Process Integration (PI)
Process Integration (PI)
LECTURE # 1
ShimelisKebede(PhD)
AssistantprofessorofChemical(ProcessandEnvironmental)Engineering
SchoolofChemicalandBioEngineering/AAiT/AAU
Example
The application of pinch analysis (in industrial sectors such as oil refining,
chemicals, iron and steel, pulp and paper, petrochemicals, and food & drink)
can typically identify:
There are four key steps of pinch analysis in the design of heat
recovery systems for both new and existing processes:
The “kinked” nature of the composites means that ∆Tmin can occur
anywhere in the interchange region and not just at one end. For a
given value of ∆Tmin, the utility quantities predicted are the
minima required to solve the heat recovery problem.
Note that although there are many streams in the problem, in general
∆Tmin occurs at only one point of closest approach, which is
called the pinch. This means that it is possible to design a network
which uses the minimum utility equirements, where only the heat
exchangers at the pinch need to operate at ∆T values down to ∆Tmin.
Importance of Tmin
Grand composite curves
any heat available in interval i is hot enough to supply any duty in interval i+1.
Instead of sending the 60kW of surplus heat from interval 1 into cold utility,
it can be sent down into interval 2. It is therefore possible to set up a heat
“cascade” as shown in Figure (a)
Assuming that no heat is supplied to the hottest interval 1 from hot utility,
then the surplus of 60kW from interval 1 is cascaded into interval 2. There it
joins the 2.5kW surplus from interval 2, making 62.5kW to cascade into
interval 3. Interval 3 has a 82.5kW deficit, hence after accepting the 62.5kW
it can be regarded as passing on a 20kW deficit to interval 4. Interval 4 has a
75kW surplus and so passes on a 55kW surplus to interval 5. Finally, the
15kW deficit in interval 5 means that 40kW is the final cascaded energy to
cold utility. This in fact is the net enthalpy balance on the whole problem (i.e.
cold utility will always exceed hot utility by 40kW, whatever their individual
values).
Looking back at the heat flows between intervals in Figure (a), clearly
the negative flow of 20kW between intervals 3 and 4 is
thermodynamically infeasible. To make it just feasible (i.e. equal to
zero), 20kW of heat must be added from hot utility as shown in Figure
(b), and cascaded right through the system. By enthalpy balance this
means that all flows are increased by 20kW. The net result of this
operation is that the minimum utilities requirements have been
predicted (i.e. 20kW hot and 60kW cold). Furthermore, the position of
the pinch has been located. This is at the interval boundary with a
shifted temperature of 85°C (i.e. hot streams at 90°C and cold at 80°C)
where the heat flow is zero.
example
To perform MER design for the problem, the grid diagram is divided
into two parts i.e. above the pinch and below the pinch. Then following
the pinch design criteria placement of heat exchangers is carried out
as:
For the above pinch design of the stream network, two criteria must
be fulfilled
1) No. of stream criterion: NH ≤ NC