Costing Example

This document provides an input/output points list for a building automation system at CT College in New London, CT. It includes 27 points that require input or output field interface devices, such as temperature, humidity, pressure, and flow sensors, output relays and transducers, equipment status monitoring, and meter inputs. The points cover a variety of types including discrete inputs and outputs as well as analog inputs and outputs.

Uploaded by

Nico Dimas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views

Costing Example

This document provides an input/output points list for a building automation system at CT College in New London, CT. It includes 27 points that require input or output field interface devices, such as temperature, humidity, pressure, and flow sensors, output relays and transducers, equipment status monitoring, and meter inputs. The points cover a variety of types including discrete inputs and outputs as well as analog inputs and outputs.

Uploaded by

Nico Dimas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

Input Or Field Interface Devices Required

Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI AI
CT College Hardware

Analog Pneumatic Transducer

Space Temp w/ Override Push

(including sensor, power, and


New London, CT

Duct Temperature - Average


Control Relay & Contactors

Hydro. Differential Pressure


Pipe Temperature - Surface
Analog Voltage Or Current

Pressure Sensor - Analog

(existing meter; includes

(existing meter; includes


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Building(s):

Space Carbon Dioxide

Pushbutton Or Switch
Analog Output
Digital Output
Analog Input

Damper and Actuator

Duct Carbon Dioxide


Digital Input

Outside Air Humidity


Duct Static Pressure

Hydronic Flow Meter


(ultrasonic low cost)
Summary

Space Temperature
Valve and Actuator

Duct Temperature

Auxiliary Contact
Damper Actuator

Pressure Switch
Space Humidity

(existing ports)

(existing ports)
Valve Actuator

(varies widely)

(varies widely)

pulse adaptor)

pulse adaptor)
Duct Humidity
Project:

(existing well)
Control Relay

Electric Meter
Level Sensor

Project Total
Flow Switch
integration)

Occupancy

Pilot Relay

Gas Meter
Campus Efficiency Now

Timer
Turnkey Direct Unit Prices (Material + Labor) ===> $ 650 $ 650 $ 650 $ 650 $ 350 $ 650 $ 250 $ 250 $ 750 $ 500 $ 2,500 $ 1,000 $ 350 $ 400 $ 450 $ 250 $ 400 $ 750 $ 350 $ 600 $ 700 $ 250 $ 250 $ 600 $ 3,000 $ 850 $ 350 $ 350 $ 150 $ 250 $ 300 $ 350 $ 350 $ 250 $ 250 $ 1,000 $ 350 $ 1,500 $ 1,500
Cummings Arts Center $ -
Base Bid 3 2 2 2 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 9,100
Add. Alt. 1 – CHW Pumps VFD Integration 3 4 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 6,800
Add. Alt. 2 – Upgrade AHU Controls to DDC 0 1 0 18 0 0 0 0 9 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 $ 23,950
Add. Alt. 3 – Upgrade HW System Controls to DDC 0 0 0 6 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 6,900
College Center Crozier Williams $ -
Base Bid 10 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 6 0 0 0 0 0 0 0 0 0 0 0 $ 22,700
Add. Alt. 1 – CHW Pumps VFD Integrations 3 7 3 3 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 $ 13,100
Blaustine Humanities Center $ -
Base Bid 3 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 3,150
Add. Alt. 1 – CHW Pumps VFD Integration 2 3 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 4,900
Add. Alt. 2 – Upgrade AHU Controls to DDC 0 0 0 10 0 0 0 0 6 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 13,000
Add. Alt. 3 – Upgrade Zone Controls to DDC 4 45 4 102 4 0 0 0 31 0 71 45 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 $ 213,550
Add. Alt. 4 – Upgrade HW System Controls to DDC 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 $ 1,150
Athletic Complex $ -
Base Bid 5 6 5 5 5 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 5 0 0 0 0 0 0 0 $ 19,450
Add. Alt. 1 – Brine Pumps VFD Integration 2 3 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 $ 6,100
Add. Alt. 2 – Ice Rink AHU VFD Integration 2 2 2 1 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 $ 5,950

$ -

Totals By Point Type 37 79 19 151 19 0 0 0 47 21 0 71 45 3 0 0 0 0 0 0 0 2 0 2 0 15 0 11 0 0 0 15 0 0 0 0 0 0 0


Total Points 286
Budgetary Estimates $ 24,050 $ 51,350 $ 12,350 $ 98,150 $ 6,650 $ - $ - $ - $ 35,250 $ 10,500 $ - $ 71,000 $ 15,750 $ 1,200 $ - $ - $ - $ - $ - $ - $ - $ 500 $ - $ 1,200 $ - $ 12,750 $ - $ 3,850 $ - $ - $ - $ 5,250 $ - $ - $ - $ - $ - $ - $ - $ -
Total $ 349,800

Version Notes: $ 1,223 per point

Building Automation System - New I/O Points Page 1 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Cummings Arts Center

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cummings Arts Center


Base Bid

AC-2 Supply & Return Fan VFD's


Start / Stop 2 2
Fan Status 2
VFD Speed Feedback 2
VFD Speed Command 2

Zone Occupancy Sensor Integration


Recital Hall 1 3

Totals By Point Type 3 2 2 2 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0


Total Points 9

Building Automation System - New I/O Points Page 2 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Cummings Arts Center

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cummings Arts Center


Add. Alt. 1 – CHW Pumps VFD Integration

(1) Chilled Water Pump VFD's


Start / Stop 1 1
Pump Status 3
VFD Speed Feedback 1
VFD Speed Command 1

CHW flow (or DP) Across Chillers 2

CHW System Remote DP Sensor 1 1

Totals By Point Type 3 4 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


Total Points 9

Building Automation System - New I/O Points Page 3 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Cummings Arts Center

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cummings Arts Center


Add. Alt. 2 – Upgrade AHU Controls to DDC

AC-1, AC-2, and AC-3


Outside Air Damper Actuator 3 3
Return Air Damper Actuator 3 3
Exhaust Air Damper Actuator 3 3
CHW Coil 2-Way Valve Actuator 3 3
Steam Preheat 1/3 Valve Actuator 3 3
Steam Preheat 2/3 Valve Actuator 3 3

Demand Controlled Ventilation


AC-2, EF-4 - Recital Hall 1 1

Totals By Point Type 0 1 0 18 0 0 0 0 9 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0


Total Points 19

Building Automation System - New I/O Points Page 4 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Cummings Arts Center

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cummings Arts Center


Add. Alt. 3 – Upgrade HW System Controls to DDC

Steam-HW HX (Perimeter HTG Loop)


HX Steam Valve 1 1
3-Way HW Zone Control Valve 4 4

Steam-HW HX (VAV Reheat Loop)


HX Steam Valve 1 1

Totals By Point Type 0 0 0 6 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


Total Points 6

Building Automation System - New I/O Points Page 5 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Crozier Willimas

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cro College Center


Base Bid

Demand Controlled Ventilation


AHU-8, EF-14 - Loft 201 1 1
AHU-2, EF-15 - Large Studio 402 1 1
AHU-6, EF-17 - Large Mtg 309 1 1
AHU-6, EF-18 - Small Mtg 312 1 1
AHU-5, EF-20 - Dance Studio 306 1 1
AHU-5, EF-21 - Movement 304 1 1

Zone Occupancy Sensor Integration


AHU-1, EF16 - Small Studio 401 1 1
AHU-2, EF15 - Large Studio 402 1 1
AHU-3 - Connection 206 1 1
AHU-4 - Campus Store 208 1 2
AHU-5, EF-20 - Dance Studio 306 1 1
AHU-5, EF-21 - Movement 304 1 1
AHU-6, EF-17 - Large Mtg Rm 309 1 1
AHU-6, EF-18 - Small Mtg Rm 312 1 1
AHU-8, EF-14 - Loft 201 1 2
AHU-10 - Coffee 315 1 1

Totals By Point Type 10 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 6 0 0 0 0 0 0 0 0 0 0 0


Total Points 16

Building Automation System - New I/O Points Page 6 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Crozier Willimas

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Cro College Center


Add. Alt. 1 – CHW Pumps VFD Integrations

(3) Chilled Water Pump VFD's


Start / Stop 3 3
Pump Status 3 3
VFD Speed Feedback 3
VFD Speed Command 3

CHW flow (or DP) Across Chillers 3

CHW System Remote DP Sensor 1 1

Totals By Point Type 3 7 3 3 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0


Total Points 16

Building Automation System - New I/O Points Page 7 of 15


Page 8 of 15

Gas Meter
AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
Inputs

0
Meter

Electric Meter
0

Level Sensor
0

Flow Switch
0
Equipment Status

Pressure Sensor - Analog


0
Monitoring

Pressure Switch
0

Current Sensor - Analog


0

Current Switch - Digital


0

Pushbutton Or Switch
0
Pilot Relay
Auxiliary Contact 0
0
Duct Carbon Dioxide

0
Sensors - Temperature, Humidity, Pressure, Flow

Space Carbon Dioxide

0
Occupancy
Field Interface Devices Required

0
Hydronic Flow Meter

0
Hydro. Differential Pressure

0
Occupancy, & IAQ

Pipe Temperature - Well

0
Pipe Temperature - Surface

0
Outside Air Humidity

Building Automation System - New I/O Points


Outside Air Temperature

0
Duct Humidity

0
Duct Temperature - Average

0
Duct Static Pressure

0
Duct Temperature

0
Space Humidity

0
Space Temp w/ Override Push Timer
3

3
Space Temperature

0
Valve And Actuator

0
Damper and Actuator
Hardware

0
New

Valve Actuator
And Transducers

0
Output Relays

Damper Actuator

0
DI AI DO AO DO DO AO AO

Analog Pneumatic Transducer

0
Analog Voltage Or Current

0
Control Relay & Contactors

0
Control Relay

0
Analog Output

0
Input Or

Digital Output

0
Output
Point
Type

Analog Input

0
Digital Input

3
3 Total Points
Totals By Point Type
3rd Flr Office (3) Wings
Building Automation System (BAS)

Zone Override Push Timers


Input/Output Points List

Campus Efficiency Now


Blaustine Humanities
New London, CT
CT College

Blaustine Humanities Center


Base Bid
Building(s):

Project:
Site:
Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Blaustine Humanities

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Blaustine Humanities Center


Add. Alt. 1 – CHW Pumps VFD Integration

(1) Chilled Water Pump VFD's


Start / Stop 1 1
Pump Status 2
VFD Speed Feedback 1
VFD Speed Command 1

CHW flow (or DP) Across Chillers 2

Totals By Point Type 2 3 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


Total Points 7

Building Automation System - New I/O Points Page 9 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Blaustine Humanities

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Blaustine Humanities Center


Add. Alt. 2 – Upgrade AHU Controls to DDC

AC-1 and AC-2


Outside Air Damper Actuator 2 2
Return Air Damper Actuator 2 2
Exhaust Air Damper Actuator 2 2
CHW Coil 3-Way Valve Actuator 2 2
HW Coil 2-Way Valve Actuator 2 2

Totals By Point Type 0 0 0 10 0 0 0 0 6 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


Total Points 10

Building Automation System - New I/O Points Page 10 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Blaustine Humanities

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Blaustine Humanities Center


Add. Alt. 3 – Upgrade Zone Controls to DDC

VAV Boxes
Damper Actuators 27 27

Fan Powered VAV Reheat Boxes


Damper Actuators 4 4
Reheat Valves 4 4
Fan Start / Stop 4 4
Fan Run Status 4 4

Floor Mounted Fan Coil Units


Dual Temp 2-Way Valves 48 48

Baseboard Finned Tube Radiators


HW 2-Way Valves 14 14

Cabinet Unit Heaters


HW 2-Way Valves 5 5

Zone Temperature Sensors 45 45

Totals By Point Type 4 45 4 102 4 0 0 0 31 0 0 71 45 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0


Total Points 155

Building Automation System - New I/O Points Page 11 of 15


Page 12 of 15

Gas Meter
AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
Inputs

0
Meter

Electric Meter
0

Level Sensor
0

Flow Switch
0
Equipment Status

Pressure Sensor - Analog


0
Monitoring

Pressure Switch
0

Current Sensor - Analog


0

Current Switch - Digital


0

Pushbutton Or Switch
0
Pilot Relay
Auxiliary Contact 0
0
Duct Carbon Dioxide

0
Sensors - Temperature, Humidity, Pressure, Flow

Space Carbon Dioxide

0
Occupancy
Field Interface Devices Required

0
Hydronic Flow Meter

0
Hydro. Differential Pressure

0
Occupancy, & IAQ

Pipe Temperature - Well

0
Pipe Temperature - Surface

0
Outside Air Humidity

Building Automation System - New I/O Points


Outside Air Temperature

0
Duct Humidity

0
Duct Temperature - Average

0
Duct Static Pressure

0
Duct Temperature

0
Space Humidity

0
Space Temp w/ Override Push Timer

0
Space Temperature

0
Valve And Actuator

0
Damper and Actuator
Hardware

0
New

Valve Actuator
And Transducers

1
Output Relays

Damper Actuator

0
DI AI DO AO DO DO AO AO

Analog Pneumatic Transducer

0
Analog Voltage Or Current

0
Control Relay & Contactors

0
Control Relay

0
Analog Output
1

1
Input Or

Digital Output

0
Output
Point
Type

Analog Input

0
Add. Alt. 4 – Upgrade HW System Controls to DDC
Digital Input

0
1 Total Points
Totals By Point Type
HX Steam Valve
Building Automation System (BAS)
Input/Output Points List

Campus Efficiency Now


Blaustine Humanities
New London, CT

Steam-HW HX
CT College

Blaustine Humanities Center


Building(s):

Project:
Site:
Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Athletic Complex

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Athletic Complex
Base Bid

Fieldhouse AHU Supply Fan VFD


Start / Stop 1 1
Fan Status 1 1
VFD Speed Feedback 1
VFD Speed Command 1

Fieldhouse Addition HV-1 Fan VFD


Start / Stop 1 1
Fan Status 1 1
VFD Speed Feedback 1
VFD Speed Command 1

Fieldhouse Addition HV-2 Fan VFD


Start / Stop 1 1
Fan Status 1 1
VFD Speed Feedback 1
VFD Speed Command 1

Upgrade Fieldhouse AHU Controls to DDC


Mixed Air Damper Actuator 1 1
HW Coil 3-Way Valve 1 1

Add Exhaust Fans EF-2&3 to BAS


Fan Start / Stop 2 2
Fan Run Status 2 2

Demand Controlled Ventilation


Fieldhouse AHU, EF-2&3 1 1
Fieldhouse Addition Upper Level - HV-1 1 1
Fieldhouse Addition Lower Level - HV-2 1 1

Totals By Point Type 5 6 5 5 5 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 5 0 0 0 0 0 0 0


Total Points 21

Building Automation System - New I/O Points Page 13 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Athletic Complex

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Athletic Complex
Add. Alt. 1 – Brine Pumps VFD Integration

(1) Brine Pump VFD's


Start / Stop 1 1
Pump Status 2 2
VFD Speed Feedback 1
VFD Speed Command 1

Brine Supply Temperature 1 1


Brine Return Temperature 1 1

Totals By Point Type 2 3 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0


Total Points 7

Building Automation System - New I/O Points Page 14 of 15


Input Or Field Interface Devices Required
Output
Building Automation System (BAS) Point Output Relays Sensors - Temperature, Humidity, Pressure, Flow Equipment Status Meter
Input/Output Points List Type And Transducers Occupancy, & IAQ Monitoring Inputs
Site: DI AI DO AO DO DO AO AO New AI AI AI AI AI AI AI AI AI AI AI AI AI DI AI AI DI DI DI DI AI DI AI DI AI AI AI
CT College Hardware

Space Temp w/ Override Push Timer


Analog Pneumatic Transducer
New London, CT

Hydro. Differential Pressure


Duct Temperature - Average
Control Relay & Contactors

Pipe Temperature - Surface


Analog Voltage Or Current

Pressure Sensor - Analog


Outside Air Temperature

Current Sensor - Analog


Pipe Temperature - Well

Current Switch - Digital


Space Carbon Dioxide

Pushbutton Or Switch
Damper and Actuator

Outside Air Humidity

Duct Carbon Dioxide


Hydronic Flow Meter
Duct Static Pressure
Space Temperature
Valve And Actuator

Duct Temperature

Auxiliary Contact
Building(s):

Damper Actuator

Pressure Switch
Space Humidity
Analog Output

Valve Actuator

Duct Humidity
Digital Output

Electric Meter
Control Relay

Level Sensor
Analog Input
Digital Input

Flow Switch
Occupancy
Athletic Complex

Pilot Relay

Gas Meter
Project:

Campus Efficiency Now

Athletic Complex
Add. Alt. 2 – Ice Rink AHU VFD Integration

(1) Ice Rink AHU Supply Fan VFD


Start / Stop 1 1
Fan Status 1
VFD Speed Feedback 1
VFD Speed Command 1

Ice Rink Exhaust Fan


Fan Start / Stop 1 1
Fan Run Status 1 1

Demand Controlled Ventilation


Ice Rink AHU, & EF 1 1

Totals By Point Type 2 2 2 1 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0


Total Points 7

Building Automation System - New I/O Points Page 15 of 15