SIPROTEC 7UT85

Transformer Differential Protection

www.siemens.com/siprotec

Description
The SIPROTEC 7UT85 transformer differential protection
device has been designed specifically for the protection of
two-winding transformers (2 sides). It is the main protec-
tion for the transformer and contains many other protec-
tion and monitoring functions. The additional protection
functions can also be used as backup protection for pro-
tected downstream objects (such as cables or lines). In this
regard you are also supported by the modular expandabil-
ity of the hardware. With its modular structure, flexibility
and the powerful DIGSI 5 engineering tool, SIPROTEC
7UT85 offers future-oriented system solutions with high
investment security and low operating costs.
SIPROTEC 7UT85
Main function 1 differential protection function (standard or
auto transformer) with additional stabiliza-
tion; up to 2 restricted ground-fault protection • Transformer differential protection for phase-angle
functions regulating transformers of the single core type and
Usable measur- 5 x 3-phase current measuring points, special transformers
ing 3 x 1-phase current measuring points,
• Applicable from average up to extra-high voltage
points 3 x 3-phase voltage measuring points;
expandable to 3 sides • Protection of standard power transformers, auto
Inputs and 2 predefined standard variants with transformers and motors
outputs 8 current transformers, 7 to 19 binary • Typical properties of a transformer differential protec-
inputs, 7 to 23 binary outputs tion such as flexible adaptation to the transformer
Hardware Flexibly adjustable and expandable vector group, control of inrush and overexcitation
flexibility I/O quantity structure within the scope processes, safe behavior in the case of current-
of the SIPROTEC 5 modular system transformer saturation with different degrees of
Housing width 1/3 × 19 inch to 2/1 × 19 inch saturation
• Adaptive adaptation of the operate curve to the
Functions transformer tap position
DIGSI 5 permits all functions to be configured and com-
bined as required. • Increased sensitivity with near-neutral-point ground
faults through a separate restricted ground-fault
• Transformer differential protection for two-winding protection
transformers with versatile, additional protection
functions; expandable to 3 windings • Additional current and voltage inputs can be supple-
ments for standard protection functions, such as
overcurrent, voltage frequency and others
Modular and flexible

• Arc protection Benefits


• Voltage controller function ANSI 90V for two-winding • Safety due to powerful protection functions
transformers, three-winding transformers and grid
coupling transformers with parallel control • Data security and transparency over the entire
(master/follower, circuit reactive current lifecycle of the plant save time and money
minimization) • Purposeful and simple operation of the devices and
• Graphical logic editor to create powerful automation software thanks to user-friendly design
functions in the device • Increased reliability and quality of the engineering
• Up to 4 pluggable communication modules, usable for process
different and redundant protocols (IEC 61850, • High safety due to a consistent implementation of
IEC 60870-5-103, IEC 60870-5-104, DNP3 serial and safety and security
TCP, Modbus TCP, PROFINET IO)
• Powerful communication components ensure safe
• Redundancy protocols PRP and HSR and effective solutions
• Cyber security to NERC CIP and BDWE Whitepaper • Full compatibility between IEC 61850 Editions 1 and 2
requirements
• Highly available Ethernet communication due to inte-
• Secure serial protection data communication, even grated Ethernet redundancy protocols PRP and HSR
over great distances and all available physical media
(optical fiber cable, 2-wire connections and
communication networks)
• Capturing operational measured variables and protec-
tion function measured values to evaluate the plant
state, to support commissioning, and to analyze faults
• Phasor measurement unit (PMU) for synchrophasor
measured values and IEEE C37.118 protocol
• Powerful fault recording (buffer for a max. record
time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
• Auxiliary functions for simple tests and
commissioning
• Flexibly adjustable I/O quantity structure within the
scope of the SIPROTEC 5 modular system

For all products using


security features of
OpenSSL, the
Siemens AG following shall apply:
Energy Management Division This product includes
Freyeslebenstraße 1 software developed
91058 Erlangen, Germany by the OpenSSL
Project for use in the
SIPROTEC 7UT85 Profile E7.5.docx OpenSSL Toolkit
(www.openssl.org),
Printed in Germany | © 09.17 Siemens AG cryptographic soft-
ware written by Eric
E-Mail: [email protected] Young
Tel: +49 180 524 70 00 ([email protected])
and software devel-
oped by Bodo
Moeller.

You might also like