Air Conditioning Equipment
Air Conditioning Equipment
Air-Conditioning Equipment
TABLE OF CONTENTS
Introduction 3
Operation 5
Types 6
Equipment 12
Equipment Parts and its Function 13
Experiments 18
Latest Equipment 24
I. INTRODUCTION
The first modern air conditioning system was developed in 1902 by a young
electrical engineer named Willis Haviland Carrier. It was designed to solve a
humidity problem at the Sackett-Wilhelms Lithographing and Publishing Company
in Brooklyn, N.Y. Paper stock at the plant would sometimes absorb moisture from
the warm summer air, making it difficult to apply the layered inking techniques of
the time. Carrier treated the air inside the building by blowing it across chilled
pipes. The air cooled as it passed across the cold pipes, and since cool air cannot
carry as much moisture as warm air, the process reduced the humidity in the plant
and stabilized the moisture content of the paper. Reducing the humidity also had
the side benefit of lowering the air temperature and a new technology was born.
When hot air flows over the cold, low-pressure evaporator coils, the
refrigerant inside absorbs heat as it changes from a liquid to a gaseous state. To
keep cooling efficiently, the air conditioner has to convert the refrigerant gas
back to a liquid again. To do that, a compressor puts the gas under high pressure,
a process that creates unwanted heat. All the extra heat created by compressing
the gas is then evacuated to the outdoors with the help of a second set of coils
called condenser coils, and a second fan. As the gas cools, it changes back to a
liquid, and the process starts all over again. Think of it as an endless, elegant cycle:
liquid refrigerant, phase conversion to a gas/ heat absorption, compression and
phase transition back to a liquid again.
II. OPERATION
An air conditioner uses a cold indoor coil called the evaporator. The
condenser, a hot outdoor coil, releases the collected heat outside. The
evaporator and condenser coils are serpentine tubing surrounded by aluminum
fins. This tubing is usually made of copper.
A pump, called the compressor, moves a heat transfer fluid (or refrigerant)
between the evaporator and the condenser. The pump forces the refrigerant
through the circuit of tubing and fins in the coils.
The liquid refrigerant evaporates in the indoor evaporator coil, pulling heat
out of indoor air and thereby cooling your home. The hot refrigerant gas is
pumped outdoors into the condenser where it reverts back to a liquid, giving up
its heat to the outside air flowing over the condenser's metal tubing and fins.
III. TYPES
A central system uses chilled water or hot water from a central plant to cool
and heat the air at the coils in an air handling unit (AHU) as shown in Figure 6. For
energy transport, the heat capacity of water is about 3400 times greater than that
of air. Central systems are built-up systems assembled and installed on the site.
E. Air Systems
An air system is also called an air handling system or the air side of an air-
conditioning or HVAC&R system. Its function is to condition the air, distribute it,
F. Water Systems
These systems include chilled water, hot water, and condenser water
systems. A water system consists of pumps, piping work, and accessories. The
H. Control Systems
IV. EQUIPMENT
2 3 4
1
8 5 6
9 10 7
13
11
12
14
15
PARTS FUNCTIONS
Condenser Fan & Compressor Motor
These switches turn on or off the
Switches
condenser fan and compressor motor,
respectively. The condenser fan motor
keeps an air conditioner’s compressor
from becoming overheated. It cools
the superheated refrigerant that
moved through condensing coils of
your outside air conditioning unit.
Voltmeter
Ammeter
It is an instrument used for measuring
electric current in units of amperes. An
ammeter must be connected in series
with the path of the current being
measured.
Temperature Controller
Terminal Box
Sight Glass
This is used for checking the refrigerant
charge. If the air conditioner is working
properly, you'll be able to see a
continuous flow of clear refrigerant
through the sight glass, with perhaps
an occasional bubble at very high
temperatures.
VI. EXPERIMENTS
Listed below are the set of experiments that can be conducted using the
air-conditioning equipment:
Objectives:
Theory:
The air conditioner cycle works the same way as refrigeration cycle. The
process is similar to each other. The refrigerant (acting as a heat transfer fluid) is
used to transfer heat from a lower temperature to a higher temperature. The
refrigerant is evaporated at a temperature lower than the desired temperature in
the freezer or cooler. The condensing temperature of the refrigerant is increased
by compression so that it can either be rejected to the environment or recovered
as useful heat. The basic air conditioner cycle, with all steps combined, is shown
below. The standard refrigeration cycle works as follows:
For the calculations involved, take readings of properties directly from the
pressure–enthalpy diagram. By applying the energy equation to a compressor,
we get the following equation assuming that the process is adiabatic (compressor
work in kJ/kg)
h1 - h4
COP =
h2 - h1
Procedure:
Data Sheet:
Description Temperature, °C
Temperature at compressor inlet (T1)
Description L/min
Flow rate
Description
The RA3 also includes pressure gauges and temperature sensors to allow
the refrigerant temperature change across the condenser and evaporator to be
established. The refrigerant flow rate is also measured using a variable area flow
meter.
Demonstration Capabilities
Features
• Transparent duct for full visibility of the process and the components
• Includes pre-heaters, humidifier, chiller/dehumidifier and reheaters
• Fully instrumented, with temperature and relative humidity sensors at every
stage of the process, plus an air flow sensor
• RH sensors calibrated for maximum accuracy
• Suitable for both vocational training and for rigorous academic analysis of
the thermodynamic principles involved
• Fully computer controlled with real-time data logging of results (requires a
PC not supplied by Armfield)
• Capability of using PID control for preheat, humidity and reheat allows
stable conditions to be set up for investigations
• Enclosed climate control chamber
• Adjustable recirculation of air leaving the chamber back into the
conditioning duct
• Additional sensors, including refrigerant pressures and flow
Technical Specifications
Item Value
Duct size 200mm x 200mm
Air speed Variable to > 1m/s
Preheaters 400W
Final heaters 200W
Refrigerant R134a
Boiler power 2KW nominal
Chiller power 500W nominal
Chamber volume (RA3) 230l
Overall Dimension
• Length 2.45 m
• Depth 0.71 m
• Height 1.20 m
Description
Many of the components used are automotive, but the process is the same
in vehicle, building services and refrigeration units. A DC compressor has been
selected to provide drive, due to its low-voltage, low-noise operation against an
automotive-style belt-driven compressor typical of high-current AC motors.
Three switches are fitted to the system to demonstrate typical faults found
in refrigeration or air-conditioning circuits. When any of the three switches are
selected, the student can observe the displayed information on the control panel
to diagnose the fault condition being demonstrated. The three faults that can be
selected are:
Demonstration Capabilities
Features
Technical Specifications
Overall Dimension
• Length 0.90 m
• Depth 0.50 m