85 kNm

Mu /bd2 = 2.85x10^6/1000/113^2= 0.223 N/mm2

Percentage Steel Required, pt = 0.05 %

Area of steel Required = 0.05 x 1000 x 113 / 100 = 56.5 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x5.06= 7.59 kN

tve = 7.59x1000/(1000x113) = 0.067 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 750 mm

Area of steel Required = 56.5 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 48.6105617089

fig 4, IS:456 Modification Factor = 2

span / effective depth = 7

< 7x 2 = 14
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Cover Slab over Stilling Chamber

6.75 kN/m

1.2

Span of Slab l = 1.2 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 3 kN/m

Total load acting on the beam = 6.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 1.22 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 8.1 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x1.22= 1.83 kNm

Mu /bd2 = 1.83x10^6/1000/113^2= 0.143 N/mm2

Percentage Steel Required, pt = 0.03 %

Area of steel Required = 0.03 x 1000 x 113 / 100 = 33.9 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x8.1= 12.15 kN

tve = 12.15x1000/(1000x113) = 0.108 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1200 mm

Area of steel Required = 136.0 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 117.0094936709

fig 4, IS:456 Modification Factor = 2

span / effective depth = 11

< 20x 2 = 40
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Cover Slab over Flash Mixer

8.75 kN/m

1.9

Span of Slab l = 1.9 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 3= 5 kN/m

Total load acting on the beam = 8.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 3.95 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 29.75 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x3.95= 5.925 kNm

Mu /bd2 = 5.925x10^6/1000/113^2= 0.464 N/mm2

Percentage Steel Required, pt = 0.11 %

Area of steel Required = 0.11 x 1000 x 113 / 100 = 124.3 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x29.75= 44.63 kN

tve = 44.63x1000/(1000x113) = 0.395 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1900 mm

Area of steel Required = 124.3 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 106.9432357595

fig 4, IS:456 Modification Factor = 2

span / effective depth = 17

< 20x 2 = 40
PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Inter Connection Slab

8.75 kN/m

1.5

Span of Slab l = 1.5 m

Size of Slab : Width of the Slab = 1000 mm

Depth of the Slab = 150 mm

Dead load due to self weight of beam = 25x1x0.15= 3.75 kN/m

Live load due to Walkway Slab= 5= 5 kN/m

Total load acting on the beam = 8.75 kN/m

Clear Cover to Main Reinforcement = 25 mm

Characteristic Strength of Concrete, fck = 20 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 8 mm

Diameter of bottom reinforcement = 8 mm

Effective depth for top reinforcement = 150-25-8-4= 113 mm

Effective depth for bottom reinforcement = 150-25-8-4= 113 mm

Max Bending moment at mid span = 2.46 kNm

Max Bending moment at supports = 0 kNm

Max Shear force = 26.25 kN

Reinforcement at bottom face of beam


Mu (Factored moment) = 1.5x2.46= 3.69 kNm

Mu /bd2 = 3.69x10^6/1000/113^2= 0.289 N/mm2

Percentage Steel Required, pt = 0.07 %

Area of steel Required = 0.07 x 1000 x 113 / 100 = 79.1 mm2


PROJECT: WATER SUPPLY DISTRIBUTION NETWORK FOR PALAKOLLU TOWN

TITLE AERATOR AND FLASH MIXER - 11MLD WTP

Astmin = 0.0012 x 1000 x 113 = 136.0 mm2

Spacing required = 150.0 mm

Ast Provided = (8 @150mm C/C) = 337.1 mm2

Shear Reinforcement

Vu = 1.5x26.25= 39.38 kN

tve = 39.38x1000/(1000x113) = 0.348 N/mm2

pt = = 0.298 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

Check for Deflection

Span Length = 1500 mm

Area of steel Required = 79.1 mm2

Ast Provided = 337.1 mm2

Percentage Steel provided, pt 0.299

fs = 0.58 x fy x Astreq / Astprov= 68.0547863924

fig 4, IS:456 Modification Factor = 2

span / effective depth = 14

< 20x 2 = 40
L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -32xx 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
WET WELL at LS 15 SBS JSR

Design of beam B3

Span of beam, l = 4.85 m

Size of beam : Width of the beam = 300 mm

Depth of the beam = 500 mm

Dead load due to self weight of beam = 25x0.3x0.5= 3.75 kN/m

Dead load due to floor finish = 1.15x(25x0.04)= 1.15 kN/m

Load due to live load acting on floor slab = 10x1.15= 11.5 kN/m

Total load acting on the beam = 16.4 kN/m

Clear Cover to Main Reinforcement = 30 mm

Characteristic Strength of Concrete, fck = 25 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 12 mm

Diameter of bottom reinforcement = 16 mm

Effective depth for top reinforcement = 500-30-6= 464 mm

Effective depth for bottom reinforcement = 500-30-8= 462 mm

Max Bending moment at mid span 16.4x4.85x4.85/8= 48.22 kNm

Max Shear force 16.4x4.85/2= 39.77 kN

Reinforcement at top face of beam

Astmin = 0.85 x 300 x 464 / 500 = 237 mm2

Ast Provided = = 226.2 mm2

Provide 2-12 dia bars on top face

Reinforcement at bottom face of beam

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -32xx 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
WET WELL at LS 15 SBS JSR
Mu (Factored moment) = 1.5x48.22= 72.33 kNm

SP:16-1980 Mu /bd2 = 72.33x10^6/300/462^2= 1.130 N/mm2

Table : 3 Percentage Steel Required, pt = #MACRO? %

#MACRO? #MACRO? mm2

Astmin = 0.85 x 300 x 462 / 500 = 236.0 mm2

Ast Provided = = 402.1 mm2

Provide 2-16dia bars on bottom face

Shear Reinforcement

Vu = 59.655 kN

tve = 59.655x1000/(300x462) = 0.429 N/mm2

pt = = 0.29 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

#VALUE! #VALUE! #VALUE! #VALUE!

Spacing for min shear reinforcement = 364 mm

0.75 d = 0.75 x 464 = 348 mm

#VALUE!

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -3170 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
MCC Room at LS 15 SBS JSR

29.87
Design of beam B3 kN/m

4.3175 4.3175

Span of beam, l = 4.3175 m

Size of beam : Width of the beam = 300 mm

Depth of the beam = 500 mm

Dead load due to self weight of beam = 25x0.3x0.5= 3.75 kN/m

Dead load due to cover slab= 1.1625x(25x0.15)= 4.359375 kN/m

Dead load due to Grating= 0.9x(78.5x0.008)= 0.5652 kN/m

Dead load due to floor finish = 1.1625x(25x0.04)= 0.575 kN/m

Load due to live load acting on floor slab = 10x(1.1625+0.9)= 20.625 kN/m

Total load acting on the beam = 29.87 kN/m

Clear Cover to Main Reinforcement = 30 mm

Characteristic Strength of Concrete, fck = 25 N/mm2

Characteristic Strength of Steel, fy = 500 N/mm2

Diameter of top reinforcement = 12 mm

Diameter of bottom reinforcement = 16 mm

Effective depth for top reinforcement = 500-30-6= 464 mm

Effective depth for bottom reinforcement = 500-30-16-8= 446 mm

Max Bending moment at mid span 29.87x4.3175x4.3175/8= 69.6 kNm

Max Shear force 29.87x4.3175/2= 64.48 kN

Reinforcement at top face of beam

# Sensitivity: LNT Construction Internal Use


L & T Construction
Water & Renewable Energy
PROJECT: DOCUMENT NO. DATE
Bhatpara Sewerage Network & WWT Project
LE 130089 - C - WW- SW - DC -3170 04-Aug-2018
TITLE DESIGNED CHECKED PAGE
MCC Room at LS 15 SBS JSR
Astmin = 0.85 x 300 x 464 / 500 = 237 mm2

Ast Provided = = 339.3 mm2

Provide 3-12 dia bars on top face

Reinforcement at bottom face of beam

Mu (Factored moment) = 1.5x69.6= 104.4 kNm

SP:16-1980 Mu /bd2 = 104.4x10^6/300/446^2= 1.749 N/mm2

Table : 3 Percentage Steel Required, pt = #MACRO? %

#MACRO? #MACRO? mm2

Astmin = 0.85 x 300 x 446 / 500 = 227.0 mm2

Ast Provided = = 603.2 mm2

Provide 3-16dia bars on bottom face

Shear Reinforcement

Vu = 96.72 kN

tve = 96.72x1000/(300x446) = 0.695 N/mm2

pt = = 0.451 %

Table 19, tc = = #VALUE! N/mm2

IS:456 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

#VALUE! #VALUE! #VALUE! #VALUE!

Spacing for min shear reinforcement = 364 mm

0.75 d = 0.75 x 464 = 348 mm

#VALUE!